05-working-docs/A3-route-lengths.yaml
YAML sourcemetadata:
project: Kingsford Hotel Bacolod — BMS (AB-Run-6)
skeleton_emitted_by: generate-a3-cable-schedule.py --emit-skeleton
next_step: 'Annotate each route: set method to ''measured'' (with length_m + drawing_ref
+ breakdown) OR ''typical_range'' (with typical_range_key referencing the typical_ranges
block you author below per measure-cable-routes sub-routine).'
annotated_by: _scripts/annotate-a3-routes.py
annotation_basis: 'Per-context reasoned typical ranges per Operating Principle #11.
Drawing-availability triage in 03-doc-inventory.md committed all routes to typical-range
method (no measurable architectural floor plans provided; ECE auxiliary footprints
+ EE-24 riser used only for context calibration).'
typical_ranges:
mstp_riser_2f_to_rd:
length_m: 250
applies_to: BACnet MS/TP field backbone routed via service-core IDF stack (west end of building per ECE auxiliary layouts) plus horizontal BOH-corridor segments connecting all 8 BMS panels (DDC-2F-CHILLER, DDC-2F-BOH, DDC-2M-CASINO, DDC-RD-PLANT, DDC-LG-PLANT, DDC-GF-BOH, DDC-B1-BOH, DDC-3F).
basis: "Vertical span B1 → RD ≈ 13 floors × 4.5 m = 58.5 m. 8 horizontal panel-side segments at ~25 m each = 200 m. Routing factor 25% for tray sag + reserve = ~325 m. Refined to 250 m typical reflecting that not every panel sits at the same vertical line — some share corridor segments."
sources: ["EE-24 power riser", "ECE-05..ECE-15 service-core IDF stack", "industry typical for hospitality service-core MS/TP backbone"]
breakdown:
horizontal_m: 200
vertical_m: 50
bacnet_ip_backbone_riser:
length_m: 150
applies_to: BACnet/IP backbone — fibre riser from head-end at Lower Ground to per-floor IDF edge switches, plus Cat6 horizontal trunk to each DDC field panel.
basis: "Vertical fibre run LG → RD ≈ 13 floors × 4.5 m = 58.5 m. 8 horizontal Cat6 trunk segments at ~5 m each = 40 m. Plus 50 m reserve for service-core routing complexity. Total ~150 m typical."
sources: ["EE-24 power riser", "ECE auxiliary IDF stack"]
breakdown:
horizontal_m: 40
vertical_m: 60
cornering_m: 50
plant_room_chiller_2f:
length_m: 12
applies_to: Field cables from DDC-2F-CHILLER to chillers, primary/secondary CHW
pumps, condenser-water pumps, CHW supply/return/bypass headers — all in or directly
adjacent to the 2F chiller room.
basis: 'Industry-typical plant-room same-room run with allowances for tray drop
+ cornering + 0.5 m terminations on each end. Baseline: chiller room ~10×8 m
envelope; longest run from panel corner to far chiller skid ≈ 10 m + 1 m vertical
drop + 1 m termination tails.'
sources:
- MC Standards ME chiller block
- BMS-01 Chilled Water System I/O matrix
- industry typical for hospitality chiller plant 1500-3000 RT
breakdown:
horizontal_m: 9
vertical_m: 1
terminations_m: 1
cornering_m: 1
plant_room_lg_boiler_hwl:
length_m: 12
applies_to: Field cables from DDC-LG-PLANT to steam boilers SB-1/SB-2, calorifier
HWT-LZ, heat pump HP-LZ, recirculating pump RP-LZ, hot-water header set HWH-LZ
— all in or directly adjacent to the Lower Ground boiler/HWL plant room.
basis: Industry-typical plant-room same-room run. Boiler room and HWL plant adjacent
on Lower Ground; combined envelope ~12×8 m with panel central. Longest run ≈
9 m horizontal + 1 m vertical drop + 1 m termination + 1 m cornering.
sources:
- MC Standards ME boiler block
- MC Standards PL
- BMS-01 boiler-laundry table
- industry typical
breakdown:
horizontal_m: 9
vertical_m: 1
terminations_m: 1
cornering_m: 1
plant_room_rd_plant:
length_m: 15
applies_to: Field cables from DDC-RD-PLANT to cooling towers CT-1/CT-2/CT-3, common
CT sensors, condenser water headers, DOAS-RD, PAHU-r, calorifier HWT-HZ, heat
pump HP-HZ, recirculating pump RP-HZ, hot-water header set HWH-HZ — Roof Deck
plant area.
basis: Roof-deck plant area is more spread out than indoor plant rooms (cooling
towers separated for thermal isolation, calorifiers in adjacent enclosure).
Allow 15 m typical with breakdown 12 m horizontal + 1.5 m vertical drop + 1
m termination + 0.5 m cornering. Roof Deck exhaust fans (EF-RD.1, EF-RO.2, EF-1)
also covered by this panel — same envelope.
sources:
- BMS-02 Cooling Tower table
- MC Standards ME CT block
- MC Standards PL
- industry typical for rooftop plant
breakdown:
horizontal_m: 12
vertical_m: 1.5
terminations_m: 1
cornering_m: 0.5
casino_2m_localized:
length_m: 18
applies_to: Field cables from DDC-2M-CASINO to DOAS-2M, AHU-2M.1/2M.2, Air Ionizers
— Casino 2nd Mezzanine equipment localized in casino MEP zone.
basis: Casino mezzanine plant zone is mid-sized; AHU and DOAS spread across the
2M MEP corridor with the panel central. Allow 18 m typical (15 horizontal +
1.5 vertical + 1 termination + 0.5 cornering).
sources:
- BMS-02 Casino MVAC table
breakdown:
horizontal_m: 15
vertical_m: 1.5
terminations_m: 1
cornering_m: 0.5
boh_2f:
length_m: 25
applies_to: Field cables from DDC-2F-BOH to AHU-B.1/B.2/B.3, AHU-PF, AHU-EL, AHU-FR2,
AHU-FR3, PAHU-B.1/B.2/B.3, PAHU-PF, PAHU-FR, and 2F exhaust fans (TEF-2.1/2.2,
TEF-2B.3, EF-2B.1/2B.2, EF-GS.1/GS.2, EF-2.1..2.4, EF-OHRv2).
basis: 2nd Floor BOH zone is large (function-room program + multiple AHU rooms
+ service areas); panel sited near 2F service-core IDF on the west end. Average
run from panel to BOH AHU/PAHU rooms ≈ 22 m horizontal + 1 m vertical (slab
pen) + 1 m termination + 1 m cornering.
sources:
- BMS-01 Basement-Podium BOH AHU/PAHU table
- ECE-08 2F auxiliary layout
- industry-typical service-core to remote-AHU run
breakdown:
horizontal_m: 22
vertical_m: 1
terminations_m: 1
cornering_m: 1
boh_gf:
length_m: 25
applies_to: Field cables from DDC-GF-BOH to AHU-1.1/1.2/1.3 (Ground Floor BOH
AHU), GF main-lobby toilet exhaust fans TEF-1.1..1.4, and FACP gateway at the
Fire Command Center.
basis: Ground Floor includes lobby + F&B + retail + BOH; AHUs are spread across
BOH zones, FACP at FCC near main entrance. Average run from panel (service-core
IDF) to remote AHU ≈ 22 m horizontal + 1 m vertical + 1 m termination + 1 m
cornering.
sources:
- BMS-01 BOH AHU table
- ECE-07 GF + Mezz layout
- industry-typical
breakdown:
horizontal_m: 22
vertical_m: 1
terminations_m: 1
cornering_m: 1
boh_b1:
length_m: 28
applies_to: Field cables from DDC-B1-BOH to PAHU-0.1, basement toilet exhaust
TEF-B.1/B.2, and basement general exhaust EF-B.1/B.2/EF-BS.1/2/EF-GL.1/2/EF-FOST.1/EF-BR.1/2/EF-WS.1/EF-MP.1/EF-PR.1/3/EF-MFR.1.
basis: Basement-1 has parking + service + multiple equipment rooms (sewage, fuel,
pump, battery, mechanical); fans are widely scattered. Panel sited near B1 service-core
IDF / mechanical room. Average run 25 m horizontal + 1 m vertical + 1 m termination
+ 1 m cornering = 28 m.
sources:
- BMS-01 Basement General Ventilation block (long fan tag list)
- ECE-05/06 B1 layouts (multiple equipment rooms incl fuel/sewage tanks per insets)
breakdown:
horizontal_m: 25
vertical_m: 1
terminations_m: 1
cornering_m: 1
amenity_3f:
length_m: 35
applies_to: Field cables from DDC-3F to 3rd Floor amenity / first-guestroom-floor
toilet exhaust TEF-3A/3B/3C/30.20 and general exhaust EF-3.1..3.4/EF-3B-G/EF-3C.1-G
— long double-loaded corridor floor with pool/amenity zone.
basis: 3rd Floor is amenity + first guestroom floor with a long corridor (~75-90
m visible in ECE-09). Field devices distributed along corridor and at amenity-zone
perimeter. Panel sited at service-core west end. Average run ≈ 32 m horizontal
+ 1 m vertical + 1 m termination + 1 m cornering.
sources:
- BMS-01 General Ventilation 3rd Floor block
- ECE-09 3F PABX/FDAS layout (corridor scale calibrated against doorway = 900
mm per A-011)
breakdown:
horizontal_m: 32
vertical_m: 1
terminations_m: 1
cornering_m: 1
panel_power_feed_local:
length_m: 10
applies_to: 240V single-phase power feed from local floor distribution panelboard
(DBV-BMS / DBV-MECH per EE-24) to BMS DDC field panel.
basis: Each BMS DDC panel sits adjacent to the floor's electrical closet / IDF.
Industry typical 8-12 m from the floor distribution panelboard breaker to the
BMS panel. Allow 10 m with breakdown 7 m horizontal + 1.5 m vertical drop +
1 m termination + 0.5 m cornering.
sources:
- EE-24 power riser (Q-014 vector re-export pending for per-circuit IDs)
- industry typical for service-core panel-to-panel
breakdown:
horizontal_m: 7
vertical_m: 1.5
terminations_m: 1
cornering_m: 0.5
routes:
- from: DDC-GF-BOH
to: AHU-1.1 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: boh_gf
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 5
notes: ''
- from: DDC-GF-BOH
to: AHU-1.1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_gf
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 1
AO: 1
DI: 2
notes: ''
- from: DDC-GF-BOH
to: AHU-1.1 (ME Contractor)
method: typical_range
length_m: null
typical_range_key: boh_gf
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 1
AO: 2
notes: ''
- from: DDC-GF-BOH
to: AHU-1.2 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: boh_gf
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 5
notes: ''
- from: DDC-GF-BOH
to: AHU-1.2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_gf
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 1
AO: 1
DI: 2
notes: ''
- from: DDC-GF-BOH
to: AHU-1.2 (ME Contractor)
method: typical_range
length_m: null
typical_range_key: boh_gf
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 1
AO: 2
notes: ''
- from: DDC-GF-BOH
to: AHU-1.3 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: boh_gf
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 5
notes: ''
- from: DDC-GF-BOH
to: AHU-1.3 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_gf
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 1
AO: 1
DI: 2
notes: ''
- from: DDC-GF-BOH
to: AHU-1.3 (ME Contractor)
method: typical_range
length_m: null
typical_range_key: boh_gf
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 1
AO: 2
notes: ''
- from: DDC-2M-CASINO
to: AHU-2M.1 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: casino_2m_localized
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 5
notes: ''
- from: DDC-2M-CASINO
to: AHU-2M.1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: casino_2m_localized
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 1
AO: 1
DI: 2
notes: ''
- from: DDC-2M-CASINO
to: AHU-2M.1 (ME Contractor)
method: typical_range
length_m: null
typical_range_key: casino_2m_localized
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 1
AO: 2
notes: ''
- from: DDC-2M-CASINO
to: AHU-2M.2 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: casino_2m_localized
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 5
notes: ''
- from: DDC-2M-CASINO
to: AHU-2M.2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: casino_2m_localized
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 1
AO: 1
DI: 2
notes: ''
- from: DDC-2M-CASINO
to: AHU-2M.2 (ME Contractor)
method: typical_range
length_m: null
typical_range_key: casino_2m_localized
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 1
AO: 2
notes: ''
- from: DDC-2F-BOH
to: AHU-B.1 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 5
notes: ''
- from: DDC-2F-BOH
to: AHU-B.1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 1
AO: 1
DI: 2
notes: ''
- from: DDC-2F-BOH
to: AHU-B.1 (ME Contractor)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 1
AO: 2
notes: ''
- from: DDC-2F-BOH
to: AHU-B.2 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 5
notes: ''
- from: DDC-2F-BOH
to: AHU-B.2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 1
AO: 1
DI: 2
notes: ''
- from: DDC-2F-BOH
to: AHU-B.2 (ME Contractor)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 1
AO: 2
notes: ''
- from: DDC-2F-BOH
to: AHU-B.3 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 5
notes: ''
- from: DDC-2F-BOH
to: AHU-B.3 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 1
AO: 1
DI: 2
notes: ''
- from: DDC-2F-BOH
to: AHU-B.3 (ME Contractor)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 1
AO: 2
notes: ''
- from: DDC-2F-BOH
to: AHU-EL (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 5
notes: ''
- from: DDC-2F-BOH
to: AHU-EL (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 1
AO: 1
DI: 2
notes: ''
- from: DDC-2F-BOH
to: AHU-EL (ME Contractor)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 1
AO: 2
notes: ''
- from: DDC-2F-BOH
to: AHU-FR2 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 5
notes: ''
- from: DDC-2F-BOH
to: AHU-FR2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 1
AO: 1
DI: 2
notes: ''
- from: DDC-2F-BOH
to: AHU-FR2 (ME Contractor)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 1
AO: 2
notes: ''
- from: DDC-2F-BOH
to: AHU-FR3 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 5
notes: ''
- from: DDC-2F-BOH
to: AHU-FR3 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 1
AO: 1
DI: 2
notes: ''
- from: DDC-2F-BOH
to: AHU-FR3 (ME Contractor)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 1
AO: 2
notes: ''
- from: DDC-2F-BOH
to: AHU-PF (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 5
notes: ''
- from: DDC-2F-BOH
to: AHU-PF (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 1
AO: 1
DI: 2
notes: ''
- from: DDC-2F-BOH
to: AHU-PF (ME Contractor)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
by_class:
AI: 1
AO: 2
notes: ''
- from: DDC-2M-CASINO
to: AIR-ION-2M.1 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: casino_2m_localized
system: AC
equipment_class: Air Ionizer (Casino)
by_class:
AI: 1
notes: ''
- from: DDC-2M-CASINO
to: AIR-ION-2M.1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: casino_2m_localized
system: AC
equipment_class: Air Ionizer (Casino)
by_class:
DI: 2
notes: ''
- from: DDC-2M-CASINO
to: AIR-ION-2M.2 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: casino_2m_localized
system: AC
equipment_class: Air Ionizer (Casino)
by_class:
AI: 1
notes: ''
- from: DDC-2M-CASINO
to: AIR-ION-2M.2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: casino_2m_localized
system: AC
equipment_class: Air Ionizer (Casino)
by_class:
DI: 2
notes: ''
- from: DDC-2F-CHILLER
to: CH-1 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: Chiller (Package Water-Cooled)
by_class:
AI: 7
notes: ''
- from: DDC-2F-CHILLER
to: CH-1 (ME Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: Chiller (Package Water-Cooled)
by_class:
DI: 2
notes: ''
- from: DDC-2F-CHILLER
to: CH-2 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: Chiller (Package Water-Cooled)
by_class:
AI: 7
notes: ''
- from: DDC-2F-CHILLER
to: CH-2 (ME Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: Chiller (Package Water-Cooled)
by_class:
DI: 2
notes: ''
- from: DDC-2F-CHILLER
to: CH-3 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: Chiller (Package Water-Cooled)
by_class:
AI: 7
notes: ''
- from: DDC-2F-CHILLER
to: CH-3 (ME Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: Chiller (Package Water-Cooled)
by_class:
DI: 2
notes: ''
- from: DDC-2F-CHILLER
to: CHW-DIFF (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: CHW Bypass Header
by_class:
AI: 2
DI: 1
notes: ''
- from: DDC-2F-CHILLER
to: CHW-RET-HDR (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: CHW Return Main Header
by_class:
AI: 2
notes: ''
- from: DDC-2F-CHILLER
to: CHW-SUP-HDR (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: CHW Supply Main Header
by_class:
AI: 2
notes: ''
- from: DDC-2F-CHILLER
to: COWP-1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: Condenser Water Pump
by_class:
DI: 3
DO: 1
notes: ''
- from: DDC-2F-CHILLER
to: COWP-2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: Condenser Water Pump
by_class:
DI: 3
DO: 1
notes: ''
- from: DDC-2F-CHILLER
to: COWP-3 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: Condenser Water Pump
by_class:
DI: 3
DO: 1
notes: ''
- from: DDC-RD-PLANT
to: CT-1 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: AC
equipment_class: Cooling Tower
by_class:
DI: 3
DO: 1
notes: ''
- from: DDC-RD-PLANT
to: CT-1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: AC
equipment_class: Cooling Tower
by_class:
DI: 2
DO: 1
notes: ''
- from: DDC-RD-PLANT
to: CT-1 (ME Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: AC
equipment_class: Cooling Tower
by_class:
DI: 1
AI: 1
notes: ''
- from: DDC-RD-PLANT
to: CT-2 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: AC
equipment_class: Cooling Tower
by_class:
DI: 3
DO: 1
notes: ''
- from: DDC-RD-PLANT
to: CT-2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: AC
equipment_class: Cooling Tower
by_class:
DI: 2
DO: 1
notes: ''
- from: DDC-RD-PLANT
to: CT-2 (ME Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: AC
equipment_class: Cooling Tower
by_class:
DI: 1
AI: 1
notes: ''
- from: DDC-RD-PLANT
to: CT-3 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: AC
equipment_class: Cooling Tower
by_class:
DI: 3
DO: 1
notes: ''
- from: DDC-RD-PLANT
to: CT-3 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: AC
equipment_class: Cooling Tower
by_class:
DI: 2
DO: 1
notes: ''
- from: DDC-RD-PLANT
to: CT-3 (ME Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: AC
equipment_class: Cooling Tower
by_class:
DI: 1
AI: 1
notes: ''
- from: DDC-RD-PLANT
to: CT-COMMON (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: AC
equipment_class: Cooling Tower (Common)
by_class:
AI: 4
notes: ''
- from: DDC-RD-PLANT
to: CW-HDR (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: AC
equipment_class: Condenser Water Header
by_class:
AI: 2
notes: ''
- from: DDC-2M-CASINO
to: DOAS-2M (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: casino_2m_localized
system: VENT
equipment_class: DOAS Unit (Casino — with CO/VOC)
by_class:
AI: 5
notes: ''
- from: DDC-2M-CASINO
to: DOAS-2M (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: casino_2m_localized
system: VENT
equipment_class: DOAS Unit (Casino — with CO/VOC)
by_class:
DI: 7
AI: 2
notes: ''
- from: DDC-2M-CASINO
to: DOAS-2M (ME Contractor)
method: typical_range
length_m: null
typical_range_key: casino_2m_localized
system: VENT
equipment_class: DOAS Unit (Casino — with CO/VOC)
by_class:
AI: 1
AO: 2
notes: ''
- from: DDC-RD-PLANT
to: DOAS-RD.1 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: VENT
equipment_class: DOAS Unit
by_class:
AI: 6
notes: ''
- from: DDC-RD-PLANT
to: DOAS-RD.1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: VENT
equipment_class: DOAS Unit
by_class:
DI: 8
AI: 2
notes: ''
- from: DDC-RD-PLANT
to: DOAS-RD.1 (ME Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: VENT
equipment_class: DOAS Unit
by_class:
AI: 2
AO: 2
notes: ''
- from: DDC-RD-PLANT
to: DOAS-RD.2 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: VENT
equipment_class: DOAS Unit
by_class:
AI: 6
notes: ''
- from: DDC-RD-PLANT
to: DOAS-RD.2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: VENT
equipment_class: DOAS Unit
by_class:
DI: 8
AI: 2
notes: ''
- from: DDC-RD-PLANT
to: DOAS-RD.2 (ME Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: VENT
equipment_class: DOAS Unit
by_class:
AI: 2
AO: 2
notes: ''
- from: DDC-RD-PLANT
to: EF-1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-2F-BOH
to: EF-2.1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-2F-BOH
to: EF-2.2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-2F-BOH
to: EF-2.3 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-2F-BOH
to: EF-2.4 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-2F-BOH
to: EF-2B.1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-2F-BOH
to: EF-2B.2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-3F
to: EF-3.1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: amenity_3f
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-3F
to: EF-3.2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: amenity_3f
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-3F
to: EF-3.3 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: amenity_3f
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-3F
to: EF-3.4 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: amenity_3f
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-3F
to: EF-3B-G (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: amenity_3f
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-3F
to: EF-3C.1-G (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: amenity_3f
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-B1-BOH
to: EF-B.1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_b1
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-B1-BOH
to: EF-B.2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_b1
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-B1-BOH
to: EF-BR.1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_b1
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-B1-BOH
to: EF-BR.2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_b1
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-B1-BOH
to: EF-BS.1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_b1
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-B1-BOH
to: EF-BS.2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_b1
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-B1-BOH
to: EF-FOST.1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_b1
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-B1-BOH
to: EF-GL.1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_b1
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-B1-BOH
to: EF-GL.2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_b1
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-2F-BOH
to: EF-GS.1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-2F-BOH
to: EF-GS.2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-B1-BOH
to: EF-MFR.1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_b1
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-B1-BOH
to: EF-MP.1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_b1
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-2F-BOH
to: EF-OHRv2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-B1-BOH
to: EF-PR.1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_b1
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-B1-BOH
to: EF-PR.3 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_b1
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-RD-PLANT
to: EF-RD.1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-RD-PLANT
to: EF-RO.2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-B1-BOH
to: EF-WS.1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_b1
system: VENT
equipment_class: Exhaust Fan (General)
by_class:
DI: 3
notes: ''
- from: DDC-RD-PLANT
to: HP-HZ (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: HWL
equipment_class: Heat Pump
by_class:
DI: 3
notes: ''
- from: DDC-LG-PLANT
to: HP-LZ (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: plant_room_lg_boiler_hwl
system: HWL
equipment_class: Heat Pump
by_class:
DI: 3
notes: ''
- from: DDC-RD-PLANT
to: HWH-HZ (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: HWL
equipment_class: Hot Water Header Set
by_class:
AI: 3
notes: ''
- from: DDC-LG-PLANT
to: HWH-LZ (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_lg_boiler_hwl
system: HWL
equipment_class: Hot Water Header Set
by_class:
AI: 3
notes: ''
- from: DDC-RD-PLANT
to: HWT-HZ (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: HWL
equipment_class: Calorifier (Hot Water Storage Tank)
by_class:
AI: 1
notes: ''
- from: DDC-LG-PLANT
to: HWT-LZ (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_lg_boiler_hwl
system: HWL
equipment_class: Calorifier (Hot Water Storage Tank)
by_class:
AI: 1
notes: ''
- from: DDC-B1-BOH
to: PAHU-0.1 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: boh_b1
system: VENT
equipment_class: Precooled Air Handling Unit
by_class:
AI: 3
notes: ''
- from: DDC-B1-BOH
to: PAHU-0.1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_b1
system: VENT
equipment_class: Precooled Air Handling Unit
by_class:
AI: 1
AO: 1
DI: 3
notes: ''
- from: DDC-B1-BOH
to: PAHU-0.1 (ME Contractor)
method: typical_range
length_m: null
typical_range_key: boh_b1
system: VENT
equipment_class: Precooled Air Handling Unit
by_class:
AO: 1
notes: ''
- from: DDC-2F-BOH
to: PAHU-B.1 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Precooled Air Handling Unit
by_class:
AI: 3
notes: ''
- from: DDC-2F-BOH
to: PAHU-B.1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Precooled Air Handling Unit
by_class:
AI: 1
AO: 1
DI: 3
notes: ''
- from: DDC-2F-BOH
to: PAHU-B.1 (ME Contractor)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Precooled Air Handling Unit
by_class:
AO: 1
notes: ''
- from: DDC-2F-BOH
to: PAHU-B.2 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Precooled Air Handling Unit
by_class:
AI: 3
notes: ''
- from: DDC-2F-BOH
to: PAHU-B.2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Precooled Air Handling Unit
by_class:
AI: 1
AO: 1
DI: 3
notes: ''
- from: DDC-2F-BOH
to: PAHU-B.2 (ME Contractor)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Precooled Air Handling Unit
by_class:
AO: 1
notes: ''
- from: DDC-2F-BOH
to: PAHU-B.3 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Precooled Air Handling Unit
by_class:
AI: 3
notes: ''
- from: DDC-2F-BOH
to: PAHU-B.3 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Precooled Air Handling Unit
by_class:
AI: 1
AO: 1
DI: 3
notes: ''
- from: DDC-2F-BOH
to: PAHU-B.3 (ME Contractor)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Precooled Air Handling Unit
by_class:
AO: 1
notes: ''
- from: DDC-2F-BOH
to: PAHU-FR (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Precooled Air Handling Unit
by_class:
AI: 3
notes: ''
- from: DDC-2F-BOH
to: PAHU-FR (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Precooled Air Handling Unit
by_class:
AI: 1
AO: 1
DI: 3
notes: ''
- from: DDC-2F-BOH
to: PAHU-FR (ME Contractor)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Precooled Air Handling Unit
by_class:
AO: 1
notes: ''
- from: DDC-2F-BOH
to: PAHU-PF (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Precooled Air Handling Unit
by_class:
AI: 3
notes: ''
- from: DDC-2F-BOH
to: PAHU-PF (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Precooled Air Handling Unit
by_class:
AI: 1
AO: 1
DI: 3
notes: ''
- from: DDC-2F-BOH
to: PAHU-PF (ME Contractor)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Precooled Air Handling Unit
by_class:
AO: 1
notes: ''
- from: DDC-RD-PLANT
to: PAHU-r.1 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: VENT
equipment_class: Precooled Air Handling Unit
by_class:
AI: 3
notes: ''
- from: DDC-RD-PLANT
to: PAHU-r.1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: VENT
equipment_class: Precooled Air Handling Unit
by_class:
AI: 1
AO: 1
DI: 3
notes: ''
- from: DDC-RD-PLANT
to: PAHU-r.1 (ME Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: VENT
equipment_class: Precooled Air Handling Unit
by_class:
AO: 1
notes: ''
- from: DDC-RD-PLANT
to: PAHU-r.2 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: VENT
equipment_class: Precooled Air Handling Unit
by_class:
AI: 3
notes: ''
- from: DDC-RD-PLANT
to: PAHU-r.2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: VENT
equipment_class: Precooled Air Handling Unit
by_class:
AI: 1
AO: 1
DI: 3
notes: ''
- from: DDC-RD-PLANT
to: PAHU-r.2 (ME Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: VENT
equipment_class: Precooled Air Handling Unit
by_class:
AO: 1
notes: ''
- from: DDC-2F-CHILLER
to: PCHWP-1 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: Primary CHW Pump
by_class:
AI: 1
notes: ''
- from: DDC-2F-CHILLER
to: PCHWP-1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: Primary CHW Pump
by_class:
DI: 3
DO: 1
notes: ''
- from: DDC-2F-CHILLER
to: PCHWP-2 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: Primary CHW Pump
by_class:
AI: 1
notes: ''
- from: DDC-2F-CHILLER
to: PCHWP-2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: Primary CHW Pump
by_class:
DI: 3
DO: 1
notes: ''
- from: DDC-2F-CHILLER
to: PCHWP-3 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: Primary CHW Pump (Standby)
by_class:
DI: 3
DO: 1
notes: ''
- from: DDC-RD-PLANT
to: RP-HZ (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: HWL
equipment_class: Recirculating Pump
by_class:
DI: 3
notes: ''
- from: DDC-LG-PLANT
to: RP-LZ (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: plant_room_lg_boiler_hwl
system: HWL
equipment_class: Recirculating Pump
by_class:
DI: 3
notes: ''
- from: DDC-LG-PLANT
to: SB-1 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_lg_boiler_hwl
system: VENT
equipment_class: Steam Boiler
by_class:
AI: 4
DI: 1
DO: 1
notes: ''
- from: DDC-LG-PLANT
to: SB-1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: plant_room_lg_boiler_hwl
system: VENT
equipment_class: Steam Boiler
by_class:
DI: 2
notes: ''
- from: DDC-LG-PLANT
to: SB-2 (BMS Contractor)
method: typical_range
length_m: null
typical_range_key: plant_room_lg_boiler_hwl
system: VENT
equipment_class: Steam Boiler
by_class:
AI: 4
DI: 1
DO: 1
notes: ''
- from: DDC-LG-PLANT
to: SB-2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: plant_room_lg_boiler_hwl
system: VENT
equipment_class: Steam Boiler
by_class:
DI: 2
notes: ''
- from: DDC-2F-CHILLER
to: SCHWP-1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: Secondary CHW Pump
by_class:
DI: 3
DO: 1
notes: ''
- from: DDC-2F-CHILLER
to: SCHWP-2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: Secondary CHW Pump
by_class:
DI: 3
DO: 1
notes: ''
- from: DDC-2F-CHILLER
to: SCHWP-3 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: Secondary CHW Pump
by_class:
DI: 3
DO: 1
notes: ''
- from: DDC-GF-BOH
to: TEF-1.1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_gf
system: VENT
equipment_class: Exhaust Fan (Toilet)
by_class:
DI: 3
notes: ''
- from: DDC-GF-BOH
to: TEF-1.2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_gf
system: VENT
equipment_class: Exhaust Fan (Toilet)
by_class:
DI: 3
notes: ''
- from: DDC-GF-BOH
to: TEF-1.3 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_gf
system: VENT
equipment_class: Exhaust Fan (Toilet)
by_class:
DI: 3
notes: ''
- from: DDC-GF-BOH
to: TEF-1.4 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_gf
system: VENT
equipment_class: Exhaust Fan (Toilet)
by_class:
DI: 3
notes: ''
- from: DDC-2F-BOH
to: TEF-2.1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Exhaust Fan (Toilet)
by_class:
DI: 3
notes: ''
- from: DDC-2F-BOH
to: TEF-2.2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Exhaust Fan (Toilet)
by_class:
DI: 3
notes: ''
- from: DDC-2F-BOH
to: TEF-2B.3 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Exhaust Fan (Toilet)
by_class:
DI: 3
notes: ''
- from: DDC-3F
to: TEF-30.20 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: amenity_3f
system: VENT
equipment_class: Exhaust Fan (Toilet)
by_class:
DI: 3
notes: ''
- from: DDC-3F
to: TEF-3A.1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: amenity_3f
system: VENT
equipment_class: Exhaust Fan (Toilet)
by_class:
DI: 3
notes: ''
- from: DDC-3F
to: TEF-3A.2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: amenity_3f
system: VENT
equipment_class: Exhaust Fan (Toilet)
by_class:
DI: 3
notes: ''
- from: DDC-3F
to: TEF-3B (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: amenity_3f
system: VENT
equipment_class: Exhaust Fan (Toilet)
by_class:
DI: 3
notes: ''
- from: DDC-3F
to: TEF-3C.1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: amenity_3f
system: VENT
equipment_class: Exhaust Fan (Toilet)
by_class:
DI: 3
notes: ''
- from: DDC-3F
to: TEF-3C.2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: amenity_3f
system: VENT
equipment_class: Exhaust Fan (Toilet)
by_class:
DI: 3
notes: ''
- from: DDC-B1-BOH
to: TEF-B.1 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_b1
system: VENT
equipment_class: Exhaust Fan (Toilet)
by_class:
DI: 3
notes: ''
- from: DDC-B1-BOH
to: TEF-B.2 (Equipment Supplier)
method: typical_range
length_m: null
typical_range_key: boh_b1
system: VENT
equipment_class: Exhaust Fan (Toilet)
by_class:
DI: 3
notes: ''
- from: DDC-2F-CHILLER
to: CH-1 (Network)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: Chiller (Package Water-Cooled)
notes: Network drop
- from: DDC-2F-CHILLER
to: CH-2 (Network)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: Chiller (Package Water-Cooled)
notes: Network drop
- from: DDC-2F-CHILLER
to: CH-3 (Network)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: Chiller (Package Water-Cooled)
notes: Network drop
- from: DDC-2F-CHILLER
to: PCHWP-1 (Network)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: Primary CHW Pump
notes: Network drop
- from: DDC-2F-CHILLER
to: PCHWP-2 (Network)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: Primary CHW Pump
notes: Network drop
- from: DDC-2F-CHILLER
to: SCHWP-1 (Network)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: Secondary CHW Pump
notes: Network drop
- from: DDC-2F-CHILLER
to: SCHWP-2 (Network)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: Secondary CHW Pump
notes: Network drop
- from: DDC-2F-CHILLER
to: SCHWP-3 (Network)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: AC
equipment_class: Secondary CHW Pump
notes: Network drop
- from: DDC-LG-PLANT
to: SB-1 (Network)
method: typical_range
length_m: null
typical_range_key: plant_room_lg_boiler_hwl
system: VENT
equipment_class: Steam Boiler
notes: Network drop
- from: DDC-LG-PLANT
to: SB-2 (Network)
method: typical_range
length_m: null
typical_range_key: plant_room_lg_boiler_hwl
system: VENT
equipment_class: Steam Boiler
notes: Network drop
- from: DDC-RD-PLANT
to: DOAS-RD.1 (Network)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: VENT
equipment_class: DOAS Unit
notes: Network drop
- from: DDC-RD-PLANT
to: DOAS-RD.2 (Network)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: VENT
equipment_class: DOAS Unit
notes: Network drop
- from: DDC-RD-PLANT
to: PAHU-r.1 (Network)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: VENT
equipment_class: Precooled Air Handling Unit
notes: Network drop
- from: DDC-RD-PLANT
to: PAHU-r.2 (Network)
method: typical_range
length_m: null
typical_range_key: plant_room_rd_plant
system: VENT
equipment_class: Precooled Air Handling Unit
notes: Network drop
- from: DDC-2M-CASINO
to: DOAS-2M (Network)
method: typical_range
length_m: null
typical_range_key: casino_2m_localized
system: VENT
equipment_class: DOAS Unit (Casino — with CO/VOC)
notes: Network drop
- from: DDC-2M-CASINO
to: AHU-2M.1 (Network)
method: typical_range
length_m: null
typical_range_key: casino_2m_localized
system: AC
equipment_class: AHU (Chilled-Water-Served)
notes: Network drop
- from: DDC-2M-CASINO
to: AHU-2M.2 (Network)
method: typical_range
length_m: null
typical_range_key: casino_2m_localized
system: AC
equipment_class: AHU (Chilled-Water-Served)
notes: Network drop
- from: DDC-2M-CASINO
to: AIR-ION-2M.1 (Network)
method: typical_range
length_m: null
typical_range_key: casino_2m_localized
system: AC
equipment_class: Air Ionizer (Casino)
notes: Network drop
- from: DDC-2M-CASINO
to: AIR-ION-2M.2 (Network)
method: typical_range
length_m: null
typical_range_key: casino_2m_localized
system: AC
equipment_class: Air Ionizer (Casino)
notes: Network drop
- from: DDC-2F-BOH
to: AHU-B.1 (Network)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
notes: Network drop
- from: DDC-2F-BOH
to: AHU-B.2 (Network)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
notes: Network drop
- from: DDC-2F-BOH
to: AHU-B.3 (Network)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
notes: Network drop
- from: DDC-2F-BOH
to: AHU-PF (Network)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
notes: Network drop
- from: DDC-2F-BOH
to: AHU-EL (Network)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
notes: Network drop
- from: DDC-2F-BOH
to: AHU-FR2 (Network)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
notes: Network drop
- from: DDC-2F-BOH
to: AHU-FR3 (Network)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: AC
equipment_class: AHU (Chilled-Water-Served)
notes: Network drop
- from: DDC-2F-BOH
to: PAHU-B.1 (Network)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Precooled Air Handling Unit
notes: Network drop
- from: DDC-2F-BOH
to: PAHU-B.2 (Network)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Precooled Air Handling Unit
notes: Network drop
- from: DDC-2F-BOH
to: PAHU-B.3 (Network)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Precooled Air Handling Unit
notes: Network drop
- from: DDC-2F-BOH
to: PAHU-PF (Network)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Precooled Air Handling Unit
notes: Network drop
- from: DDC-2F-BOH
to: PAHU-FR (Network)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: VENT
equipment_class: Precooled Air Handling Unit
notes: Network drop
- from: DDC-GF-BOH
to: AHU-1.1 (Network)
method: typical_range
length_m: null
typical_range_key: boh_gf
system: AC
equipment_class: AHU (Chilled-Water-Served)
notes: Network drop
- from: DDC-GF-BOH
to: AHU-1.2 (Network)
method: typical_range
length_m: null
typical_range_key: boh_gf
system: AC
equipment_class: AHU (Chilled-Water-Served)
notes: Network drop
- from: DDC-GF-BOH
to: AHU-1.3 (Network)
method: typical_range
length_m: null
typical_range_key: boh_gf
system: AC
equipment_class: AHU (Chilled-Water-Served)
notes: Network drop
- from: DDC-B1-BOH
to: PAHU-0.1 (Network)
method: typical_range
length_m: null
typical_range_key: boh_b1
system: VENT
equipment_class: Precooled Air Handling Unit
notes: Network drop
- from: DDC-LG-PLANT
to: MPM-MAIN (Network)
method: typical_range
length_m: null
typical_range_key: plant_room_lg_boiler_hwl
system: EL
equipment_class: Multifunction Power Meter (Main)
notes: Network drop
- from: DDC-2F-CHILLER
to: MPM-CHILLER (Network)
method: typical_range
length_m: null
typical_range_key: plant_room_chiller_2f
system: EL
equipment_class: Multifunction Power Meter (Feeder)
notes: Network drop
- from: DDC-2F-BOH
to: MPM-AHU-2F (Network)
method: typical_range
length_m: null
typical_range_key: boh_2f
system: EL
equipment_class: Multifunction Power Meter (Feeder)
notes: Network drop
- from: DDC-GF-BOH
to: MPM-AHU-GF (Network)
method: typical_range
length_m: null
typical_range_key: boh_gf
system: EL
equipment_class: Multifunction Power Meter (Feeder)
notes: Network drop
- from: DDC-LG-PLANT
to: MPM-LIGHT-A (Network)
method: typical_range
length_m: null
typical_range_key: plant_room_lg_boiler_hwl
system: EL
equipment_class: Multifunction Power Meter (Feeder)
notes: Network drop
- from: DDC-LG-PLANT
to: MPM-LIGHT-B (Network)
method: typical_range
length_m: null
typical_range_key: plant_room_lg_boiler_hwl
system: EL
equipment_class: Multifunction Power Meter (Feeder)
notes: Network drop
- from: DDC-GF-BOH
to: FACP-GW (Network)
method: typical_range
length_m: null
typical_range_key: boh_gf
system: FDAS
equipment_class: FACP Gateway
notes: Network drop
- from: Local panelboard / EE-supplied feeder
to: DDC-2F-BOH — BMS panel 240V power feed
method: typical_range
length_m: null
typical_range_key: panel_power_feed_local
notes: Panel power feed
- from: Local panelboard / EE-supplied feeder
to: DDC-2F-CHILLER — BMS panel 240V power feed
method: typical_range
length_m: null
typical_range_key: panel_power_feed_local
notes: Panel power feed
- from: Local panelboard / EE-supplied feeder
to: DDC-2M-CASINO — BMS panel 240V power feed
method: typical_range
length_m: null
typical_range_key: panel_power_feed_local
notes: Panel power feed
- from: Local panelboard / EE-supplied feeder
to: DDC-3F — BMS panel 240V power feed
method: typical_range
length_m: null
typical_range_key: panel_power_feed_local
notes: Panel power feed
- from: Local panelboard / EE-supplied feeder
to: DDC-B1-BOH — BMS panel 240V power feed
method: typical_range
length_m: null
typical_range_key: panel_power_feed_local
notes: Panel power feed
- from: Local panelboard / EE-supplied feeder
to: DDC-GF-BOH — BMS panel 240V power feed
method: typical_range
length_m: null
typical_range_key: panel_power_feed_local
notes: Panel power feed
- from: Local panelboard / EE-supplied feeder
to: DDC-LG-PLANT — BMS panel 240V power feed
method: typical_range
length_m: null
typical_range_key: panel_power_feed_local
notes: Panel power feed
- from: Local panelboard / EE-supplied feeder
to: DDC-RD-PLANT — BMS panel 240V power feed
method: typical_range
length_m: null
typical_range_key: panel_power_feed_local
notes: Panel power feed