Summary

A3 — Cable Schedule Summary
Total field cable runs205
Total field cable length (m)4293
Total trunk cable length (m)800
Total power feed length (m)80
GRAND TOTAL cable length (m)5173
By cable type (m)
4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)2097
4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)802
Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)796
4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)598

Field Cables

IDFromToEquipment ClassSystemLocationCable TypeConductors RequiredConductors SpecifiedLength (m)I/O Points CarriedNotes
C0001DDC-GF-BOHAHU-1.1 (BMS Contractor)AHU (Chilled-Water-Served)ACGround Floor BOH4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)662555 I/O points carried, 6C cable; length 25 m (typical_range:boh_gf)
C0002DDC-GF-BOHAHU-1.1 (Equipment Supplier)AHU (Chilled-Water-Served)ACGround Floor BOH4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)442544 I/O points carried, 4C cable; length 25 m (typical_range:boh_gf)
C0003DDC-GF-BOHAHU-1.1 (ME Contractor)AHU (Chilled-Water-Served)ACGround Floor BOH4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)342533 I/O points carried, 4C cable; length 25 m (typical_range:boh_gf)
C0004DDC-GF-BOHAHU-1.2 (BMS Contractor)AHU (Chilled-Water-Served)ACGround Floor BOH4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)662555 I/O points carried, 6C cable; length 25 m (typical_range:boh_gf)
C0005DDC-GF-BOHAHU-1.2 (Equipment Supplier)AHU (Chilled-Water-Served)ACGround Floor BOH4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)442544 I/O points carried, 4C cable; length 25 m (typical_range:boh_gf)
C0006DDC-GF-BOHAHU-1.2 (ME Contractor)AHU (Chilled-Water-Served)ACGround Floor BOH4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)342533 I/O points carried, 4C cable; length 25 m (typical_range:boh_gf)
C0007DDC-GF-BOHAHU-1.3 (BMS Contractor)AHU (Chilled-Water-Served)ACGround Floor BOH4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)662555 I/O points carried, 6C cable; length 25 m (typical_range:boh_gf)
C0008DDC-GF-BOHAHU-1.3 (Equipment Supplier)AHU (Chilled-Water-Served)ACGround Floor BOH4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)442544 I/O points carried, 4C cable; length 25 m (typical_range:boh_gf)
C0009DDC-GF-BOHAHU-1.3 (ME Contractor)AHU (Chilled-Water-Served)ACGround Floor BOH4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)342533 I/O points carried, 4C cable; length 25 m (typical_range:boh_gf)
C0010DDC-2M-CASINOAHU-2M.1 (BMS Contractor)AHU (Chilled-Water-Served)AC2nd Mezzanine (Casino)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)661855 I/O points carried, 6C cable; length 18 m (typical_range:casino_2m_localized)
C0011DDC-2M-CASINOAHU-2M.1 (Equipment Supplier)AHU (Chilled-Water-Served)AC2nd Mezzanine (Casino)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)441844 I/O points carried, 4C cable; length 18 m (typical_range:casino_2m_localized)
C0012DDC-2M-CASINOAHU-2M.1 (ME Contractor)AHU (Chilled-Water-Served)AC2nd Mezzanine (Casino)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)341833 I/O points carried, 4C cable; length 18 m (typical_range:casino_2m_localized)
C0013DDC-2M-CASINOAHU-2M.2 (BMS Contractor)AHU (Chilled-Water-Served)AC2nd Mezzanine (Casino)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)661855 I/O points carried, 6C cable; length 18 m (typical_range:casino_2m_localized)
C0014DDC-2M-CASINOAHU-2M.2 (Equipment Supplier)AHU (Chilled-Water-Served)AC2nd Mezzanine (Casino)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)441844 I/O points carried, 4C cable; length 18 m (typical_range:casino_2m_localized)
C0015DDC-2M-CASINOAHU-2M.2 (ME Contractor)AHU (Chilled-Water-Served)AC2nd Mezzanine (Casino)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)341833 I/O points carried, 4C cable; length 18 m (typical_range:casino_2m_localized)
C0016DDC-2F-BOHAHU-B.1 (BMS Contractor)AHU (Chilled-Water-Served)AC2nd Level BOH4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)662555 I/O points carried, 6C cable; length 25 m (typical_range:boh_2f)
C0017DDC-2F-BOHAHU-B.1 (Equipment Supplier)AHU (Chilled-Water-Served)AC2nd Level BOH4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)442544 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0018DDC-2F-BOHAHU-B.1 (ME Contractor)AHU (Chilled-Water-Served)AC2nd Level BOH4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)342533 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0019DDC-2F-BOHAHU-B.2 (BMS Contractor)AHU (Chilled-Water-Served)AC2nd Level BOH4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)662555 I/O points carried, 6C cable; length 25 m (typical_range:boh_2f)
C0020DDC-2F-BOHAHU-B.2 (Equipment Supplier)AHU (Chilled-Water-Served)AC2nd Level BOH4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)442544 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0021DDC-2F-BOHAHU-B.2 (ME Contractor)AHU (Chilled-Water-Served)AC2nd Level BOH4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)342533 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0022DDC-2F-BOHAHU-B.3 (BMS Contractor)AHU (Chilled-Water-Served)AC2nd Level BOH4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)662555 I/O points carried, 6C cable; length 25 m (typical_range:boh_2f)
C0023DDC-2F-BOHAHU-B.3 (Equipment Supplier)AHU (Chilled-Water-Served)AC2nd Level BOH4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)442544 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0024DDC-2F-BOHAHU-B.3 (ME Contractor)AHU (Chilled-Water-Served)AC2nd Level BOH4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)342533 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0025DDC-2F-BOHAHU-EL (BMS Contractor)AHU (Chilled-Water-Served)AC2nd Level Executive Lounge4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)662555 I/O points carried, 6C cable; length 25 m (typical_range:boh_2f)
C0026DDC-2F-BOHAHU-EL (Equipment Supplier)AHU (Chilled-Water-Served)AC2nd Level Executive Lounge4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)442544 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0027DDC-2F-BOHAHU-EL (ME Contractor)AHU (Chilled-Water-Served)AC2nd Level Executive Lounge4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)342533 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0028DDC-2F-BOHAHU-FR2 (BMS Contractor)AHU (Chilled-Water-Served)AC2nd Level Function Room 24C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)662555 I/O points carried, 6C cable; length 25 m (typical_range:boh_2f)
C0029DDC-2F-BOHAHU-FR2 (Equipment Supplier)AHU (Chilled-Water-Served)AC2nd Level Function Room 24C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)442544 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0030DDC-2F-BOHAHU-FR2 (ME Contractor)AHU (Chilled-Water-Served)AC2nd Level Function Room 24C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)342533 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0031DDC-2F-BOHAHU-FR3 (BMS Contractor)AHU (Chilled-Water-Served)AC2nd Level Function Room 34C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)662555 I/O points carried, 6C cable; length 25 m (typical_range:boh_2f)
C0032DDC-2F-BOHAHU-FR3 (Equipment Supplier)AHU (Chilled-Water-Served)AC2nd Level Function Room 34C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)442544 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0033DDC-2F-BOHAHU-FR3 (ME Contractor)AHU (Chilled-Water-Served)AC2nd Level Function Room 34C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)342533 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0034DDC-2F-BOHAHU-PF (BMS Contractor)AHU (Chilled-Water-Served)AC2nd Level Pre-Function4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)662555 I/O points carried, 6C cable; length 25 m (typical_range:boh_2f)
C0035DDC-2F-BOHAHU-PF (Equipment Supplier)AHU (Chilled-Water-Served)AC2nd Level Pre-Function4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)442544 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0036DDC-2F-BOHAHU-PF (ME Contractor)AHU (Chilled-Water-Served)AC2nd Level Pre-Function4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)342533 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0037DDC-2M-CASINOAIR-ION-2M.1 (BMS Contractor)Air Ionizer (Casino)AC2nd Mezzanine (Casino)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)141811 I/O points carried, 4C cable; length 18 m (typical_range:casino_2m_localized)
C0038DDC-2M-CASINOAIR-ION-2M.1 (Equipment Supplier)Air Ionizer (Casino)AC2nd Mezzanine (Casino)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)241822 I/O points carried, 4C cable; length 18 m (typical_range:casino_2m_localized)
C0039DDC-2M-CASINOAIR-ION-2M.2 (BMS Contractor)Air Ionizer (Casino)AC2nd Mezzanine (Casino)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)141811 I/O points carried, 4C cable; length 18 m (typical_range:casino_2m_localized)
C0040DDC-2M-CASINOAIR-ION-2M.2 (Equipment Supplier)Air Ionizer (Casino)AC2nd Mezzanine (Casino)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)241822 I/O points carried, 4C cable; length 18 m (typical_range:casino_2m_localized)
C0041DDC-2F-CHILLERCH-1 (BMS Contractor)Chiller (Package Water-Cooled)AC2nd Level Chiller Room4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)9121277 I/O points carried, 12C cable; length 12 m (typical_range:plant_room_chiller_2f)
C0042DDC-2F-CHILLERCH-1 (ME Contractor)Chiller (Package Water-Cooled)AC2nd Level Chiller Room4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)241222 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_chiller_2f)
C0043DDC-2F-CHILLERCH-2 (BMS Contractor)Chiller (Package Water-Cooled)AC2nd Level Chiller Room4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)9121277 I/O points carried, 12C cable; length 12 m (typical_range:plant_room_chiller_2f)
C0044DDC-2F-CHILLERCH-2 (ME Contractor)Chiller (Package Water-Cooled)AC2nd Level Chiller Room4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)241222 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_chiller_2f)
C0045DDC-2F-CHILLERCH-3 (BMS Contractor)Chiller (Package Water-Cooled)AC2nd Level Chiller Room4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)9121277 I/O points carried, 12C cable; length 12 m (typical_range:plant_room_chiller_2f)
C0046DDC-2F-CHILLERCH-3 (ME Contractor)Chiller (Package Water-Cooled)AC2nd Level Chiller Room4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)241222 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_chiller_2f)
C0047DDC-2F-CHILLERCHW-DIFF (BMS Contractor)CHW Bypass HeaderAC2nd Level Chiller Room4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)341233 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_chiller_2f)
C0048DDC-2F-CHILLERCHW-RET-HDR (BMS Contractor)CHW Return Main HeaderAC2nd Level Chiller Room4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)241222 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_chiller_2f)
C0049DDC-2F-CHILLERCHW-SUP-HDR (BMS Contractor)CHW Supply Main HeaderAC2nd Level Chiller Room4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)241222 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_chiller_2f)
C0050DDC-2F-CHILLERCOWP-1 (Equipment Supplier)Condenser Water PumpAC2nd Level Chiller Room4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)441244 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_chiller_2f)
C0051DDC-2F-CHILLERCOWP-2 (Equipment Supplier)Condenser Water PumpAC2nd Level Chiller Room4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)441244 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_chiller_2f)
C0052DDC-2F-CHILLERCOWP-3 (Equipment Supplier)Condenser Water PumpAC2nd Level Chiller Room4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)441244 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_chiller_2f)
C0053DDC-RD-PLANTCT-1 (BMS Contractor)Cooling TowerACRoof Deck4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)441544 I/O points carried, 4C cable; length 15 m (typical_range:plant_room_rd_plant)
C0054DDC-RD-PLANTCT-1 (Equipment Supplier)Cooling TowerACRoof Deck4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)341533 I/O points carried, 4C cable; length 15 m (typical_range:plant_room_rd_plant)
C0055DDC-RD-PLANTCT-1 (ME Contractor)Cooling TowerACRoof Deck4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)241522 I/O points carried, 4C cable; length 15 m (typical_range:plant_room_rd_plant)
C0056DDC-RD-PLANTCT-2 (BMS Contractor)Cooling TowerACRoof Deck4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)441544 I/O points carried, 4C cable; length 15 m (typical_range:plant_room_rd_plant)
C0057DDC-RD-PLANTCT-2 (Equipment Supplier)Cooling TowerACRoof Deck4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)341533 I/O points carried, 4C cable; length 15 m (typical_range:plant_room_rd_plant)
C0058DDC-RD-PLANTCT-2 (ME Contractor)Cooling TowerACRoof Deck4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)241522 I/O points carried, 4C cable; length 15 m (typical_range:plant_room_rd_plant)
C0059DDC-RD-PLANTCT-3 (BMS Contractor)Cooling TowerACRoof Deck4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)441544 I/O points carried, 4C cable; length 15 m (typical_range:plant_room_rd_plant)
C0060DDC-RD-PLANTCT-3 (Equipment Supplier)Cooling TowerACRoof Deck4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)341533 I/O points carried, 4C cable; length 15 m (typical_range:plant_room_rd_plant)
C0061DDC-RD-PLANTCT-3 (ME Contractor)Cooling TowerACRoof Deck4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)241522 I/O points carried, 4C cable; length 15 m (typical_range:plant_room_rd_plant)
C0062DDC-RD-PLANTCT-COMMON (BMS Contractor)Cooling Tower (Common)ACRoof Deck4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)561544 I/O points carried, 6C cable; length 15 m (typical_range:plant_room_rd_plant)
C0063DDC-RD-PLANTCW-HDR (BMS Contractor)Condenser Water HeaderACRoof Deck CT Area4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)241522 I/O points carried, 4C cable; length 15 m (typical_range:plant_room_rd_plant)
C0064DDC-2M-CASINODOAS-2M (BMS Contractor)DOAS Unit (Casino — with CO/VOC)VENT2nd Mezzanine (Casino)4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)661855 I/O points carried, 6C cable; length 18 m (typical_range:casino_2m_localized)
C0065DDC-2M-CASINODOAS-2M (Equipment Supplier)DOAS Unit (Casino — with CO/VOC)VENT2nd Mezzanine (Casino)4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)10121899 I/O points carried, 12C cable; length 18 m (typical_range:casino_2m_localized)
C0066DDC-2M-CASINODOAS-2M (ME Contractor)DOAS Unit (Casino — with CO/VOC)VENT2nd Mezzanine (Casino)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)341833 I/O points carried, 4C cable; length 18 m (typical_range:casino_2m_localized)
C0067DDC-RD-PLANTDOAS-RD.1 (BMS Contractor)DOAS UnitVENTRoof Deck4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)881566 I/O points carried, 8C cable; length 15 m (typical_range:plant_room_rd_plant)
C0068DDC-RD-PLANTDOAS-RD.1 (Equipment Supplier)DOAS UnitVENTRoof Deck4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)1112151010 I/O points carried, 12C cable; length 15 m (typical_range:plant_room_rd_plant)
C0069DDC-RD-PLANTDOAS-RD.1 (ME Contractor)DOAS UnitVENTRoof Deck4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)441544 I/O points carried, 4C cable; length 15 m (typical_range:plant_room_rd_plant)
C0070DDC-RD-PLANTDOAS-RD.2 (BMS Contractor)DOAS UnitVENTRoof Deck4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)881566 I/O points carried, 8C cable; length 15 m (typical_range:plant_room_rd_plant)
C0071DDC-RD-PLANTDOAS-RD.2 (Equipment Supplier)DOAS UnitVENTRoof Deck4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)1112151010 I/O points carried, 12C cable; length 15 m (typical_range:plant_room_rd_plant)
C0072DDC-RD-PLANTDOAS-RD.2 (ME Contractor)DOAS UnitVENTRoof Deck4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)441544 I/O points carried, 4C cable; length 15 m (typical_range:plant_room_rd_plant)
C0073DDC-RD-PLANTEF-1 (Equipment Supplier)Exhaust Fan (General)VENTRoof Deck4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)341533 I/O points carried, 4C cable; length 15 m (typical_range:plant_room_rd_plant)
C0074DDC-2F-BOHEF-2.1 (Equipment Supplier)Exhaust Fan (General)VENT2nd Floor4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342533 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0075DDC-2F-BOHEF-2.2 (Equipment Supplier)Exhaust Fan (General)VENT2nd Floor4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342533 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0076DDC-2F-BOHEF-2.3 (Equipment Supplier)Exhaust Fan (General)VENT2nd Floor4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342533 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0077DDC-2F-BOHEF-2.4 (Equipment Supplier)Exhaust Fan (General)VENT2nd Floor4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342533 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0078DDC-2F-BOHEF-2B.1 (Equipment Supplier)Exhaust Fan (General)VENT2nd Floor BOH4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342533 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0079DDC-2F-BOHEF-2B.2 (Equipment Supplier)Exhaust Fan (General)VENT2nd Floor BOH4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342533 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0080DDC-3FEF-3.1 (Equipment Supplier)Exhaust Fan (General)VENT3rd Floor4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)343533 I/O points carried, 4C cable; length 35 m (typical_range:amenity_3f)
C0081DDC-3FEF-3.2 (Equipment Supplier)Exhaust Fan (General)VENT3rd Floor4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)343533 I/O points carried, 4C cable; length 35 m (typical_range:amenity_3f)
C0082DDC-3FEF-3.3 (Equipment Supplier)Exhaust Fan (General)VENT3rd Floor4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)343533 I/O points carried, 4C cable; length 35 m (typical_range:amenity_3f)
C0083DDC-3FEF-3.4 (Equipment Supplier)Exhaust Fan (General)VENT3rd Floor4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)343533 I/O points carried, 4C cable; length 35 m (typical_range:amenity_3f)
C0084DDC-3FEF-3B-G (Equipment Supplier)Exhaust Fan (General)VENT3rd Floor BOH4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)343533 I/O points carried, 4C cable; length 35 m (typical_range:amenity_3f)
C0085DDC-3FEF-3C.1-G (Equipment Supplier)Exhaust Fan (General)VENT3rd Floor4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)343533 I/O points carried, 4C cable; length 35 m (typical_range:amenity_3f)
C0086DDC-B1-BOHEF-B.1 (Equipment Supplier)Exhaust Fan (General)VENTBasement4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342833 I/O points carried, 4C cable; length 28 m (typical_range:boh_b1)
C0087DDC-B1-BOHEF-B.2 (Equipment Supplier)Exhaust Fan (General)VENTBasement4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342833 I/O points carried, 4C cable; length 28 m (typical_range:boh_b1)
C0088DDC-B1-BOHEF-BR.1 (Equipment Supplier)Exhaust Fan (General)VENTBasement Battery Room4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342833 I/O points carried, 4C cable; length 28 m (typical_range:boh_b1)
C0089DDC-B1-BOHEF-BR.2 (Equipment Supplier)Exhaust Fan (General)VENTBasement Battery Room4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342833 I/O points carried, 4C cable; length 28 m (typical_range:boh_b1)
C0090DDC-B1-BOHEF-BS.1 (Equipment Supplier)Exhaust Fan (General)VENTBasement Service4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342833 I/O points carried, 4C cable; length 28 m (typical_range:boh_b1)
C0091DDC-B1-BOHEF-BS.2 (Equipment Supplier)Exhaust Fan (General)VENTBasement Service4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342833 I/O points carried, 4C cable; length 28 m (typical_range:boh_b1)
C0092DDC-B1-BOHEF-FOST.1 (Equipment Supplier)Exhaust Fan (General)VENTBasement FOST Room4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342833 I/O points carried, 4C cable; length 28 m (typical_range:boh_b1)
C0093DDC-B1-BOHEF-GL.1 (Equipment Supplier)Exhaust Fan (General)VENTBasement Garbage Lobby4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342833 I/O points carried, 4C cable; length 28 m (typical_range:boh_b1)
C0094DDC-B1-BOHEF-GL.2 (Equipment Supplier)Exhaust Fan (General)VENTBasement Garbage Lobby4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342833 I/O points carried, 4C cable; length 28 m (typical_range:boh_b1)
C0095DDC-2F-BOHEF-GS.1 (Equipment Supplier)Exhaust Fan (General)VENT2nd Floor General Service4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342533 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0096DDC-2F-BOHEF-GS.2 (Equipment Supplier)Exhaust Fan (General)VENT2nd Floor General Service4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342533 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0097DDC-B1-BOHEF-MFR.1 (Equipment Supplier)Exhaust Fan (General)VENTBasement Main Fire Riser4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342833 I/O points carried, 4C cable; length 28 m (typical_range:boh_b1)
C0098DDC-B1-BOHEF-MP.1 (Equipment Supplier)Exhaust Fan (General)VENTBasement Mech / Pump4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342833 I/O points carried, 4C cable; length 28 m (typical_range:boh_b1)
C0099DDC-2F-BOHEF-OHRv2 (Equipment Supplier)Exhaust Fan (General)VENT2nd Floor OHR4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342533 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0100DDC-B1-BOHEF-PR.1 (Equipment Supplier)Exhaust Fan (General)VENTBasement Pump Room4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342833 I/O points carried, 4C cable; length 28 m (typical_range:boh_b1)
C0101DDC-B1-BOHEF-PR.3 (Equipment Supplier)Exhaust Fan (General)VENTBasement Pump Room4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342833 I/O points carried, 4C cable; length 28 m (typical_range:boh_b1)
C0102DDC-RD-PLANTEF-RD.1 (Equipment Supplier)Exhaust Fan (General)VENTRoof Deck4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)341533 I/O points carried, 4C cable; length 15 m (typical_range:plant_room_rd_plant)
C0103DDC-RD-PLANTEF-RO.2 (Equipment Supplier)Exhaust Fan (General)VENTRoof Deck4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)341533 I/O points carried, 4C cable; length 15 m (typical_range:plant_room_rd_plant)
C0104DDC-B1-BOHEF-WS.1 (Equipment Supplier)Exhaust Fan (General)VENTBasement Wash Service4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342833 I/O points carried, 4C cable; length 28 m (typical_range:boh_b1)
C0105DDC-RD-PLANTHP-HZ (Equipment Supplier)Heat PumpHWLRoof Deck HWL Area4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)341533 I/O points carried, 4C cable; length 15 m (typical_range:plant_room_rd_plant)
C0106DDC-LG-PLANTHP-LZ (Equipment Supplier)Heat PumpHWLLower Ground HWL Room4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)341233 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_lg_boiler_hwl)
C0107DDC-RD-PLANTHWH-HZ (BMS Contractor)Hot Water Header SetHWLRoof Deck HWL Area4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)441533 I/O points carried, 4C cable; length 15 m (typical_range:plant_room_rd_plant)
C0108DDC-LG-PLANTHWH-LZ (BMS Contractor)Hot Water Header SetHWLLower Ground HWL Room4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)441233 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_lg_boiler_hwl)
C0109DDC-RD-PLANTHWT-HZ (BMS Contractor)Calorifier (Hot Water Storage Tank)HWLRoof Deck HWL Area4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)141511 I/O points carried, 4C cable; length 15 m (typical_range:plant_room_rd_plant)
C0110DDC-LG-PLANTHWT-LZ (BMS Contractor)Calorifier (Hot Water Storage Tank)HWLLower Ground HWL Room4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)141211 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_lg_boiler_hwl)
C0111DDC-B1-BOHPAHU-0.1 (BMS Contractor)Precooled Air Handling UnitVENTBasement4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)442833 I/O points carried, 4C cable; length 28 m (typical_range:boh_b1)
C0112DDC-B1-BOHPAHU-0.1 (Equipment Supplier)Precooled Air Handling UnitVENTBasement4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)562855 I/O points carried, 6C cable; length 28 m (typical_range:boh_b1)
C0113DDC-B1-BOHPAHU-0.1 (ME Contractor)Precooled Air Handling UnitVENTBasement4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:boh_b1)
C0114DDC-2F-BOHPAHU-B.1 (BMS Contractor)Precooled Air Handling UnitVENT2nd Level BOH4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)442533 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0115DDC-2F-BOHPAHU-B.1 (Equipment Supplier)Precooled Air Handling UnitVENT2nd Level BOH4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)562555 I/O points carried, 6C cable; length 25 m (typical_range:boh_2f)
C0116DDC-2F-BOHPAHU-B.1 (ME Contractor)Precooled Air Handling UnitVENT2nd Level BOH4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142511 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0117DDC-2F-BOHPAHU-B.2 (BMS Contractor)Precooled Air Handling UnitVENT2nd Level BOH4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)442533 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0118DDC-2F-BOHPAHU-B.2 (Equipment Supplier)Precooled Air Handling UnitVENT2nd Level BOH4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)562555 I/O points carried, 6C cable; length 25 m (typical_range:boh_2f)
C0119DDC-2F-BOHPAHU-B.2 (ME Contractor)Precooled Air Handling UnitVENT2nd Level BOH4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142511 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0120DDC-2F-BOHPAHU-B.3 (BMS Contractor)Precooled Air Handling UnitVENT2nd Level BOH4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)442533 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0121DDC-2F-BOHPAHU-B.3 (Equipment Supplier)Precooled Air Handling UnitVENT2nd Level BOH4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)562555 I/O points carried, 6C cable; length 25 m (typical_range:boh_2f)
C0122DDC-2F-BOHPAHU-B.3 (ME Contractor)Precooled Air Handling UnitVENT2nd Level BOH4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142511 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0123DDC-2F-BOHPAHU-FR (BMS Contractor)Precooled Air Handling UnitVENT2nd Level Function Rooms4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)442533 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0124DDC-2F-BOHPAHU-FR (Equipment Supplier)Precooled Air Handling UnitVENT2nd Level Function Rooms4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)562555 I/O points carried, 6C cable; length 25 m (typical_range:boh_2f)
C0125DDC-2F-BOHPAHU-FR (ME Contractor)Precooled Air Handling UnitVENT2nd Level Function Rooms4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142511 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0126DDC-2F-BOHPAHU-PF (BMS Contractor)Precooled Air Handling UnitVENT2nd Level Pre-Function4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)442533 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0127DDC-2F-BOHPAHU-PF (Equipment Supplier)Precooled Air Handling UnitVENT2nd Level Pre-Function4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)562555 I/O points carried, 6C cable; length 25 m (typical_range:boh_2f)
C0128DDC-2F-BOHPAHU-PF (ME Contractor)Precooled Air Handling UnitVENT2nd Level Pre-Function4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142511 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0129DDC-RD-PLANTPAHU-r.1 (BMS Contractor)Precooled Air Handling UnitVENTRoof Deck4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)441533 I/O points carried, 4C cable; length 15 m (typical_range:plant_room_rd_plant)
C0130DDC-RD-PLANTPAHU-r.1 (Equipment Supplier)Precooled Air Handling UnitVENTRoof Deck4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)561555 I/O points carried, 6C cable; length 15 m (typical_range:plant_room_rd_plant)
C0131DDC-RD-PLANTPAHU-r.1 (ME Contractor)Precooled Air Handling UnitVENTRoof Deck4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)141511 I/O points carried, 4C cable; length 15 m (typical_range:plant_room_rd_plant)
C0132DDC-RD-PLANTPAHU-r.2 (BMS Contractor)Precooled Air Handling UnitVENTRoof Deck4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)441533 I/O points carried, 4C cable; length 15 m (typical_range:plant_room_rd_plant)
C0133DDC-RD-PLANTPAHU-r.2 (Equipment Supplier)Precooled Air Handling UnitVENTRoof Deck4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)561555 I/O points carried, 6C cable; length 15 m (typical_range:plant_room_rd_plant)
C0134DDC-RD-PLANTPAHU-r.2 (ME Contractor)Precooled Air Handling UnitVENTRoof Deck4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)141511 I/O points carried, 4C cable; length 15 m (typical_range:plant_room_rd_plant)
C0135DDC-2F-CHILLERPCHWP-1 (BMS Contractor)Primary CHW PumpAC2nd Level Chiller Room4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)141211 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_chiller_2f)
C0136DDC-2F-CHILLERPCHWP-1 (Equipment Supplier)Primary CHW PumpAC2nd Level Chiller Room4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)441244 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_chiller_2f)
C0137DDC-2F-CHILLERPCHWP-2 (BMS Contractor)Primary CHW PumpAC2nd Level Chiller Room4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)141211 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_chiller_2f)
C0138DDC-2F-CHILLERPCHWP-2 (Equipment Supplier)Primary CHW PumpAC2nd Level Chiller Room4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)441244 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_chiller_2f)
C0139DDC-2F-CHILLERPCHWP-3 (Equipment Supplier)Primary CHW Pump (Standby)AC2nd Level Chiller Room4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)441244 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_chiller_2f)
C0140DDC-RD-PLANTRP-HZ (Equipment Supplier)Recirculating PumpHWLRoof Deck HWL Area4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)341533 I/O points carried, 4C cable; length 15 m (typical_range:plant_room_rd_plant)
C0141DDC-LG-PLANTRP-LZ (Equipment Supplier)Recirculating PumpHWLLower Ground HWL Room4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)341233 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_lg_boiler_hwl)
C0142DDC-LG-PLANTSB-1 (BMS Contractor)Steam BoilerVENTLower Ground Boiler Room4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)781266 I/O points carried, 8C cable; length 12 m (typical_range:plant_room_lg_boiler_hwl)
C0143DDC-LG-PLANTSB-1 (Equipment Supplier)Steam BoilerVENTLower Ground Boiler Room4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)241222 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_lg_boiler_hwl)
C0144DDC-LG-PLANTSB-2 (BMS Contractor)Steam BoilerVENTLower Ground Boiler Room4C × 1.5 mm² shielded FRLS (BMS signal — BMS-supplied sensors)781266 I/O points carried, 8C cable; length 12 m (typical_range:plant_room_lg_boiler_hwl)
C0145DDC-LG-PLANTSB-2 (Equipment Supplier)Steam BoilerVENTLower Ground Boiler Room4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)241222 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_lg_boiler_hwl)
C0146DDC-2F-CHILLERSCHWP-1 (Equipment Supplier)Secondary CHW PumpAC2nd Level Chiller Room4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)441244 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_chiller_2f)
C0147DDC-2F-CHILLERSCHWP-2 (Equipment Supplier)Secondary CHW PumpAC2nd Level Chiller Room4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)441244 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_chiller_2f)
C0148DDC-2F-CHILLERSCHWP-3 (Equipment Supplier)Secondary CHW PumpAC2nd Level Chiller Room4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)441244 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_chiller_2f)
C0149DDC-GF-BOHTEF-1.1 (Equipment Supplier)Exhaust Fan (Toilet)VENTGF Main Lobby Toilet4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342533 I/O points carried, 4C cable; length 25 m (typical_range:boh_gf)
C0150DDC-GF-BOHTEF-1.2 (Equipment Supplier)Exhaust Fan (Toilet)VENTGF Main Lobby Toilet4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342533 I/O points carried, 4C cable; length 25 m (typical_range:boh_gf)
C0151DDC-GF-BOHTEF-1.3 (Equipment Supplier)Exhaust Fan (Toilet)VENTGF Main Lobby Toilet4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342533 I/O points carried, 4C cable; length 25 m (typical_range:boh_gf)
C0152DDC-GF-BOHTEF-1.4 (Equipment Supplier)Exhaust Fan (Toilet)VENTGF Main Lobby Toilet4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342533 I/O points carried, 4C cable; length 25 m (typical_range:boh_gf)
C0153DDC-2F-BOHTEF-2.1 (Equipment Supplier)Exhaust Fan (Toilet)VENT2nd Floor Toilet4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342533 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0154DDC-2F-BOHTEF-2.2 (Equipment Supplier)Exhaust Fan (Toilet)VENT2nd Floor Toilet4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342533 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0155DDC-2F-BOHTEF-2B.3 (Equipment Supplier)Exhaust Fan (Toilet)VENT2nd Floor BOH Toilet4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342533 I/O points carried, 4C cable; length 25 m (typical_range:boh_2f)
C0156DDC-3FTEF-30.20 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor Toilet4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)343533 I/O points carried, 4C cable; length 35 m (typical_range:amenity_3f)
C0157DDC-3FTEF-3A.1 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor Amenity Toilet4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)343533 I/O points carried, 4C cable; length 35 m (typical_range:amenity_3f)
C0158DDC-3FTEF-3A.2 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor Amenity Toilet4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)343533 I/O points carried, 4C cable; length 35 m (typical_range:amenity_3f)
C0159DDC-3FTEF-3B (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor Toilet4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)343533 I/O points carried, 4C cable; length 35 m (typical_range:amenity_3f)
C0160DDC-3FTEF-3C.1 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor Toilet4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)343533 I/O points carried, 4C cable; length 35 m (typical_range:amenity_3f)
C0161DDC-3FTEF-3C.2 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor Toilet4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)343533 I/O points carried, 4C cable; length 35 m (typical_range:amenity_3f)
C0162DDC-B1-BOHTEF-B.1 (Equipment Supplier)Exhaust Fan (Toilet)VENTBasement Toilet4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342833 I/O points carried, 4C cable; length 28 m (typical_range:boh_b1)
C0163DDC-B1-BOHTEF-B.2 (Equipment Supplier)Exhaust Fan (Toilet)VENTBasement Toilet4C × 1.5 mm² FRLS (equipment auxiliary contacts — status/HOA/trip/start-stop)342833 I/O points carried, 4C cable; length 28 m (typical_range:boh_b1)
C0164DDC-2F-CHILLERCH-1 (Network)Chiller (Package Water-Cooled)AC2nd Level Chiller RoomCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link121BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 12 m (typical_range:plant_room_chiller_2f)
C0165DDC-2F-CHILLERCH-2 (Network)Chiller (Package Water-Cooled)AC2nd Level Chiller RoomCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link121BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 12 m (typical_range:plant_room_chiller_2f)
C0166DDC-2F-CHILLERCH-3 (Network)Chiller (Package Water-Cooled)AC2nd Level Chiller RoomCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link121BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 12 m (typical_range:plant_room_chiller_2f)
C0167DDC-2F-CHILLERPCHWP-1 (Network)Primary CHW PumpAC2nd Level Chiller RoomCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link121BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 12 m (typical_range:plant_room_chiller_2f)
C0168DDC-2F-CHILLERPCHWP-2 (Network)Primary CHW PumpAC2nd Level Chiller RoomCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link121BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 12 m (typical_range:plant_room_chiller_2f)
C0169DDC-2F-CHILLERSCHWP-1 (Network)Secondary CHW PumpAC2nd Level Chiller RoomCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link121BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 12 m (typical_range:plant_room_chiller_2f)
C0170DDC-2F-CHILLERSCHWP-2 (Network)Secondary CHW PumpAC2nd Level Chiller RoomCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link121BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 12 m (typical_range:plant_room_chiller_2f)
C0171DDC-2F-CHILLERSCHWP-3 (Network)Secondary CHW PumpAC2nd Level Chiller RoomCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link121BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 12 m (typical_range:plant_room_chiller_2f)
C0172DDC-LG-PLANTSB-1 (Network)Steam BoilerVENTLower Ground Boiler RoomCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link121BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 12 m (typical_range:plant_room_lg_boiler_hwl)
C0173DDC-LG-PLANTSB-2 (Network)Steam BoilerVENTLower Ground Boiler RoomCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link121BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 12 m (typical_range:plant_room_lg_boiler_hwl)
C0174DDC-RD-PLANTDOAS-RD.1 (Network)DOAS UnitVENTRoof DeckCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link151BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 15 m (typical_range:plant_room_rd_plant)
C0175DDC-RD-PLANTDOAS-RD.2 (Network)DOAS UnitVENTRoof DeckCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link151BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 15 m (typical_range:plant_room_rd_plant)
C0176DDC-RD-PLANTPAHU-r.1 (Network)Precooled Air Handling UnitVENTRoof DeckCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link151BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 15 m (typical_range:plant_room_rd_plant)
C0177DDC-RD-PLANTPAHU-r.2 (Network)Precooled Air Handling UnitVENTRoof DeckCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link151BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 15 m (typical_range:plant_room_rd_plant)
C0178DDC-2M-CASINODOAS-2M (Network)DOAS Unit (Casino — with CO/VOC)VENT2nd Mezzanine (Casino)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link181BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 18 m (typical_range:casino_2m_localized)
C0179DDC-2M-CASINOAHU-2M.1 (Network)AHU (Chilled-Water-Served)AC2nd Mezzanine (Casino)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link181BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 18 m (typical_range:casino_2m_localized)
C0180DDC-2M-CASINOAHU-2M.2 (Network)AHU (Chilled-Water-Served)AC2nd Mezzanine (Casino)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link181BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 18 m (typical_range:casino_2m_localized)
C0181DDC-2M-CASINOAIR-ION-2M.1 (Network)Air Ionizer (Casino)AC2nd Mezzanine (Casino)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link181BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 18 m (typical_range:casino_2m_localized)
C0182DDC-2M-CASINOAIR-ION-2M.2 (Network)Air Ionizer (Casino)AC2nd Mezzanine (Casino)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link181BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 18 m (typical_range:casino_2m_localized)
C0183DDC-2F-BOHAHU-B.1 (Network)AHU (Chilled-Water-Served)AC2nd Level BOHCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link251BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 25 m (typical_range:boh_2f)
C0184DDC-2F-BOHAHU-B.2 (Network)AHU (Chilled-Water-Served)AC2nd Level BOHCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link251BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 25 m (typical_range:boh_2f)
C0185DDC-2F-BOHAHU-B.3 (Network)AHU (Chilled-Water-Served)AC2nd Level BOHCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link251BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 25 m (typical_range:boh_2f)
C0186DDC-2F-BOHAHU-PF (Network)AHU (Chilled-Water-Served)AC2nd Level Pre-FunctionCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link251BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 25 m (typical_range:boh_2f)
C0187DDC-2F-BOHAHU-EL (Network)AHU (Chilled-Water-Served)AC2nd Level Executive LoungeCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link251BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 25 m (typical_range:boh_2f)
C0188DDC-2F-BOHAHU-FR2 (Network)AHU (Chilled-Water-Served)AC2nd Level Function Room 2Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link251BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 25 m (typical_range:boh_2f)
C0189DDC-2F-BOHAHU-FR3 (Network)AHU (Chilled-Water-Served)AC2nd Level Function Room 3Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link251BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 25 m (typical_range:boh_2f)
C0190DDC-2F-BOHPAHU-B.1 (Network)Precooled Air Handling UnitVENT2nd Level BOHCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link251BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 25 m (typical_range:boh_2f)
C0191DDC-2F-BOHPAHU-B.2 (Network)Precooled Air Handling UnitVENT2nd Level BOHCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link251BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 25 m (typical_range:boh_2f)
C0192DDC-2F-BOHPAHU-B.3 (Network)Precooled Air Handling UnitVENT2nd Level BOHCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link251BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 25 m (typical_range:boh_2f)
C0193DDC-2F-BOHPAHU-PF (Network)Precooled Air Handling UnitVENT2nd Level Pre-FunctionCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link251BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 25 m (typical_range:boh_2f)
C0194DDC-2F-BOHPAHU-FR (Network)Precooled Air Handling UnitVENT2nd Level Function RoomsCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link251BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 25 m (typical_range:boh_2f)
C0195DDC-GF-BOHAHU-1.1 (Network)AHU (Chilled-Water-Served)ACGround Floor BOHCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link251BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 25 m (typical_range:boh_gf)
C0196DDC-GF-BOHAHU-1.2 (Network)AHU (Chilled-Water-Served)ACGround Floor BOHCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link251BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 25 m (typical_range:boh_gf)
C0197DDC-GF-BOHAHU-1.3 (Network)AHU (Chilled-Water-Served)ACGround Floor BOHCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link251BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 25 m (typical_range:boh_gf)
C0198DDC-B1-BOHPAHU-0.1 (Network)Precooled Air Handling UnitVENTBasementCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link281BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 28 m (typical_range:boh_b1)
C0199DDC-LG-PLANTMPM-MAIN (Network)Multifunction Power Meter (Main)ELLower Ground Main SwitchroomCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link121BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 12 m (typical_range:plant_room_lg_boiler_hwl)
C0200DDC-2F-CHILLERMPM-CHILLER (Network)Multifunction Power Meter (Feeder)EL2nd Level Chiller MCCCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link121BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 12 m (typical_range:plant_room_chiller_2f)
C0201DDC-2F-BOHMPM-AHU-2F (Network)Multifunction Power Meter (Feeder)EL2nd Level AHU MCCCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link251BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 25 m (typical_range:boh_2f)
C0202DDC-GF-BOHMPM-AHU-GF (Network)Multifunction Power Meter (Feeder)ELGround Floor AHU MCCCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link251BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 25 m (typical_range:boh_gf)
C0203DDC-LG-PLANTMPM-LIGHT-A (Network)Multifunction Power Meter (Feeder)ELLower Ground Lighting Panel ACat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link121BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 12 m (typical_range:plant_room_lg_boiler_hwl)
C0204DDC-LG-PLANTMPM-LIGHT-B (Network)Multifunction Power Meter (Feeder)ELLower Ground Lighting Panel BCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link121BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 12 m (typical_range:plant_room_lg_boiler_hwl)
C0205DDC-GF-BOHFACP-GW (Network)FACP GatewayFDASGround Floor Fire Command CenterCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link251BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 25 m (typical_range:boh_gf)

Trunks

IDFromToCable TypeLength (m)Notes
T0206BMS Server Room (head-end)All BMS panels at 2nd FloorCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80Network trunk for 2nd Floor — fiber to floor switch + Cat6 distribution to floor's BMS panels
T0207BMS Server Room (head-end)All BMS panels at 3rd FloorCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80Network trunk for 3rd Floor — fiber to floor switch + Cat6 distribution to floor's BMS panels
T0208BMS Server Room (head-end)All BMS panels at BasementCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80Network trunk for Basement — fiber to floor switch + Cat6 distribution to floor's BMS panels
T0209BMS Server Room (head-end)All BMS panels at GroundCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80Network trunk for Ground — fiber to floor switch + Cat6 distribution to floor's BMS panels
T0210BMS Server Room (head-end)All BMS panels at Lower GroundCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80Network trunk for Lower Ground — fiber to floor switch + Cat6 distribution to floor's BMS panels
T0211BMS Server Room (head-end)BMS panel controllers (per topology id mstp_field_backbone)BACnet MS/TP shielded twisted-pair trunk, 1pr × 22 AWG low-cap250MS/TP field backbone connects DDC-2F-CHILLER, DDC-2F-BOH, DDC-2M-CASINO, DDC-RD-PLANT, DDC-LG-PLANT, DDC-GF-BOH, DDC-B1-BOH, DDC-3F. Routed via service-core IDF stack on west end (per ECE auxiliary layouts) + horizontal BOH-corridor tray on each panel's floor. Vertical span B1 → RD ≈ 13 floors × 4.5 m = 58.5 m + 8 panel-side horizontal segments at ~25 m each ≈ 200 m + 25% routing factor ≈ 250 m typical.
T0212BMS Server Room (head-end)BMS panel controllers (per topology id bacnet_ip_backbone)BACnet MS/TP shielded twisted-pair trunk, 1pr × 22 AWG low-cap150BACnet/IP backbone is fibre + Cat6: head-end (Lower Ground IT room per Q-011) → core switch → riser fibre to per-floor IDF edge switches → Cat6 to each DDC field panel. Vertical fibre run LG → RD ≈ 13 floors × 4.5 m = 58.5 m. 8 horizontal fibre segments at ~5 m each. Total ≈ 100-150 m measured; allow 150 m typical.

Panel Power Feeds

IDFromToCable TypeLength (m)Notes
P0213Local panelboard / EE-supplied feederDDC-2F-BOH — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)10240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 10 m (typical_range:panel_power_feed_local)
P0214Local panelboard / EE-supplied feederDDC-2F-CHILLER — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)10240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 10 m (typical_range:panel_power_feed_local)
P0215Local panelboard / EE-supplied feederDDC-2M-CASINO — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)10240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 10 m (typical_range:panel_power_feed_local)
P0216Local panelboard / EE-supplied feederDDC-3F — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)10240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 10 m (typical_range:panel_power_feed_local)
P0217Local panelboard / EE-supplied feederDDC-B1-BOH — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)10240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 10 m (typical_range:panel_power_feed_local)
P0218Local panelboard / EE-supplied feederDDC-GF-BOH — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)10240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 10 m (typical_range:panel_power_feed_local)
P0219Local panelboard / EE-supplied feederDDC-LG-PLANT — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)10240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 10 m (typical_range:panel_power_feed_local)
P0220Local panelboard / EE-supplied feederDDC-RD-PLANT — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)10240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 10 m (typical_range:panel_power_feed_local)