Summary

A4 — Panel Schedule, Audit View
ProjectKingsford Hotel Bacolod — BMS
Canonical sourceA4-panel-schedule.yaml
How to record correctionsEdit the canonical YAML directly — add a verification: block to the affected row(s)
Totals
Total panels8
Total physical I/O561
Total HLI sub-points141
Total controllers19
Verification status
StatusCount% of total
verified00%
needs_correction00%
uncertain00%
unverified8100%
⚠ Known weak points
Verify panel locations against architectural drawings. Confirm proximity to served equipment, panel-room space allocation, and access for maintenance.
How corrections flow
Edit A4-panel-schedule.yaml — add a verification: block to the panel row when location is confirmed or revised.

Detail

PanelLocationEquipment servedPhys I/OHLINetwork dropsControllersPower (W)StatusVerified byDrawing refNotes
DDC-2F-BOH2nd Floor / 2nd Floor BOH / 2nd Floor BOH Toilet / 2nd Floor General Service / 2nd Floor OHR / 2nd Floor Toilet / 2nd Level AHU MCC / 2nd Level BOH / 2nd Level Executive Lounge / 2nd Level Function Room 2 / 2nd Level Function Room 3 / 2nd Level Function Rooms / 2nd Level Pre-Function2516525135190unverified
DDC-2F-CHILLER2nd Level Chiller MCC / 2nd Level Chiller Room1672659295unverified
DDC-2M-CASINO2nd Mezzanine (Casino)54785275unverified
DDC-3F3rd Floor / 3rd Floor Amenity Toilet / 3rd Floor BOH / 3rd Floor Toilet123600125unverified
DDC-B1-BOHBasement / Basement Battery Room / Basement FOST Room / Basement Garbage Lobby / Basement Main Fire Riser / Basement Mech / Pump / Basement Pump Room / Basement Service / Basement Toilet / Basement Wash Service175721255unverified
DDC-GF-BOHGF Main Lobby Toilet / Ground Floor AHU MCC / Ground Floor BOH / Ground Floor Fire Command Center948105275unverified
DDC-LG-PLANTLower Ground Boiler Room / Lower Ground HWL Room / Lower Ground Lighting Panel A / Lower Ground Lighting Panel B / Lower Ground Main Switchroom926195275unverified
DDC-RD-PLANTRoof Deck / Roof Deck CT Area / Roof Deck HWL Area16110124395unverified

Verification schema

How to record verification / corrections in A4-panel-schedule.yaml
Find the affected row in the YAML by ID (Detail sheet column A) and add a verification: block:
- id: PNL-AHU-3F
verification: # ADDED by team
status: needs_correction # unverified | verified | needs_correction | uncertain
corrected_location: 3F Mech Room A # team's measured / confirmed value
verified_by: J. Cruz
verified_date: 2026-05-10
drawing_ref: "EE-09 grid B-2"
notes: ""
After saving, re-run: python3 _playbook/tools/generate-deliverables.py <project>
Corrections propagate to B4 manhours, BOQ, and final deliverables automatically.
Recommended verification methods (priority order):
1. Site walkthrough with measurement (most accurate; for cable lengths, after structural completion).
2. Properly-scaled architectural drawings.
3. Mechanical contractor's tray layout combined with BMS panel locations.
4. A-001 default with ±20% contingency in BOQ — last resort.