A3 — Cable Schedule, Audit View
ProjectKingsford Hotel Bacolod — BMS
Canonical sourceA3-cable-schedule.yaml
How to record correctionsEdit the canonical YAML directly — add a verification: block to the affected row(s)
Totals
Total cables220
Total length (m)5,173
Field cables205
Trunk cables7
Panel power feeds8
Verification status
StatusCount% of total
verified00%
needs_correction00%
uncertain00%
unverified220100%
⚠ Known weak points
Cable lengths are estimates based on assumption A-001 (30 m average panel-to-device run, 80 m trunk per floor). Field-verified lengths typically vary by ±20% per cable. THIS IS THE SYSTEM'S WEAKEST AUTO-GENERATED QUANTITY — please verify before issuing the BOQ to the customer.
How corrections flow
1. Open A3-cable-schedule.yaml in any text editor.
2. Find the affected row by ID (column A in the Detail sheet).
3. Add a verification: block — see the 'Verification schema' sheet for the template.
4. Re-run: python3 _playbook/tools/generate-deliverables.py <project>
5. Corrections flow through B4 manhours, BOQ material costs, and final deliverables automatically.

By Panel

PanelCable countTotal length (m)
DDC-2F-BOH611525
DDC-B1-BOH20560
DDC-RD-PLANT34510
DDC-GF-BOH18450
DDC-3F12420
DDC-2F-CHILLER29348
DDC-2M-CASINO18324
DDC-LG-PLANT13156
TOTAL (field cables)2054293

By Floor

FloorCable countTotal length (m)
2nd Floor901873
Basement20560
Roofdeck34510
Ground18450
3rd Floor12420
2nd Mezzanine (Casino)18324
Lower Ground13156
TOTAL2054293

By Cable Type

Cable typeCountTotal length (m)
4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)902097
4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)44802
Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)42796
4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)29598

Detail (cables)

IDFromToCable typeLength (m)StatusCorrected (m)Verified byDateDrawing refNotes
C0001DDC-GF-BOHAHU-1.1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)25unverified
C0002DDC-GF-BOHAHU-1.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0003DDC-GF-BOHAHU-1.1 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)25unverified
C0004DDC-GF-BOHAHU-1.2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)25unverified
C0005DDC-GF-BOHAHU-1.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0006DDC-GF-BOHAHU-1.2 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)25unverified
C0007DDC-GF-BOHAHU-1.3 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)25unverified
C0008DDC-GF-BOHAHU-1.3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0009DDC-GF-BOHAHU-1.3 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)25unverified
C0010DDC-2M-CASINOAHU-2M.1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)18unverified
C0011DDC-2M-CASINOAHU-2M.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)18unverified
C0012DDC-2M-CASINOAHU-2M.1 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)18unverified
C0013DDC-2M-CASINOAHU-2M.2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)18unverified
C0014DDC-2M-CASINOAHU-2M.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)18unverified
C0015DDC-2M-CASINOAHU-2M.2 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)18unverified
C0016DDC-2F-BOHAHU-B.1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)25unverified
C0017DDC-2F-BOHAHU-B.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0018DDC-2F-BOHAHU-B.1 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)25unverified
C0019DDC-2F-BOHAHU-B.2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)25unverified
C0020DDC-2F-BOHAHU-B.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0021DDC-2F-BOHAHU-B.2 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)25unverified
C0022DDC-2F-BOHAHU-B.3 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)25unverified
C0023DDC-2F-BOHAHU-B.3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0024DDC-2F-BOHAHU-B.3 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)25unverified
C0025DDC-2F-BOHAHU-EL (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)25unverified
C0026DDC-2F-BOHAHU-EL (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0027DDC-2F-BOHAHU-EL (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)25unverified
C0028DDC-2F-BOHAHU-FR2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)25unverified
C0029DDC-2F-BOHAHU-FR2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0030DDC-2F-BOHAHU-FR2 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)25unverified
C0031DDC-2F-BOHAHU-FR3 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)25unverified
C0032DDC-2F-BOHAHU-FR3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0033DDC-2F-BOHAHU-FR3 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)25unverified
C0034DDC-2F-BOHAHU-PF (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)25unverified
C0035DDC-2F-BOHAHU-PF (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0036DDC-2F-BOHAHU-PF (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)25unverified
C0037DDC-2M-CASINOAIR-ION-2M.1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)18unverified
C0038DDC-2M-CASINOAIR-ION-2M.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)18unverified
C0039DDC-2M-CASINOAIR-ION-2M.2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)18unverified
C0040DDC-2M-CASINOAIR-ION-2M.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)18unverified
C0041DDC-2F-CHILLERCH-1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)12unverified
C0042DDC-2F-CHILLERCH-1 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)12unverified
C0043DDC-2F-CHILLERCH-2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)12unverified
C0044DDC-2F-CHILLERCH-2 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)12unverified
C0045DDC-2F-CHILLERCH-3 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)12unverified
C0046DDC-2F-CHILLERCH-3 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)12unverified
C0047DDC-2F-CHILLERCHW-DIFF (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)12unverified
C0048DDC-2F-CHILLERCHW-RET-HDR (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)12unverified
C0049DDC-2F-CHILLERCHW-SUP-HDR (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)12unverified
C0050DDC-2F-CHILLERCOWP-1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)12unverified
C0051DDC-2F-CHILLERCOWP-2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)12unverified
C0052DDC-2F-CHILLERCOWP-3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)12unverified
C0053DDC-RD-PLANTCT-1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)15unverified
C0054DDC-RD-PLANTCT-1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)15unverified
C0055DDC-RD-PLANTCT-1 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)15unverified
C0056DDC-RD-PLANTCT-2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)15unverified
C0057DDC-RD-PLANTCT-2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)15unverified
C0058DDC-RD-PLANTCT-2 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)15unverified
C0059DDC-RD-PLANTCT-3 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)15unverified
C0060DDC-RD-PLANTCT-3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)15unverified
C0061DDC-RD-PLANTCT-3 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)15unverified
C0062DDC-RD-PLANTCT-COMMON (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)15unverified
C0063DDC-RD-PLANTCW-HDR (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)15unverified
C0064DDC-2M-CASINODOAS-2M (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)18unverified
C0065DDC-2M-CASINODOAS-2M (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)18unverified
C0066DDC-2M-CASINODOAS-2M (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)18unverified
C0067DDC-RD-PLANTDOAS-RD.1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)15unverified
C0068DDC-RD-PLANTDOAS-RD.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)15unverified
C0069DDC-RD-PLANTDOAS-RD.1 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)15unverified
C0070DDC-RD-PLANTDOAS-RD.2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)15unverified
C0071DDC-RD-PLANTDOAS-RD.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)15unverified
C0072DDC-RD-PLANTDOAS-RD.2 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)15unverified
C0073DDC-RD-PLANTEF-1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)15unverified
C0074DDC-2F-BOHEF-2.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0075DDC-2F-BOHEF-2.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0076DDC-2F-BOHEF-2.3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0077DDC-2F-BOHEF-2.4 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0078DDC-2F-BOHEF-2B.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0079DDC-2F-BOHEF-2B.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0080DDC-3FEF-3.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)35unverified
C0081DDC-3FEF-3.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)35unverified
C0082DDC-3FEF-3.3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)35unverified
C0083DDC-3FEF-3.4 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)35unverified
C0084DDC-3FEF-3B-G (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)35unverified
C0085DDC-3FEF-3C.1-G (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)35unverified
C0086DDC-B1-BOHEF-B.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)28unverified
C0087DDC-B1-BOHEF-B.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)28unverified
C0088DDC-B1-BOHEF-BR.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)28unverified
C0089DDC-B1-BOHEF-BR.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)28unverified
C0090DDC-B1-BOHEF-BS.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)28unverified
C0091DDC-B1-BOHEF-BS.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)28unverified
C0092DDC-B1-BOHEF-FOST.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)28unverified
C0093DDC-B1-BOHEF-GL.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)28unverified
C0094DDC-B1-BOHEF-GL.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)28unverified
C0095DDC-2F-BOHEF-GS.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0096DDC-2F-BOHEF-GS.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0097DDC-B1-BOHEF-MFR.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)28unverified
C0098DDC-B1-BOHEF-MP.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)28unverified
C0099DDC-2F-BOHEF-OHRv2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0100DDC-B1-BOHEF-PR.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)28unverified
C0101DDC-B1-BOHEF-PR.3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)28unverified
C0102DDC-RD-PLANTEF-RD.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)15unverified
C0103DDC-RD-PLANTEF-RO.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)15unverified
C0104DDC-B1-BOHEF-WS.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)28unverified
C0105DDC-RD-PLANTHP-HZ (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)15unverified
C0106DDC-LG-PLANTHP-LZ (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)12unverified
C0107DDC-RD-PLANTHWH-HZ (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)15unverified
C0108DDC-LG-PLANTHWH-LZ (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)12unverified
C0109DDC-RD-PLANTHWT-HZ (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)15unverified
C0110DDC-LG-PLANTHWT-LZ (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)12unverified
C0111DDC-B1-BOHPAHU-0.1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)28unverified
C0112DDC-B1-BOHPAHU-0.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)28unverified
C0113DDC-B1-BOHPAHU-0.1 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)28unverified
C0114DDC-2F-BOHPAHU-B.1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)25unverified
C0115DDC-2F-BOHPAHU-B.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0116DDC-2F-BOHPAHU-B.1 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)25unverified
C0117DDC-2F-BOHPAHU-B.2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)25unverified
C0118DDC-2F-BOHPAHU-B.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0119DDC-2F-BOHPAHU-B.2 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)25unverified
C0120DDC-2F-BOHPAHU-B.3 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)25unverified
C0121DDC-2F-BOHPAHU-B.3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0122DDC-2F-BOHPAHU-B.3 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)25unverified
C0123DDC-2F-BOHPAHU-FR (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)25unverified
C0124DDC-2F-BOHPAHU-FR (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0125DDC-2F-BOHPAHU-FR (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)25unverified
C0126DDC-2F-BOHPAHU-PF (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)25unverified
C0127DDC-2F-BOHPAHU-PF (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0128DDC-2F-BOHPAHU-PF (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)25unverified
C0129DDC-RD-PLANTPAHU-r.1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)15unverified
C0130DDC-RD-PLANTPAHU-r.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)15unverified
C0131DDC-RD-PLANTPAHU-r.1 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)15unverified
C0132DDC-RD-PLANTPAHU-r.2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)15unverified
C0133DDC-RD-PLANTPAHU-r.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)15unverified
C0134DDC-RD-PLANTPAHU-r.2 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)15unverified
C0135DDC-2F-CHILLERPCHWP-1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)12unverified
C0136DDC-2F-CHILLERPCHWP-1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)12unverified
C0137DDC-2F-CHILLERPCHWP-2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)12unverified
C0138DDC-2F-CHILLERPCHWP-2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)12unverified
C0139DDC-2F-CHILLERPCHWP-3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)12unverified
C0140DDC-RD-PLANTRP-HZ (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)15unverified
C0141DDC-LG-PLANTRP-LZ (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)12unverified
C0142DDC-LG-PLANTSB-1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)12unverified
C0143DDC-LG-PLANTSB-1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)12unverified
C0144DDC-LG-PLANTSB-2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)12unverified
C0145DDC-LG-PLANTSB-2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)12unverified
C0146DDC-2F-CHILLERSCHWP-1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)12unverified
C0147DDC-2F-CHILLERSCHWP-2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)12unverified
C0148DDC-2F-CHILLERSCHWP-3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)12unverified
C0149DDC-GF-BOHTEF-1.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0150DDC-GF-BOHTEF-1.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0151DDC-GF-BOHTEF-1.3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0152DDC-GF-BOHTEF-1.4 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0153DDC-2F-BOHTEF-2.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0154DDC-2F-BOHTEF-2.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0155DDC-2F-BOHTEF-2B.3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)25unverified
C0156DDC-3FTEF-30.20 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)35unverified
C0157DDC-3FTEF-3A.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)35unverified
C0158DDC-3FTEF-3A.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)35unverified
C0159DDC-3FTEF-3B (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)35unverified
C0160DDC-3FTEF-3C.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)35unverified
C0161DDC-3FTEF-3C.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)35unverified
C0162DDC-B1-BOHTEF-B.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)28unverified
C0163DDC-B1-BOHTEF-B.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)28unverified
C0164DDC-2F-CHILLERCH-1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0165DDC-2F-CHILLERCH-2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0166DDC-2F-CHILLERCH-3 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0167DDC-2F-CHILLERPCHWP-1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0168DDC-2F-CHILLERPCHWP-2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0169DDC-2F-CHILLERSCHWP-1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0170DDC-2F-CHILLERSCHWP-2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0171DDC-2F-CHILLERSCHWP-3 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0172DDC-LG-PLANTSB-1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0173DDC-LG-PLANTSB-2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0174DDC-RD-PLANTDOAS-RD.1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0175DDC-RD-PLANTDOAS-RD.2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0176DDC-RD-PLANTPAHU-r.1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0177DDC-RD-PLANTPAHU-r.2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0178DDC-2M-CASINODOAS-2M (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)18unverified
C0179DDC-2M-CASINOAHU-2M.1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)18unverified
C0180DDC-2M-CASINOAHU-2M.2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)18unverified
C0181DDC-2M-CASINOAIR-ION-2M.1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)18unverified
C0182DDC-2M-CASINOAIR-ION-2M.2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)18unverified
C0183DDC-2F-BOHAHU-B.1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)25unverified
C0184DDC-2F-BOHAHU-B.2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)25unverified
C0185DDC-2F-BOHAHU-B.3 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)25unverified
C0186DDC-2F-BOHAHU-PF (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)25unverified
C0187DDC-2F-BOHAHU-EL (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)25unverified
C0188DDC-2F-BOHAHU-FR2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)25unverified
C0189DDC-2F-BOHAHU-FR3 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)25unverified
C0190DDC-2F-BOHPAHU-B.1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)25unverified
C0191DDC-2F-BOHPAHU-B.2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)25unverified
C0192DDC-2F-BOHPAHU-B.3 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)25unverified
C0193DDC-2F-BOHPAHU-PF (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)25unverified
C0194DDC-2F-BOHPAHU-FR (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)25unverified
C0195DDC-GF-BOHAHU-1.1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)25unverified
C0196DDC-GF-BOHAHU-1.2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)25unverified
C0197DDC-GF-BOHAHU-1.3 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)25unverified
C0198DDC-B1-BOHPAHU-0.1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)28unverified
C0199DDC-LG-PLANTMPM-MAIN (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0200DDC-2F-CHILLERMPM-CHILLER (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0201DDC-2F-BOHMPM-AHU-2F (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)25unverified
C0202DDC-GF-BOHMPM-AHU-GF (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)25unverified
C0203DDC-LG-PLANTMPM-LIGHT-A (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0204DDC-LG-PLANTMPM-LIGHT-B (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0205DDC-GF-BOHFACP-GW (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)25unverified
T0206BMS Server Room (head-end)All BMS panels at 2nd FloorCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80unverified
T0207BMS Server Room (head-end)All BMS panels at 3rd FloorCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80unverified
T0208BMS Server Room (head-end)All BMS panels at BasementCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80unverified
T0209BMS Server Room (head-end)All BMS panels at GroundCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80unverified
T0210BMS Server Room (head-end)All BMS panels at Lower GroundCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80unverified
T0211BMS Server Room (head-end)BMS panel controllers (per topology id mstp_field_backbone)BACnet MS/TP shielded twisted-pair trunk, 1pr × 22 AWG low-cap250unverified
T0212BMS Server Room (head-end)BMS panel controllers (per topology id bacnet_ip_backbone)BACnet MS/TP shielded twisted-pair trunk, 1pr × 22 AWG low-cap150unverified
P0213Local panelboard / EE-supplied feederDDC-2F-BOH — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)10unverified
P0214Local panelboard / EE-supplied feederDDC-2F-CHILLER — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)10unverified
P0215Local panelboard / EE-supplied feederDDC-2M-CASINO — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)10unverified
P0216Local panelboard / EE-supplied feederDDC-3F — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)10unverified
P0217Local panelboard / EE-supplied feederDDC-B1-BOH — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)10unverified
P0218Local panelboard / EE-supplied feederDDC-GF-BOH — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)10unverified
P0219Local panelboard / EE-supplied feederDDC-LG-PLANT — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)10unverified
P0220Local panelboard / EE-supplied feederDDC-RD-PLANT — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)10unverified

Verification schema

How to record verification / corrections in A3-cable-schedule.yaml
Find the affected row in the YAML by ID (Detail sheet column A) and add a verification: block:
- id: C0001
from: PNL-CH-PLANT-GND
to: CH-1 (BMS Contractor)
cable_type: 4C × 1.5 mm² shielded FRLS
length_m: 30
verification: # ADDED by team
status: needs_correction # unverified | verified | needs_correction | uncertain
corrected_length_m: 42 # team's measured / confirmed value
verified_by: J. Cruz
verified_date: 2026-05-10
drawing_ref: "EE-09 grid B-2"
notes: ""
After saving, re-run: python3 _playbook/tools/generate-deliverables.py <project>
Corrections propagate to B4 manhours, BOQ, and final deliverables automatically.
Recommended verification methods (priority order):
1. Site walkthrough with measurement (most accurate; for cable lengths, after structural completion).
2. Properly-scaled architectural drawings.
3. Mechanical contractor's tray layout combined with BMS panel locations.
4. A-001 default with ±20% contingency in BOQ — last resort.