Summary

A1 — Consolidated I/O List Summary
ProjectKingsford Hotel Bacolod BMS
Total I/O rows716
By type
DI348
HLI166
AI126
AO29
Network27
DO20
By C/O
Equipment Supplier447
BMS Contractor215
ME Contractor54
By system
General Ventilation204
Chilled Water159
Power Metering78
DOAS - Hotel/Roofdeck52
BOH Air Handling51
Plumbing & Sanitary Hotwater48
Boiler/Laundry32
AHU - Casino32
PAHU - Roofdeck28
DOAS - Casino MVAC26
AHU - Casino (Ozonizer)6
By panel
PNL-CH-PLANT-GND84
PNL-VENT-L381
PNL-EE-DIST60
PNL-DOAS-RD52
PNL-CHWP-GND51
PNL-VENT-BSMT48
PNL-CHWP-L244
PNL-VENT-L239
PNL-AHU-L238
PNL-BL-LZ32
PNL-CT-RD31
PNL-PAHU-RD28
PNL-VENT-GF27
PNL-DOAS-L226
PNL-PL-LZ24
PNL-PL-HZ24
PNL-EE-MAIN18
PNL-VENT-RD9

All IO Points

IDSystemEquipment ClassEquipment InstanceLocationPoint DescriptionTypeField DeviceC/ODoO RefPanelSourceNotes
chws.ch-1.networkChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomBACnet/IP gateway from chiller controllerNetwork-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-1..36PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller Room1 network drop per chiller; chiller native BACnet
chws.ch-1.entering-chw-tempChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomEntering Chilled Water TemperatureAITemperature Sensor (immersion/thermowell)BMS ContractorBMS-03/Package Water Chiller P&ID/MR-11PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller Room
chws.ch-1.leaving-chw-tempChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomLeaving Chilled Water TemperatureAITemperature Sensor (immersion/thermowell)BMS ContractorBMS-03/Package Water Chiller P&ID/MR-12PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller Room
chws.ch-1.entering-cw-tempChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomEntering Condenser Water TemperatureAITemperature Sensor (immersion/thermowell)BMS ContractorBMS-03/Package Water Chiller P&ID/MR-21PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller Room
chws.ch-1.leaving-cw-tempChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomLeaving Condenser Water TemperatureAITemperature Sensor (immersion/thermowell)BMS ContractorBMS-03/Package Water Chiller P&ID/MR-22PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller Room
chws.ch-1.chw-supply-flowChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomChilled Water Supply Flow MeteringAIFlow Sensor (insertion or in-line)BMS ContractorBMS-03/Package Water Chiller P&IDPNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomPer-chiller branch flow
chws.ch-1.chw-return-flowChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomChilled Water Return Flow MeteringAIFlow Sensor (insertion or in-line)BMS ContractorBMS-03/Package Water Chiller P&IDPNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomPer-chiller branch flow
chws.ch-1.cw-supply-flowChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomCondenser Water Supply Flow MeteringAIFlow Sensor (insertion or in-line)BMS ContractorBMS-03/Package Water Chiller P&IDPNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomPer-chiller condenser branch flow
chws.ch-1.iso-vlv-chw-rsChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomIsolation Motorized Valve Status — CHW Return & SupplyDIElectric Valve Actuator (limit switch)ME ContractorBMS-03/Package Water Chiller P&ID/MR-9PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomValves supplied by ME; status DI to BMS
chws.ch-1.iso-vlv-cw-rsChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomIsolation Motorized Valve Status — COW Return & SupplyDIElectric Valve Actuator (limit switch)ME ContractorBMS-03/Package Water Chiller P&ID/MR-10PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomValves supplied by ME; status DI to BMS
chws.ch-1.evap-approach-dtChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomEvaporator Approach Delta TemperatureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-13PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet; sub-point of chws.ch-1.network
chws.ch-1.evap-approach-dpChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomEvaporator Approach Delta PressureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-14PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-1.evap-refrig-pressChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomEvaporator Refrigerant PressureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-15PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-1.evap-refrig-tempChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomEvaporator Refrigerant TemperatureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-16PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-1.cond-refrig-pressChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomCondenser Refrigerant PressureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-17PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-1.cond-refrig-tempChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomCondenser Refrigerant TemperatureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-18PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-1.cond-approach-dtChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomCondenser Approach Delta TemperatureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-19PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-1.cond-approach-dpChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomCondenser Approach Delta PressureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-20PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-1.oil-sump-pressChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomOil Sump PressureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-7PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-1.oil-sump-tempChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomOil Sump TemperatureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-8PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-1.oil-pump-statusChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomOil Pump Status (ON/OFF)HLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-6PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-1.oil-pump-tripChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomOil Pump Trip StatusHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/Alarm-2PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-1.compressor-onoffChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomChiller Compressor Pump On/Off StatusHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-1PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-1.compressor-hoaChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomChiller Compressor Hand/Off/Auto StatusHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-2PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-1.compressor-tripChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomChiller Compressor Trip Alarm StatusHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/Alarm-1PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-1.motor-load-currentChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomMotor Load CurrentHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-3PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-1.motor-consumptionChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomMotor Consumption (KW-Hr / BTU Monitoring)HLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-4PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-1.winding-tempChilled WaterChiller (Package Water-Cooled)CH-1GND/Chiller Plant RoomWinding TemperatureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-5PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-2.networkChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomBACnet/IP gateway from chiller controllerNetwork-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-1..36PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller Room
chws.ch-2.entering-chw-tempChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomEntering Chilled Water TemperatureAITemperature Sensor (immersion/thermowell)BMS ContractorBMS-03/Package Water Chiller P&ID/MR-11PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller Room
chws.ch-2.leaving-chw-tempChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomLeaving Chilled Water TemperatureAITemperature Sensor (immersion/thermowell)BMS ContractorBMS-03/Package Water Chiller P&ID/MR-12PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller Room
chws.ch-2.entering-cw-tempChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomEntering Condenser Water TemperatureAITemperature Sensor (immersion/thermowell)BMS ContractorBMS-03/Package Water Chiller P&ID/MR-21PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller Room
chws.ch-2.leaving-cw-tempChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomLeaving Condenser Water TemperatureAITemperature Sensor (immersion/thermowell)BMS ContractorBMS-03/Package Water Chiller P&ID/MR-22PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller Room
chws.ch-2.chw-supply-flowChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomChilled Water Supply Flow MeteringAIFlow Sensor (insertion or in-line)BMS ContractorBMS-03/Package Water Chiller P&IDPNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomPer-chiller branch flow
chws.ch-2.chw-return-flowChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomChilled Water Return Flow MeteringAIFlow Sensor (insertion or in-line)BMS ContractorBMS-03/Package Water Chiller P&IDPNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomPer-chiller branch flow
chws.ch-2.cw-supply-flowChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomCondenser Water Supply Flow MeteringAIFlow Sensor (insertion or in-line)BMS ContractorBMS-03/Package Water Chiller P&IDPNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomPer-chiller condenser branch flow
chws.ch-2.iso-vlv-chw-rsChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomIsolation Motorized Valve Status — CHW Return & SupplyDIElectric Valve Actuator (limit switch)ME ContractorBMS-03/Package Water Chiller P&ID/MR-9PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomValves supplied by ME; status DI to BMS
chws.ch-2.iso-vlv-cw-rsChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomIsolation Motorized Valve Status — COW Return & SupplyDIElectric Valve Actuator (limit switch)ME ContractorBMS-03/Package Water Chiller P&ID/MR-10PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomValves supplied by ME; status DI to BMS
chws.ch-2.evap-approach-dtChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomEvaporator Approach Delta TemperatureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-13PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-2.evap-approach-dpChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomEvaporator Approach Delta PressureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-14PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-2.evap-refrig-pressChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomEvaporator Refrigerant PressureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-15PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-2.evap-refrig-tempChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomEvaporator Refrigerant TemperatureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-16PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-2.cond-refrig-pressChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomCondenser Refrigerant PressureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-17PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-2.cond-refrig-tempChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomCondenser Refrigerant TemperatureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-18PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-2.cond-approach-dtChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomCondenser Approach Delta TemperatureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-19PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-2.cond-approach-dpChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomCondenser Approach Delta PressureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-20PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-2.oil-sump-pressChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomOil Sump PressureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-7PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-2.oil-sump-tempChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomOil Sump TemperatureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-8PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-2.oil-pump-statusChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomOil Pump Status (ON/OFF)HLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-6PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-2.oil-pump-tripChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomOil Pump Trip StatusHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/Alarm-2PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-2.compressor-onoffChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomChiller Compressor Pump On/Off StatusHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-1PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-2.compressor-hoaChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomChiller Compressor Hand/Off/Auto StatusHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-2PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-2.compressor-tripChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomChiller Compressor Trip Alarm StatusHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/Alarm-1PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-2.motor-load-currentChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomMotor Load CurrentHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-3PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-2.motor-consumptionChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomMotor Consumption (KW-Hr / BTU Monitoring)HLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-4PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-2.winding-tempChilled WaterChiller (Package Water-Cooled)CH-2GND/Chiller Plant RoomWinding TemperatureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-5PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-3.networkChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomBACnet/IP gateway from chiller controllerNetwork-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-1..36PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller Room
chws.ch-3.entering-chw-tempChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomEntering Chilled Water TemperatureAITemperature Sensor (immersion/thermowell)BMS ContractorBMS-03/Package Water Chiller P&ID/MR-11PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller Room
chws.ch-3.leaving-chw-tempChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomLeaving Chilled Water TemperatureAITemperature Sensor (immersion/thermowell)BMS ContractorBMS-03/Package Water Chiller P&ID/MR-12PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller Room
chws.ch-3.entering-cw-tempChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomEntering Condenser Water TemperatureAITemperature Sensor (immersion/thermowell)BMS ContractorBMS-03/Package Water Chiller P&ID/MR-21PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller Room
chws.ch-3.leaving-cw-tempChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomLeaving Condenser Water TemperatureAITemperature Sensor (immersion/thermowell)BMS ContractorBMS-03/Package Water Chiller P&ID/MR-22PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller Room
chws.ch-3.chw-supply-flowChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomChilled Water Supply Flow MeteringAIFlow Sensor (insertion or in-line)BMS ContractorBMS-03/Package Water Chiller P&IDPNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomPer-chiller branch flow
chws.ch-3.chw-return-flowChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomChilled Water Return Flow MeteringAIFlow Sensor (insertion or in-line)BMS ContractorBMS-03/Package Water Chiller P&IDPNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomPer-chiller branch flow
chws.ch-3.cw-supply-flowChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomCondenser Water Supply Flow MeteringAIFlow Sensor (insertion or in-line)BMS ContractorBMS-03/Package Water Chiller P&IDPNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomPer-chiller condenser branch flow
chws.ch-3.iso-vlv-chw-rsChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomIsolation Motorized Valve Status — CHW Return & SupplyDIElectric Valve Actuator (limit switch)ME ContractorBMS-03/Package Water Chiller P&ID/MR-9PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomValves supplied by ME; status DI to BMS
chws.ch-3.iso-vlv-cw-rsChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomIsolation Motorized Valve Status — COW Return & SupplyDIElectric Valve Actuator (limit switch)ME ContractorBMS-03/Package Water Chiller P&ID/MR-10PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomValves supplied by ME; status DI to BMS
chws.ch-3.evap-approach-dtChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomEvaporator Approach Delta TemperatureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-13PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-3.evap-approach-dpChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomEvaporator Approach Delta PressureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-14PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-3.evap-refrig-pressChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomEvaporator Refrigerant PressureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-15PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-3.evap-refrig-tempChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomEvaporator Refrigerant TemperatureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-16PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-3.cond-refrig-pressChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomCondenser Refrigerant PressureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-17PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-3.cond-refrig-tempChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomCondenser Refrigerant TemperatureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-18PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-3.cond-approach-dtChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomCondenser Approach Delta TemperatureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-19PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-3.cond-approach-dpChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomCondenser Approach Delta PressureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-20PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-3.oil-sump-pressChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomOil Sump PressureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-7PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-3.oil-sump-tempChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomOil Sump TemperatureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-8PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-3.oil-pump-statusChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomOil Pump Status (ON/OFF)HLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-6PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-3.oil-pump-tripChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomOil Pump Trip StatusHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/Alarm-2PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-3.compressor-onoffChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomChiller Compressor Pump On/Off StatusHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-1PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-3.compressor-hoaChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomChiller Compressor Hand/Off/Auto StatusHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-2PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-3.compressor-tripChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomChiller Compressor Trip Alarm StatusHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/Alarm-1PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-3.motor-load-currentChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomMotor Load CurrentHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-3PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-3.motor-consumptionChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomMotor Consumption (KW-Hr / BTU Monitoring)HLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-4PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.ch-3.winding-tempChilled WaterChiller (Package Water-Cooled)CH-3GND/Chiller Plant RoomWinding TemperatureHLI-Equipment SupplierBMS-03/Package Water Chiller P&ID/MR-5PNL-CH-PLANT-GNDBMS-01:r0c1; MC-ME:Chiller RoomVia chiller BACnet
chws.pchwp-1.run-statusChilled WaterPrimary CHW PumpPCHWP-12F/CHW Pump RoomOn/Off Status (run feedback)DIAuxiliary ContactEquipment SupplierBMS-03/Primary CHW & CW P&ID/MR-1PNL-CHWP-L2BMS-03:r0c0; MC-ME:Primary CHW Pumps
chws.pchwp-1.hoaChilled WaterPrimary CHW PumpPCHWP-12F/CHW Pump RoomHand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierBMS-03/Primary CHW & CW P&IDPNL-CHWP-L2BMS-03:r0c0; MC-ME:Primary CHW Pumps
chws.pchwp-1.tripChilled WaterPrimary CHW PumpPCHWP-12F/CHW Pump RoomTrip AlarmDIAuxiliary ContactEquipment SupplierBMS-03/Primary CHW & CW P&ID/Alarm-1PNL-CHWP-L2BMS-03:r0c0; MC-ME:Primary CHW Pumps
chws.pchwp-1.vfd-speed-fbChilled WaterPrimary CHW PumpPCHWP-12F/CHW Pump RoomVariable Speed Monitoring (VFD speed feedback)AIVFDEquipment SupplierBMS-03/Primary CHW & CW P&ID/MR-2PNL-CHWP-L2BMS-03:r0c0; MC-ME:Primary CHW Pumps
chws.pchwp-1.vfd-speed-cmdChilled WaterPrimary CHW PumpPCHWP-12F/CHW Pump RoomVFD Speed Command (modulating start/stop/speed)AOVFDEquipment SupplierBMS-03/Primary CHW & CW P&ID/Turn ON/OFFPNL-CHWP-L2BMS-03:r0c0; MC-ME:Primary CHW PumpsOr HLI if VFD has BACnet
chws.pchwp-2.run-statusChilled WaterPrimary CHW PumpPCHWP-22F/CHW Pump RoomOn/Off Status (run feedback)DIAuxiliary ContactEquipment SupplierBMS-03/Primary CHW & CW P&ID/MR-1PNL-CHWP-L2BMS-03:r0c0; MC-ME:Primary CHW Pumps
chws.pchwp-2.hoaChilled WaterPrimary CHW PumpPCHWP-22F/CHW Pump RoomHand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierBMS-03/Primary CHW & CW P&IDPNL-CHWP-L2BMS-03:r0c0; MC-ME:Primary CHW Pumps
chws.pchwp-2.tripChilled WaterPrimary CHW PumpPCHWP-22F/CHW Pump RoomTrip AlarmDIAuxiliary ContactEquipment SupplierBMS-03/Primary CHW & CW P&ID/Alarm-1PNL-CHWP-L2BMS-03:r0c0; MC-ME:Primary CHW Pumps
chws.pchwp-2.vfd-speed-fbChilled WaterPrimary CHW PumpPCHWP-22F/CHW Pump RoomVariable Speed Monitoring (VFD speed feedback)AIVFDEquipment SupplierBMS-03/Primary CHW & CW P&ID/MR-2PNL-CHWP-L2BMS-03:r0c0; MC-ME:Primary CHW Pumps
chws.pchwp-2.vfd-speed-cmdChilled WaterPrimary CHW PumpPCHWP-22F/CHW Pump RoomVFD Speed CommandAOVFDEquipment SupplierBMS-03/Primary CHW & CW P&ID/Turn ON/OFFPNL-CHWP-L2BMS-03:r0c0; MC-ME:Primary CHW Pumps
chws.pchwp-3.run-statusChilled WaterPrimary CHW PumpPCHWP-32F/CHW Pump RoomOn/Off Status (run feedback)DIAuxiliary ContactEquipment SupplierBMS-03/Primary CHW & CW P&ID/MR-1PNL-CHWP-L2BMS-03:r0c0; MC-ME:Primary CHW Pumps
chws.pchwp-3.hoaChilled WaterPrimary CHW PumpPCHWP-32F/CHW Pump RoomHand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierBMS-03/Primary CHW & CW P&IDPNL-CHWP-L2BMS-03:r0c0; MC-ME:Primary CHW Pumps
chws.pchwp-3.tripChilled WaterPrimary CHW PumpPCHWP-32F/CHW Pump RoomTrip AlarmDIAuxiliary ContactEquipment SupplierBMS-03/Primary CHW & CW P&ID/Alarm-1PNL-CHWP-L2BMS-03:r0c0; MC-ME:Primary CHW Pumps
chws.pchwp-3.vfd-speed-fbChilled WaterPrimary CHW PumpPCHWP-32F/CHW Pump RoomVariable Speed Monitoring (VFD speed feedback)AIVFDEquipment SupplierBMS-03/Primary CHW & CW P&ID/MR-2PNL-CHWP-L2BMS-03:r0c0; MC-ME:Primary CHW Pumps
chws.pchwp-3.vfd-speed-cmdChilled WaterPrimary CHW PumpPCHWP-32F/CHW Pump RoomVFD Speed CommandAOVFDEquipment SupplierBMS-03/Primary CHW & CW P&ID/Turn ON/OFFPNL-CHWP-L2BMS-03:r0c0; MC-ME:Primary CHW Pumps
chws.pchwp-4.run-statusChilled WaterPrimary CHW Pump (Standby)PCHWP-42F/CHW Pump RoomOn/Off Status (run feedback)DIAuxiliary ContactEquipment SupplierBMS-03/Primary CHW & CW P&ID/MR-1PNL-CHWP-L2MC-ME:Primary CHW Pumps; A-CHW-001Standby pump assumed; refine count after Q-005/Q-008
chws.pchwp-4.hoaChilled WaterPrimary CHW Pump (Standby)PCHWP-42F/CHW Pump RoomHand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierBMS-03/Primary CHW & CW P&IDPNL-CHWP-L2MC-ME:Primary CHW Pumps; A-CHW-001
chws.pchwp-4.tripChilled WaterPrimary CHW Pump (Standby)PCHWP-42F/CHW Pump RoomTrip AlarmDIAuxiliary ContactEquipment SupplierBMS-03/Primary CHW & CW P&ID/Alarm-1PNL-CHWP-L2MC-ME:Primary CHW Pumps; A-CHW-001
chws.pchwp-4.vfd-speed-fbChilled WaterPrimary CHW Pump (Standby)PCHWP-42F/CHW Pump RoomVariable Speed MonitoringAIVFDEquipment SupplierBMS-03/Primary CHW & CW P&ID/MR-2PNL-CHWP-L2MC-ME:Primary CHW Pumps; A-CHW-001
chws.pchwp-4.vfd-speed-cmdChilled WaterPrimary CHW Pump (Standby)PCHWP-42F/CHW Pump RoomVFD Speed CommandAOVFDEquipment SupplierBMS-03/Primary CHW & CW P&ID/Turn ON/OFFPNL-CHWP-L2MC-ME:Primary CHW Pumps; A-CHW-001
chws.comp-1.run-statusChilled WaterCondenser Water PumpCOMP-12F/CHW Pump RoomPump Motor Start/Stop Control feedback (On/Off Status)DIAuxiliary ContactEquipment SupplierBMS-03/CW Pump P&ID/MR-1PNL-CHWP-L2BMS-01:r1c1; MC-ME:Condenser Water Pumps
chws.comp-1.hoaChilled WaterCondenser Water PumpCOMP-12F/CHW Pump RoomHand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierBMS-03/CW Pump P&ID/MR-2PNL-CHWP-L2BMS-01:r1c1; MC-ME:Condenser Water Pumps
chws.comp-1.tripChilled WaterCondenser Water PumpCOMP-12F/CHW Pump RoomPump Trip AlarmDIAuxiliary ContactEquipment SupplierBMS-03/CW Pump P&ID/Alarm-1PNL-CHWP-L2BMS-01:r1c1; MC-ME:Condenser Water Pumps
chws.comp-1.start-cmdChilled WaterCondenser Water PumpCOMP-12F/CHW Pump RoomStart/Stop ControlDOContactor relayEquipment SupplierBMS-03/CW Pump P&ID/Turn ON/OFFPNL-CHWP-L2BMS-01:r1c1; MC-ME:Condenser Water PumpsBMS commands pump start sequenced with chiller
chws.comp-2.run-statusChilled WaterCondenser Water PumpCOMP-22F/CHW Pump RoomPump Motor Start/Stop Control feedback (On/Off Status)DIAuxiliary ContactEquipment SupplierBMS-03/CW Pump P&ID/MR-1PNL-CHWP-L2BMS-01:r1c1; MC-ME:Condenser Water Pumps
chws.comp-2.hoaChilled WaterCondenser Water PumpCOMP-22F/CHW Pump RoomHand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierBMS-03/CW Pump P&ID/MR-2PNL-CHWP-L2BMS-01:r1c1; MC-ME:Condenser Water Pumps
chws.comp-2.tripChilled WaterCondenser Water PumpCOMP-22F/CHW Pump RoomPump Trip AlarmDIAuxiliary ContactEquipment SupplierBMS-03/CW Pump P&ID/Alarm-1PNL-CHWP-L2BMS-01:r1c1; MC-ME:Condenser Water Pumps
chws.comp-2.start-cmdChilled WaterCondenser Water PumpCOMP-22F/CHW Pump RoomStart/Stop ControlDOContactor relayEquipment SupplierBMS-03/CW Pump P&ID/Turn ON/OFFPNL-CHWP-L2BMS-01:r1c1; MC-ME:Condenser Water Pumps
chws.comp-3.run-statusChilled WaterCondenser Water PumpCOMP-32F/CHW Pump RoomPump Motor Start/Stop Control feedback (On/Off Status)DIAuxiliary ContactEquipment SupplierBMS-03/CW Pump P&ID/MR-1PNL-CHWP-L2BMS-01:r1c1; MC-ME:Condenser Water Pumps
chws.comp-3.hoaChilled WaterCondenser Water PumpCOMP-32F/CHW Pump RoomHand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierBMS-03/CW Pump P&ID/MR-2PNL-CHWP-L2BMS-01:r1c1; MC-ME:Condenser Water Pumps
chws.comp-3.tripChilled WaterCondenser Water PumpCOMP-32F/CHW Pump RoomPump Trip AlarmDIAuxiliary ContactEquipment SupplierBMS-03/CW Pump P&ID/Alarm-1PNL-CHWP-L2BMS-01:r1c1; MC-ME:Condenser Water Pumps
chws.comp-3.start-cmdChilled WaterCondenser Water PumpCOMP-32F/CHW Pump RoomStart/Stop ControlDOContactor relayEquipment SupplierBMS-03/CW Pump P&ID/Turn ON/OFFPNL-CHWP-L2BMS-01:r1c1; MC-ME:Condenser Water Pumps
chws.ct-1.fan-statusChilled WaterCooling TowerCT-1Roofdeck/Cooling Tower AreaFan Motor StatusDIAuxiliary ContactEquipment SupplierBMS-03/Cooling Tower P&ID/MR-1PNL-CT-RDBMS-02:r1c2; MC-ME:Cooling Tower
chws.ct-1.fan-tripChilled WaterCooling TowerCT-1Roofdeck/Cooling Tower AreaFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierBMS-03/Cooling Tower P&ID/Alarm-1PNL-CT-RDBMS-02:r1c2; MC-ME:Cooling Tower
chws.ct-1.fan-start-cmdChilled WaterCooling TowerCT-1Roofdeck/Cooling Tower AreaFan Motor Start/Stop CommandDOContactor relayEquipment SupplierBMS-03/Cooling Tower P&ID/Turn ON/OFFPNL-CT-RDBMS-02:r1c2; MC-ME:Cooling TowerSequenced with COW pump and chiller
chws.ct-1.basin-level-lowChilled WaterCooling TowerCT-1Roofdeck/Cooling Tower AreaLevel Alarm Low (CT Basin)DILevel Sensor / ElectrodeBMS ContractorBMS-03/Cooling Tower P&ID/Alarm-2PNL-CT-RDBMS-02:r1c2; MC-ME:Cooling Tower
chws.ct-1.basin-level-highChilled WaterCooling TowerCT-1Roofdeck/Cooling Tower AreaLevel Alarm High (CT Basin)DILevel Sensor / ElectrodeBMS ContractorBMS-03/Cooling Tower P&ID/Alarm-2PNL-CT-RDBMS-02:r1c2; MC-ME:Cooling Tower
chws.ct-1.iso-vlv-cw-rsChilled WaterCooling TowerCT-1Roofdeck/Cooling Tower AreaIsolation Motorized Valve Status — COW R&SDIElectric Valve ActuatorME ContractorBMS-03/Cooling Tower P&ID/MR-12PNL-CT-RDBMS-02:r1c2; MC-ME:Cooling Tower
chws.ct-1.blowdown-vlv-cmdChilled WaterCooling TowerCT-1Roofdeck/Cooling Tower AreaMotorized Blowdown Valve ControlDOElectric Valve ActuatorBMS ContractorBMS-03/Cooling Tower P&ID/Turn ON/OFF blowdownPNL-CT-RDBMS-02:r1c2; MC-ME:Cooling Tower
chws.ct-1.blowdown-vlv-statChilled WaterCooling TowerCT-1Roofdeck/Cooling Tower AreaMotorized Blowdown Valve StatusDIElectric Valve ActuatorBMS ContractorBMS-03/Cooling Tower P&ID/MR-14PNL-CT-RDBMS-02:r1c2; MC-ME:Cooling Tower
chws.ct-1.blowdown-phChilled WaterCooling TowerCT-1Roofdeck/Cooling Tower AreaBlowdown Corrosion/Scale Monitoring (pH/Conductivity)AIpH Sensor / Conductivity SensorME ContractorBMS-03/Cooling Tower P&ID/MR-13PNL-CT-RDBMS-02:r1c2; MC-ME:Cooling TowerField device by ME; signal to BMS
chws.ct-2.fan-statusChilled WaterCooling TowerCT-2Roofdeck/Cooling Tower AreaFan Motor StatusDIAuxiliary ContactEquipment SupplierBMS-03/Cooling Tower P&ID/MR-1PNL-CT-RDBMS-02:r1c2; MC-ME:Cooling Tower
chws.ct-2.fan-tripChilled WaterCooling TowerCT-2Roofdeck/Cooling Tower AreaFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierBMS-03/Cooling Tower P&ID/Alarm-1PNL-CT-RDBMS-02:r1c2; MC-ME:Cooling Tower
chws.ct-2.fan-start-cmdChilled WaterCooling TowerCT-2Roofdeck/Cooling Tower AreaFan Motor Start/Stop CommandDOContactor relayEquipment SupplierBMS-03/Cooling Tower P&ID/Turn ON/OFFPNL-CT-RDBMS-02:r1c2; MC-ME:Cooling Tower
chws.ct-2.basin-level-lowChilled WaterCooling TowerCT-2Roofdeck/Cooling Tower AreaLevel Alarm Low (CT Basin)DILevel Sensor / ElectrodeBMS ContractorBMS-03/Cooling Tower P&ID/Alarm-2PNL-CT-RDBMS-02:r1c2; MC-ME:Cooling Tower
chws.ct-2.basin-level-highChilled WaterCooling TowerCT-2Roofdeck/Cooling Tower AreaLevel Alarm High (CT Basin)DILevel Sensor / ElectrodeBMS ContractorBMS-03/Cooling Tower P&ID/Alarm-2PNL-CT-RDBMS-02:r1c2; MC-ME:Cooling Tower
chws.ct-2.iso-vlv-cw-rsChilled WaterCooling TowerCT-2Roofdeck/Cooling Tower AreaIsolation Motorized Valve Status — COW R&SDIElectric Valve ActuatorME ContractorBMS-03/Cooling Tower P&ID/MR-12PNL-CT-RDBMS-02:r1c2; MC-ME:Cooling Tower
chws.ct-2.blowdown-vlv-cmdChilled WaterCooling TowerCT-2Roofdeck/Cooling Tower AreaMotorized Blowdown Valve ControlDOElectric Valve ActuatorBMS ContractorBMS-03/Cooling Tower P&ID/Turn ON/OFF blowdownPNL-CT-RDBMS-02:r1c2; MC-ME:Cooling Tower
chws.ct-2.blowdown-vlv-statChilled WaterCooling TowerCT-2Roofdeck/Cooling Tower AreaMotorized Blowdown Valve StatusDIElectric Valve ActuatorBMS ContractorBMS-03/Cooling Tower P&ID/MR-14PNL-CT-RDBMS-02:r1c2; MC-ME:Cooling Tower
chws.ct-2.blowdown-phChilled WaterCooling TowerCT-2Roofdeck/Cooling Tower AreaBlowdown Corrosion/Scale MonitoringAIpH Sensor / Conductivity SensorME ContractorBMS-03/Cooling Tower P&ID/MR-13PNL-CT-RDBMS-02:r1c2; MC-ME:Cooling Tower
chws.ct-3.fan-statusChilled WaterCooling TowerCT-3Roofdeck/Cooling Tower AreaFan Motor StatusDIAuxiliary ContactEquipment SupplierBMS-03/Cooling Tower P&ID/MR-1PNL-CT-RDBMS-02:r1c2; MC-ME:Cooling Tower
chws.ct-3.fan-tripChilled WaterCooling TowerCT-3Roofdeck/Cooling Tower AreaFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierBMS-03/Cooling Tower P&ID/Alarm-1PNL-CT-RDBMS-02:r1c2; MC-ME:Cooling Tower
chws.ct-3.fan-start-cmdChilled WaterCooling TowerCT-3Roofdeck/Cooling Tower AreaFan Motor Start/Stop CommandDOContactor relayEquipment SupplierBMS-03/Cooling Tower P&ID/Turn ON/OFFPNL-CT-RDBMS-02:r1c2; MC-ME:Cooling Tower
chws.ct-3.basin-level-lowChilled WaterCooling TowerCT-3Roofdeck/Cooling Tower AreaLevel Alarm Low (CT Basin)DILevel Sensor / ElectrodeBMS ContractorBMS-03/Cooling Tower P&ID/Alarm-2PNL-CT-RDBMS-02:r1c2; MC-ME:Cooling Tower
chws.ct-3.basin-level-highChilled WaterCooling TowerCT-3Roofdeck/Cooling Tower AreaLevel Alarm High (CT Basin)DILevel Sensor / ElectrodeBMS ContractorBMS-03/Cooling Tower P&ID/Alarm-2PNL-CT-RDBMS-02:r1c2; MC-ME:Cooling Tower
chws.ct-3.iso-vlv-cw-rsChilled WaterCooling TowerCT-3Roofdeck/Cooling Tower AreaIsolation Motorized Valve Status — COW R&SDIElectric Valve ActuatorME ContractorBMS-03/Cooling Tower P&ID/MR-12PNL-CT-RDBMS-02:r1c2; MC-ME:Cooling Tower
chws.ct-3.blowdown-vlv-cmdChilled WaterCooling TowerCT-3Roofdeck/Cooling Tower AreaMotorized Blowdown Valve ControlDOElectric Valve ActuatorBMS ContractorBMS-03/Cooling Tower P&ID/Turn ON/OFF blowdownPNL-CT-RDBMS-02:r1c2; MC-ME:Cooling Tower
chws.ct-3.blowdown-vlv-statChilled WaterCooling TowerCT-3Roofdeck/Cooling Tower AreaMotorized Blowdown Valve StatusDIElectric Valve ActuatorBMS ContractorBMS-03/Cooling Tower P&ID/MR-14PNL-CT-RDBMS-02:r1c2; MC-ME:Cooling Tower
chws.ct-3.blowdown-phChilled WaterCooling TowerCT-3Roofdeck/Cooling Tower AreaBlowdown Corrosion/Scale MonitoringAIpH Sensor / Conductivity SensorME ContractorBMS-03/Cooling Tower P&ID/MR-13PNL-CT-RDBMS-02:r1c2; MC-ME:Cooling Tower
chws.ct-common.outside-air-tempChilled WaterCooling Tower (Common)CT-COMMONRoofdeck/Cooling Tower AreaOutside Air Temperature MonitoringAITemperature Sensor (outdoor)BMS ContractorBMS-03/Cooling Tower P&ID/MR-4PNL-CT-RDBMS-02:r1c2; MC-ME:Cooling TowerSingle OA sensor serves all CTs
chws.ct-common.outside-air-rhChilled WaterCooling Tower (Common)CT-COMMONRoofdeck/Cooling Tower AreaOutside Air Humidity MonitoringAIHumidity Sensor (outdoor)BMS ContractorBMS-03/Cooling Tower P&ID/MR-5PNL-CT-RDBMS-02:r1c2; MC-ME:Cooling TowerSingle OA RH sensor serves all CTs
chws.hdr-cws-rd.tempChilled WaterCondenser Water HeaderHDR-CWS-RDRoofdeck/Cooling Tower AreaMain Condenser Water Supply Header TemperatureAITemperature Sensor (immersion)BMS ContractorBMS-03/Cooling Tower P&ID/MR-2PNL-CT-RDBMS-02:r1c2; MC-ME:Cooling Tower
chws.hdr-cwr-rd.tempChilled WaterCondenser Water HeaderHDR-CWR-RDRoofdeck/Cooling Tower AreaMain Condenser Water Return Header TemperatureAITemperature Sensor (immersion)BMS ContractorBMS-03/Cooling Tower P&ID/MR-3PNL-CT-RDBMS-02:r1c2; MC-ME:Cooling Tower
chws.hdr-chws-l2.tempChilled WaterCHW Supply Main HeaderHDR-CHWS2F/CHW Pump RoomCHW Supply Main Header TemperatureAITemperature Sensor (immersion)BMS ContractorBMS-03/Primary CHW & CW P&ID — headerPNL-CHWP-L2BMS-01:r1c1; MC-ME:CHW Supply Header
chws.hdr-chws-l2.pressChilled WaterCHW Supply Main HeaderHDR-CHWS2F/CHW Pump RoomCHW Supply Main Header PressureAIPressure SensorBMS ContractorBMS-03/Primary CHW & CW P&ID — headerPNL-CHWP-L2BMS-01:r1c1; MC-ME:CHW Supply Header
chws.hdr-chwr-l2.tempChilled WaterCHW Return Main HeaderHDR-CHWR2F/CHW Pump RoomCHW Return Main Header TemperatureAITemperature Sensor (immersion)BMS ContractorBMS-03/Primary CHW & CW P&ID — headerPNL-CHWP-L2BMS-01:r1c1; MC-ME:CHW Return Header
chws.hdr-chwr-l2.pressChilled WaterCHW Return Main HeaderHDR-CHWR2F/CHW Pump RoomCHW Return Main Header PressureAIPressure SensorBMS ContractorBMS-03/Primary CHW & CW P&ID — headerPNL-CHWP-L2BMS-01:r1c1; MC-ME:CHW Return Header
chws.hdr-chw-bp.diff-pressChilled WaterCHW Bypass HeaderHDR-CHW-BP2F/CHW Pump RoomCHW Differential Pressure (Supply vs. Return)AIDifferential Pressure SensorBMS ContractorBMS-03/Primary CHW & CW P&ID — bypassPNL-CHWP-L2BMS-01:r1c1; MC-ME:CHW Main HeaderDrives PCHWP VFD speed control
chws.hdr-chw-bp.diff-tempChilled WaterCHW Bypass HeaderHDR-CHW-BP2F/CHW Pump RoomCHW Differential Temperature (Supply vs. Return)AIDifferential Temp SensorBMS ContractorBMS-03/Primary CHW & CW P&ID — bypassPNL-CHWP-L2BMS-01:r1c1; MC-ME:CHW Main Header
chws.hdr-chw-bp.iso-vlv-statChilled WaterCHW Bypass HeaderHDR-CHW-BP2F/CHW Pump RoomIsolation Motorized Valve Status — CHW BypassDIElectric Valve ActuatorBMS ContractorBMS-03/Primary CHW & CW P&ID — bypassPNL-CHWP-L2BMS-01:r1c1; MC-ME:CHW Main HeaderBMS-supplied actuator on bypass
chws.hdr-chw-bp.iso-vlv-cmdChilled WaterCHW Bypass HeaderHDR-CHW-BP2F/CHW Pump RoomIsolation Motorized Valve Control — CHW BypassDOElectric Valve ActuatorBMS ContractorBMS-03/Primary CHW & CW P&ID — bypassPNL-CHWP-L2BMS-01:r1c1; MC-ME:CHW Main Header
chws.btu-chws-main.networkChilled WaterBTU MeterBTU-CHWS-MAIN2F/CHW Pump RoomBTU Meter Modbus Network connectionNetworkBTU Meter (Modbus RTU/IP)BMS ContractorBMS-03/Primary CHW & CW P&ID — BTU meterPNL-CHWP-L2BMS-03:r0c0/r0c1; MC-ME:Chiller (CHW flow)Plant-level kWh + Btu energy submetering
chws.btu-chws-main.energyChilled WaterBTU MeterBTU-CHWS-MAIN2F/CHW Pump RoomCumulative thermal energy (kBtu)HLI-BMS ContractorBMS-03/Primary CHW & CW P&ID — BTU meterPNL-CHWP-L2BMS-03:r0c0/r0c1; MC-ME:Chiller (CHW flow)
chws.btu-chws-main.flowChilled WaterBTU MeterBTU-CHWS-MAIN2F/CHW Pump RoomCHW Mass FlowHLI-BMS ContractorBMS-03/Primary CHW & CW P&ID — BTU meterPNL-CHWP-L2BMS-03:r0c0/r0c1; MC-ME:Chiller (CHW flow)
chws.btu-chws-main.dtChilled WaterBTU MeterBTU-CHWS-MAIN2F/CHW Pump RoomCHW Supply-Return Delta TemperatureHLI-BMS ContractorBMS-03/Primary CHW & CW P&ID — BTU meterPNL-CHWP-L2BMS-03:r0c0/r0c1; MC-ME:Chiller (CHW flow)
boh.chwp-1-1.networkBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.1GND/BOH AHU AreaBACnet/Modbus network to AHU VFD/controllerNetworkVFD with BACnetEquipment SupplierMC-ME:AHU-AC at 2nd Level/Common Areas; BMS-01 BOH tablePNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC1 network drop per AHU's VFD
boh.chwp-1-1.fan-motor-statusBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.1GND/BOH AHU AreaFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:AHU-AC/MR-1PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-1.fan-trip-statusBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.1GND/BOH AHU AreaFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:AHU-AC/Alarm-1PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-1.fan-hoa-statusBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.1GND/BOH AHU AreaFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:AHU-ACPNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-1.vfd-speed-fbBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.1GND/BOH AHU AreaVariable Frequency Drive (VFD) Speed Monitoring (feedback)HLIVFDEquipment SupplierMC-ME:AHU-AC/MR-7PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-ACVia VFD BACnet
boh.chwp-1-1.fan-control-cmdBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.1GND/BOH AHU AreaFan Control On/Off/Modulating (speed command)HLIVFDEquipment SupplierMC-ME:AHU-AC/Turn ON/OFFPNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-ACVia VFD BACnet
boh.chwp-1-1.supply-air-tempBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.1GND/BOH AHU AreaSupply Air TemperatureAITemperature Sensor (duct insertion)BMS ContractorMC-ME:AHU-AC/MR-6PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-1.mixed-air-tempBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.1GND/BOH AHU AreaMixed Air TemperatureAITemperature Sensor (duct insertion)BMS ContractorMC-ME:AHU-AC/MR-5PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-1.supply-air-rhBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.1GND/BOH AHU AreaSupply Air Humidity MonitoringAIHumidity Sensor (duct insertion)BMS ContractorMC-ME:AHU-ACPNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-1.return-air-tempBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.1GND/BOH AHU AreaIndoor Return Air TemperatureAITemperature Sensor (duct insertion)BMS ContractorMC-ME:AHU-AC/MR-3PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-1.return-air-co2BOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.1GND/BOH AHU AreaIndoor Return Air CO2 LevelAICO2 Sensor (duct)BMS ContractorMC-ME:AHU-AC/MR-4PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-ACDrives DCV (demand-controlled ventilation)
boh.chwp-1-1.chw-vlv-statusBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.1GND/BOH AHU AreaTwo-Way CHW Modulating Valve StatusDIElectric Valve Actuator (limit/feedback switch)ME ContractorMC-ME:AHU-ACPNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-ACValve supplied by ME
boh.chwp-1-1.chw-vlv-cmdBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.1GND/BOH AHU AreaCHW Modulating Valve Control On/Off/ModulatingAOElectric Valve Actuator (0-10V or 4-20mA)ME ContractorMC-ME:AHU-AC/Modulate-1PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-ACDrives valve to maintain supply air temp
boh.chwp-1-1.oa-damper-statusBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.1GND/BOH AHU AreaOutdoor Air Motorized Damper StatusDIDamper Controller (limit/feedback switch)ME ContractorMC-ME:AHU-AC/MR-9PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-ACDamper supplied by ME
boh.chwp-1-1.oa-damper-cmdBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.1GND/BOH AHU AreaOutdoor Air Motorized Damper Control On/Off/ModulatingAODamper Controller (0-10V or 4-20mA)ME ContractorMC-ME:AHU-AC/Turn ON/OFF/ModulatePNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-1.ra-damper-statusBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.1GND/BOH AHU AreaReturn Air Motorized Damper StatusDIDamper Controller (limit/feedback switch)ME ContractorMC-ME:AHU-AC/MR-8PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-1.ra-damper-cmdBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.1GND/BOH AHU AreaReturn Air Motorized Damper Control On/Off/ModulatingAODamper Controller (0-10V or 4-20mA)ME ContractorMC-ME:AHU-AC/Turn ON/OFF/ModulatePNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-2.networkBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.2GND/BOH AHU AreaBACnet/Modbus network to AHU VFD/controllerNetworkVFD with BACnetEquipment SupplierMC-ME:AHU-AC at 2nd Level/Common Areas; BMS-01 BOH tablePNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-2.fan-motor-statusBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.2GND/BOH AHU AreaFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:AHU-AC/MR-1PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-2.fan-trip-statusBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.2GND/BOH AHU AreaFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:AHU-AC/Alarm-1PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-2.fan-hoa-statusBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.2GND/BOH AHU AreaFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:AHU-ACPNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-2.vfd-speed-fbBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.2GND/BOH AHU AreaVariable Frequency Drive (VFD) Speed Monitoring (feedback)HLIVFDEquipment SupplierMC-ME:AHU-AC/MR-7PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-ACVia VFD BACnet
boh.chwp-1-2.fan-control-cmdBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.2GND/BOH AHU AreaFan Control On/Off/Modulating (speed command)HLIVFDEquipment SupplierMC-ME:AHU-AC/Turn ON/OFFPNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-ACVia VFD BACnet
boh.chwp-1-2.supply-air-tempBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.2GND/BOH AHU AreaSupply Air TemperatureAITemperature Sensor (duct insertion)BMS ContractorMC-ME:AHU-AC/MR-6PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-2.mixed-air-tempBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.2GND/BOH AHU AreaMixed Air TemperatureAITemperature Sensor (duct insertion)BMS ContractorMC-ME:AHU-AC/MR-5PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-2.supply-air-rhBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.2GND/BOH AHU AreaSupply Air Humidity MonitoringAIHumidity Sensor (duct insertion)BMS ContractorMC-ME:AHU-ACPNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-2.return-air-tempBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.2GND/BOH AHU AreaIndoor Return Air TemperatureAITemperature Sensor (duct insertion)BMS ContractorMC-ME:AHU-AC/MR-3PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-2.return-air-co2BOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.2GND/BOH AHU AreaIndoor Return Air CO2 LevelAICO2 Sensor (duct)BMS ContractorMC-ME:AHU-AC/MR-4PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-2.chw-vlv-statusBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.2GND/BOH AHU AreaTwo-Way CHW Modulating Valve StatusDIElectric Valve Actuator (limit/feedback switch)ME ContractorMC-ME:AHU-ACPNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-2.chw-vlv-cmdBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.2GND/BOH AHU AreaCHW Modulating Valve Control On/Off/ModulatingAOElectric Valve Actuator (0-10V or 4-20mA)ME ContractorMC-ME:AHU-AC/Modulate-1PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-2.oa-damper-statusBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.2GND/BOH AHU AreaOutdoor Air Motorized Damper StatusDIDamper Controller (limit/feedback switch)ME ContractorMC-ME:AHU-AC/MR-9PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-2.oa-damper-cmdBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.2GND/BOH AHU AreaOutdoor Air Motorized Damper Control On/Off/ModulatingAODamper Controller (0-10V or 4-20mA)ME ContractorMC-ME:AHU-AC/Turn ON/OFF/ModulatePNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-2.ra-damper-statusBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.2GND/BOH AHU AreaReturn Air Motorized Damper StatusDIDamper Controller (limit/feedback switch)ME ContractorMC-ME:AHU-AC/MR-8PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-2.ra-damper-cmdBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.2GND/BOH AHU AreaReturn Air Motorized Damper Control On/Off/ModulatingAODamper Controller (0-10V or 4-20mA)ME ContractorMC-ME:AHU-AC/Turn ON/OFF/ModulatePNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-3.networkBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.3GND/BOH AHU AreaBACnet/Modbus network to AHU VFD/controllerNetworkVFD with BACnetEquipment SupplierMC-ME:AHU-AC at 2nd Level/Common Areas; BMS-01 BOH tablePNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-3.fan-motor-statusBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.3GND/BOH AHU AreaFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:AHU-AC/MR-1PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-3.fan-trip-statusBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.3GND/BOH AHU AreaFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:AHU-AC/Alarm-1PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-3.fan-hoa-statusBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.3GND/BOH AHU AreaFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:AHU-ACPNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-3.vfd-speed-fbBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.3GND/BOH AHU AreaVariable Frequency Drive (VFD) Speed Monitoring (feedback)HLIVFDEquipment SupplierMC-ME:AHU-AC/MR-7PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-ACVia VFD BACnet
boh.chwp-1-3.fan-control-cmdBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.3GND/BOH AHU AreaFan Control On/Off/Modulating (speed command)HLIVFDEquipment SupplierMC-ME:AHU-AC/Turn ON/OFFPNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-ACVia VFD BACnet
boh.chwp-1-3.supply-air-tempBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.3GND/BOH AHU AreaSupply Air TemperatureAITemperature Sensor (duct insertion)BMS ContractorMC-ME:AHU-AC/MR-6PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-3.mixed-air-tempBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.3GND/BOH AHU AreaMixed Air TemperatureAITemperature Sensor (duct insertion)BMS ContractorMC-ME:AHU-AC/MR-5PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-3.supply-air-rhBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.3GND/BOH AHU AreaSupply Air Humidity MonitoringAIHumidity Sensor (duct insertion)BMS ContractorMC-ME:AHU-ACPNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-3.return-air-tempBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.3GND/BOH AHU AreaIndoor Return Air TemperatureAITemperature Sensor (duct insertion)BMS ContractorMC-ME:AHU-AC/MR-3PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-3.return-air-co2BOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.3GND/BOH AHU AreaIndoor Return Air CO2 LevelAICO2 Sensor (duct)BMS ContractorMC-ME:AHU-AC/MR-4PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-3.chw-vlv-statusBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.3GND/BOH AHU AreaTwo-Way CHW Modulating Valve StatusDIElectric Valve Actuator (limit/feedback switch)ME ContractorMC-ME:AHU-ACPNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-3.chw-vlv-cmdBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.3GND/BOH AHU AreaCHW Modulating Valve Control On/Off/ModulatingAOElectric Valve Actuator (0-10V or 4-20mA)ME ContractorMC-ME:AHU-AC/Modulate-1PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-3.oa-damper-statusBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.3GND/BOH AHU AreaOutdoor Air Motorized Damper StatusDIDamper Controller (limit/feedback switch)ME ContractorMC-ME:AHU-AC/MR-9PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-3.oa-damper-cmdBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.3GND/BOH AHU AreaOutdoor Air Motorized Damper Control On/Off/ModulatingAODamper Controller (0-10V or 4-20mA)ME ContractorMC-ME:AHU-AC/Turn ON/OFF/ModulatePNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-3.ra-damper-statusBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.3GND/BOH AHU AreaReturn Air Motorized Damper StatusDIDamper Controller (limit/feedback switch)ME ContractorMC-ME:AHU-AC/MR-8PNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
boh.chwp-1-3.ra-damper-cmdBOH Air HandlingAHU (Chilled-Water-Served)CHWP-1.3GND/BOH AHU AreaReturn Air Motorized Damper Control On/Off/ModulatingAODamper Controller (0-10V or 4-20mA)ME ContractorMC-ME:AHU-AC/Turn ON/OFF/ModulatePNL-CHWP-GNDBMS-01:r0c1; MC-ME:AHU-AC
pl.hwt-lz-1.tank-tempPlumbing & Sanitary HotwaterCalorifier (Hot Water Storage Tank)HWT-LZ-1Lower Ground/HW PlantTank TemperatureAITemperature Sensor (immersion/thermowell)BMS ContractorMC-PL:Calorifiers/MR-1PNL-PL-LZBMS-01:r0c2; MC-PL:Calorifiers
pl.hwt-lz-2.tank-tempPlumbing & Sanitary HotwaterCalorifier (Hot Water Storage Tank)HWT-LZ-2Lower Ground/HW PlantTank TemperatureAITemperature Sensor (immersion/thermowell)BMS ContractorMC-PL:Calorifiers/MR-1PNL-PL-LZBMS-01:r0c2; MC-PL:Calorifiers
pl.hwt-lz-3.tank-tempPlumbing & Sanitary HotwaterCalorifier (Hot Water Storage Tank)HWT-LZ-3Lower Ground/HW PlantTank TemperatureAITemperature Sensor (immersion/thermowell)BMS ContractorMC-PL:Calorifiers/MR-1PNL-PL-LZBMS-01:r0c2; MC-PL:Calorifiers
pl.hwt-hz-1.tank-tempPlumbing & Sanitary HotwaterCalorifier (Hot Water Storage Tank)HWT-HZ-1Roofdeck/HW PlantTank TemperatureAITemperature Sensor (immersion/thermowell)BMS ContractorMC-PL:Calorifiers/MR-1PNL-PL-HZBMS-01:r0c2; MC-PL:Calorifiers
pl.hwt-hz-2.tank-tempPlumbing & Sanitary HotwaterCalorifier (Hot Water Storage Tank)HWT-HZ-2Roofdeck/HW PlantTank TemperatureAITemperature Sensor (immersion/thermowell)BMS ContractorMC-PL:Calorifiers/MR-1PNL-PL-HZBMS-01:r0c2; MC-PL:Calorifiers
pl.hwt-hz-3.tank-tempPlumbing & Sanitary HotwaterCalorifier (Hot Water Storage Tank)HWT-HZ-3Roofdeck/HW PlantTank TemperatureAITemperature Sensor (immersion/thermowell)BMS ContractorMC-PL:Calorifiers/MR-1PNL-PL-HZBMS-01:r0c2; MC-PL:Calorifiers
pl.hdr-hw-lz.supply-tempPlumbing & Sanitary HotwaterHot Water Header SetHDR-HW-LZLower Ground/HW PlantHot Water Supply Header TemperatureAITemperature Sensor (immersion/thermowell)BMS ContractorMC-PL:Supply & Return Headers/MR-1PNL-PL-LZBMS-01:r0c2; MC-PL:Supply&Return Headers
pl.hdr-hw-lz.return-tempPlumbing & Sanitary HotwaterHot Water Header SetHDR-HW-LZLower Ground/HW PlantHot Water Return Header TemperatureAITemperature Sensor (immersion/thermowell)BMS ContractorMC-PL:Supply & Return Headers/MR-3PNL-PL-LZBMS-01:r0c2; MC-PL:Supply&Return Headers
pl.hdr-hw-lz.makeup-tempPlumbing & Sanitary HotwaterHot Water Header SetHDR-HW-LZLower Ground/HW PlantMake Up Cold Water Header TemperatureAITemperature Sensor (immersion/thermowell)BMS ContractorMC-PL:Supply & Return Headers/MR-2PNL-PL-LZBMS-01:r0c2; MC-PL:Supply&Return Headers
pl.hdr-hw-hz.supply-tempPlumbing & Sanitary HotwaterHot Water Header SetHDR-HW-HZRoofdeck/HW PlantHot Water Supply Header TemperatureAITemperature Sensor (immersion/thermowell)BMS ContractorMC-PL:Supply & Return Headers/MR-1PNL-PL-HZBMS-01:r0c2; MC-PL:Supply&Return Headers
pl.hdr-hw-hz.return-tempPlumbing & Sanitary HotwaterHot Water Header SetHDR-HW-HZRoofdeck/HW PlantHot Water Return Header TemperatureAITemperature Sensor (immersion/thermowell)BMS ContractorMC-PL:Supply & Return Headers/MR-3PNL-PL-HZBMS-01:r0c2; MC-PL:Supply&Return Headers
pl.hdr-hw-hz.makeup-tempPlumbing & Sanitary HotwaterHot Water Header SetHDR-HW-HZRoofdeck/HW PlantMake Up Cold Water Header TemperatureAITemperature Sensor (immersion/thermowell)BMS ContractorMC-PL:Supply & Return Headers/MR-2PNL-PL-HZBMS-01:r0c2; MC-PL:Supply&Return Headers
pl.hp-lz-1.motor-statusPlumbing & Sanitary HotwaterHeat PumpHP-LZ-1Lower Ground/HW PlantPump Motor Status (Run feedback)DIAuxiliary ContactEquipment SupplierMC-PL:Heat Pump/MR-1PNL-PL-LZBMS-01:r0c2; MC-PL:Heat Pump; A-PL-001Hardwired DI per A-PL-001
pl.hp-lz-1.hoa-statusPlumbing & Sanitary HotwaterHeat PumpHP-LZ-1Lower Ground/HW PlantPump Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-PL:Heat Pump/MR-2PNL-PL-LZBMS-01:r0c2; MC-PL:Heat Pump; A-PL-001
pl.hp-lz-1.trip-alarmPlumbing & Sanitary HotwaterHeat PumpHP-LZ-1Lower Ground/HW PlantPump Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-PL:Heat Pump/Alarm-1PNL-PL-LZBMS-01:r0c2; MC-PL:Heat Pump; A-PL-001
pl.hp-lz-2.motor-statusPlumbing & Sanitary HotwaterHeat PumpHP-LZ-2Lower Ground/HW PlantPump Motor Status (Run feedback)DIAuxiliary ContactEquipment SupplierMC-PL:Heat Pump/MR-1PNL-PL-LZBMS-01:r0c2; MC-PL:Heat Pump; A-PL-001
pl.hp-lz-2.hoa-statusPlumbing & Sanitary HotwaterHeat PumpHP-LZ-2Lower Ground/HW PlantPump Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-PL:Heat Pump/MR-2PNL-PL-LZBMS-01:r0c2; MC-PL:Heat Pump; A-PL-001
pl.hp-lz-2.trip-alarmPlumbing & Sanitary HotwaterHeat PumpHP-LZ-2Lower Ground/HW PlantPump Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-PL:Heat Pump/Alarm-1PNL-PL-LZBMS-01:r0c2; MC-PL:Heat Pump; A-PL-001
pl.hp-lz-3.motor-statusPlumbing & Sanitary HotwaterHeat PumpHP-LZ-3Lower Ground/HW PlantPump Motor Status (Run feedback)DIAuxiliary ContactEquipment SupplierMC-PL:Heat Pump/MR-1PNL-PL-LZBMS-01:r0c2; MC-PL:Heat Pump; A-PL-001
pl.hp-lz-3.hoa-statusPlumbing & Sanitary HotwaterHeat PumpHP-LZ-3Lower Ground/HW PlantPump Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-PL:Heat Pump/MR-2PNL-PL-LZBMS-01:r0c2; MC-PL:Heat Pump; A-PL-001
pl.hp-lz-3.trip-alarmPlumbing & Sanitary HotwaterHeat PumpHP-LZ-3Lower Ground/HW PlantPump Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-PL:Heat Pump/Alarm-1PNL-PL-LZBMS-01:r0c2; MC-PL:Heat Pump; A-PL-001
pl.rp-lz-1.motor-statusPlumbing & Sanitary HotwaterRecirculating PumpRP-LZ-1Lower Ground/HW PlantPump Motor Status (Run feedback)DIAuxiliary ContactEquipment SupplierMC-PL:Circulating Pumps/MR-1PNL-PL-LZBMS-01:r0c2; MC-PL:Circulating Pumps; A-PL-001
pl.rp-lz-1.hoa-statusPlumbing & Sanitary HotwaterRecirculating PumpRP-LZ-1Lower Ground/HW PlantPump Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-PL:Circulating Pumps/MR-2PNL-PL-LZBMS-01:r0c2; MC-PL:Circulating Pumps; A-PL-001
pl.rp-lz-1.trip-alarmPlumbing & Sanitary HotwaterRecirculating PumpRP-LZ-1Lower Ground/HW PlantPump Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-PL:Circulating Pumps/Alarm-1PNL-PL-LZBMS-01:r0c2; MC-PL:Circulating Pumps; A-PL-001
pl.rp-lz-2.motor-statusPlumbing & Sanitary HotwaterRecirculating PumpRP-LZ-2Lower Ground/HW PlantPump Motor Status (Run feedback)DIAuxiliary ContactEquipment SupplierMC-PL:Circulating Pumps/MR-1PNL-PL-LZBMS-01:r0c2; MC-PL:Circulating Pumps; A-PL-001
pl.rp-lz-2.hoa-statusPlumbing & Sanitary HotwaterRecirculating PumpRP-LZ-2Lower Ground/HW PlantPump Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-PL:Circulating Pumps/MR-2PNL-PL-LZBMS-01:r0c2; MC-PL:Circulating Pumps; A-PL-001
pl.rp-lz-2.trip-alarmPlumbing & Sanitary HotwaterRecirculating PumpRP-LZ-2Lower Ground/HW PlantPump Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-PL:Circulating Pumps/Alarm-1PNL-PL-LZBMS-01:r0c2; MC-PL:Circulating Pumps; A-PL-001
pl.rp-lz-3.motor-statusPlumbing & Sanitary HotwaterRecirculating PumpRP-LZ-3Lower Ground/HW PlantPump Motor Status (Run feedback)DIAuxiliary ContactEquipment SupplierMC-PL:Circulating Pumps/MR-1PNL-PL-LZBMS-01:r0c2; MC-PL:Circulating Pumps; A-PL-001
pl.rp-lz-3.hoa-statusPlumbing & Sanitary HotwaterRecirculating PumpRP-LZ-3Lower Ground/HW PlantPump Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-PL:Circulating Pumps/MR-2PNL-PL-LZBMS-01:r0c2; MC-PL:Circulating Pumps; A-PL-001
pl.rp-lz-3.trip-alarmPlumbing & Sanitary HotwaterRecirculating PumpRP-LZ-3Lower Ground/HW PlantPump Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-PL:Circulating Pumps/Alarm-1PNL-PL-LZBMS-01:r0c2; MC-PL:Circulating Pumps; A-PL-001
pl.hp-hz-1.motor-statusPlumbing & Sanitary HotwaterHeat PumpHP-HZ-1Roofdeck/HW PlantPump Motor Status (Run feedback)HLIAuxiliary Contact (via equipment-panel gateway)Equipment SupplierMC-PL:Heat Pump/MR-1PNL-PL-HZBMS-01:r0c2; MC-PL:Heat Pump; A-PL-001Via HZ equipment-panel HLI per A-PL-001
pl.hp-hz-1.hoa-statusPlumbing & Sanitary HotwaterHeat PumpHP-HZ-1Roofdeck/HW PlantPump Motor Hand/Off/Auto StatusHLIAuxiliary Contact (via equipment-panel gateway)Equipment SupplierMC-PL:Heat Pump/MR-2PNL-PL-HZBMS-01:r0c2; MC-PL:Heat Pump; A-PL-001
pl.hp-hz-1.trip-alarmPlumbing & Sanitary HotwaterHeat PumpHP-HZ-1Roofdeck/HW PlantPump Trip Alarm StatusHLIAuxiliary Contact (via equipment-panel gateway)Equipment SupplierMC-PL:Heat Pump/Alarm-1PNL-PL-HZBMS-01:r0c2; MC-PL:Heat Pump; A-PL-001
pl.hp-hz-2.motor-statusPlumbing & Sanitary HotwaterHeat PumpHP-HZ-2Roofdeck/HW PlantPump Motor Status (Run feedback)HLIAuxiliary Contact (via equipment-panel gateway)Equipment SupplierMC-PL:Heat Pump/MR-1PNL-PL-HZBMS-01:r0c2; MC-PL:Heat Pump; A-PL-001
pl.hp-hz-2.hoa-statusPlumbing & Sanitary HotwaterHeat PumpHP-HZ-2Roofdeck/HW PlantPump Motor Hand/Off/Auto StatusHLIAuxiliary Contact (via equipment-panel gateway)Equipment SupplierMC-PL:Heat Pump/MR-2PNL-PL-HZBMS-01:r0c2; MC-PL:Heat Pump; A-PL-001
pl.hp-hz-2.trip-alarmPlumbing & Sanitary HotwaterHeat PumpHP-HZ-2Roofdeck/HW PlantPump Trip Alarm StatusHLIAuxiliary Contact (via equipment-panel gateway)Equipment SupplierMC-PL:Heat Pump/Alarm-1PNL-PL-HZBMS-01:r0c2; MC-PL:Heat Pump; A-PL-001
pl.hp-hz-3.motor-statusPlumbing & Sanitary HotwaterHeat PumpHP-HZ-3Roofdeck/HW PlantPump Motor Status (Run feedback)HLIAuxiliary Contact (via equipment-panel gateway)Equipment SupplierMC-PL:Heat Pump/MR-1PNL-PL-HZBMS-01:r0c2; MC-PL:Heat Pump; A-PL-001
pl.hp-hz-3.hoa-statusPlumbing & Sanitary HotwaterHeat PumpHP-HZ-3Roofdeck/HW PlantPump Motor Hand/Off/Auto StatusHLIAuxiliary Contact (via equipment-panel gateway)Equipment SupplierMC-PL:Heat Pump/MR-2PNL-PL-HZBMS-01:r0c2; MC-PL:Heat Pump; A-PL-001
pl.hp-hz-3.trip-alarmPlumbing & Sanitary HotwaterHeat PumpHP-HZ-3Roofdeck/HW PlantPump Trip Alarm StatusHLIAuxiliary Contact (via equipment-panel gateway)Equipment SupplierMC-PL:Heat Pump/Alarm-1PNL-PL-HZBMS-01:r0c2; MC-PL:Heat Pump; A-PL-001
pl.rp-hz-1.motor-statusPlumbing & Sanitary HotwaterRecirculating PumpRP-HZ-1Roofdeck/HW PlantPump Motor Status (Run feedback)HLIAuxiliary Contact (via equipment-panel gateway)Equipment SupplierMC-PL:Circulating Pumps/MR-1PNL-PL-HZBMS-01:r0c2; MC-PL:Circulating Pumps; A-PL-001
pl.rp-hz-1.hoa-statusPlumbing & Sanitary HotwaterRecirculating PumpRP-HZ-1Roofdeck/HW PlantPump Motor Hand/Off/Auto StatusHLIAuxiliary Contact (via equipment-panel gateway)Equipment SupplierMC-PL:Circulating Pumps/MR-2PNL-PL-HZBMS-01:r0c2; MC-PL:Circulating Pumps; A-PL-001
pl.rp-hz-1.trip-alarmPlumbing & Sanitary HotwaterRecirculating PumpRP-HZ-1Roofdeck/HW PlantPump Trip Alarm StatusHLIAuxiliary Contact (via equipment-panel gateway)Equipment SupplierMC-PL:Circulating Pumps/Alarm-1PNL-PL-HZBMS-01:r0c2; MC-PL:Circulating Pumps; A-PL-001
pl.rp-hz-2.motor-statusPlumbing & Sanitary HotwaterRecirculating PumpRP-HZ-2Roofdeck/HW PlantPump Motor Status (Run feedback)HLIAuxiliary Contact (via equipment-panel gateway)Equipment SupplierMC-PL:Circulating Pumps/MR-1PNL-PL-HZBMS-01:r0c2; MC-PL:Circulating Pumps; A-PL-001
pl.rp-hz-2.hoa-statusPlumbing & Sanitary HotwaterRecirculating PumpRP-HZ-2Roofdeck/HW PlantPump Motor Hand/Off/Auto StatusHLIAuxiliary Contact (via equipment-panel gateway)Equipment SupplierMC-PL:Circulating Pumps/MR-2PNL-PL-HZBMS-01:r0c2; MC-PL:Circulating Pumps; A-PL-001
pl.rp-hz-2.trip-alarmPlumbing & Sanitary HotwaterRecirculating PumpRP-HZ-2Roofdeck/HW PlantPump Trip Alarm StatusHLIAuxiliary Contact (via equipment-panel gateway)Equipment SupplierMC-PL:Circulating Pumps/Alarm-1PNL-PL-HZBMS-01:r0c2; MC-PL:Circulating Pumps; A-PL-001
pl.rp-hz-3.motor-statusPlumbing & Sanitary HotwaterRecirculating PumpRP-HZ-3Roofdeck/HW PlantPump Motor Status (Run feedback)HLIAuxiliary Contact (via equipment-panel gateway)Equipment SupplierMC-PL:Circulating Pumps/MR-1PNL-PL-HZBMS-01:r0c2; MC-PL:Circulating Pumps; A-PL-001
pl.rp-hz-3.hoa-statusPlumbing & Sanitary HotwaterRecirculating PumpRP-HZ-3Roofdeck/HW PlantPump Motor Hand/Off/Auto StatusHLIAuxiliary Contact (via equipment-panel gateway)Equipment SupplierMC-PL:Circulating Pumps/MR-2PNL-PL-HZBMS-01:r0c2; MC-PL:Circulating Pumps; A-PL-001
pl.rp-hz-3.trip-alarmPlumbing & Sanitary HotwaterRecirculating PumpRP-HZ-3Roofdeck/HW PlantPump Trip Alarm StatusHLIAuxiliary Contact (via equipment-panel gateway)Equipment SupplierMC-PL:Circulating Pumps/Alarm-1PNL-PL-HZBMS-01:r0c2; MC-PL:Circulating Pumps; A-PL-001
vent.tef-1-1.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-1.1GF Main LobbyFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-GFBMS-01:r0c2; MC-ME:EAS
vent.tef-1-1.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-1.1GF Main LobbyFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-GFBMS-01:r0c2; MC-ME:EAS
vent.tef-1-1.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-1.1GF Main LobbyFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-GFBMS-01:r0c2; MC-ME:EAS
vent.tef-1-2.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-1.2GF Main LobbyFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-GFBMS-01:r0c2; MC-ME:EAS
vent.tef-1-2.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-1.2GF Main LobbyFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-GFBMS-01:r0c2; MC-ME:EAS
vent.tef-1-2.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-1.2GF Main LobbyFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-GFBMS-01:r0c2; MC-ME:EAS
vent.tef-1-3.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-1.3GF Main LobbyFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-GFBMS-01:r0c2; MC-ME:EAS
vent.tef-1-3.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-1.3GF Main LobbyFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-GFBMS-01:r0c2; MC-ME:EAS
vent.tef-1-3.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-1.3GF Main LobbyFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-GFBMS-01:r0c2; MC-ME:EAS
vent.tef-1-4.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-1.4GF Main LobbyFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-GFBMS-01:r0c2; MC-ME:EAS
vent.tef-1-4.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-1.4GF Main LobbyFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-GFBMS-01:r0c2; MC-ME:EAS
vent.tef-1-4.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-1.4GF Main LobbyFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-GFBMS-01:r0c2; MC-ME:EAS
vent.ef-1-2a.motor-statusGeneral VentilationExhaust Fan (General)EF-1.2AGF Main LobbyFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-GFBMS-01:r0c2; MC-ME:EAS
vent.ef-1-2a.hoa-statusGeneral VentilationExhaust Fan (General)EF-1.2AGF Main LobbyFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-GFBMS-01:r0c2; MC-ME:EAS
vent.ef-1-2a.trip-alarmGeneral VentilationExhaust Fan (General)EF-1.2AGF Main LobbyFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-GFBMS-01:r0c2; MC-ME:EAS
vent.ef-lpg-1.motor-statusGeneral VentilationExhaust Fan (General)EF-LPG.1GF Main LobbyFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-GFBMS-01:r0c2; MC-ME:EASLPG room exhaust
vent.ef-lpg-1.hoa-statusGeneral VentilationExhaust Fan (General)EF-LPG.1GF Main LobbyFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-GFBMS-01:r0c2; MC-ME:EAS
vent.ef-lpg-1.trip-alarmGeneral VentilationExhaust Fan (General)EF-LPG.1GF Main LobbyFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-GFBMS-01:r0c2; MC-ME:EAS
vent.ef-1mr-1.motor-statusGeneral VentilationExhaust Fan (General)EF-1MR.1GF Main LobbyFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-GFBMS-01:r0c2; MC-ME:EASMechanical room exhaust
vent.ef-1mr-1.hoa-statusGeneral VentilationExhaust Fan (General)EF-1MR.1GF Main LobbyFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-GFBMS-01:r0c2; MC-ME:EAS
vent.ef-1mr-1.trip-alarmGeneral VentilationExhaust Fan (General)EF-1MR.1GF Main LobbyFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-GFBMS-01:r0c2; MC-ME:EAS
vent.ef-1st0-1.motor-statusGeneral VentilationExhaust Fan (General)EF-1ST0.1GF Main LobbyFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-GFBMS-01:r0c2; MC-ME:EASStorage room exhaust
vent.ef-1st0-1.hoa-statusGeneral VentilationExhaust Fan (General)EF-1ST0.1GF Main LobbyFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-GFBMS-01:r0c2; MC-ME:EAS
vent.ef-1st0-1.trip-alarmGeneral VentilationExhaust Fan (General)EF-1ST0.1GF Main LobbyFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-GFBMS-01:r0c2; MC-ME:EAS
vent.ef-mrf-1.motor-statusGeneral VentilationExhaust Fan (General)EF-MRF.1GF Main LobbyFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-GFBMS-01:r0c2; MC-ME:EAS
vent.ef-mrf-1.hoa-statusGeneral VentilationExhaust Fan (General)EF-MRF.1GF Main LobbyFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-GFBMS-01:r0c2; MC-ME:EAS
vent.ef-mrf-1.trip-alarmGeneral VentilationExhaust Fan (General)EF-MRF.1GF Main LobbyFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-GFBMS-01:r0c2; MC-ME:EAS
vent.tef-2-1.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-2.12nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.tef-2-1.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-2.12nd FloorFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.tef-2-1.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-2.12nd FloorFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.tef-2-3.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-2.32nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.tef-2-3.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-2.32nd FloorFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.tef-2-3.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-2.32nd FloorFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.tef-2b-3.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-2B.32nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.tef-2b-3.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-2B.32nd FloorFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.tef-2b-3.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-2B.32nd FloorFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-2b-1.motor-statusGeneral VentilationExhaust Fan (General)EF-2B.12nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-2b-1.hoa-statusGeneral VentilationExhaust Fan (General)EF-2B.12nd FloorFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-2b-1.trip-alarmGeneral VentilationExhaust Fan (General)EF-2B.12nd FloorFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-2b-2.motor-statusGeneral VentilationExhaust Fan (General)EF-2B.22nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-2b-2.hoa-statusGeneral VentilationExhaust Fan (General)EF-2B.22nd FloorFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-2b-2.trip-alarmGeneral VentilationExhaust Fan (General)EF-2B.22nd FloorFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-gs-1.motor-statusGeneral VentilationExhaust Fan (General)EF-GS.12nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-gs-1.hoa-statusGeneral VentilationExhaust Fan (General)EF-GS.12nd FloorFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-gs-1.trip-alarmGeneral VentilationExhaust Fan (General)EF-GS.12nd FloorFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-gs-2.motor-statusGeneral VentilationExhaust Fan (General)EF-GS.22nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-gs-2.hoa-statusGeneral VentilationExhaust Fan (General)EF-GS.22nd FloorFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-gs-2.trip-alarmGeneral VentilationExhaust Fan (General)EF-GS.22nd FloorFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-2-1.motor-statusGeneral VentilationExhaust Fan (General)EF-2.12nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-2-1.hoa-statusGeneral VentilationExhaust Fan (General)EF-2.12nd FloorFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-2-1.trip-alarmGeneral VentilationExhaust Fan (General)EF-2.12nd FloorFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-2-2.motor-statusGeneral VentilationExhaust Fan (General)EF-2.22nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-2-2.hoa-statusGeneral VentilationExhaust Fan (General)EF-2.22nd FloorFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-2-2.trip-alarmGeneral VentilationExhaust Fan (General)EF-2.22nd FloorFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-2-3.motor-statusGeneral VentilationExhaust Fan (General)EF-2.32nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-2-3.hoa-statusGeneral VentilationExhaust Fan (General)EF-2.32nd FloorFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-2-3.trip-alarmGeneral VentilationExhaust Fan (General)EF-2.32nd FloorFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-2-4.motor-statusGeneral VentilationExhaust Fan (General)EF-2.42nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-2-4.hoa-statusGeneral VentilationExhaust Fan (General)EF-2.42nd FloorFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-2-4.trip-alarmGeneral VentilationExhaust Fan (General)EF-2.42nd FloorFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-chr-1.motor-statusGeneral VentilationExhaust Fan (General)EF-CHR.12nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L2BMS-01:r0c2; MC-ME:EASChiller room exhaust
vent.ef-chr-1.hoa-statusGeneral VentilationExhaust Fan (General)EF-CHR.12nd FloorFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-chr-1.trip-alarmGeneral VentilationExhaust Fan (General)EF-CHR.12nd FloorFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-chr-2.motor-statusGeneral VentilationExhaust Fan (General)EF-CHR.22nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-chr-2.hoa-statusGeneral VentilationExhaust Fan (General)EF-CHR.22nd FloorFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.ef-chr-2.trip-alarmGeneral VentilationExhaust Fan (General)EF-CHR.22nd FloorFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L2BMS-01:r0c2; MC-ME:EAS
vent.tef-3a-1.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-3A.13rd Amenity & GuestroomFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3a-1.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-3A.13rd Amenity & GuestroomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3a-1.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-3A.13rd Amenity & GuestroomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3a-2.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-3A.23rd Amenity & GuestroomFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3a-2.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-3A.23rd Amenity & GuestroomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3a-2.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-3A.23rd Amenity & GuestroomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3b.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-3B3rd Amenity & GuestroomFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3b.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-3B3rd Amenity & GuestroomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3b.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-3B3rd Amenity & GuestroomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3c-1.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-3C.13rd Amenity & GuestroomFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3c-1.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-3C.13rd Amenity & GuestroomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3c-1.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-3C.13rd Amenity & GuestroomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3c-2.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-3C.23rd Amenity & GuestroomFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3c-2.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-3C.23rd Amenity & GuestroomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3c-2.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-3C.23rd Amenity & GuestroomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-01.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.13rd Amenity & GuestroomFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-01.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.13rd Amenity & GuestroomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-01.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-3D.13rd Amenity & GuestroomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-02.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.23rd Amenity & GuestroomFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-02.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.23rd Amenity & GuestroomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-02.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-3D.23rd Amenity & GuestroomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-03.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.33rd Amenity & GuestroomFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-03.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.33rd Amenity & GuestroomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-03.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-3D.33rd Amenity & GuestroomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-04.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.43rd Amenity & GuestroomFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-04.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.43rd Amenity & GuestroomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-04.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-3D.43rd Amenity & GuestroomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-05.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.53rd Amenity & GuestroomFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-05.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.53rd Amenity & GuestroomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-05.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-3D.53rd Amenity & GuestroomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-06.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.63rd Amenity & GuestroomFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-06.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.63rd Amenity & GuestroomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-06.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-3D.63rd Amenity & GuestroomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-07.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.73rd Amenity & GuestroomFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-07.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.73rd Amenity & GuestroomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-07.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-3D.73rd Amenity & GuestroomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-08.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.83rd Amenity & GuestroomFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-08.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.83rd Amenity & GuestroomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-08.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-3D.83rd Amenity & GuestroomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-09.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.93rd Amenity & GuestroomFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-09.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.93rd Amenity & GuestroomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-09.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-3D.93rd Amenity & GuestroomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-10.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.103rd Amenity & GuestroomFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-10.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.103rd Amenity & GuestroomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-10.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-3D.103rd Amenity & GuestroomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-11.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.113rd Amenity & GuestroomFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-11.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.113rd Amenity & GuestroomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-11.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-3D.113rd Amenity & GuestroomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-12.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.123rd Amenity & GuestroomFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-12.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.123rd Amenity & GuestroomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-12.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-3D.123rd Amenity & GuestroomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-13.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.133rd Amenity & GuestroomFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-13.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.133rd Amenity & GuestroomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-13.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-3D.133rd Amenity & GuestroomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-14.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.143rd Amenity & GuestroomFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-14.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.143rd Amenity & GuestroomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-14.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-3D.143rd Amenity & GuestroomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-15.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.153rd Amenity & GuestroomFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-15.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.153rd Amenity & GuestroomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-15.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-3D.153rd Amenity & GuestroomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-16.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.163rd Amenity & GuestroomFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-16.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.163rd Amenity & GuestroomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-16.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-3D.163rd Amenity & GuestroomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-17.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.173rd Amenity & GuestroomFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-17.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.173rd Amenity & GuestroomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-17.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-3D.173rd Amenity & GuestroomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-18.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.183rd Amenity & GuestroomFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-18.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.183rd Amenity & GuestroomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-18.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-3D.183rd Amenity & GuestroomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-19.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.193rd Amenity & GuestroomFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-19.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.193rd Amenity & GuestroomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-19.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-3D.193rd Amenity & GuestroomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-20.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.203rd Amenity & GuestroomFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-20.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-3D.203rd Amenity & GuestroomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.tef-3d-20.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-3D.203rd Amenity & GuestroomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L3BMS-01:r0c2; MC-ME:EAS
vent.ef-3-1.motor-statusGeneral VentilationExhaust Fan (General)EF-3.13rd Amenity & GuestroomFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L3BMS-01:r1c2; MC-ME:EAS
vent.ef-3-1.hoa-statusGeneral VentilationExhaust Fan (General)EF-3.13rd Amenity & GuestroomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L3BMS-01:r1c2; MC-ME:EAS
vent.ef-3-1.trip-alarmGeneral VentilationExhaust Fan (General)EF-3.13rd Amenity & GuestroomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L3BMS-01:r1c2; MC-ME:EAS
vent.ef-3-2.motor-statusGeneral VentilationExhaust Fan (General)EF-3.23rd Amenity & GuestroomFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-L3BMS-01:r1c2; MC-ME:EAS
vent.ef-3-2.hoa-statusGeneral VentilationExhaust Fan (General)EF-3.23rd Amenity & GuestroomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-L3BMS-01:r1c2; MC-ME:EAS
vent.ef-3-2.trip-alarmGeneral VentilationExhaust Fan (General)EF-3.23rd Amenity & GuestroomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-L3BMS-01:r1c2; MC-ME:EAS
vent.tef-b-1.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-B.1BasementFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.tef-b-1.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-B.1BasementFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.tef-b-1.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-B.1BasementFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.tef-b-2.motor-statusGeneral VentilationExhaust Fan (Toilet)TEF-B.2BasementFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.tef-b-2.hoa-statusGeneral VentilationExhaust Fan (Toilet)TEF-B.2BasementFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.tef-b-2.trip-alarmGeneral VentilationExhaust Fan (Toilet)TEF-B.2BasementFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-b-1.motor-statusGeneral VentilationExhaust Fan (General)EF-B.1BasementFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-b-1.hoa-statusGeneral VentilationExhaust Fan (General)EF-B.1BasementFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-b-1.trip-alarmGeneral VentilationExhaust Fan (General)EF-B.1BasementFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-b-2.motor-statusGeneral VentilationExhaust Fan (General)EF-B.2BasementFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-b-2.hoa-statusGeneral VentilationExhaust Fan (General)EF-B.2BasementFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-b-2.trip-alarmGeneral VentilationExhaust Fan (General)EF-B.2BasementFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-bs-1.motor-statusGeneral VentilationExhaust Fan (General)EF-BS.1BasementFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-bs-1.hoa-statusGeneral VentilationExhaust Fan (General)EF-BS.1BasementFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-bs-1.trip-alarmGeneral VentilationExhaust Fan (General)EF-BS.1BasementFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-bs-2.motor-statusGeneral VentilationExhaust Fan (General)EF-BS.2BasementFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-bs-2.hoa-statusGeneral VentilationExhaust Fan (General)EF-BS.2BasementFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-bs-2.trip-alarmGeneral VentilationExhaust Fan (General)EF-BS.2BasementFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-glz-1.motor-statusGeneral VentilationExhaust Fan (General)EF-GLZ.1BasementFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-glz-1.hoa-statusGeneral VentilationExhaust Fan (General)EF-GLZ.1BasementFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-glz-1.trip-alarmGeneral VentilationExhaust Fan (General)EF-GLZ.1BasementFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-glz-2.motor-statusGeneral VentilationExhaust Fan (General)EF-GLZ.2BasementFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-glz-2.hoa-statusGeneral VentilationExhaust Fan (General)EF-GLZ.2BasementFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-glz-2.trip-alarmGeneral VentilationExhaust Fan (General)EF-GLZ.2BasementFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-3sf-2.motor-statusGeneral VentilationExhaust Fan (General)EF-3SF.2BasementFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-3sf-2.hoa-statusGeneral VentilationExhaust Fan (General)EF-3SF.2BasementFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-3sf-2.trip-alarmGeneral VentilationExhaust Fan (General)EF-3SF.2BasementFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-8r-1.motor-statusGeneral VentilationExhaust Fan (General)EF-8R.1BasementFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EASTag as-read; verify Q-008
vent.ef-8r-1.hoa-statusGeneral VentilationExhaust Fan (General)EF-8R.1BasementFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-8r-1.trip-alarmGeneral VentilationExhaust Fan (General)EF-8R.1BasementFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-rr-2.motor-statusGeneral VentilationExhaust Fan (General)EF-RR.2BasementFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EASTag as-read; verify Q-008
vent.ef-rr-2.hoa-statusGeneral VentilationExhaust Fan (General)EF-RR.2BasementFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-rr-2.trip-alarmGeneral VentilationExhaust Fan (General)EF-RR.2BasementFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-mc-1.motor-statusGeneral VentilationExhaust Fan (General)EF-MC.1BasementFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-mc-1.hoa-statusGeneral VentilationExhaust Fan (General)EF-MC.1BasementFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-mc-1.trip-alarmGeneral VentilationExhaust Fan (General)EF-MC.1BasementFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-hp-1.motor-statusGeneral VentilationExhaust Fan (General)EF-HP.1BasementFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-hp-1.hoa-statusGeneral VentilationExhaust Fan (General)EF-HP.1BasementFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-hp-1.trip-alarmGeneral VentilationExhaust Fan (General)EF-HP.1BasementFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-pr-1.motor-statusGeneral VentilationExhaust Fan (General)EF-PR.1BasementFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-pr-1.hoa-statusGeneral VentilationExhaust Fan (General)EF-PR.1BasementFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-pr-1.trip-alarmGeneral VentilationExhaust Fan (General)EF-PR.1BasementFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-mfp-1.motor-statusGeneral VentilationExhaust Fan (General)EF-MFP.1BasementFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-mfp-1.hoa-statusGeneral VentilationExhaust Fan (General)EF-MFP.1BasementFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-mfp-1.trip-alarmGeneral VentilationExhaust Fan (General)EF-MFP.1BasementFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-pr-2.motor-statusGeneral VentilationExhaust Fan (General)EF-PR.2BasementFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-pr-2.hoa-statusGeneral VentilationExhaust Fan (General)EF-PR.2BasementFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-pr-2.trip-alarmGeneral VentilationExhaust Fan (General)EF-PR.2BasementFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-BSMTBMS-01:r1c2; MC-ME:EAS
vent.ef-rd-1.motor-statusGeneral VentilationExhaust Fan (General)EF-RD.1RoofdeckFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-RDBMS-01:r1c2; MC-ME:EAS
vent.ef-rd-1.hoa-statusGeneral VentilationExhaust Fan (General)EF-RD.1RoofdeckFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-RDBMS-01:r1c2; MC-ME:EAS
vent.ef-rd-1.trip-alarmGeneral VentilationExhaust Fan (General)EF-RD.1RoofdeckFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-RDBMS-01:r1c2; MC-ME:EAS
vent.ef-rd-2.motor-statusGeneral VentilationExhaust Fan (General)EF-RD.2RoofdeckFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-RDBMS-01:r1c2; MC-ME:EAS
vent.ef-rd-2.hoa-statusGeneral VentilationExhaust Fan (General)EF-RD.2RoofdeckFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-RDBMS-01:r1c2; MC-ME:EAS
vent.ef-rd-2.trip-alarmGeneral VentilationExhaust Fan (General)EF-RD.2RoofdeckFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-RDBMS-01:r1c2; MC-ME:EAS
vent.ef-rd-extra.motor-statusGeneral VentilationExhaust Fan (General)EF-1 (RD)RoofdeckFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-1PNL-VENT-RDBMS-01:r1c2; MC-ME:EASTag '(EF-1)' as-read; refine if Q-008 reveals different tag
vent.ef-rd-extra.hoa-statusGeneral VentilationExhaust Fan (General)EF-1 (RD)RoofdeckFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/MR-2PNL-VENT-RDBMS-01:r1c2; MC-ME:EAS
vent.ef-rd-extra.trip-alarmGeneral VentilationExhaust Fan (General)EF-1 (RD)RoofdeckFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:EAS/Alarm-1PNL-VENT-RDBMS-01:r1c2; MC-ME:EAS
bl.sb-1.steam-pressureBoiler/LaundrySteam BoilerSB-1Lower Ground/Boiler RoomSupply Steam PressureAIPressure SensorBMS ContractorMC-ME:Boiler/MR-11PNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-1.feedwater-tempBoiler/LaundrySteam BoilerSB-1Lower Ground/Boiler RoomFeedwater Supply TemperatureAITemperature Sensor (immersion/thermowell)BMS ContractorMC-ME:BoilerPNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-1.fluegas-tempBoiler/LaundrySteam BoilerSB-1Lower Ground/Boiler RoomFluegas TemperatureAITemperature Sensor (high-temp/duct insertion)BMS ContractorMC-ME:Boiler/MR-8PNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-1.fluegas-o2Boiler/LaundrySteam BoilerSB-1Lower Ground/Boiler RoomFluegas Oxygen LevelAIOxygen SensorBMS ContractorMC-ME:Boiler/MR-9PNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-1.water-level-lowBoiler/LaundrySteam BoilerSB-1Lower Ground/Boiler RoomLow Water LevelDILevel SensorEquipment SupplierMC-ME:Boiler/Alarm-3PNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-1.water-level-highBoiler/LaundrySteam BoilerSB-1Lower Ground/Boiler RoomHigh Water LevelDILevel SensorEquipment SupplierMC-ME:Boiler/Alarm-3PNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-1.burner-powerBoiler/LaundrySteam BoilerSB-1Lower Ground/Boiler RoomBurner PowerDIAuxiliary ContactEquipment SupplierMC-ME:BoilerPNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-1.fire-smallBoiler/LaundrySteam BoilerSB-1Lower Ground/Boiler RoomSmall Fire Control SignalDIAuxiliary ContactEquipment SupplierMC-ME:Boiler/MR-5PNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-1.fire-bigBoiler/LaundrySteam BoilerSB-1Lower Ground/Boiler RoomBig Fire Control SignalDIAuxiliary ContactEquipment SupplierMC-ME:Boiler/MR-6PNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-1.waterfeed-pumpBoiler/LaundrySteam BoilerSB-1Lower Ground/Boiler RoomWaterfeed Pump StatusDIAuxiliary ContactEquipment SupplierMC-ME:Boiler/MR-4PNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-1.burner-statusBoiler/LaundrySteam BoilerSB-1Lower Ground/Boiler RoomBurner StatusDIAuxiliary ContactEquipment SupplierMC-ME:Boiler/MR-2PNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-1.burner-runningBoiler/LaundrySteam BoilerSB-1Lower Ground/Boiler RoomBurner Fire Running StatusDIAuxiliary ContactEquipment SupplierMC-ME:BoilerPNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-1.blower-statusBoiler/LaundrySteam BoilerSB-1Lower Ground/Boiler RoomBlower Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:Boiler/MR-3PNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-1.fuel-oil-pumpBoiler/LaundrySteam BoilerSB-1Lower Ground/Boiler RoomFuel Oil Pump StatusDIAuxiliary ContactEquipment SupplierMC-ME:Boiler/MR-1PNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-1.blowdown-vlv-statBoiler/LaundrySteam BoilerSB-1Lower Ground/Boiler RoomMotorized Valve Status — Blowdown WaterDIElectric Valve Actuator (limit switch)BMS ContractorMC-ME:Boiler/MR-7PNL-BL-LZBMS-01:r1c1; MC-ME:BoilerBMS-supplied actuator
bl.sb-1.blowdown-vlv-cmdBoiler/LaundrySteam BoilerSB-1Lower Ground/Boiler RoomMotorized Valve Control — Blowdown WaterDOElectric Valve ActuatorBMS ContractorMC-ME:Boiler/Turn ON/OFF blowdownPNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-2.steam-pressureBoiler/LaundrySteam BoilerSB-2Lower Ground/Boiler RoomSupply Steam PressureAIPressure SensorBMS ContractorMC-ME:Boiler/MR-11PNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-2.feedwater-tempBoiler/LaundrySteam BoilerSB-2Lower Ground/Boiler RoomFeedwater Supply TemperatureAITemperature Sensor (immersion/thermowell)BMS ContractorMC-ME:BoilerPNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-2.fluegas-tempBoiler/LaundrySteam BoilerSB-2Lower Ground/Boiler RoomFluegas TemperatureAITemperature Sensor (high-temp/duct insertion)BMS ContractorMC-ME:Boiler/MR-8PNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-2.fluegas-o2Boiler/LaundrySteam BoilerSB-2Lower Ground/Boiler RoomFluegas Oxygen LevelAIOxygen SensorBMS ContractorMC-ME:Boiler/MR-9PNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-2.water-level-lowBoiler/LaundrySteam BoilerSB-2Lower Ground/Boiler RoomLow Water LevelDILevel SensorEquipment SupplierMC-ME:Boiler/Alarm-3PNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-2.water-level-highBoiler/LaundrySteam BoilerSB-2Lower Ground/Boiler RoomHigh Water LevelDILevel SensorEquipment SupplierMC-ME:Boiler/Alarm-3PNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-2.burner-powerBoiler/LaundrySteam BoilerSB-2Lower Ground/Boiler RoomBurner PowerDIAuxiliary ContactEquipment SupplierMC-ME:BoilerPNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-2.fire-smallBoiler/LaundrySteam BoilerSB-2Lower Ground/Boiler RoomSmall Fire Control SignalDIAuxiliary ContactEquipment SupplierMC-ME:Boiler/MR-5PNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-2.fire-bigBoiler/LaundrySteam BoilerSB-2Lower Ground/Boiler RoomBig Fire Control SignalDIAuxiliary ContactEquipment SupplierMC-ME:Boiler/MR-6PNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-2.waterfeed-pumpBoiler/LaundrySteam BoilerSB-2Lower Ground/Boiler RoomWaterfeed Pump StatusDIAuxiliary ContactEquipment SupplierMC-ME:Boiler/MR-4PNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-2.burner-statusBoiler/LaundrySteam BoilerSB-2Lower Ground/Boiler RoomBurner StatusDIAuxiliary ContactEquipment SupplierMC-ME:Boiler/MR-2PNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-2.burner-runningBoiler/LaundrySteam BoilerSB-2Lower Ground/Boiler RoomBurner Fire Running StatusDIAuxiliary ContactEquipment SupplierMC-ME:BoilerPNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-2.blower-statusBoiler/LaundrySteam BoilerSB-2Lower Ground/Boiler RoomBlower Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:Boiler/MR-3PNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-2.fuel-oil-pumpBoiler/LaundrySteam BoilerSB-2Lower Ground/Boiler RoomFuel Oil Pump StatusDIAuxiliary ContactEquipment SupplierMC-ME:Boiler/MR-1PNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-2.blowdown-vlv-statBoiler/LaundrySteam BoilerSB-2Lower Ground/Boiler RoomMotorized Valve Status — Blowdown WaterDIElectric Valve Actuator (limit switch)BMS ContractorMC-ME:Boiler/MR-7PNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
bl.sb-2.blowdown-vlv-cmdBoiler/LaundrySteam BoilerSB-2Lower Ground/Boiler RoomMotorized Valve Control — Blowdown WaterDOElectric Valve ActuatorBMS ContractorMC-ME:Boiler/Turn ON/OFF blowdownPNL-BL-LZBMS-01:r1c1; MC-ME:Boiler
doas.doas-2w.networkDOAS - Casino MVACDOAS UnitDOAS-2W2nd Level/Casino MVAC PlantBACnet/IP gateway to DOAS controllerNetworkDOAS Controller (BACnet)Equipment SupplierMC-ME:Common Areas DOAS; BMS-02 Casino MVACPNL-DOAS-L2BMS-02:r0c1; MC-ME:DOAS
doas.doas-2w.faf-start-cmdDOAS - Casino MVACDOAS UnitDOAS-2W2nd Level/Casino MVAC PlantFresh Air Fan Start/Stop ControlDOContactor relayEquipment SupplierMC-ME:DOAS/Turn ON/OFFPNL-DOAS-L2BMS-02:r0c1; MC-ME:DOAS
doas.doas-2w.faf-motor-statusDOAS - Casino MVACDOAS UnitDOAS-2W2nd Level/Casino MVAC PlantFresh Air Fan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:DOAS/MR-1PNL-DOAS-L2BMS-02:r0c1; MC-ME:DOAS
doas.doas-2w.faf-hoa-statusDOAS - Casino MVACDOAS UnitDOAS-2W2nd Level/Casino MVAC PlantFresh Air Fan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:DOAS/MR-2PNL-DOAS-L2BMS-02:r0c1; MC-ME:DOAS
doas.doas-2w.faf-trip-alarmDOAS - Casino MVACDOAS UnitDOAS-2W2nd Level/Casino MVAC PlantFresh Air Fan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:DOAS/Alarm-1PNL-DOAS-L2BMS-02:r0c1; MC-ME:DOAS
doas.doas-2w.faf-vfd-speed-fbDOAS - Casino MVACDOAS UnitDOAS-2W2nd Level/Casino MVAC PlantFresh Air Fan VFD Speed Monitoring (feedback)HLIVFDEquipment SupplierMC-ME:DOAS/MR-4PNL-DOAS-L2BMS-02:r0c1; MC-ME:DOASVia VFD BACnet
doas.doas-2w.faf-vfd-controlDOAS - Casino MVACDOAS UnitDOAS-2W2nd Level/Casino MVAC PlantFresh Air Fan Control On/Off/ModulatingHLIVFDEquipment SupplierMC-ME:DOAS/Turn ON/OFF/ModulatePNL-DOAS-L2BMS-02:r0c1; MC-ME:DOASVia VFD BACnet
doas.doas-2w.oa-db-tempDOAS - Casino MVACDOAS UnitDOAS-2W2nd Level/Casino MVAC PlantOutdoor (Ambient) Dry-Bulb TemperatureAITemperature Sensor (outdoor/duct)BMS ContractorMC-ME:DOAS/MR-7PNL-DOAS-L2BMS-02:r0c1; MC-ME:DOAS
doas.doas-2w.oa-flowDOAS - Casino MVACDOAS UnitDOAS-2W2nd Level/Casino MVAC PlantOutdoor Air Flow Monitoring (Outside-Supply Air)AIFlow Sensor (duct insertion)BMS ContractorMC-ME:DOAS/MR-7PNL-DOAS-L2BMS-02:r0c1; MC-ME:DOAS
doas.doas-2w.oa-rhDOAS - Casino MVACDOAS UnitDOAS-2W2nd Level/Casino MVAC PlantOutdoor Air Humidity Monitoring (Outdoor-Supply Air)AIHumidity Sensor (outdoor/duct)BMS ContractorMC-ME:DOAS/MR-7PNL-DOAS-L2BMS-02:r0c1; MC-ME:DOAS
doas.doas-2w.oa-damper-statusDOAS - Casino MVACDOAS UnitDOAS-2W2nd Level/Casino MVAC PlantOutdoor Air Motorized Damper StatusDIDamper Controller (limit/feedback)ME ContractorMC-ME:DOAS/MR-5PNL-DOAS-L2BMS-02:r0c1; MC-ME:DOASDamper supplied by ME
doas.doas-2w.oa-damper-cmdDOAS - Casino MVACDOAS UnitDOAS-2W2nd Level/Casino MVAC PlantOutdoor Air Motorized Damper Control On/Off/ModulatingAODamper Controller (0-10V or 4-20mA)ME ContractorMC-ME:DOAS/Turn ON/OFF/Modulate-3PNL-DOAS-L2BMS-02:r0c1; MC-ME:DOAS
doas.doas-2w.mixed-air-tempDOAS - Casino MVACDOAS UnitDOAS-2W2nd Level/Casino MVAC PlantIndoor Mixed Air TemperatureAITemperature Sensor (duct insertion)BMS ContractorMC-ME:DOAS/MR-8PNL-DOAS-L2BMS-02:r0c1; MC-ME:DOAS
doas.doas-2w.mixed-air-rhDOAS - Casino MVACDOAS UnitDOAS-2W2nd Level/Casino MVAC PlantIndoor Mixed Air HumidityAIHumidity Sensor (duct insertion)BMS ContractorMC-ME:DOAS/MR-9PNL-DOAS-L2BMS-02:r0c1; MC-ME:DOAS
doas.doas-2w.chw-vlv-statusDOAS - Casino MVACDOAS UnitDOAS-2W2nd Level/Casino MVAC PlantTwo-Way CHW Modulating Valve StatusDIElectric Valve Actuator (limit switch)ME ContractorMC-ME:DOAS/MR-6PNL-DOAS-L2BMS-02:r0c1; MC-ME:DOASValve supplied by ME
doas.doas-2w.chw-vlv-cmdDOAS - Casino MVACDOAS UnitDOAS-2W2nd Level/Casino MVAC PlantCHW Modulating Valve Control On/Off/ModulatingAOElectric Valve Actuator (0-10V/4-20mA)ME ContractorMC-ME:DOAS/Modulate-4PNL-DOAS-L2BMS-02:r0c1; MC-ME:DOAS
doas.doas-2w.supply-air-tempDOAS - Casino MVACDOAS UnitDOAS-2W2nd Level/Casino MVAC PlantIndoor Supply Air TemperatureAITemperature Sensor (duct insertion)BMS ContractorMC-ME:DOAS/MR-10PNL-DOAS-L2BMS-02:r0c1; MC-ME:DOAS
doas.doas-2w.supply-air-rhDOAS - Casino MVACDOAS UnitDOAS-2W2nd Level/Casino MVAC PlantIndoor Supply Air HumidityAIHumidity Sensor (duct insertion)BMS ContractorMC-ME:DOASPNL-DOAS-L2BMS-02:r0c1; MC-ME:DOAS
doas.doas-2w.exhaust-air-tempDOAS - Casino MVACDOAS UnitDOAS-2W2nd Level/Casino MVAC PlantIndoor Exhaust Air TemperatureAITemperature Sensor (duct insertion)BMS ContractorMC-ME:DOAS/MR-11PNL-DOAS-L2BMS-02:r0c1; MC-ME:DOAS
doas.doas-2w.eaf-start-cmdDOAS - Casino MVACDOAS UnitDOAS-2W2nd Level/Casino MVAC PlantExhaust Fan Start/Stop ControlDOContactor relayEquipment SupplierMC-ME:DOAS/Turn ON/OFFPNL-DOAS-L2BMS-02:r0c1; MC-ME:DOAS
doas.doas-2w.eaf-motor-statusDOAS - Casino MVACDOAS UnitDOAS-2W2nd Level/Casino MVAC PlantExhaust Fan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:DOAS/MR-1PNL-DOAS-L2BMS-02:r0c1; MC-ME:DOAS
doas.doas-2w.eaf-hoa-statusDOAS - Casino MVACDOAS UnitDOAS-2W2nd Level/Casino MVAC PlantExhaust Fan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:DOAS/MR-2PNL-DOAS-L2BMS-02:r0c1; MC-ME:DOAS
doas.doas-2w.eaf-trip-alarmDOAS - Casino MVACDOAS UnitDOAS-2W2nd Level/Casino MVAC PlantExhaust Fan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:DOAS/Alarm-1PNL-DOAS-L2BMS-02:r0c1; MC-ME:DOAS
doas.doas-2w.eaf-static-pressDOAS - Casino MVACDOAS UnitDOAS-2W2nd Level/Casino MVAC PlantExhaust Fan Static Pressure TransmitterAIDifferential Pressure Sensor (duct)BMS ContractorMC-ME:DOASPNL-DOAS-L2BMS-02:r0c1; MC-ME:DOAS
doas.doas-2w.eaf-vfd-speed-fbDOAS - Casino MVACDOAS UnitDOAS-2W2nd Level/Casino MVAC PlantExhaust Fan VFD Speed Monitoring (feedback)HLIVFDEquipment SupplierMC-ME:DOAS/MR-4PNL-DOAS-L2BMS-02:r0c1; MC-ME:DOASVia VFD BACnet
doas.doas-2w.eaf-vfd-controlDOAS - Casino MVACDOAS UnitDOAS-2W2nd Level/Casino MVAC PlantExhaust Fan Control On/Off/ModulatingHLIVFDEquipment SupplierMC-ME:DOAS/Turn ON/OFFPNL-DOAS-L2BMS-02:r0c1; MC-ME:DOASVia VFD BACnet
doas.doas-rd-1.networkDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.1Roofdeck/Hotel DOAS PlantBACnet/IP gateway to DOAS controllerNetworkDOAS Controller (BACnet)Equipment SupplierMC-ME:Roof Deck DOAS Serving Guestrooms; BMS-02 Hotel/RoofdeckPNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-1.faf-start-cmdDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.1Roofdeck/Hotel DOAS PlantFresh Air Fan Start/Stop ControlDOContactor relayEquipment SupplierMC-ME:DOAS/Turn ON/OFFPNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-1.faf-motor-statusDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.1Roofdeck/Hotel DOAS PlantFresh Air Fan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:DOAS/MR-1PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-1.faf-hoa-statusDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.1Roofdeck/Hotel DOAS PlantFresh Air Fan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:DOAS/MR-2PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-1.faf-trip-alarmDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.1Roofdeck/Hotel DOAS PlantFresh Air Fan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:DOAS/Alarm-1PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-1.faf-vfd-speed-fbDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.1Roofdeck/Hotel DOAS PlantFresh Air Fan VFD Speed Monitoring (feedback)HLIVFDEquipment SupplierMC-ME:DOAS/MR-4PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-1.faf-vfd-controlDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.1Roofdeck/Hotel DOAS PlantFresh Air Fan Control On/Off/ModulatingHLIVFDEquipment SupplierMC-ME:DOAS/Turn ON/OFF/ModulatePNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-1.oa-db-tempDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.1Roofdeck/Hotel DOAS PlantOutdoor (Ambient) Dry-Bulb TemperatureAITemperature Sensor (outdoor/duct)BMS ContractorMC-ME:DOAS/MR-7PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-1.oa-flowDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.1Roofdeck/Hotel DOAS PlantOutdoor Air Flow Monitoring (Outside-Supply Air)AIFlow Sensor (duct insertion)BMS ContractorMC-ME:DOAS/MR-7PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-1.oa-rhDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.1Roofdeck/Hotel DOAS PlantOutdoor Air Humidity Monitoring (Outdoor-Supply Air)AIHumidity Sensor (outdoor/duct)BMS ContractorMC-ME:DOAS/MR-7PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-1.oa-damper-statusDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.1Roofdeck/Hotel DOAS PlantOutdoor Air Motorized Damper StatusDIDamper Controller (limit/feedback)ME ContractorMC-ME:DOAS/MR-5PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-1.oa-damper-cmdDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.1Roofdeck/Hotel DOAS PlantOutdoor Air Motorized Damper Control On/Off/ModulatingAODamper Controller (0-10V or 4-20mA)ME ContractorMC-ME:DOAS/Turn ON/OFF/Modulate-3PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-1.mixed-air-tempDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.1Roofdeck/Hotel DOAS PlantIndoor Mixed Air TemperatureAITemperature Sensor (duct insertion)BMS ContractorMC-ME:DOAS/MR-8PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-1.mixed-air-rhDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.1Roofdeck/Hotel DOAS PlantIndoor Mixed Air HumidityAIHumidity Sensor (duct insertion)BMS ContractorMC-ME:DOAS/MR-9PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-1.chw-vlv-statusDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.1Roofdeck/Hotel DOAS PlantTwo-Way CHW Modulating Valve StatusDIElectric Valve Actuator (limit switch)ME ContractorMC-ME:DOAS/MR-6PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-1.chw-vlv-cmdDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.1Roofdeck/Hotel DOAS PlantCHW Modulating Valve Control On/Off/ModulatingAOElectric Valve Actuator (0-10V/4-20mA)ME ContractorMC-ME:DOAS/Modulate-4PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-1.supply-air-tempDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.1Roofdeck/Hotel DOAS PlantIndoor Supply Air TemperatureAITemperature Sensor (duct insertion)BMS ContractorMC-ME:DOAS/MR-10PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-1.exhaust-air-rhDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.1Roofdeck/Hotel DOAS PlantIndoor Exhaust Air HumidityAIHumidity Sensor (duct insertion)BMS ContractorMC-ME:DOASPNL-DOAS-RDBMS-02:r1c1; MC-ME:DOASRoofdeck DOAS uses exhaust RH (not supply) per MC Standards Roof Deck section
doas.doas-rd-1.exhaust-air-tempDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.1Roofdeck/Hotel DOAS PlantIndoor Exhaust Air TemperatureAITemperature Sensor (duct insertion)BMS ContractorMC-ME:DOAS/MR-11PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-1.eaf-start-cmdDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.1Roofdeck/Hotel DOAS PlantExhaust Fan Start/Stop ControlDOContactor relayEquipment SupplierMC-ME:DOAS/Turn ON/OFFPNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-1.eaf-motor-statusDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.1Roofdeck/Hotel DOAS PlantExhaust Fan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:DOAS/MR-1PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-1.eaf-hoa-statusDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.1Roofdeck/Hotel DOAS PlantExhaust Fan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:DOAS/MR-2PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-1.eaf-trip-alarmDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.1Roofdeck/Hotel DOAS PlantExhaust Fan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:DOAS/Alarm-1PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-1.eaf-static-pressDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.1Roofdeck/Hotel DOAS PlantExhaust Fan Static Pressure TransmitterAIDifferential Pressure Sensor (duct)BMS ContractorMC-ME:DOASPNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-1.eaf-vfd-speed-fbDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.1Roofdeck/Hotel DOAS PlantExhaust Fan VFD Speed Monitoring (feedback)HLIVFDEquipment SupplierMC-ME:DOAS/MR-4PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-1.eaf-vfd-controlDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.1Roofdeck/Hotel DOAS PlantExhaust Fan Control On/Off/ModulatingHLIVFDEquipment SupplierMC-ME:DOAS/Turn ON/OFFPNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-2.networkDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.2Roofdeck/Hotel DOAS PlantBACnet/IP gateway to DOAS controllerNetworkDOAS Controller (BACnet)Equipment SupplierMC-ME:Roof Deck DOAS Serving Guestrooms; BMS-02 Hotel/RoofdeckPNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-2.faf-start-cmdDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.2Roofdeck/Hotel DOAS PlantFresh Air Fan Start/Stop ControlDOContactor relayEquipment SupplierMC-ME:DOAS/Turn ON/OFFPNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-2.faf-motor-statusDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.2Roofdeck/Hotel DOAS PlantFresh Air Fan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:DOAS/MR-1PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-2.faf-hoa-statusDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.2Roofdeck/Hotel DOAS PlantFresh Air Fan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:DOAS/MR-2PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-2.faf-trip-alarmDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.2Roofdeck/Hotel DOAS PlantFresh Air Fan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:DOAS/Alarm-1PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-2.faf-vfd-speed-fbDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.2Roofdeck/Hotel DOAS PlantFresh Air Fan VFD Speed Monitoring (feedback)HLIVFDEquipment SupplierMC-ME:DOAS/MR-4PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-2.faf-vfd-controlDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.2Roofdeck/Hotel DOAS PlantFresh Air Fan Control On/Off/ModulatingHLIVFDEquipment SupplierMC-ME:DOAS/Turn ON/OFF/ModulatePNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-2.oa-db-tempDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.2Roofdeck/Hotel DOAS PlantOutdoor (Ambient) Dry-Bulb TemperatureAITemperature Sensor (outdoor/duct)BMS ContractorMC-ME:DOAS/MR-7PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-2.oa-flowDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.2Roofdeck/Hotel DOAS PlantOutdoor Air Flow Monitoring (Outside-Supply Air)AIFlow Sensor (duct insertion)BMS ContractorMC-ME:DOAS/MR-7PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-2.oa-rhDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.2Roofdeck/Hotel DOAS PlantOutdoor Air Humidity Monitoring (Outdoor-Supply Air)AIHumidity Sensor (outdoor/duct)BMS ContractorMC-ME:DOAS/MR-7PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-2.oa-damper-statusDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.2Roofdeck/Hotel DOAS PlantOutdoor Air Motorized Damper StatusDIDamper Controller (limit/feedback)ME ContractorMC-ME:DOAS/MR-5PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-2.oa-damper-cmdDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.2Roofdeck/Hotel DOAS PlantOutdoor Air Motorized Damper Control On/Off/ModulatingAODamper Controller (0-10V or 4-20mA)ME ContractorMC-ME:DOAS/Turn ON/OFF/Modulate-3PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-2.mixed-air-tempDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.2Roofdeck/Hotel DOAS PlantIndoor Mixed Air TemperatureAITemperature Sensor (duct insertion)BMS ContractorMC-ME:DOAS/MR-8PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-2.mixed-air-rhDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.2Roofdeck/Hotel DOAS PlantIndoor Mixed Air HumidityAIHumidity Sensor (duct insertion)BMS ContractorMC-ME:DOAS/MR-9PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-2.chw-vlv-statusDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.2Roofdeck/Hotel DOAS PlantTwo-Way CHW Modulating Valve StatusDIElectric Valve Actuator (limit switch)ME ContractorMC-ME:DOAS/MR-6PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-2.chw-vlv-cmdDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.2Roofdeck/Hotel DOAS PlantCHW Modulating Valve Control On/Off/ModulatingAOElectric Valve Actuator (0-10V/4-20mA)ME ContractorMC-ME:DOAS/Modulate-4PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-2.supply-air-tempDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.2Roofdeck/Hotel DOAS PlantIndoor Supply Air TemperatureAITemperature Sensor (duct insertion)BMS ContractorMC-ME:DOAS/MR-10PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-2.exhaust-air-rhDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.2Roofdeck/Hotel DOAS PlantIndoor Exhaust Air HumidityAIHumidity Sensor (duct insertion)BMS ContractorMC-ME:DOASPNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-2.exhaust-air-tempDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.2Roofdeck/Hotel DOAS PlantIndoor Exhaust Air TemperatureAITemperature Sensor (duct insertion)BMS ContractorMC-ME:DOAS/MR-11PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-2.eaf-start-cmdDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.2Roofdeck/Hotel DOAS PlantExhaust Fan Start/Stop ControlDOContactor relayEquipment SupplierMC-ME:DOAS/Turn ON/OFFPNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-2.eaf-motor-statusDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.2Roofdeck/Hotel DOAS PlantExhaust Fan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:DOAS/MR-1PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-2.eaf-hoa-statusDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.2Roofdeck/Hotel DOAS PlantExhaust Fan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:DOAS/MR-2PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-2.eaf-trip-alarmDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.2Roofdeck/Hotel DOAS PlantExhaust Fan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:DOAS/Alarm-1PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-2.eaf-static-pressDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.2Roofdeck/Hotel DOAS PlantExhaust Fan Static Pressure TransmitterAIDifferential Pressure Sensor (duct)BMS ContractorMC-ME:DOASPNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-2.eaf-vfd-speed-fbDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.2Roofdeck/Hotel DOAS PlantExhaust Fan VFD Speed Monitoring (feedback)HLIVFDEquipment SupplierMC-ME:DOAS/MR-4PNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
doas.doas-rd-2.eaf-vfd-controlDOAS - Hotel/RoofdeckDOAS UnitDOAS-RD.2Roofdeck/Hotel DOAS PlantExhaust Fan Control On/Off/ModulatingHLIVFDEquipment SupplierMC-ME:DOAS/Turn ON/OFFPNL-DOAS-RDBMS-02:r1c1; MC-ME:DOAS
ahu.ahu-2m-1.networkAHU - CasinoAHU (Modulating CHW-served)AHU-2M.12nd Level/Casino MVAC PlantBACnet/IP gateway to AHU controllerNetworkAHU Controller (BACnet)Equipment SupplierMC-ME:AHU-AC at 2nd Level; BMS-02 AHU 2nd LevelPNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-AC
ahu.ahu-2m-1.fan-motor-statusAHU - CasinoAHU (Modulating CHW-served)AHU-2M.12nd Level/Casino MVAC PlantFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:AHU-AC/MR-1PNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-AC
ahu.ahu-2m-1.fan-trip-statusAHU - CasinoAHU (Modulating CHW-served)AHU-2M.12nd Level/Casino MVAC PlantFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:AHU-AC/Alarm-1PNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-AC
ahu.ahu-2m-1.vfd-speed-fbAHU - CasinoAHU (Modulating CHW-served)AHU-2M.12nd Level/Casino MVAC PlantVFD Speed Monitoring (feedback)HLIVFDEquipment SupplierMC-ME:AHU-AC/MR-7PNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-ACVia VFD BACnet
ahu.ahu-2m-1.fan-control-cmdAHU - CasinoAHU (Modulating CHW-served)AHU-2M.12nd Level/Casino MVAC PlantFan Control On/Off/ModulatingHLIVFDEquipment SupplierMC-ME:AHU-AC/Turn ON/OFFPNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-ACVia VFD BACnet
ahu.ahu-2m-1.supply-air-tempAHU - CasinoAHU (Modulating CHW-served)AHU-2M.12nd Level/Casino MVAC PlantSupply Air TemperatureAITemperature Sensor (duct insertion)BMS ContractorMC-ME:AHU-AC/MR-6PNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-AC
ahu.ahu-2m-1.mixed-air-tempAHU - CasinoAHU (Modulating CHW-served)AHU-2M.12nd Level/Casino MVAC PlantMixed Air TemperatureAITemperature Sensor (duct insertion)BMS ContractorMC-ME:AHU-AC/MR-5PNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-AC
ahu.ahu-2m-1.supply-air-rhAHU - CasinoAHU (Modulating CHW-served)AHU-2M.12nd Level/Casino MVAC PlantSupply Air Humidity MonitoringAIHumidity Sensor (duct insertion)BMS ContractorMC-ME:AHU-ACPNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-AC
ahu.ahu-2m-1.chw-vlv-cmdAHU - CasinoAHU (Modulating CHW-served)AHU-2M.12nd Level/Casino MVAC PlantCHW Modulating Valve Control On/Off/ModulatingAOElectric Valve Actuator (0-10V/4-20mA)ME ContractorMC-ME:AHU-AC/Modulate-1PNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-ACModulating valve — feedback via AO command, status implied
ahu.ahu-2m-1.oa-damper-fbAHU - CasinoAHU (Modulating CHW-served)AHU-2M.12nd Level/Casino MVAC PlantOutdoor Air Motorized Damper Position FeedbackAIDamper Controller (0-10V or 4-20mA fb)ME ContractorMC-ME:AHU-AC/MR-9PNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-ACModulating damper — % position via AI
ahu.ahu-2m-1.oa-damper-cmdAHU - CasinoAHU (Modulating CHW-served)AHU-2M.12nd Level/Casino MVAC PlantOutdoor Air Motorized Damper Control On/Off/ModulatingAODamper Controller (0-10V or 4-20mA)ME ContractorMC-ME:AHU-AC/Turn ON/OFF/ModulatePNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-AC
ahu.ahu-2m-1.ra-damper-fbAHU - CasinoAHU (Modulating CHW-served)AHU-2M.12nd Level/Casino MVAC PlantReturn Air Motorized Damper Position FeedbackAIDamper Controller (0-10V or 4-20mA fb)ME ContractorMC-ME:AHU-AC/MR-8PNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-ACModulating damper — % position via AI
ahu.ahu-2m-1.ra-damper-cmdAHU - CasinoAHU (Modulating CHW-served)AHU-2M.12nd Level/Casino MVAC PlantReturn Air Motorized Damper Control On/Off/ModulatingAODamper Controller (0-10V or 4-20mA)ME ContractorMC-ME:AHU-AC/Turn ON/OFF/ModulatePNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-AC
ahu.ahu-2m-1.return-air-co2AHU - CasinoAHU (Modulating CHW-served)AHU-2M.12nd Level/Casino MVAC PlantCarbon Dioxide (CO2) Sensor at Return DuctAICO2 Sensor (duct)BMS ContractorMC-ME:AHU-AC/MR-4PNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-AC
ahu.ahu-2m-1.return-air-coAHU - CasinoAHU (Modulating CHW-served)AHU-2M.12nd Level/Casino MVAC PlantCarbon Monoxide (CO) Sensor at Return DuctAICO Sensor (duct)BMS ContractorMC-ME:AHU-ACPNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-ACCasino-specific (smoking area air quality)
ahu.ahu-2m-1.return-air-tempAHU - CasinoAHU (Modulating CHW-served)AHU-2M.12nd Level/Casino MVAC PlantIndoor Return Air TemperatureAITemperature Sensor (duct insertion)BMS ContractorMC-ME:AHU-AC/MR-3PNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-AC
ahu.ahu-2m-2.networkAHU - CasinoAHU (Modulating CHW-served)AHU-2M.22nd Level/Casino MVAC PlantBACnet/IP gateway to AHU controllerNetworkAHU Controller (BACnet)Equipment SupplierMC-ME:AHU-AC at 2nd Level; BMS-02 AHU 2nd LevelPNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-AC
ahu.ahu-2m-2.fan-motor-statusAHU - CasinoAHU (Modulating CHW-served)AHU-2M.22nd Level/Casino MVAC PlantFan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:AHU-AC/MR-1PNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-AC
ahu.ahu-2m-2.fan-trip-statusAHU - CasinoAHU (Modulating CHW-served)AHU-2M.22nd Level/Casino MVAC PlantFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:AHU-AC/Alarm-1PNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-AC
ahu.ahu-2m-2.vfd-speed-fbAHU - CasinoAHU (Modulating CHW-served)AHU-2M.22nd Level/Casino MVAC PlantVFD Speed Monitoring (feedback)HLIVFDEquipment SupplierMC-ME:AHU-AC/MR-7PNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-AC
ahu.ahu-2m-2.fan-control-cmdAHU - CasinoAHU (Modulating CHW-served)AHU-2M.22nd Level/Casino MVAC PlantFan Control On/Off/ModulatingHLIVFDEquipment SupplierMC-ME:AHU-AC/Turn ON/OFFPNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-AC
ahu.ahu-2m-2.supply-air-tempAHU - CasinoAHU (Modulating CHW-served)AHU-2M.22nd Level/Casino MVAC PlantSupply Air TemperatureAITemperature Sensor (duct insertion)BMS ContractorMC-ME:AHU-AC/MR-6PNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-AC
ahu.ahu-2m-2.mixed-air-tempAHU - CasinoAHU (Modulating CHW-served)AHU-2M.22nd Level/Casino MVAC PlantMixed Air TemperatureAITemperature Sensor (duct insertion)BMS ContractorMC-ME:AHU-AC/MR-5PNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-AC
ahu.ahu-2m-2.supply-air-rhAHU - CasinoAHU (Modulating CHW-served)AHU-2M.22nd Level/Casino MVAC PlantSupply Air Humidity MonitoringAIHumidity Sensor (duct insertion)BMS ContractorMC-ME:AHU-ACPNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-AC
ahu.ahu-2m-2.chw-vlv-cmdAHU - CasinoAHU (Modulating CHW-served)AHU-2M.22nd Level/Casino MVAC PlantCHW Modulating Valve Control On/Off/ModulatingAOElectric Valve Actuator (0-10V/4-20mA)ME ContractorMC-ME:AHU-AC/Modulate-1PNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-AC
ahu.ahu-2m-2.oa-damper-fbAHU - CasinoAHU (Modulating CHW-served)AHU-2M.22nd Level/Casino MVAC PlantOutdoor Air Motorized Damper Position FeedbackAIDamper Controller (0-10V or 4-20mA fb)ME ContractorMC-ME:AHU-AC/MR-9PNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-AC
ahu.ahu-2m-2.oa-damper-cmdAHU - CasinoAHU (Modulating CHW-served)AHU-2M.22nd Level/Casino MVAC PlantOutdoor Air Motorized Damper Control On/Off/ModulatingAODamper Controller (0-10V or 4-20mA)ME ContractorMC-ME:AHU-AC/Turn ON/OFF/ModulatePNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-AC
ahu.ahu-2m-2.ra-damper-fbAHU - CasinoAHU (Modulating CHW-served)AHU-2M.22nd Level/Casino MVAC PlantReturn Air Motorized Damper Position FeedbackAIDamper Controller (0-10V or 4-20mA fb)ME ContractorMC-ME:AHU-AC/MR-8PNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-AC
ahu.ahu-2m-2.ra-damper-cmdAHU - CasinoAHU (Modulating CHW-served)AHU-2M.22nd Level/Casino MVAC PlantReturn Air Motorized Damper Control On/Off/ModulatingAODamper Controller (0-10V or 4-20mA)ME ContractorMC-ME:AHU-AC/Turn ON/OFF/ModulatePNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-AC
ahu.ahu-2m-2.return-air-co2AHU - CasinoAHU (Modulating CHW-served)AHU-2M.22nd Level/Casino MVAC PlantCarbon Dioxide (CO2) Sensor at Return DuctAICO2 Sensor (duct)BMS ContractorMC-ME:AHU-AC/MR-4PNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-AC
ahu.ahu-2m-2.return-air-coAHU - CasinoAHU (Modulating CHW-served)AHU-2M.22nd Level/Casino MVAC PlantCarbon Monoxide (CO) Sensor at Return DuctAICO Sensor (duct)BMS ContractorMC-ME:AHU-ACPNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-AC
ahu.ahu-2m-2.return-air-tempAHU - CasinoAHU (Modulating CHW-served)AHU-2M.22nd Level/Casino MVAC PlantIndoor Return Air TemperatureAITemperature Sensor (duct insertion)BMS ContractorMC-ME:AHU-AC/MR-3PNL-AHU-L2BMS-02:r0c2; MC-ME:AHU-AC
ahu.oz-2m-1.equipment-statusAHU - Casino (Ozonizer)Ozone Generator (UV-light or Corona)OZ-2M.12nd Level/Casino MVAC PlantEquipment StatusDIAuxiliary ContactEquipment SupplierBMS-02:r0c2 OZONIZERSPNL-AHU-L2BMS-02:r0c2Casino air-treatment device paired with AHU-2M.1
ahu.oz-2m-1.equipment-tripAHU - Casino (Ozonizer)Ozone Generator (UV-light or Corona)OZ-2M.12nd Level/Casino MVAC PlantEquipment Trip StatusDIAuxiliary ContactEquipment SupplierBMS-02:r0c2 OZONIZERSPNL-AHU-L2BMS-02:r0c2
ahu.oz-2m-1.vocAHU - Casino (Ozonizer)Ozone Generator (UV-light or Corona)OZ-2M.12nd Level/Casino MVAC PlantVOC Monitoring (downstream air quality)AIVOC Sensor (duct)BMS ContractorBMS-02:r0c2 OZONIZERSPNL-AHU-L2BMS-02:r0c2
ahu.oz-2m-2.equipment-statusAHU - Casino (Ozonizer)Ozone Generator (UV-light or Corona)OZ-2M.22nd Level/Casino MVAC PlantEquipment StatusDIAuxiliary ContactEquipment SupplierBMS-02:r0c2 OZONIZERSPNL-AHU-L2BMS-02:r0c2Casino air-treatment device paired with AHU-2M.2
ahu.oz-2m-2.equipment-tripAHU - Casino (Ozonizer)Ozone Generator (UV-light or Corona)OZ-2M.22nd Level/Casino MVAC PlantEquipment Trip StatusDIAuxiliary ContactEquipment SupplierBMS-02:r0c2 OZONIZERSPNL-AHU-L2BMS-02:r0c2
ahu.oz-2m-2.vocAHU - Casino (Ozonizer)Ozone Generator (UV-light or Corona)OZ-2M.22nd Level/Casino MVAC PlantVOC Monitoring (downstream air quality)AIVOC Sensor (duct)BMS ContractorBMS-02:r0c2 OZONIZERSPNL-AHU-L2BMS-02:r0c2
pahu.pahu-rd-1.networkPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.1Roofdeck/PAHU PlantBACnet/IP gateway to PAHU controllerNetworkPAHU Controller (BACnet)Equipment SupplierMC-ME:Roof Deck PAHU; BMS-02 PAHU RoofdeckPNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
pahu.pahu-rd-1.faf-start-cmdPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.1Roofdeck/PAHU PlantFresh Air Fan Start/Stop ControlDOContactor relayEquipment SupplierMC-ME:PAHU/Turn ON/OFFPNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
pahu.pahu-rd-1.faf-motor-statusPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.1Roofdeck/PAHU PlantFresh Air Fan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:PAHU/MR-1PNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
pahu.pahu-rd-1.faf-tripPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.1Roofdeck/PAHU PlantFresh Air Fan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:PAHU/Alarm-1PNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
pahu.pahu-rd-1.faf-hoaPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.1Roofdeck/PAHU PlantFresh Air Fan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:PAHU/MR-2PNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
pahu.pahu-rd-1.vfd-speed-fbPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.1Roofdeck/PAHU PlantVFD Speed Monitoring (feedback)HLIVFDEquipment SupplierMC-ME:PAHU/MR-3PNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
pahu.pahu-rd-1.fan-control-cmdPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.1Roofdeck/PAHU PlantFan Control On/Off/ModulatingHLIVFDEquipment SupplierMC-ME:PAHU/Turn ON/OFF/ModulatePNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
pahu.pahu-rd-1.oa-tempPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.1Roofdeck/PAHU PlantOutdoor (Outside) Supply Air TemperatureAITemperature Sensor (outdoor/duct)BMS ContractorMC-ME:PAHU/MR-6PNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
pahu.pahu-rd-1.oa-flowPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.1Roofdeck/PAHU PlantOutdoor Air Flow MonitoringAIFlow Sensor (duct insertion)BMS ContractorMC-ME:PAHU/MR-6PNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
pahu.pahu-rd-1.supply-tempPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.1Roofdeck/PAHU PlantIndoor Supply Air TemperatureAITemperature Sensor (duct insertion)BMS ContractorMC-ME:PAHU/MR-7PNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
pahu.pahu-rd-1.faf-static-pressPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.1Roofdeck/PAHU PlantFresh Air Fan Static Pressure TransmitterAIDifferential Pressure Sensor (duct)BMS ContractorMC-ME:PAHUPNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
pahu.pahu-rd-1.oa-damper-statusPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.1Roofdeck/PAHU PlantOutdoor Air Motorized Damper StatusDIDamper Controller (limit/feedback)Equipment SupplierMC-ME:PAHU/MR-4PNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
pahu.pahu-rd-1.oa-damper-cmdPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.1Roofdeck/PAHU PlantOutdoor Air Motorized Damper Control On/Off/ModulatingAODamper Controller (0-10V or 4-20mA)Equipment SupplierMC-ME:PAHU/Turn ON/OFF/Modulate-2PNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
pahu.pahu-rd-1.chw-vlv-cmdPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.1Roofdeck/PAHU PlantCHW Modulating Valve Control On/Off/ModulatingAOElectric Valve Actuator (0-10V/4-20mA)ME ContractorMC-ME:PAHU/Modulate-3PNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
pahu.pahu-rd-2.networkPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.2Roofdeck/PAHU PlantBACnet/IP gateway to PAHU controllerNetworkPAHU Controller (BACnet)Equipment SupplierMC-ME:Roof Deck PAHU; BMS-02 PAHU RoofdeckPNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
pahu.pahu-rd-2.faf-start-cmdPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.2Roofdeck/PAHU PlantFresh Air Fan Start/Stop ControlDOContactor relayEquipment SupplierMC-ME:PAHU/Turn ON/OFFPNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
pahu.pahu-rd-2.faf-motor-statusPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.2Roofdeck/PAHU PlantFresh Air Fan Motor StatusDIAuxiliary ContactEquipment SupplierMC-ME:PAHU/MR-1PNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
pahu.pahu-rd-2.faf-tripPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.2Roofdeck/PAHU PlantFresh Air Fan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierMC-ME:PAHU/Alarm-1PNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
pahu.pahu-rd-2.faf-hoaPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.2Roofdeck/PAHU PlantFresh Air Fan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierMC-ME:PAHU/MR-2PNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
pahu.pahu-rd-2.vfd-speed-fbPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.2Roofdeck/PAHU PlantVFD Speed Monitoring (feedback)HLIVFDEquipment SupplierMC-ME:PAHU/MR-3PNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
pahu.pahu-rd-2.fan-control-cmdPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.2Roofdeck/PAHU PlantFan Control On/Off/ModulatingHLIVFDEquipment SupplierMC-ME:PAHU/Turn ON/OFF/ModulatePNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
pahu.pahu-rd-2.oa-tempPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.2Roofdeck/PAHU PlantOutdoor (Outside) Supply Air TemperatureAITemperature Sensor (outdoor/duct)BMS ContractorMC-ME:PAHU/MR-6PNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
pahu.pahu-rd-2.oa-flowPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.2Roofdeck/PAHU PlantOutdoor Air Flow MonitoringAIFlow Sensor (duct insertion)BMS ContractorMC-ME:PAHU/MR-6PNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
pahu.pahu-rd-2.supply-tempPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.2Roofdeck/PAHU PlantIndoor Supply Air TemperatureAITemperature Sensor (duct insertion)BMS ContractorMC-ME:PAHU/MR-7PNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
pahu.pahu-rd-2.faf-static-pressPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.2Roofdeck/PAHU PlantFresh Air Fan Static Pressure TransmitterAIDifferential Pressure Sensor (duct)BMS ContractorMC-ME:PAHUPNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
pahu.pahu-rd-2.oa-damper-statusPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.2Roofdeck/PAHU PlantOutdoor Air Motorized Damper StatusDIDamper Controller (limit/feedback)Equipment SupplierMC-ME:PAHU/MR-4PNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
pahu.pahu-rd-2.oa-damper-cmdPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.2Roofdeck/PAHU PlantOutdoor Air Motorized Damper Control On/Off/ModulatingAODamper Controller (0-10V or 4-20mA)Equipment SupplierMC-ME:PAHU/Turn ON/OFF/Modulate-2PNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
pahu.pahu-rd-2.chw-vlv-cmdPAHU - RoofdeckPrecooled Air Handling UnitPAHU-RD.2Roofdeck/PAHU PlantCHW Modulating Valve Control On/Off/ModulatingAOElectric Valve Actuator (0-10V/4-20mA)ME ContractorMC-ME:PAHU/Modulate-3PNL-PAHU-RDBMS-02:r0c2; MC-ME:PAHU
ee.mtr-main-1.networkPower MeteringMultifunction Power Meter (Main)MTR-MAIN-1Main Switchgear RoomModbus RTU/IP gateway connectionNetworkModbus Power Meter (e.g.BMS ContractorBMS-01 BMS general spec — Electrical Max Demand Control; A-EE-001PNL-EE-MAINA-004 / A-EE-001Main 1 — refine after Q-011
ee.mtr-main-1.kwPower MeteringMultifunction Power Meter (Main)MTR-MAIN-1Main Switchgear RoomActive Power (kW total)HLI-BMS ContractorA-EE-001PNL-EE-MAINA-004 / A-EE-001Modbus register
ee.mtr-main-1.kwhPower MeteringMultifunction Power Meter (Main)MTR-MAIN-1Main Switchgear RoomCumulative Energy (kWh total)HLI-BMS ContractorA-EE-001PNL-EE-MAINA-004 / A-EE-001
ee.mtr-main-1.kvarPower MeteringMultifunction Power Meter (Main)MTR-MAIN-1Main Switchgear RoomReactive Power (kVAR total)HLI-BMS ContractorA-EE-001PNL-EE-MAINA-004 / A-EE-001
ee.mtr-main-1.v-avgPower MeteringMultifunction Power Meter (Main)MTR-MAIN-1Main Switchgear RoomAverage Voltage (3-phase RMS)HLI-BMS ContractorA-EE-001PNL-EE-MAINA-004 / A-EE-001
ee.mtr-main-1.i-avgPower MeteringMultifunction Power Meter (Main)MTR-MAIN-1Main Switchgear RoomAverage Current (3-phase RMS)HLI-BMS ContractorA-EE-001PNL-EE-MAINA-004 / A-EE-001
ee.mtr-main-2.networkPower MeteringMultifunction Power Meter (Main)MTR-MAIN-2Main Switchgear RoomModbus RTU/IP gateway connectionNetworkModbus Power MeterBMS ContractorA-EE-001PNL-EE-MAINA-004 / A-EE-001Main 2 (e.g., Generator)
ee.mtr-main-2.kwPower MeteringMultifunction Power Meter (Main)MTR-MAIN-2Main Switchgear RoomActive Power (kW total)HLI-BMS ContractorA-EE-001PNL-EE-MAINA-004 / A-EE-001
ee.mtr-main-2.kwhPower MeteringMultifunction Power Meter (Main)MTR-MAIN-2Main Switchgear RoomCumulative Energy (kWh total)HLI-BMS ContractorA-EE-001PNL-EE-MAINA-004 / A-EE-001
ee.mtr-main-2.kvarPower MeteringMultifunction Power Meter (Main)MTR-MAIN-2Main Switchgear RoomReactive Power (kVAR total)HLI-BMS ContractorA-EE-001PNL-EE-MAINA-004 / A-EE-001
ee.mtr-main-2.v-avgPower MeteringMultifunction Power Meter (Main)MTR-MAIN-2Main Switchgear RoomAverage Voltage (3-phase RMS)HLI-BMS ContractorA-EE-001PNL-EE-MAINA-004 / A-EE-001
ee.mtr-main-2.i-avgPower MeteringMultifunction Power Meter (Main)MTR-MAIN-2Main Switchgear RoomAverage Current (3-phase RMS)HLI-BMS ContractorA-EE-001PNL-EE-MAINA-004 / A-EE-001
ee.mtr-main-3.networkPower MeteringMultifunction Power Meter (Main)MTR-MAIN-3Main Switchgear RoomModbus RTU/IP gateway connectionNetworkModbus Power MeterBMS ContractorA-EE-001PNL-EE-MAINA-004 / A-EE-001Main 3 (e.g., ATS bus tie)
ee.mtr-main-3.kwPower MeteringMultifunction Power Meter (Main)MTR-MAIN-3Main Switchgear RoomActive Power (kW total)HLI-BMS ContractorA-EE-001PNL-EE-MAINA-004 / A-EE-001
ee.mtr-main-3.kwhPower MeteringMultifunction Power Meter (Main)MTR-MAIN-3Main Switchgear RoomCumulative Energy (kWh total)HLI-BMS ContractorA-EE-001PNL-EE-MAINA-004 / A-EE-001
ee.mtr-main-3.kvarPower MeteringMultifunction Power Meter (Main)MTR-MAIN-3Main Switchgear RoomReactive Power (kVAR total)HLI-BMS ContractorA-EE-001PNL-EE-MAINA-004 / A-EE-001
ee.mtr-main-3.v-avgPower MeteringMultifunction Power Meter (Main)MTR-MAIN-3Main Switchgear RoomAverage Voltage (3-phase RMS)HLI-BMS ContractorA-EE-001PNL-EE-MAINA-004 / A-EE-001
ee.mtr-main-3.i-avgPower MeteringMultifunction Power Meter (Main)MTR-MAIN-3Main Switchgear RoomAverage Current (3-phase RMS)HLI-BMS ContractorA-EE-001PNL-EE-MAINA-004 / A-EE-001
ee.mtr-fdr-01.networkPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-01Distribution (per A4)Modbus RTU/IP gateway connectionNetworkModbus Power MeterBMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001Chiller plant feeder
ee.mtr-fdr-01.kwPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-01Distribution (per A4)Active Power (kW total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-01.kwhPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-01Distribution (per A4)Cumulative Energy (kWh total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-01.kvarPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-01Distribution (per A4)Reactive Power (kVAR total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-01.v-avgPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-01Distribution (per A4)Average Voltage (3-phase RMS)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-01.i-avgPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-01Distribution (per A4)Average Current (3-phase RMS)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-02.networkPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-02Distribution (per A4)Modbus RTU/IP gateway connectionNetworkModbus Power MeterBMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001AHU plant feeder
ee.mtr-fdr-02.kwPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-02Distribution (per A4)Active Power (kW total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-02.kwhPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-02Distribution (per A4)Cumulative Energy (kWh total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-02.kvarPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-02Distribution (per A4)Reactive Power (kVAR total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-02.v-avgPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-02Distribution (per A4)Average Voltage (3-phase RMS)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-02.i-avgPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-02Distribution (per A4)Average Current (3-phase RMS)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-03.networkPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-03Distribution (per A4)Modbus RTU/IP gateway connectionNetworkModbus Power MeterBMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001Kitchen feeder
ee.mtr-fdr-03.kwPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-03Distribution (per A4)Active Power (kW total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-03.kwhPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-03Distribution (per A4)Cumulative Energy (kWh total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-03.kvarPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-03Distribution (per A4)Reactive Power (kVAR total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-03.v-avgPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-03Distribution (per A4)Average Voltage (3-phase RMS)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-03.i-avgPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-03Distribution (per A4)Average Current (3-phase RMS)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-04.networkPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-04Distribution (per A4)Modbus RTU/IP gateway connectionNetworkModbus Power MeterBMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001Lighting feeder
ee.mtr-fdr-04.kwPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-04Distribution (per A4)Active Power (kW total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-04.kwhPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-04Distribution (per A4)Cumulative Energy (kWh total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-04.kvarPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-04Distribution (per A4)Reactive Power (kVAR total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-04.v-avgPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-04Distribution (per A4)Average Voltage (3-phase RMS)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-04.i-avgPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-04Distribution (per A4)Average Current (3-phase RMS)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-05.networkPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-05Distribution (per A4)Modbus RTU/IP gateway connectionNetworkModbus Power MeterBMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001Hotwater plant feeder
ee.mtr-fdr-05.kwPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-05Distribution (per A4)Active Power (kW total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-05.kwhPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-05Distribution (per A4)Cumulative Energy (kWh total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-05.kvarPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-05Distribution (per A4)Reactive Power (kVAR total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-05.v-avgPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-05Distribution (per A4)Average Voltage (3-phase RMS)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-05.i-avgPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-05Distribution (per A4)Average Current (3-phase RMS)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-06.networkPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-06Distribution (per A4)Modbus RTU/IP gateway connectionNetworkModbus Power MeterBMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001Lifts feeder
ee.mtr-fdr-06.kwPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-06Distribution (per A4)Active Power (kW total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-06.kwhPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-06Distribution (per A4)Cumulative Energy (kWh total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-06.kvarPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-06Distribution (per A4)Reactive Power (kVAR total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-06.v-avgPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-06Distribution (per A4)Average Voltage (3-phase RMS)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-06.i-avgPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-06Distribution (per A4)Average Current (3-phase RMS)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-07.networkPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-07Distribution (per A4)Modbus RTU/IP gateway connectionNetworkModbus Power MeterBMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001BMS UPS feeder
ee.mtr-fdr-07.kwPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-07Distribution (per A4)Active Power (kW total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-07.kwhPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-07Distribution (per A4)Cumulative Energy (kWh total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-07.kvarPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-07Distribution (per A4)Reactive Power (kVAR total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-07.v-avgPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-07Distribution (per A4)Average Voltage (3-phase RMS)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-07.i-avgPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-07Distribution (per A4)Average Current (3-phase RMS)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-08.networkPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-08Distribution (per A4)Modbus RTU/IP gateway connectionNetworkModbus Power MeterBMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001Mechanical/Pumps feeder
ee.mtr-fdr-08.kwPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-08Distribution (per A4)Active Power (kW total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-08.kwhPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-08Distribution (per A4)Cumulative Energy (kWh total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-08.kvarPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-08Distribution (per A4)Reactive Power (kVAR total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-08.v-avgPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-08Distribution (per A4)Average Voltage (3-phase RMS)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-08.i-avgPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-08Distribution (per A4)Average Current (3-phase RMS)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-09.networkPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-09Distribution (per A4)Modbus RTU/IP gateway connectionNetworkModbus Power MeterBMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001Boiler/Laundry feeder
ee.mtr-fdr-09.kwPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-09Distribution (per A4)Active Power (kW total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-09.kwhPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-09Distribution (per A4)Cumulative Energy (kWh total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-09.kvarPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-09Distribution (per A4)Reactive Power (kVAR total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-09.v-avgPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-09Distribution (per A4)Average Voltage (3-phase RMS)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-09.i-avgPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-09Distribution (per A4)Average Current (3-phase RMS)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-10.networkPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-10Distribution (per A4)Modbus RTU/IP gateway connectionNetworkModbus Power MeterBMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001Fire pump feeder
ee.mtr-fdr-10.kwPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-10Distribution (per A4)Active Power (kW total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-10.kwhPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-10Distribution (per A4)Cumulative Energy (kWh total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-10.kvarPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-10Distribution (per A4)Reactive Power (kVAR total)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-10.v-avgPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-10Distribution (per A4)Average Voltage (3-phase RMS)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001
ee.mtr-fdr-10.i-avgPower MeteringMultifunction Power Meter (Feeder)MTR-FDR-10Distribution (per A4)Average Current (3-phase RMS)HLI-BMS ContractorA-EE-001PNL-EE-DISTA-004 / A-EE-001