Summary

A2 — Equipment Takeoff Summary
Total instances135
By equipment class
Exhaust Fan (General)34
Exhaust Fan (Toilet)34
Multifunction Power Meter (Feeder)10
Heat Pump6
Calorifier (Hot Water Storage Tank)6
Recirculating Pump6
Chiller (Package Water-Cooled)3
AHU (Chilled-Water-Served)3
Condenser Water Pump3
Cooling Tower3
DOAS Unit3
Multifunction Power Meter (Main)3
Primary CHW Pump3
AHU (Modulating CHW-served)2
Condenser Water Header2
Hot Water Header Set2
Ozone Generator (UV-light or Corona)2
Precooled Air Handling Unit2
Steam Boiler2
BTU Meter1
Cooling Tower (Common)1
CHW Bypass Header1
CHW Return Main Header1
CHW Supply Main Header1
Primary CHW Pump (Standby)1
By location
3rd Amenity & Guestroom27
Basement16
2nd Floor13
2F/CHW Pump Room11
Roofdeck/HW Plant10
Lower Ground/HW Plant10
Distribution (per A4)10
GF Main Lobby9
Roofdeck/Cooling Tower Area6
2nd Level/Casino MVAC Plant5
GND/Chiller Plant Room3
GND/BOH AHU Area3
Roofdeck3
Main Switchgear Room3
Roofdeck/Hotel DOAS Plant2
Roofdeck/PAHU Plant2
Lower Ground/Boiler Room2
By panel
PNL-VENT-L327
PNL-VENT-BSMT16
PNL-VENT-L213
PNL-CHWP-L211
PNL-PL-HZ10
PNL-PL-LZ10
PNL-EE-DIST10
PNL-VENT-GF9
PNL-CT-RD6
PNL-AHU-L24
PNL-CH-PLANT-GND3
PNL-CHWP-GND3
PNL-VENT-RD3
PNL-EE-MAIN3
PNL-DOAS-RD2
PNL-PAHU-RD2
PNL-BL-LZ2
PNL-DOAS-L21

Equipment Takeoff

IDEquipment ClassQuantityLocationSystemPanelPrimary C/OPhysical I/OHLI SubpointsNetwork DropsTotal I/OMake/Model AssumedNetwork TypeTypical SupplierNotes
AHU-2M.1AHU (Modulating CHW-served)12nd Level/Casino MVAC PlantAHU - CasinoPNL-AHU-L2BMS Contractor132116Modulating CHW-served AHU with VFD, modulating valve and dampers (position feedback)Hardwired (VFD via BACnet HLI)Mechanical contractorCasino-spec AHU — modulating actuators with position feedback; CO/CO2 monitoring at return duct.
AHU-2M.2AHU (Modulating CHW-served)12nd Level/Casino MVAC PlantAHU - CasinoPNL-AHU-L2BMS Contractor132116Modulating CHW-served AHU with VFD, modulating valve and dampers (position feedback)Hardwired (VFD via BACnet HLI)Mechanical contractorCasino-spec AHU — modulating actuators with position feedback; CO/CO2 monitoring at return duct.
BTU-CHWS-MAINBTU Meter12F/CHW Pump RoomChilled WaterPNL-CHWP-L2BMS Contractor0314Ultrasonic or insertion-type BTU meter with Modbus output (Onicon, Aichi, Kamstrup)Modbus RTU/TCPBMS contractorSystem-level energy submeter.
CH-1Chiller (Package Water-Cooled)1GND/Chiller Plant RoomChilled WaterPNL-CH-PLANT-GNDEquipment Supplier918128Tier-1 BACnet IP chiller (Trane/York/Carrier/Daikin), water-cooled centrifugal or screw, sized per design cooling loadBACnet/IPMechanical contractor / Equipment supplierBMS reads via chiller's native BACnet gateway. BMS supplies external T-sensors on entering/leaving CHW & CW pipes.
CH-2Chiller (Package Water-Cooled)1GND/Chiller Plant RoomChilled WaterPNL-CH-PLANT-GNDEquipment Supplier918128Tier-1 BACnet IP chiller (Trane/York/Carrier/Daikin), water-cooled centrifugal or screw, sized per design cooling loadBACnet/IPMechanical contractor / Equipment supplierBMS reads via chiller's native BACnet gateway. BMS supplies external T-sensors on entering/leaving CHW & CW pipes.
CH-3Chiller (Package Water-Cooled)1GND/Chiller Plant RoomChilled WaterPNL-CH-PLANT-GNDEquipment Supplier918128Tier-1 BACnet IP chiller (Trane/York/Carrier/Daikin), water-cooled centrifugal or screw, sized per design cooling loadBACnet/IPMechanical contractor / Equipment supplierBMS reads via chiller's native BACnet gateway. BMS supplies external T-sensors on entering/leaving CHW & CW pipes.
CHWP-1.1AHU (Chilled-Water-Served)1GND/BOH AHU AreaBOH Air HandlingPNL-CHWP-GNDEquipment Supplier142117Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
CHWP-1.2AHU (Chilled-Water-Served)1GND/BOH AHU AreaBOH Air HandlingPNL-CHWP-GNDEquipment Supplier142117Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
CHWP-1.3AHU (Chilled-Water-Served)1GND/BOH AHU AreaBOH Air HandlingPNL-CHWP-GNDEquipment Supplier142117Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
COMP-1Condenser Water Pump12F/CHW Pump RoomChilled WaterPNL-CHWP-L2Equipment Supplier4004End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious)HardwiredMechanical contractorBMS reads aux contacts; commands start via DO.
COMP-2Condenser Water Pump12F/CHW Pump RoomChilled WaterPNL-CHWP-L2Equipment Supplier4004End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious)HardwiredMechanical contractorBMS reads aux contacts; commands start via DO.
COMP-3Condenser Water Pump12F/CHW Pump RoomChilled WaterPNL-CHWP-L2Equipment Supplier4004End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious)HardwiredMechanical contractorBMS reads aux contacts; commands start via DO.
CT-1Cooling Tower1Roofdeck/Cooling Tower AreaChilled WaterPNL-CT-RDBMS Contractor9009Induced-draft counterflow open cooling tower (Marley/BAC/EVAPCO), sized per condenser water flowHardwiredMechanical contractor / Equipment supplierBMS supplies basin level sensors and condenser water header T-sensors.
CT-2Cooling Tower1Roofdeck/Cooling Tower AreaChilled WaterPNL-CT-RDBMS Contractor9009Induced-draft counterflow open cooling tower (Marley/BAC/EVAPCO), sized per condenser water flowHardwiredMechanical contractor / Equipment supplierBMS supplies basin level sensors and condenser water header T-sensors.
CT-3Cooling Tower1Roofdeck/Cooling Tower AreaChilled WaterPNL-CT-RDBMS Contractor9009Induced-draft counterflow open cooling tower (Marley/BAC/EVAPCO), sized per condenser water flowHardwiredMechanical contractor / Equipment supplierBMS supplies basin level sensors and condenser water header T-sensors.
CT-COMMONCooling Tower (Common)1Roofdeck/Cooling Tower AreaChilled WaterPNL-CT-RDBMS Contractor2002Common BMS sensors at cooling tower area (OA T/RH, condenser headers)HardwiredBMS contractorField instrumentation only — no equipment per se.
DOAS-2WDOAS Unit12nd Level/Casino MVAC PlantDOAS - Casino MVACPNL-DOAS-L2Equipment Supplier214126Dedicated Outdoor Air System with energy recovery wheel, supply + exhaust fans, CHW coilBACnet/IPMechanical contractor / Equipment supplierNative BACnet controller typical. BMS supplies external sensors (OA T/RH/Flow, indoor T/RH, exhaust T) and modulating valve actuator.
DOAS-RD.1DOAS Unit1Roofdeck/Hotel DOAS PlantDOAS - Hotel/RoofdeckPNL-DOAS-RDEquipment Supplier214126Dedicated Outdoor Air System with energy recovery wheel, supply + exhaust fans, CHW coilBACnet/IPMechanical contractor / Equipment supplierNative BACnet controller typical. BMS supplies external sensors (OA T/RH/Flow, indoor T/RH, exhaust T) and modulating valve actuator.
DOAS-RD.2DOAS Unit1Roofdeck/Hotel DOAS PlantDOAS - Hotel/RoofdeckPNL-DOAS-RDEquipment Supplier214126Dedicated Outdoor Air System with energy recovery wheel, supply + exhaust fans, CHW coilBACnet/IPMechanical contractor / Equipment supplierNative BACnet controller typical. BMS supplies external sensors (OA T/RH/Flow, indoor T/RH, exhaust T) and modulating valve actuator.
EF-1 (RD)Exhaust Fan (General)1RoofdeckGeneral VentilationPNL-VENT-RDEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-1.2AExhaust Fan (General)1GF Main LobbyGeneral VentilationPNL-VENT-GFEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-1MR.1Exhaust Fan (General)1GF Main LobbyGeneral VentilationPNL-VENT-GFEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-1ST0.1Exhaust Fan (General)1GF Main LobbyGeneral VentilationPNL-VENT-GFEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-2.1Exhaust Fan (General)12nd FloorGeneral VentilationPNL-VENT-L2Equipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-2.2Exhaust Fan (General)12nd FloorGeneral VentilationPNL-VENT-L2Equipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-2.3Exhaust Fan (General)12nd FloorGeneral VentilationPNL-VENT-L2Equipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-2.4Exhaust Fan (General)12nd FloorGeneral VentilationPNL-VENT-L2Equipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-2B.1Exhaust Fan (General)12nd FloorGeneral VentilationPNL-VENT-L2Equipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-2B.2Exhaust Fan (General)12nd FloorGeneral VentilationPNL-VENT-L2Equipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-3.1Exhaust Fan (General)13rd Amenity & GuestroomGeneral VentilationPNL-VENT-L3Equipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-3.2Exhaust Fan (General)13rd Amenity & GuestroomGeneral VentilationPNL-VENT-L3Equipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-3SF.2Exhaust Fan (General)1BasementGeneral VentilationPNL-VENT-BSMTEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-8R.1Exhaust Fan (General)1BasementGeneral VentilationPNL-VENT-BSMTEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-B.1Exhaust Fan (General)1BasementGeneral VentilationPNL-VENT-BSMTEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-B.2Exhaust Fan (General)1BasementGeneral VentilationPNL-VENT-BSMTEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-BS.1Exhaust Fan (General)1BasementGeneral VentilationPNL-VENT-BSMTEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-BS.2Exhaust Fan (General)1BasementGeneral VentilationPNL-VENT-BSMTEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-CHR.1Exhaust Fan (General)12nd FloorGeneral VentilationPNL-VENT-L2Equipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-CHR.2Exhaust Fan (General)12nd FloorGeneral VentilationPNL-VENT-L2Equipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-GLZ.1Exhaust Fan (General)1BasementGeneral VentilationPNL-VENT-BSMTEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-GLZ.2Exhaust Fan (General)1BasementGeneral VentilationPNL-VENT-BSMTEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-GS.1Exhaust Fan (General)12nd FloorGeneral VentilationPNL-VENT-L2Equipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-GS.2Exhaust Fan (General)12nd FloorGeneral VentilationPNL-VENT-L2Equipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-HP.1Exhaust Fan (General)1BasementGeneral VentilationPNL-VENT-BSMTEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-LPG.1Exhaust Fan (General)1GF Main LobbyGeneral VentilationPNL-VENT-GFEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-MC.1Exhaust Fan (General)1BasementGeneral VentilationPNL-VENT-BSMTEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-MFP.1Exhaust Fan (General)1BasementGeneral VentilationPNL-VENT-BSMTEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-MRF.1Exhaust Fan (General)1GF Main LobbyGeneral VentilationPNL-VENT-GFEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-PR.1Exhaust Fan (General)1BasementGeneral VentilationPNL-VENT-BSMTEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-PR.2Exhaust Fan (General)1BasementGeneral VentilationPNL-VENT-BSMTEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-RD.1Exhaust Fan (General)1RoofdeckGeneral VentilationPNL-VENT-RDEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-RD.2Exhaust Fan (General)1RoofdeckGeneral VentilationPNL-VENT-RDEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-RR.2Exhaust Fan (General)1BasementGeneral VentilationPNL-VENT-BSMTEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
HDR-CHW-BPCHW Bypass Header12F/CHW Pump RoomChilled WaterPNL-CHWP-L2BMS Contractor4004BMS dP/dT sensors + motorized bypass valve (BMS-supplied)HardwiredBMS contractorBMS controls bypass valve to maintain CHW differential.
HDR-CHWRCHW Return Main Header12F/CHW Pump RoomChilled WaterPNL-CHWP-L2BMS Contractor2002BMS T+P sensors on CHW return manifoldHardwiredBMS contractorField instrumentation only.
HDR-CHWSCHW Supply Main Header12F/CHW Pump RoomChilled WaterPNL-CHWP-L2BMS Contractor2002BMS T+P sensors on CHW supply manifoldHardwiredBMS contractorField instrumentation only.
HDR-CWR-RDCondenser Water Header1Roofdeck/Cooling Tower AreaChilled WaterPNL-CT-RDBMS Contractor1001BMS T sensors on condenser water headers at roofdeckHardwiredBMS contractorField instrumentation only.
HDR-CWS-RDCondenser Water Header1Roofdeck/Cooling Tower AreaChilled WaterPNL-CT-RDBMS Contractor1001BMS T sensors on condenser water headers at roofdeckHardwiredBMS contractorField instrumentation only.
HDR-HW-HZHot Water Header Set1Roofdeck/HW PlantPlumbing & Sanitary HotwaterPNL-PL-HZBMS Contractor3003Hot water supply/return manifolds with BMS T sensors and make-up cold water T sensorHardwiredBMS contractorField instrumentation on existing piping.
HDR-HW-LZHot Water Header Set1Lower Ground/HW PlantPlumbing & Sanitary HotwaterPNL-PL-LZBMS Contractor3003Hot water supply/return manifolds with BMS T sensors and make-up cold water T sensorHardwiredBMS contractorField instrumentation on existing piping.
HP-HZ-1Heat Pump1Roofdeck/HW PlantPlumbing & Sanitary HotwaterPNL-PL-HZEquipment Supplier0303Air-source or water-source heat pump for hot water heatingHardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractor / Equipment supplierBMS reads pump status/HOA/trip via aux contacts.
HP-HZ-2Heat Pump1Roofdeck/HW PlantPlumbing & Sanitary HotwaterPNL-PL-HZEquipment Supplier0303Air-source or water-source heat pump for hot water heatingHardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractor / Equipment supplierBMS reads pump status/HOA/trip via aux contacts.
HP-HZ-3Heat Pump1Roofdeck/HW PlantPlumbing & Sanitary HotwaterPNL-PL-HZEquipment Supplier0303Air-source or water-source heat pump for hot water heatingHardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractor / Equipment supplierBMS reads pump status/HOA/trip via aux contacts.
HP-LZ-1Heat Pump1Lower Ground/HW PlantPlumbing & Sanitary HotwaterPNL-PL-LZEquipment Supplier3003Air-source or water-source heat pump for hot water heatingHardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractor / Equipment supplierBMS reads pump status/HOA/trip via aux contacts.
HP-LZ-2Heat Pump1Lower Ground/HW PlantPlumbing & Sanitary HotwaterPNL-PL-LZEquipment Supplier3003Air-source or water-source heat pump for hot water heatingHardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractor / Equipment supplierBMS reads pump status/HOA/trip via aux contacts.
HP-LZ-3Heat Pump1Lower Ground/HW PlantPlumbing & Sanitary HotwaterPNL-PL-LZEquipment Supplier3003Air-source or water-source heat pump for hot water heatingHardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractor / Equipment supplierBMS reads pump status/HOA/trip via aux contacts.
HWT-HZ-1Calorifier (Hot Water Storage Tank)1Roofdeck/HW PlantPlumbing & Sanitary HotwaterPNL-PL-HZBMS Contractor1001Pressurised hot-water storage tank with internal coil, sized per design hot water demandHardwiredPlumbing contractorBMS supplies tank temperature sensor (immersion or strapped probe).
HWT-HZ-2Calorifier (Hot Water Storage Tank)1Roofdeck/HW PlantPlumbing & Sanitary HotwaterPNL-PL-HZBMS Contractor1001Pressurised hot-water storage tank with internal coil, sized per design hot water demandHardwiredPlumbing contractorBMS supplies tank temperature sensor (immersion or strapped probe).
HWT-HZ-3Calorifier (Hot Water Storage Tank)1Roofdeck/HW PlantPlumbing & Sanitary HotwaterPNL-PL-HZBMS Contractor1001Pressurised hot-water storage tank with internal coil, sized per design hot water demandHardwiredPlumbing contractorBMS supplies tank temperature sensor (immersion or strapped probe).
HWT-LZ-1Calorifier (Hot Water Storage Tank)1Lower Ground/HW PlantPlumbing & Sanitary HotwaterPNL-PL-LZBMS Contractor1001Pressurised hot-water storage tank with internal coil, sized per design hot water demandHardwiredPlumbing contractorBMS supplies tank temperature sensor (immersion or strapped probe).
HWT-LZ-2Calorifier (Hot Water Storage Tank)1Lower Ground/HW PlantPlumbing & Sanitary HotwaterPNL-PL-LZBMS Contractor1001Pressurised hot-water storage tank with internal coil, sized per design hot water demandHardwiredPlumbing contractorBMS supplies tank temperature sensor (immersion or strapped probe).
HWT-LZ-3Calorifier (Hot Water Storage Tank)1Lower Ground/HW PlantPlumbing & Sanitary HotwaterPNL-PL-LZBMS Contractor1001Pressurised hot-water storage tank with internal coil, sized per design hot water demandHardwiredPlumbing contractorBMS supplies tank temperature sensor (immersion or strapped probe).
MTR-FDR-01Multifunction Power Meter (Feeder)1Distribution (per A4)Power MeteringPNL-EE-DISTBMS Contractor0516Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
MTR-FDR-02Multifunction Power Meter (Feeder)1Distribution (per A4)Power MeteringPNL-EE-DISTBMS Contractor0516Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
MTR-FDR-03Multifunction Power Meter (Feeder)1Distribution (per A4)Power MeteringPNL-EE-DISTBMS Contractor0516Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
MTR-FDR-04Multifunction Power Meter (Feeder)1Distribution (per A4)Power MeteringPNL-EE-DISTBMS Contractor0516Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
MTR-FDR-05Multifunction Power Meter (Feeder)1Distribution (per A4)Power MeteringPNL-EE-DISTBMS Contractor0516Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
MTR-FDR-06Multifunction Power Meter (Feeder)1Distribution (per A4)Power MeteringPNL-EE-DISTBMS Contractor0516Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
MTR-FDR-07Multifunction Power Meter (Feeder)1Distribution (per A4)Power MeteringPNL-EE-DISTBMS Contractor0516Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
MTR-FDR-08Multifunction Power Meter (Feeder)1Distribution (per A4)Power MeteringPNL-EE-DISTBMS Contractor0516Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
MTR-FDR-09Multifunction Power Meter (Feeder)1Distribution (per A4)Power MeteringPNL-EE-DISTBMS Contractor0516Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
MTR-FDR-10Multifunction Power Meter (Feeder)1Distribution (per A4)Power MeteringPNL-EE-DISTBMS Contractor0516Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
MTR-MAIN-1Multifunction Power Meter (Main)1Main Switchgear RoomPower MeteringPNL-EE-MAINBMS Contractor0516Multifunction power meter with Modbus output (Schneider PM-series, ABB M2M, Siemens SENTRON), main switchgear classModbus RTU/TCPBMS contractorMounted in main switchgear or on dedicated BMS-side panel.
MTR-MAIN-2Multifunction Power Meter (Main)1Main Switchgear RoomPower MeteringPNL-EE-MAINBMS Contractor0516Multifunction power meter with Modbus output (Schneider PM-series, ABB M2M, Siemens SENTRON), main switchgear classModbus RTU/TCPBMS contractorMounted in main switchgear or on dedicated BMS-side panel.
MTR-MAIN-3Multifunction Power Meter (Main)1Main Switchgear RoomPower MeteringPNL-EE-MAINBMS Contractor0516Multifunction power meter with Modbus output (Schneider PM-series, ABB M2M, Siemens SENTRON), main switchgear classModbus RTU/TCPBMS contractorMounted in main switchgear or on dedicated BMS-side panel.
OZ-2M.1Ozone Generator (UV-light or Corona)12nd Level/Casino MVAC PlantAHU - Casino (Ozonizer)PNL-AHU-L2Equipment Supplier3003UV-light or corona-discharge ozone generator (paired with Casino AHU)HardwiredEquipment supplierCasino-specific air-treatment device. BMS monitors status/trip and reads VOC sensor (BMS-supplied).
OZ-2M.2Ozone Generator (UV-light or Corona)12nd Level/Casino MVAC PlantAHU - Casino (Ozonizer)PNL-AHU-L2Equipment Supplier3003UV-light or corona-discharge ozone generator (paired with Casino AHU)HardwiredEquipment supplierCasino-specific air-treatment device. BMS monitors status/trip and reads VOC sensor (BMS-supplied).
PAHU-RD.1Precooled Air Handling Unit1Roofdeck/PAHU PlantPAHU - RoofdeckPNL-PAHU-RDEquipment Supplier112114Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust pathHardwired (VFD via BACnet HLI)Mechanical contractor / Equipment supplierPrecool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors.
PAHU-RD.2Precooled Air Handling Unit1Roofdeck/PAHU PlantPAHU - RoofdeckPNL-PAHU-RDEquipment Supplier112114Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust pathHardwired (VFD via BACnet HLI)Mechanical contractor / Equipment supplierPrecool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors.
PCHWP-1Primary CHW Pump12F/CHW Pump RoomChilled WaterPNL-CHWP-L2Equipment Supplier5005End-suction or split-case centrifugal with VFD, sized per design CHW flowHardwired (BMS reads VFD via BACnet HLI)Mechanical contractorVFD typically Equipment Supplier provided with BACnet card.
PCHWP-2Primary CHW Pump12F/CHW Pump RoomChilled WaterPNL-CHWP-L2Equipment Supplier5005End-suction or split-case centrifugal with VFD, sized per design CHW flowHardwired (BMS reads VFD via BACnet HLI)Mechanical contractorVFD typically Equipment Supplier provided with BACnet card.
PCHWP-3Primary CHW Pump12F/CHW Pump RoomChilled WaterPNL-CHWP-L2Equipment Supplier5005End-suction or split-case centrifugal with VFD, sized per design CHW flowHardwired (BMS reads VFD via BACnet HLI)Mechanical contractorVFD typically Equipment Supplier provided with BACnet card.
PCHWP-4Primary CHW Pump (Standby)12F/CHW Pump RoomChilled WaterPNL-CHWP-L2Equipment Supplier5005Same as Primary CHW Pump (1 standby for N+1 redundancy)Hardwired (BMS reads VFD via BACnet HLI)Mechanical contractorStandby unit per A-CHW-001.
RP-HZ-1Recirculating Pump1Roofdeck/HW PlantPlumbing & Sanitary HotwaterPNL-PL-HZEquipment Supplier0303Hot water recirculating pump, fixed-speed (typical for hotwater systems)Hardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractorBMS reads aux contacts only.
RP-HZ-2Recirculating Pump1Roofdeck/HW PlantPlumbing & Sanitary HotwaterPNL-PL-HZEquipment Supplier0303Hot water recirculating pump, fixed-speed (typical for hotwater systems)Hardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractorBMS reads aux contacts only.
RP-HZ-3Recirculating Pump1Roofdeck/HW PlantPlumbing & Sanitary HotwaterPNL-PL-HZEquipment Supplier0303Hot water recirculating pump, fixed-speed (typical for hotwater systems)Hardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractorBMS reads aux contacts only.
RP-LZ-1Recirculating Pump1Lower Ground/HW PlantPlumbing & Sanitary HotwaterPNL-PL-LZEquipment Supplier3003Hot water recirculating pump, fixed-speed (typical for hotwater systems)Hardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractorBMS reads aux contacts only.
RP-LZ-2Recirculating Pump1Lower Ground/HW PlantPlumbing & Sanitary HotwaterPNL-PL-LZEquipment Supplier3003Hot water recirculating pump, fixed-speed (typical for hotwater systems)Hardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractorBMS reads aux contacts only.
RP-LZ-3Recirculating Pump1Lower Ground/HW PlantPlumbing & Sanitary HotwaterPNL-PL-LZEquipment Supplier3003Hot water recirculating pump, fixed-speed (typical for hotwater systems)Hardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractorBMS reads aux contacts only.
SB-1Steam Boiler1Lower Ground/Boiler RoomBoiler/LaundryPNL-BL-LZEquipment Supplier160016Fire-tube steam boiler with multi-stage burner, fuel-oil fired (typical for hotel laundry)HardwiredMechanical contractor / Equipment supplierBMS supplies steam pressure, feedwater T, fluegas T+O2 sensors. Boiler equipment provides aux contacts for status/HOA/trip points.
SB-2Steam Boiler1Lower Ground/Boiler RoomBoiler/LaundryPNL-BL-LZEquipment Supplier160016Fire-tube steam boiler with multi-stage burner, fuel-oil fired (typical for hotel laundry)HardwiredMechanical contractor / Equipment supplierBMS supplies steam pressure, feedwater T, fluegas T+O2 sensors. Boiler equipment provides aux contacts for status/HOA/trip points.
TEF-1.1Exhaust Fan (Toilet)1GF Main LobbyGeneral VentilationPNL-VENT-GFEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-1.2Exhaust Fan (Toilet)1GF Main LobbyGeneral VentilationPNL-VENT-GFEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-1.3Exhaust Fan (Toilet)1GF Main LobbyGeneral VentilationPNL-VENT-GFEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-1.4Exhaust Fan (Toilet)1GF Main LobbyGeneral VentilationPNL-VENT-GFEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-2.1Exhaust Fan (Toilet)12nd FloorGeneral VentilationPNL-VENT-L2Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-2.3Exhaust Fan (Toilet)12nd FloorGeneral VentilationPNL-VENT-L2Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-2B.3Exhaust Fan (Toilet)12nd FloorGeneral VentilationPNL-VENT-L2Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3A.1Exhaust Fan (Toilet)13rd Amenity & GuestroomGeneral VentilationPNL-VENT-L3Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3A.2Exhaust Fan (Toilet)13rd Amenity & GuestroomGeneral VentilationPNL-VENT-L3Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3BExhaust Fan (Toilet)13rd Amenity & GuestroomGeneral VentilationPNL-VENT-L3Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3C.1Exhaust Fan (Toilet)13rd Amenity & GuestroomGeneral VentilationPNL-VENT-L3Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3C.2Exhaust Fan (Toilet)13rd Amenity & GuestroomGeneral VentilationPNL-VENT-L3Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.1Exhaust Fan (Toilet)13rd Amenity & GuestroomGeneral VentilationPNL-VENT-L3Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.10Exhaust Fan (Toilet)13rd Amenity & GuestroomGeneral VentilationPNL-VENT-L3Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.11Exhaust Fan (Toilet)13rd Amenity & GuestroomGeneral VentilationPNL-VENT-L3Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.12Exhaust Fan (Toilet)13rd Amenity & GuestroomGeneral VentilationPNL-VENT-L3Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.13Exhaust Fan (Toilet)13rd Amenity & GuestroomGeneral VentilationPNL-VENT-L3Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.14Exhaust Fan (Toilet)13rd Amenity & GuestroomGeneral VentilationPNL-VENT-L3Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.15Exhaust Fan (Toilet)13rd Amenity & GuestroomGeneral VentilationPNL-VENT-L3Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.16Exhaust Fan (Toilet)13rd Amenity & GuestroomGeneral VentilationPNL-VENT-L3Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.17Exhaust Fan (Toilet)13rd Amenity & GuestroomGeneral VentilationPNL-VENT-L3Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.18Exhaust Fan (Toilet)13rd Amenity & GuestroomGeneral VentilationPNL-VENT-L3Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.19Exhaust Fan (Toilet)13rd Amenity & GuestroomGeneral VentilationPNL-VENT-L3Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.2Exhaust Fan (Toilet)13rd Amenity & GuestroomGeneral VentilationPNL-VENT-L3Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.20Exhaust Fan (Toilet)13rd Amenity & GuestroomGeneral VentilationPNL-VENT-L3Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.3Exhaust Fan (Toilet)13rd Amenity & GuestroomGeneral VentilationPNL-VENT-L3Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.4Exhaust Fan (Toilet)13rd Amenity & GuestroomGeneral VentilationPNL-VENT-L3Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.5Exhaust Fan (Toilet)13rd Amenity & GuestroomGeneral VentilationPNL-VENT-L3Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.6Exhaust Fan (Toilet)13rd Amenity & GuestroomGeneral VentilationPNL-VENT-L3Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.7Exhaust Fan (Toilet)13rd Amenity & GuestroomGeneral VentilationPNL-VENT-L3Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.8Exhaust Fan (Toilet)13rd Amenity & GuestroomGeneral VentilationPNL-VENT-L3Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.9Exhaust Fan (Toilet)13rd Amenity & GuestroomGeneral VentilationPNL-VENT-L3Equipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-B.1Exhaust Fan (Toilet)1BasementGeneral VentilationPNL-VENT-BSMTEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-B.2Exhaust Fan (Toilet)1BasementGeneral VentilationPNL-VENT-BSMTEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.