Summary

A3 — Cable Schedule, Audit View
ProjectKingsford Hotel Bacolod BMS
Canonical sourceA3-cable-schedule.yaml
How to record correctionsEdit the canonical YAML directly — add a verification: block to the affected row(s)
Totals
Total cables200
Total length (m)6,810
Field cables175
Trunk cables7
Panel power feeds18
Verification status
StatusCount% of total
verified00%
needs_correction00%
uncertain00%
unverified200100%
⚠ Known weak points
Cable lengths are estimates based on assumption A-001 (30 m average panel-to-device run, 80 m trunk per floor). Field-verified lengths typically vary by ±20% per cable. THIS IS THE SYSTEM'S WEAKEST AUTO-GENERATED QUANTITY — please verify before issuing the BOQ to the customer.
How corrections flow
1. Open A3-cable-schedule.yaml in any text editor.
2. Find the affected row by ID (column A in the Detail sheet).
3. Add a verification: block — see the 'Verification schema' sheet for the template.
4. Re-run: python3 _playbook/tools/generate-deliverables.py <project>
5. Corrections flow through B4 manhours, BOQ material costs, and final deliverables automatically.

By Panel

PanelCable countTotal length (m)
PNL-VENT-L327810
PNL-VENT-BSMT16480
PNL-VENT-L213390
PNL-AHU-L212360
PNL-CHWP-GND12360
PNL-CT-RD12360
PNL-CHWP-L211330
PNL-PL-LZ10300
PNL-EE-DIST10300
PNL-CH-PLANT-GND9270
PNL-VENT-GF9270
PNL-DOAS-RD8240
PNL-PAHU-RD8240
PNL-DOAS-L24120
PNL-PL-HZ4120
PNL-BL-LZ4120
PNL-VENT-RD390
PNL-EE-MAIN390
TOTAL (field cables)1755250

By Floor

FloorCable countTotal length (m)
2nd Floor401200
Roofdeck351050
3rd Floor27810
GND21630
Basement16480
Lower Ground14420
Electrical13390
Ground9270
TOTAL1755250

By Cable Type

Cable typeCountTotal length (m)
4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)982940
4C × 1.5 mm² shielded FRLS (BMS signal — sensors)341020
Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)27810
4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)16480

Detail (cables)

IDFromToCable typeLength (m)StatusCorrected (m)Verified byDateDrawing refNotes
C0001PNL-AHU-L2AHU-2M.1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0002PNL-AHU-L2AHU-2M.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0003PNL-AHU-L2AHU-2M.1 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0004PNL-AHU-L2AHU-2M.2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0005PNL-AHU-L2AHU-2M.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0006PNL-AHU-L2AHU-2M.2 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0007PNL-CH-PLANT-GNDCH-1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0008PNL-CH-PLANT-GNDCH-1 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0009PNL-CH-PLANT-GNDCH-2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0010PNL-CH-PLANT-GNDCH-2 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0011PNL-CH-PLANT-GNDCH-3 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0012PNL-CH-PLANT-GNDCH-3 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0013PNL-CHWP-GNDCHWP-1.1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0014PNL-CHWP-GNDCHWP-1.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0015PNL-CHWP-GNDCHWP-1.1 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0016PNL-CHWP-GNDCHWP-1.2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0017PNL-CHWP-GNDCHWP-1.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0018PNL-CHWP-GNDCHWP-1.2 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0019PNL-CHWP-GNDCHWP-1.3 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0020PNL-CHWP-GNDCHWP-1.3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0021PNL-CHWP-GNDCHWP-1.3 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0022PNL-CHWP-L2COMP-1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0023PNL-CHWP-L2COMP-2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0024PNL-CHWP-L2COMP-3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0025PNL-CT-RDCT-1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0026PNL-CT-RDCT-1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0027PNL-CT-RDCT-1 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0028PNL-CT-RDCT-2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0029PNL-CT-RDCT-2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0030PNL-CT-RDCT-2 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0031PNL-CT-RDCT-3 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0032PNL-CT-RDCT-3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0033PNL-CT-RDCT-3 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0034PNL-CT-RDCT-COMMON (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0035PNL-DOAS-L2DOAS-2W (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0036PNL-DOAS-L2DOAS-2W (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0037PNL-DOAS-L2DOAS-2W (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0038PNL-DOAS-RDDOAS-RD.1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0039PNL-DOAS-RDDOAS-RD.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0040PNL-DOAS-RDDOAS-RD.1 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0041PNL-DOAS-RDDOAS-RD.2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0042PNL-DOAS-RDDOAS-RD.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0043PNL-DOAS-RDDOAS-RD.2 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0044PNL-VENT-RDEF-1 (RD) (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0045PNL-VENT-GFEF-1.2A (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0046PNL-VENT-GFEF-1MR.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0047PNL-VENT-GFEF-1ST0.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0048PNL-VENT-L2EF-2.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0049PNL-VENT-L2EF-2.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0050PNL-VENT-L2EF-2.3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0051PNL-VENT-L2EF-2.4 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0052PNL-VENT-L2EF-2B.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0053PNL-VENT-L2EF-2B.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0054PNL-VENT-L3EF-3.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0055PNL-VENT-L3EF-3.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0056PNL-VENT-BSMTEF-3SF.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0057PNL-VENT-BSMTEF-8R.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0058PNL-VENT-BSMTEF-B.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0059PNL-VENT-BSMTEF-B.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0060PNL-VENT-BSMTEF-BS.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0061PNL-VENT-BSMTEF-BS.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0062PNL-VENT-L2EF-CHR.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0063PNL-VENT-L2EF-CHR.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0064PNL-VENT-BSMTEF-GLZ.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0065PNL-VENT-BSMTEF-GLZ.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0066PNL-VENT-L2EF-GS.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0067PNL-VENT-L2EF-GS.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0068PNL-VENT-BSMTEF-HP.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0069PNL-VENT-GFEF-LPG.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0070PNL-VENT-BSMTEF-MC.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0071PNL-VENT-BSMTEF-MFP.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0072PNL-VENT-GFEF-MRF.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0073PNL-VENT-BSMTEF-PR.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0074PNL-VENT-BSMTEF-PR.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0075PNL-VENT-RDEF-RD.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0076PNL-VENT-RDEF-RD.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0077PNL-VENT-BSMTEF-RR.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0078PNL-CHWP-L2HDR-CHW-BP (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0079PNL-CHWP-L2HDR-CHWR (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0080PNL-CHWP-L2HDR-CHWS (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0081PNL-CT-RDHDR-CWR-RD (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0082PNL-CT-RDHDR-CWS-RD (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0083PNL-PL-HZHDR-HW-HZ (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0084PNL-PL-LZHDR-HW-LZ (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0085PNL-PL-LZHP-LZ-1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0086PNL-PL-LZHP-LZ-2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0087PNL-PL-LZHP-LZ-3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0088PNL-PL-HZHWT-HZ-1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0089PNL-PL-HZHWT-HZ-2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0090PNL-PL-HZHWT-HZ-3 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0091PNL-PL-LZHWT-LZ-1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0092PNL-PL-LZHWT-LZ-2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0093PNL-PL-LZHWT-LZ-3 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0094PNL-AHU-L2OZ-2M.1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0095PNL-AHU-L2OZ-2M.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0096PNL-AHU-L2OZ-2M.2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0097PNL-AHU-L2OZ-2M.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0098PNL-PAHU-RDPAHU-RD.1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0099PNL-PAHU-RDPAHU-RD.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0100PNL-PAHU-RDPAHU-RD.1 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0101PNL-PAHU-RDPAHU-RD.2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0102PNL-PAHU-RDPAHU-RD.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0103PNL-PAHU-RDPAHU-RD.2 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0104PNL-CHWP-L2PCHWP-1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0105PNL-CHWP-L2PCHWP-2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0106PNL-CHWP-L2PCHWP-3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0107PNL-CHWP-L2PCHWP-4 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0108PNL-PL-LZRP-LZ-1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0109PNL-PL-LZRP-LZ-2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0110PNL-PL-LZRP-LZ-3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0111PNL-BL-LZSB-1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0112PNL-BL-LZSB-1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0113PNL-BL-LZSB-2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0114PNL-BL-LZSB-2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0115PNL-VENT-GFTEF-1.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0116PNL-VENT-GFTEF-1.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0117PNL-VENT-GFTEF-1.3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0118PNL-VENT-GFTEF-1.4 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0119PNL-VENT-L2TEF-2.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0120PNL-VENT-L2TEF-2.3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0121PNL-VENT-L2TEF-2B.3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0122PNL-VENT-L3TEF-3A.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0123PNL-VENT-L3TEF-3A.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0124PNL-VENT-L3TEF-3B (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0125PNL-VENT-L3TEF-3C.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0126PNL-VENT-L3TEF-3C.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0127PNL-VENT-L3TEF-3D.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0128PNL-VENT-L3TEF-3D.10 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0129PNL-VENT-L3TEF-3D.11 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0130PNL-VENT-L3TEF-3D.12 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0131PNL-VENT-L3TEF-3D.13 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0132PNL-VENT-L3TEF-3D.14 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0133PNL-VENT-L3TEF-3D.15 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0134PNL-VENT-L3TEF-3D.16 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0135PNL-VENT-L3TEF-3D.17 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0136PNL-VENT-L3TEF-3D.18 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0137PNL-VENT-L3TEF-3D.19 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0138PNL-VENT-L3TEF-3D.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0139PNL-VENT-L3TEF-3D.20 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0140PNL-VENT-L3TEF-3D.3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0141PNL-VENT-L3TEF-3D.4 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0142PNL-VENT-L3TEF-3D.5 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0143PNL-VENT-L3TEF-3D.6 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0144PNL-VENT-L3TEF-3D.7 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0145PNL-VENT-L3TEF-3D.8 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0146PNL-VENT-L3TEF-3D.9 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0147PNL-VENT-BSMTTEF-B.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0148PNL-VENT-BSMTTEF-B.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0149PNL-CH-PLANT-GNDCH-1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0150PNL-CH-PLANT-GNDCH-2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0151PNL-CH-PLANT-GNDCH-3 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0152PNL-CHWP-L2BTU-CHWS-MAIN (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0153PNL-CHWP-GNDCHWP-1.1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0154PNL-CHWP-GNDCHWP-1.2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0155PNL-CHWP-GNDCHWP-1.3 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0156PNL-DOAS-L2DOAS-2W (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0157PNL-DOAS-RDDOAS-RD.1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0158PNL-DOAS-RDDOAS-RD.2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0159PNL-AHU-L2AHU-2M.1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0160PNL-AHU-L2AHU-2M.2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0161PNL-PAHU-RDPAHU-RD.1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0162PNL-PAHU-RDPAHU-RD.2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0163PNL-EE-MAINMTR-MAIN-1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0164PNL-EE-MAINMTR-MAIN-2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0165PNL-EE-MAINMTR-MAIN-3 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0166PNL-EE-DISTMTR-FDR-01 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0167PNL-EE-DISTMTR-FDR-02 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0168PNL-EE-DISTMTR-FDR-03 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0169PNL-EE-DISTMTR-FDR-04 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0170PNL-EE-DISTMTR-FDR-05 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0171PNL-EE-DISTMTR-FDR-06 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0172PNL-EE-DISTMTR-FDR-07 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0173PNL-EE-DISTMTR-FDR-08 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0174PNL-EE-DISTMTR-FDR-09 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0175PNL-EE-DISTMTR-FDR-10 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
T0176BMS Server Room (head-end)All BMS panels at 2nd FloorCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80unverified
T0177BMS Server Room (head-end)All BMS panels at 3rd FloorCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80unverified
T0178BMS Server Room (head-end)All BMS panels at BasementCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80unverified
T0179BMS Server Room (head-end)All BMS panels at GroundCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80unverified
T0180BMS Server Room (head-end)All BMS panels at Lower GroundCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80unverified
T0181BMS Server Room (head-end)All BMS panels at RoofdeckCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80unverified
T0182BMS Server Room (head-end)All BMS panel controllers (MS/TP daisy-chain or branched)BACnet MS/TP shielded twisted-pair trunk, 1pr × 22 AWG low-cap540unverified
P0183Local panelboard / EE-supplied feederPNL-AHU-L2 — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30unverified
P0184Local panelboard / EE-supplied feederPNL-BL-LZ — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30unverified
P0185Local panelboard / EE-supplied feederPNL-CH-PLANT-GND — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30unverified
P0186Local panelboard / EE-supplied feederPNL-CHWP-GND — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30unverified
P0187Local panelboard / EE-supplied feederPNL-CHWP-L2 — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30unverified
P0188Local panelboard / EE-supplied feederPNL-CT-RD — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30unverified
P0189Local panelboard / EE-supplied feederPNL-DOAS-L2 — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30unverified
P0190Local panelboard / EE-supplied feederPNL-DOAS-RD — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30unverified
P0191Local panelboard / EE-supplied feederPNL-EE-DIST — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30unverified
P0192Local panelboard / EE-supplied feederPNL-EE-MAIN — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30unverified
P0193Local panelboard / EE-supplied feederPNL-PAHU-RD — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30unverified
P0194Local panelboard / EE-supplied feederPNL-PL-HZ — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30unverified
P0195Local panelboard / EE-supplied feederPNL-PL-LZ — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30unverified
P0196Local panelboard / EE-supplied feederPNL-VENT-BSMT — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30unverified
P0197Local panelboard / EE-supplied feederPNL-VENT-GF — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30unverified
P0198Local panelboard / EE-supplied feederPNL-VENT-L2 — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30unverified
P0199Local panelboard / EE-supplied feederPNL-VENT-L3 — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30unverified
P0200Local panelboard / EE-supplied feederPNL-VENT-RD — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30unverified

Verification schema

How to record verification / corrections in A3-cable-schedule.yaml
Find the affected row in the YAML by ID (Detail sheet column A) and add a verification: block:
- id: C0001
from: PNL-CH-PLANT-GND
to: CH-1 (BMS Contractor)
cable_type: 4C × 1.5 mm² shielded FRLS
length_m: 30
verification: # ADDED by team
status: needs_correction # unverified | verified | needs_correction | uncertain
corrected_length_m: 42 # team's measured / confirmed value
verified_by: J. Cruz
verified_date: 2026-05-10
drawing_ref: "EE-09 grid B-2"
notes: ""
After saving, re-run: python3 _playbook/tools/generate-deliverables.py <project>
Corrections propagate to B4 manhours, BOQ, and final deliverables automatically.
Recommended verification methods (priority order):
1. Site walkthrough with measurement (most accurate; for cable lengths, after structural completion).
2. Properly-scaled architectural drawings.
3. Mechanical contractor's tray layout combined with BMS panel locations.
4. A-001 default with ±20% contingency in BOQ — last resort.