Summary
| A4 — Panel Schedule Summary | |
| Total panels | 8 |
| Total physical I/O | 561 |
| Total HLI subpoints | 141 |
| Total network drops | 42 |
| Total I/O points | 744 |
| Estimated total controllers | 19 |
| Estimated total power (W) | 685 |
Panel Schedule
| Panel | Location | System Scope | Equipment Count | Physical I/O | HLI Subpoints | Network Drops | Total I/O | DDC Controllers | Network Gateway | Total Controllers | Power (W) | Enclosure |
| DDC-2F-BOH | 2nd Floor / 2nd Floor BOH / 2nd Floor BOH Toilet / 2nd Floor General Service / 2nd Floor OHR / 2nd Floor Toilet / 2nd Level AHU MCC / 2nd Level BOH / 2nd Level Executive Lounge / 2nd Level Function Room 2 / 2nd Level Function Room 3 / 2nd Level Function Rooms / 2nd Level Pre-Function | AC, EL, VENT | 25 | 165 | 25 | 13 | 203 | 5 | 1 | 5 | 190 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| DDC-2F-CHILLER | 2nd Level Chiller MCC / 2nd Level Chiller Room | AC, EL | 16 | 72 | 65 | 9 | 146 | 2 | 1 | 2 | 95 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| DDC-2M-CASINO | 2nd Mezzanine (Casino) | AC, VENT | 5 | 47 | 8 | 5 | 60 | 2 | 1 | 2 | 75 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| DDC-3F | 3rd Floor / 3rd Floor Amenity Toilet / 3rd Floor BOH / 3rd Floor Toilet | VENT | 12 | 36 | 0 | 0 | 36 | 1 | 0 | 1 | 25 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| DDC-B1-BOH | Basement / Basement Battery Room / Basement FOST Room / Basement Garbage Lobby / Basement Main Fire Riser / Basement Mech / Pump / Basement Pump Room / Basement Service / Basement Toilet / Basement Wash Service | VENT | 17 | 57 | 2 | 1 | 60 | 2 | 1 | 2 | 55 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| DDC-GF-BOH | GF Main Lobby Toilet / Ground Floor AHU MCC / Ground Floor BOH / Ground Floor Fire Command Center | AC, EL, FDAS, VENT | 9 | 48 | 10 | 5 | 63 | 2 | 1 | 2 | 75 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| DDC-LG-PLANT | Lower Ground Boiler Room / Lower Ground HWL Room / Lower Ground Lighting Panel A / Lower Ground Lighting Panel B / Lower Ground Main Switchroom | EL, HWL, VENT | 9 | 26 | 19 | 5 | 50 | 1 | 1 | 2 | 75 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| DDC-RD-PLANT | Roof Deck / Roof Deck CT Area / Roof Deck HWL Area | AC, HWL, VENT | 16 | 110 | 12 | 4 | 126 | 3 | 1 | 3 | 95 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
Equipment per Panel
| Panel | Equipment Instance |
| DDC-2F-BOH | AHU-B.1 |
| DDC-2F-BOH | AHU-B.2 |
| DDC-2F-BOH | AHU-B.3 |
| DDC-2F-BOH | AHU-EL |
| DDC-2F-BOH | AHU-FR2 |
| DDC-2F-BOH | AHU-FR3 |
| DDC-2F-BOH | AHU-PF |
| DDC-2F-BOH | EF-2.1 |
| DDC-2F-BOH | EF-2.2 |
| DDC-2F-BOH | EF-2.3 |
| DDC-2F-BOH | EF-2.4 |
| DDC-2F-BOH | EF-2B.1 |
| DDC-2F-BOH | EF-2B.2 |
| DDC-2F-BOH | EF-GS.1 |
| DDC-2F-BOH | EF-GS.2 |
| DDC-2F-BOH | EF-OHRv2 |
| DDC-2F-BOH | MPM-AHU-2F |
| DDC-2F-BOH | PAHU-B.1 |
| DDC-2F-BOH | PAHU-B.2 |
| DDC-2F-BOH | PAHU-B.3 |
| DDC-2F-BOH | PAHU-FR |
| DDC-2F-BOH | PAHU-PF |
| DDC-2F-BOH | TEF-2.1 |
| DDC-2F-BOH | TEF-2.2 |
| DDC-2F-BOH | TEF-2B.3 |
| DDC-2F-CHILLER | CH-1 |
| DDC-2F-CHILLER | CH-2 |
| DDC-2F-CHILLER | CH-3 |
| DDC-2F-CHILLER | CHW-DIFF |
| DDC-2F-CHILLER | CHW-RET-HDR |
| DDC-2F-CHILLER | CHW-SUP-HDR |
| DDC-2F-CHILLER | COWP-1 |
| DDC-2F-CHILLER | COWP-2 |
| DDC-2F-CHILLER | COWP-3 |
| DDC-2F-CHILLER | MPM-CHILLER |
| DDC-2F-CHILLER | PCHWP-1 |
| DDC-2F-CHILLER | PCHWP-2 |
| DDC-2F-CHILLER | PCHWP-3 |
| DDC-2F-CHILLER | SCHWP-1 |
| DDC-2F-CHILLER | SCHWP-2 |
| DDC-2F-CHILLER | SCHWP-3 |
| DDC-2M-CASINO | AHU-2M.1 |
| DDC-2M-CASINO | AHU-2M.2 |
| DDC-2M-CASINO | AIR-ION-2M.1 |
| DDC-2M-CASINO | AIR-ION-2M.2 |
| DDC-2M-CASINO | DOAS-2M |
| DDC-3F | EF-3.1 |
| DDC-3F | EF-3.2 |
| DDC-3F | EF-3.3 |
| DDC-3F | EF-3.4 |
| DDC-3F | EF-3B-G |
| DDC-3F | EF-3C.1-G |
| DDC-3F | TEF-30.20 |
| DDC-3F | TEF-3A.1 |
| DDC-3F | TEF-3A.2 |
| DDC-3F | TEF-3B |
| DDC-3F | TEF-3C.1 |
| DDC-3F | TEF-3C.2 |
| DDC-B1-BOH | EF-B.1 |
| DDC-B1-BOH | EF-B.2 |
| DDC-B1-BOH | EF-BR.1 |
| DDC-B1-BOH | EF-BR.2 |
| DDC-B1-BOH | EF-BS.1 |
| DDC-B1-BOH | EF-BS.2 |
| DDC-B1-BOH | EF-FOST.1 |
| DDC-B1-BOH | EF-GL.1 |
| DDC-B1-BOH | EF-GL.2 |
| DDC-B1-BOH | EF-MFR.1 |
| DDC-B1-BOH | EF-MP.1 |
| DDC-B1-BOH | EF-PR.1 |
| DDC-B1-BOH | EF-PR.3 |
| DDC-B1-BOH | EF-WS.1 |
| DDC-B1-BOH | PAHU-0.1 |
| DDC-B1-BOH | TEF-B.1 |
| DDC-B1-BOH | TEF-B.2 |
| DDC-GF-BOH | AHU-1.1 |
| DDC-GF-BOH | AHU-1.2 |
| DDC-GF-BOH | AHU-1.3 |
| DDC-GF-BOH | FACP-GW |
| DDC-GF-BOH | MPM-AHU-GF |
| DDC-GF-BOH | TEF-1.1 |
| DDC-GF-BOH | TEF-1.2 |
| DDC-GF-BOH | TEF-1.3 |
| DDC-GF-BOH | TEF-1.4 |
| DDC-LG-PLANT | HP-LZ |
| DDC-LG-PLANT | HWH-LZ |
| DDC-LG-PLANT | HWT-LZ |
| DDC-LG-PLANT | MPM-LIGHT-A |
| DDC-LG-PLANT | MPM-LIGHT-B |
| DDC-LG-PLANT | MPM-MAIN |
| DDC-LG-PLANT | RP-LZ |
| DDC-LG-PLANT | SB-1 |
| DDC-LG-PLANT | SB-2 |
| DDC-RD-PLANT | CT-1 |
| DDC-RD-PLANT | CT-2 |
| DDC-RD-PLANT | CT-3 |
| DDC-RD-PLANT | CT-COMMON |
| DDC-RD-PLANT | CW-HDR |
| DDC-RD-PLANT | DOAS-RD.1 |
| DDC-RD-PLANT | DOAS-RD.2 |
| DDC-RD-PLANT | EF-1 |
| DDC-RD-PLANT | EF-RD.1 |
| DDC-RD-PLANT | EF-RO.2 |
| DDC-RD-PLANT | HP-HZ |
| DDC-RD-PLANT | HWH-HZ |
| DDC-RD-PLANT | HWT-HZ |
| DDC-RD-PLANT | PAHU-r.1 |
| DDC-RD-PLANT | PAHU-r.2 |
| DDC-RD-PLANT | RP-HZ |