| ID | From | To | Cable type | Length (m) | Status | Corrected (m) | Verified by | Date | Drawing ref | Notes |
| C0001 | DDC-GF-BOH | AHU-1.1 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 25 | unverified | | | | | |
| C0002 | DDC-GF-BOH | AHU-1.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0003 | DDC-GF-BOH | AHU-1.1 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 25 | unverified | | | | | |
| C0004 | DDC-GF-BOH | AHU-1.2 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 25 | unverified | | | | | |
| C0005 | DDC-GF-BOH | AHU-1.2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0006 | DDC-GF-BOH | AHU-1.2 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 25 | unverified | | | | | |
| C0007 | DDC-GF-BOH | AHU-1.3 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 25 | unverified | | | | | |
| C0008 | DDC-GF-BOH | AHU-1.3 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0009 | DDC-GF-BOH | AHU-1.3 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 25 | unverified | | | | | |
| C0010 | DDC-2M-CASINO | AHU-2M.1 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 18 | unverified | | | | | |
| C0011 | DDC-2M-CASINO | AHU-2M.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 18 | unverified | | | | | |
| C0012 | DDC-2M-CASINO | AHU-2M.1 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 18 | unverified | | | | | |
| C0013 | DDC-2M-CASINO | AHU-2M.2 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 18 | unverified | | | | | |
| C0014 | DDC-2M-CASINO | AHU-2M.2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 18 | unverified | | | | | |
| C0015 | DDC-2M-CASINO | AHU-2M.2 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 18 | unverified | | | | | |
| C0016 | DDC-2F-BOH | AHU-B.1 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 25 | unverified | | | | | |
| C0017 | DDC-2F-BOH | AHU-B.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0018 | DDC-2F-BOH | AHU-B.1 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 25 | unverified | | | | | |
| C0019 | DDC-2F-BOH | AHU-B.2 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 25 | unverified | | | | | |
| C0020 | DDC-2F-BOH | AHU-B.2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0021 | DDC-2F-BOH | AHU-B.2 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 25 | unverified | | | | | |
| C0022 | DDC-2F-BOH | AHU-B.3 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 25 | unverified | | | | | |
| C0023 | DDC-2F-BOH | AHU-B.3 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0024 | DDC-2F-BOH | AHU-B.3 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 25 | unverified | | | | | |
| C0025 | DDC-2F-BOH | AHU-EL (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 25 | unverified | | | | | |
| C0026 | DDC-2F-BOH | AHU-EL (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0027 | DDC-2F-BOH | AHU-EL (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 25 | unverified | | | | | |
| C0028 | DDC-2F-BOH | AHU-FR2 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 25 | unverified | | | | | |
| C0029 | DDC-2F-BOH | AHU-FR2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0030 | DDC-2F-BOH | AHU-FR2 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 25 | unverified | | | | | |
| C0031 | DDC-2F-BOH | AHU-FR3 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 25 | unverified | | | | | |
| C0032 | DDC-2F-BOH | AHU-FR3 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0033 | DDC-2F-BOH | AHU-FR3 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 25 | unverified | | | | | |
| C0034 | DDC-2F-BOH | AHU-PF (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 25 | unverified | | | | | |
| C0035 | DDC-2F-BOH | AHU-PF (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0036 | DDC-2F-BOH | AHU-PF (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 25 | unverified | | | | | |
| C0037 | DDC-2M-CASINO | AIR-ION-2M.1 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 18 | unverified | | | | | |
| C0038 | DDC-2M-CASINO | AIR-ION-2M.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 18 | unverified | | | | | |
| C0039 | DDC-2M-CASINO | AIR-ION-2M.2 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 18 | unverified | | | | | |
| C0040 | DDC-2M-CASINO | AIR-ION-2M.2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 18 | unverified | | | | | |
| C0041 | DDC-2F-CHILLER | CH-1 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 12 | unverified | | | | | |
| C0042 | DDC-2F-CHILLER | CH-1 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 12 | unverified | | | | | |
| C0043 | DDC-2F-CHILLER | CH-2 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 12 | unverified | | | | | |
| C0044 | DDC-2F-CHILLER | CH-2 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 12 | unverified | | | | | |
| C0045 | DDC-2F-CHILLER | CH-3 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 12 | unverified | | | | | |
| C0046 | DDC-2F-CHILLER | CH-3 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 12 | unverified | | | | | |
| C0047 | DDC-2F-CHILLER | CHW-DIFF (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 12 | unverified | | | | | |
| C0048 | DDC-2F-CHILLER | CHW-RET-HDR (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 12 | unverified | | | | | |
| C0049 | DDC-2F-CHILLER | CHW-SUP-HDR (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 12 | unverified | | | | | |
| C0050 | DDC-2F-CHILLER | COWP-1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 12 | unverified | | | | | |
| C0051 | DDC-2F-CHILLER | COWP-2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 12 | unverified | | | | | |
| C0052 | DDC-2F-CHILLER | COWP-3 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 12 | unverified | | | | | |
| C0053 | DDC-RD-PLANT | CT-1 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 15 | unverified | | | | | |
| C0054 | DDC-RD-PLANT | CT-1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 15 | unverified | | | | | |
| C0055 | DDC-RD-PLANT | CT-1 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 15 | unverified | | | | | |
| C0056 | DDC-RD-PLANT | CT-2 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 15 | unverified | | | | | |
| C0057 | DDC-RD-PLANT | CT-2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 15 | unverified | | | | | |
| C0058 | DDC-RD-PLANT | CT-2 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 15 | unverified | | | | | |
| C0059 | DDC-RD-PLANT | CT-3 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 15 | unverified | | | | | |
| C0060 | DDC-RD-PLANT | CT-3 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 15 | unverified | | | | | |
| C0061 | DDC-RD-PLANT | CT-3 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 15 | unverified | | | | | |
| C0062 | DDC-RD-PLANT | CT-COMMON (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 15 | unverified | | | | | |
| C0063 | DDC-RD-PLANT | CW-HDR (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 15 | unverified | | | | | |
| C0064 | DDC-2M-CASINO | DOAS-2M (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 18 | unverified | | | | | |
| C0065 | DDC-2M-CASINO | DOAS-2M (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 18 | unverified | | | | | |
| C0066 | DDC-2M-CASINO | DOAS-2M (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 18 | unverified | | | | | |
| C0067 | DDC-RD-PLANT | DOAS-RD.1 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 15 | unverified | | | | | |
| C0068 | DDC-RD-PLANT | DOAS-RD.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 15 | unverified | | | | | |
| C0069 | DDC-RD-PLANT | DOAS-RD.1 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 15 | unverified | | | | | |
| C0070 | DDC-RD-PLANT | DOAS-RD.2 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 15 | unverified | | | | | |
| C0071 | DDC-RD-PLANT | DOAS-RD.2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 15 | unverified | | | | | |
| C0072 | DDC-RD-PLANT | DOAS-RD.2 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 15 | unverified | | | | | |
| C0073 | DDC-RD-PLANT | EF-1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 15 | unverified | | | | | |
| C0074 | DDC-2F-BOH | EF-2.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0075 | DDC-2F-BOH | EF-2.2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0076 | DDC-2F-BOH | EF-2.3 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0077 | DDC-2F-BOH | EF-2.4 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0078 | DDC-2F-BOH | EF-2B.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0079 | DDC-2F-BOH | EF-2B.2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0080 | DDC-3F | EF-3.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 35 | unverified | | | | | |
| C0081 | DDC-3F | EF-3.2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 35 | unverified | | | | | |
| C0082 | DDC-3F | EF-3.3 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 35 | unverified | | | | | |
| C0083 | DDC-3F | EF-3.4 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 35 | unverified | | | | | |
| C0084 | DDC-3F | EF-3B-G (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 35 | unverified | | | | | |
| C0085 | DDC-3F | EF-3C.1-G (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 35 | unverified | | | | | |
| C0086 | DDC-B1-BOH | EF-B.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 28 | unverified | | | | | |
| C0087 | DDC-B1-BOH | EF-B.2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 28 | unverified | | | | | |
| C0088 | DDC-B1-BOH | EF-BR.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 28 | unverified | | | | | |
| C0089 | DDC-B1-BOH | EF-BR.2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 28 | unverified | | | | | |
| C0090 | DDC-B1-BOH | EF-BS.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 28 | unverified | | | | | |
| C0091 | DDC-B1-BOH | EF-BS.2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 28 | unverified | | | | | |
| C0092 | DDC-B1-BOH | EF-FOST.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 28 | unverified | | | | | |
| C0093 | DDC-B1-BOH | EF-GL.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 28 | unverified | | | | | |
| C0094 | DDC-B1-BOH | EF-GL.2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 28 | unverified | | | | | |
| C0095 | DDC-2F-BOH | EF-GS.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0096 | DDC-2F-BOH | EF-GS.2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0097 | DDC-B1-BOH | EF-MFR.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 28 | unverified | | | | | |
| C0098 | DDC-B1-BOH | EF-MP.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 28 | unverified | | | | | |
| C0099 | DDC-2F-BOH | EF-OHRv2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0100 | DDC-B1-BOH | EF-PR.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 28 | unverified | | | | | |
| C0101 | DDC-B1-BOH | EF-PR.3 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 28 | unverified | | | | | |
| C0102 | DDC-RD-PLANT | EF-RD.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 15 | unverified | | | | | |
| C0103 | DDC-RD-PLANT | EF-RO.2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 15 | unverified | | | | | |
| C0104 | DDC-B1-BOH | EF-WS.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 28 | unverified | | | | | |
| C0105 | DDC-RD-PLANT | HP-HZ (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 15 | unverified | | | | | |
| C0106 | DDC-LG-PLANT | HP-LZ (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 12 | unverified | | | | | |
| C0107 | DDC-RD-PLANT | HWH-HZ (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 15 | unverified | | | | | |
| C0108 | DDC-LG-PLANT | HWH-LZ (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 12 | unverified | | | | | |
| C0109 | DDC-RD-PLANT | HWT-HZ (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 15 | unverified | | | | | |
| C0110 | DDC-LG-PLANT | HWT-LZ (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 12 | unverified | | | | | |
| C0111 | DDC-B1-BOH | PAHU-0.1 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 28 | unverified | | | | | |
| C0112 | DDC-B1-BOH | PAHU-0.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 28 | unverified | | | | | |
| C0113 | DDC-B1-BOH | PAHU-0.1 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0114 | DDC-2F-BOH | PAHU-B.1 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 25 | unverified | | | | | |
| C0115 | DDC-2F-BOH | PAHU-B.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0116 | DDC-2F-BOH | PAHU-B.1 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 25 | unverified | | | | | |
| C0117 | DDC-2F-BOH | PAHU-B.2 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 25 | unverified | | | | | |
| C0118 | DDC-2F-BOH | PAHU-B.2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0119 | DDC-2F-BOH | PAHU-B.2 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 25 | unverified | | | | | |
| C0120 | DDC-2F-BOH | PAHU-B.3 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 25 | unverified | | | | | |
| C0121 | DDC-2F-BOH | PAHU-B.3 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0122 | DDC-2F-BOH | PAHU-B.3 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 25 | unverified | | | | | |
| C0123 | DDC-2F-BOH | PAHU-FR (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 25 | unverified | | | | | |
| C0124 | DDC-2F-BOH | PAHU-FR (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0125 | DDC-2F-BOH | PAHU-FR (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 25 | unverified | | | | | |
| C0126 | DDC-2F-BOH | PAHU-PF (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 25 | unverified | | | | | |
| C0127 | DDC-2F-BOH | PAHU-PF (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0128 | DDC-2F-BOH | PAHU-PF (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 25 | unverified | | | | | |
| C0129 | DDC-RD-PLANT | PAHU-r.1 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 15 | unverified | | | | | |
| C0130 | DDC-RD-PLANT | PAHU-r.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 15 | unverified | | | | | |
| C0131 | DDC-RD-PLANT | PAHU-r.1 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 15 | unverified | | | | | |
| C0132 | DDC-RD-PLANT | PAHU-r.2 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 15 | unverified | | | | | |
| C0133 | DDC-RD-PLANT | PAHU-r.2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 15 | unverified | | | | | |
| C0134 | DDC-RD-PLANT | PAHU-r.2 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 15 | unverified | | | | | |
| C0135 | DDC-2F-CHILLER | PCHWP-1 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 12 | unverified | | | | | |
| C0136 | DDC-2F-CHILLER | PCHWP-1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 12 | unverified | | | | | |
| C0137 | DDC-2F-CHILLER | PCHWP-2 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 12 | unverified | | | | | |
| C0138 | DDC-2F-CHILLER | PCHWP-2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 12 | unverified | | | | | |
| C0139 | DDC-2F-CHILLER | PCHWP-3 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 12 | unverified | | | | | |
| C0140 | DDC-RD-PLANT | RP-HZ (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 15 | unverified | | | | | |
| C0141 | DDC-LG-PLANT | RP-LZ (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 12 | unverified | | | | | |
| C0142 | DDC-LG-PLANT | SB-1 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 12 | unverified | | | | | |
| C0143 | DDC-LG-PLANT | SB-1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 12 | unverified | | | | | |
| C0144 | DDC-LG-PLANT | SB-2 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors) | 12 | unverified | | | | | |
| C0145 | DDC-LG-PLANT | SB-2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 12 | unverified | | | | | |
| C0146 | DDC-2F-CHILLER | SCHWP-1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 12 | unverified | | | | | |
| C0147 | DDC-2F-CHILLER | SCHWP-2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 12 | unverified | | | | | |
| C0148 | DDC-2F-CHILLER | SCHWP-3 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 12 | unverified | | | | | |
| C0149 | DDC-GF-BOH | TEF-1.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0150 | DDC-GF-BOH | TEF-1.2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0151 | DDC-GF-BOH | TEF-1.3 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0152 | DDC-GF-BOH | TEF-1.4 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0153 | DDC-2F-BOH | TEF-2.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0154 | DDC-2F-BOH | TEF-2.2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0155 | DDC-2F-BOH | TEF-2B.3 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 25 | unverified | | | | | |
| C0156 | DDC-3F | TEF-30.20 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 35 | unverified | | | | | |
| C0157 | DDC-3F | TEF-3A.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 35 | unverified | | | | | |
| C0158 | DDC-3F | TEF-3A.2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 35 | unverified | | | | | |
| C0159 | DDC-3F | TEF-3B (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 35 | unverified | | | | | |
| C0160 | DDC-3F | TEF-3C.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 35 | unverified | | | | | |
| C0161 | DDC-3F | TEF-3C.2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 35 | unverified | | | | | |
| C0162 | DDC-B1-BOH | TEF-B.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 28 | unverified | | | | | |
| C0163 | DDC-B1-BOH | TEF-B.2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop) | 28 | unverified | | | | | |
| C0164 | DDC-2F-CHILLER | CH-1 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 12 | unverified | | | | | |
| C0165 | DDC-2F-CHILLER | CH-2 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 12 | unverified | | | | | |
| C0166 | DDC-2F-CHILLER | CH-3 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 12 | unverified | | | | | |
| C0167 | DDC-2F-CHILLER | PCHWP-1 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 12 | unverified | | | | | |
| C0168 | DDC-2F-CHILLER | PCHWP-2 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 12 | unverified | | | | | |
| C0169 | DDC-2F-CHILLER | SCHWP-1 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 12 | unverified | | | | | |
| C0170 | DDC-2F-CHILLER | SCHWP-2 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 12 | unverified | | | | | |
| C0171 | DDC-2F-CHILLER | SCHWP-3 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 12 | unverified | | | | | |
| C0172 | DDC-LG-PLANT | SB-1 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 12 | unverified | | | | | |
| C0173 | DDC-LG-PLANT | SB-2 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 12 | unverified | | | | | |
| C0174 | DDC-RD-PLANT | DOAS-RD.1 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 15 | unverified | | | | | |
| C0175 | DDC-RD-PLANT | DOAS-RD.2 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 15 | unverified | | | | | |
| C0176 | DDC-RD-PLANT | PAHU-r.1 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 15 | unverified | | | | | |
| C0177 | DDC-RD-PLANT | PAHU-r.2 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 15 | unverified | | | | | |
| C0178 | DDC-2M-CASINO | DOAS-2M (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 18 | unverified | | | | | |
| C0179 | DDC-2M-CASINO | AHU-2M.1 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 18 | unverified | | | | | |
| C0180 | DDC-2M-CASINO | AHU-2M.2 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 18 | unverified | | | | | |
| C0181 | DDC-2M-CASINO | AIR-ION-2M.1 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 18 | unverified | | | | | |
| C0182 | DDC-2M-CASINO | AIR-ION-2M.2 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 18 | unverified | | | | | |
| C0183 | DDC-2F-BOH | AHU-B.1 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 25 | unverified | | | | | |
| C0184 | DDC-2F-BOH | AHU-B.2 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 25 | unverified | | | | | |
| C0185 | DDC-2F-BOH | AHU-B.3 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 25 | unverified | | | | | |
| C0186 | DDC-2F-BOH | AHU-PF (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 25 | unverified | | | | | |
| C0187 | DDC-2F-BOH | AHU-EL (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 25 | unverified | | | | | |
| C0188 | DDC-2F-BOH | AHU-FR2 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 25 | unverified | | | | | |
| C0189 | DDC-2F-BOH | AHU-FR3 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 25 | unverified | | | | | |
| C0190 | DDC-2F-BOH | PAHU-B.1 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 25 | unverified | | | | | |
| C0191 | DDC-2F-BOH | PAHU-B.2 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 25 | unverified | | | | | |
| C0192 | DDC-2F-BOH | PAHU-B.3 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 25 | unverified | | | | | |
| C0193 | DDC-2F-BOH | PAHU-PF (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 25 | unverified | | | | | |
| C0194 | DDC-2F-BOH | PAHU-FR (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 25 | unverified | | | | | |
| C0195 | DDC-GF-BOH | AHU-1.1 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 25 | unverified | | | | | |
| C0196 | DDC-GF-BOH | AHU-1.2 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 25 | unverified | | | | | |
| C0197 | DDC-GF-BOH | AHU-1.3 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 25 | unverified | | | | | |
| C0198 | DDC-B1-BOH | PAHU-0.1 (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 28 | unverified | | | | | |
| C0199 | DDC-LG-PLANT | MPM-MAIN (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 12 | unverified | | | | | |
| C0200 | DDC-2F-CHILLER | MPM-CHILLER (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 12 | unverified | | | | | |
| C0201 | DDC-2F-BOH | MPM-AHU-2F (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 25 | unverified | | | | | |
| C0202 | DDC-GF-BOH | MPM-AHU-GF (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 25 | unverified | | | | | |
| C0203 | DDC-LG-PLANT | MPM-LIGHT-A (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 12 | unverified | | | | | |
| C0204 | DDC-LG-PLANT | MPM-LIGHT-B (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 12 | unverified | | | | | |
| C0205 | DDC-GF-BOH | FACP-GW (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 25 | unverified | | | | | |
| T0206 | BMS Server Room (head-end) | All BMS panels at 2nd Floor | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk | 80 | unverified | | | | | |
| T0207 | BMS Server Room (head-end) | All BMS panels at 3rd Floor | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk | 80 | unverified | | | | | |
| T0208 | BMS Server Room (head-end) | All BMS panels at Basement | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk | 80 | unverified | | | | | |
| T0209 | BMS Server Room (head-end) | All BMS panels at Ground | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk | 80 | unverified | | | | | |
| T0210 | BMS Server Room (head-end) | All BMS panels at Lower Ground | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk | 80 | unverified | | | | | |
| T0211 | BMS Server Room (head-end) | BMS panel controllers (per topology id mstp_field_backbone) | BACnet MS/TP shielded twisted-pair trunk, 1pr × 22 AWG low-cap | 250 | unverified | | | | | |
| T0212 | BMS Server Room (head-end) | BMS panel controllers (per topology id bacnet_ip_backbone) | BACnet MS/TP shielded twisted-pair trunk, 1pr × 22 AWG low-cap | 150 | unverified | | | | | |
| P0213 | Local panelboard / EE-supplied feeder | DDC-2F-BOH — BMS panel 240V power feed | 3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed) | 10 | unverified | | | | | |
| P0214 | Local panelboard / EE-supplied feeder | DDC-2F-CHILLER — BMS panel 240V power feed | 3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed) | 10 | unverified | | | | | |
| P0215 | Local panelboard / EE-supplied feeder | DDC-2M-CASINO — BMS panel 240V power feed | 3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed) | 10 | unverified | | | | | |
| P0216 | Local panelboard / EE-supplied feeder | DDC-3F — BMS panel 240V power feed | 3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed) | 10 | unverified | | | | | |
| P0217 | Local panelboard / EE-supplied feeder | DDC-B1-BOH — BMS panel 240V power feed | 3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed) | 10 | unverified | | | | | |
| P0218 | Local panelboard / EE-supplied feeder | DDC-GF-BOH — BMS panel 240V power feed | 3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed) | 10 | unverified | | | | | |
| P0219 | Local panelboard / EE-supplied feeder | DDC-LG-PLANT — BMS panel 240V power feed | 3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed) | 10 | unverified | | | | | |
| P0220 | Local panelboard / EE-supplied feeder | DDC-RD-PLANT — BMS panel 240V power feed | 3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed) | 10 | unverified | | | | | |