Summary

A2 — Equipment Takeoff Summary
Total instances109
By equipment class
Exhaust Fan (General)32
Exhaust Fan (Toilet)15
AHU (Chilled-Water-Served)12
Precooled Air Handling Unit8
Multifunction Power Meter (Feeder)5
Chiller (Package Water-Cooled)3
Condenser Water Pump3
Cooling Tower3
Secondary CHW Pump3
Air Ionizer (Casino)2
DOAS Unit2
Heat Pump2
Hot Water Header Set2
Calorifier (Hot Water Storage Tank)2
Primary CHW Pump2
Recirculating Pump2
Steam Boiler2
CHW Bypass Header1
CHW Return Main Header1
CHW Supply Main Header1
Cooling Tower (Common)1
Condenser Water Header1
DOAS Unit (Casino — with CO/VOC)1
FACP Gateway1
Multifunction Power Meter (Main)1
Primary CHW Pump (Standby)1
By location
2nd Level Chiller Room15
Roof Deck11
2nd Level BOH6
2nd Mezzanine (Casino)5
3rd Floor5
2nd Floor4
Roof Deck HWL Area4
Lower Ground HWL Room4
GF Main Lobby Toilet4
3rd Floor Toilet4
Ground Floor BOH3
Basement3
2nd Level Pre-Function2
2nd Floor BOH2
Basement Battery Room2
Basement Service2
Basement Garbage Lobby2
2nd Floor General Service2
Basement Pump Room2
Lower Ground Boiler Room2
2nd Floor Toilet2
3rd Floor Amenity Toilet2
Basement Toilet2
2nd Level Executive Lounge1
2nd Level Function Room 21
2nd Level Function Room 31
Roof Deck CT Area1
3rd Floor BOH1
Basement FOST Room1
Basement Main Fire Riser1
Basement Mech / Pump1
2nd Floor OHR1
Basement Wash Service1
Ground Floor Fire Command Center1
2nd Level AHU MCC1
Ground Floor AHU MCC1
2nd Level Chiller MCC1
Lower Ground Lighting Panel A1
Lower Ground Lighting Panel B1
Lower Ground Main Switchroom1
2nd Level Function Rooms1
2nd Floor BOH Toilet1
By panel
DDC-2F-BOH25
DDC-B1-BOH17
DDC-2F-CHILLER16
DDC-RD-PLANT16
DDC-3F12
DDC-GF-BOH9
DDC-LG-PLANT9
DDC-2M-CASINO5

Equipment Takeoff

IDEquipment ClassQuantityLocationSystemPanelPrimary C/OPhysical I/OHLI SubpointsNetwork DropsTotal I/OMake/Model AssumedNetwork TypeTypical SupplierNotes
AHU-1.1AHU (Chilled-Water-Served)1Ground Floor BOHACDDC-GF-BOHEquipment Supplier122115Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-1.2AHU (Chilled-Water-Served)1Ground Floor BOHACDDC-GF-BOHEquipment Supplier122115Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-1.3AHU (Chilled-Water-Served)1Ground Floor BOHACDDC-GF-BOHEquipment Supplier122115Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-2M.1AHU (Chilled-Water-Served)12nd Mezzanine (Casino)ACDDC-2M-CASINOEquipment Supplier122115Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-2M.2AHU (Chilled-Water-Served)12nd Mezzanine (Casino)ACDDC-2M-CASINOEquipment Supplier122115Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-B.1AHU (Chilled-Water-Served)12nd Level BOHACDDC-2F-BOHEquipment Supplier122115Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-B.2AHU (Chilled-Water-Served)12nd Level BOHACDDC-2F-BOHEquipment Supplier122115Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-B.3AHU (Chilled-Water-Served)12nd Level BOHACDDC-2F-BOHEquipment Supplier122115Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-ELAHU (Chilled-Water-Served)12nd Level Executive LoungeACDDC-2F-BOHEquipment Supplier122115Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-FR2AHU (Chilled-Water-Served)12nd Level Function Room 2ACDDC-2F-BOHEquipment Supplier122115Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-FR3AHU (Chilled-Water-Served)12nd Level Function Room 3ACDDC-2F-BOHEquipment Supplier122115Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-PFAHU (Chilled-Water-Served)12nd Level Pre-FunctionACDDC-2F-BOHEquipment Supplier122115Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AIR-ION-2M.1Air Ionizer (Casino)12nd Mezzanine (Casino)ACDDC-2M-CASINOEquipment Supplier3014(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
AIR-ION-2M.2Air Ionizer (Casino)12nd Mezzanine (Casino)ACDDC-2M-CASINOEquipment Supplier3014(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
CH-1Chiller (Package Water-Cooled)12nd Level Chiller RoomACDDC-2F-CHILLEREquipment Supplier918128Tier-1 BACnet IP chiller (Trane/York/Carrier/Daikin), water-cooled centrifugal or screw, sized per design cooling loadBACnet/IPMechanical contractor / Equipment supplierBMS reads via chiller's native BACnet gateway. BMS supplies external T-sensors on entering/leaving CHW & CW pipes.
CH-2Chiller (Package Water-Cooled)12nd Level Chiller RoomACDDC-2F-CHILLEREquipment Supplier918128Tier-1 BACnet IP chiller (Trane/York/Carrier/Daikin), water-cooled centrifugal or screw, sized per design cooling loadBACnet/IPMechanical contractor / Equipment supplierBMS reads via chiller's native BACnet gateway. BMS supplies external T-sensors on entering/leaving CHW & CW pipes.
CH-3Chiller (Package Water-Cooled)12nd Level Chiller RoomACDDC-2F-CHILLEREquipment Supplier918128Tier-1 BACnet IP chiller (Trane/York/Carrier/Daikin), water-cooled centrifugal or screw, sized per design cooling loadBACnet/IPMechanical contractor / Equipment supplierBMS reads via chiller's native BACnet gateway. BMS supplies external T-sensors on entering/leaving CHW & CW pipes.
CHW-DIFFCHW Bypass Header12nd Level Chiller RoomACDDC-2F-CHILLERBMS Contractor3003BMS dP/dT sensors + motorized bypass valve (BMS-supplied)HardwiredBMS contractorBMS controls bypass valve to maintain CHW differential.
CHW-RET-HDRCHW Return Main Header12nd Level Chiller RoomACDDC-2F-CHILLERBMS Contractor2002BMS T+P sensors on CHW return manifoldHardwiredBMS contractorField instrumentation only.
CHW-SUP-HDRCHW Supply Main Header12nd Level Chiller RoomACDDC-2F-CHILLERBMS Contractor2002BMS T+P sensors on CHW supply manifoldHardwiredBMS contractorField instrumentation only.
COWP-1Condenser Water Pump12nd Level Chiller RoomACDDC-2F-CHILLEREquipment Supplier4004End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious)HardwiredMechanical contractorBMS reads aux contacts; commands start via DO.
COWP-2Condenser Water Pump12nd Level Chiller RoomACDDC-2F-CHILLEREquipment Supplier4004End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious)HardwiredMechanical contractorBMS reads aux contacts; commands start via DO.
COWP-3Condenser Water Pump12nd Level Chiller RoomACDDC-2F-CHILLEREquipment Supplier4004End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious)HardwiredMechanical contractorBMS reads aux contacts; commands start via DO.
CT-1Cooling Tower1Roof DeckACDDC-RD-PLANTBMS Contractor9009Induced-draft counterflow open cooling tower (Marley/BAC/EVAPCO), sized per condenser water flowHardwiredMechanical contractor / Equipment supplierBMS supplies basin level sensors and condenser water header T-sensors.
CT-2Cooling Tower1Roof DeckACDDC-RD-PLANTBMS Contractor9009Induced-draft counterflow open cooling tower (Marley/BAC/EVAPCO), sized per condenser water flowHardwiredMechanical contractor / Equipment supplierBMS supplies basin level sensors and condenser water header T-sensors.
CT-3Cooling Tower1Roof DeckACDDC-RD-PLANTBMS Contractor9009Induced-draft counterflow open cooling tower (Marley/BAC/EVAPCO), sized per condenser water flowHardwiredMechanical contractor / Equipment supplierBMS supplies basin level sensors and condenser water header T-sensors.
CT-COMMONCooling Tower (Common)1Roof DeckACDDC-RD-PLANTBMS Contractor4004Common BMS sensors at cooling tower area (OA T/RH, condenser headers)HardwiredBMS contractorField instrumentation only — no equipment per se.
CW-HDRCondenser Water Header1Roof Deck CT AreaACDDC-RD-PLANTBMS Contractor2002BMS T sensors on condenser water headers at roofdeckHardwiredBMS contractorField instrumentation only.
DOAS-2MDOAS Unit (Casino — with CO/VOC)12nd Mezzanine (Casino)VENTDDC-2M-CASINOEquipment Supplier174122(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
DOAS-RD.1DOAS Unit1Roof DeckVENTDDC-RD-PLANTEquipment Supplier204125Dedicated Outdoor Air System with energy recovery wheel, supply + exhaust fans, CHW coilBACnet/IPMechanical contractor / Equipment supplierNative BACnet controller typical. BMS supplies external sensors (OA T/RH/Flow, indoor T/RH, exhaust T) and modulating valve actuator.
DOAS-RD.2DOAS Unit1Roof DeckVENTDDC-RD-PLANTEquipment Supplier204125Dedicated Outdoor Air System with energy recovery wheel, supply + exhaust fans, CHW coilBACnet/IPMechanical contractor / Equipment supplierNative BACnet controller typical. BMS supplies external sensors (OA T/RH/Flow, indoor T/RH, exhaust T) and modulating valve actuator.
EF-1Exhaust Fan (General)1Roof DeckVENTDDC-RD-PLANTEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-2.1Exhaust Fan (General)12nd FloorVENTDDC-2F-BOHEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-2.2Exhaust Fan (General)12nd FloorVENTDDC-2F-BOHEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-2.3Exhaust Fan (General)12nd FloorVENTDDC-2F-BOHEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-2.4Exhaust Fan (General)12nd FloorVENTDDC-2F-BOHEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-2B.1Exhaust Fan (General)12nd Floor BOHVENTDDC-2F-BOHEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-2B.2Exhaust Fan (General)12nd Floor BOHVENTDDC-2F-BOHEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-3.1Exhaust Fan (General)13rd FloorVENTDDC-3FEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-3.2Exhaust Fan (General)13rd FloorVENTDDC-3FEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-3.3Exhaust Fan (General)13rd FloorVENTDDC-3FEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-3.4Exhaust Fan (General)13rd FloorVENTDDC-3FEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-3B-GExhaust Fan (General)13rd Floor BOHVENTDDC-3FEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-3C.1-GExhaust Fan (General)13rd FloorVENTDDC-3FEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-B.1Exhaust Fan (General)1BasementVENTDDC-B1-BOHEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-B.2Exhaust Fan (General)1BasementVENTDDC-B1-BOHEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-BR.1Exhaust Fan (General)1Basement Battery RoomVENTDDC-B1-BOHEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-BR.2Exhaust Fan (General)1Basement Battery RoomVENTDDC-B1-BOHEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-BS.1Exhaust Fan (General)1Basement ServiceVENTDDC-B1-BOHEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-BS.2Exhaust Fan (General)1Basement ServiceVENTDDC-B1-BOHEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-FOST.1Exhaust Fan (General)1Basement FOST RoomVENTDDC-B1-BOHEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-GL.1Exhaust Fan (General)1Basement Garbage LobbyVENTDDC-B1-BOHEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-GL.2Exhaust Fan (General)1Basement Garbage LobbyVENTDDC-B1-BOHEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-GS.1Exhaust Fan (General)12nd Floor General ServiceVENTDDC-2F-BOHEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-GS.2Exhaust Fan (General)12nd Floor General ServiceVENTDDC-2F-BOHEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-MFR.1Exhaust Fan (General)1Basement Main Fire RiserVENTDDC-B1-BOHEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-MP.1Exhaust Fan (General)1Basement Mech / PumpVENTDDC-B1-BOHEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-OHRv2Exhaust Fan (General)12nd Floor OHRVENTDDC-2F-BOHEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-PR.1Exhaust Fan (General)1Basement Pump RoomVENTDDC-B1-BOHEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-PR.3Exhaust Fan (General)1Basement Pump RoomVENTDDC-B1-BOHEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-RD.1Exhaust Fan (General)1Roof DeckVENTDDC-RD-PLANTEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-RO.2Exhaust Fan (General)1Roof DeckVENTDDC-RD-PLANTEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-WS.1Exhaust Fan (General)1Basement Wash ServiceVENTDDC-B1-BOHEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
FACP-GWFACP Gateway1Ground Floor Fire Command CenterFDASDDC-GF-BOHEE Contractor0314(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
HP-HZHeat Pump1Roof Deck HWL AreaHWLDDC-RD-PLANTEquipment Supplier3003Air-source or water-source heat pump for hot water heatingHardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractor / Equipment supplierBMS reads pump status/HOA/trip via aux contacts.
HP-LZHeat Pump1Lower Ground HWL RoomHWLDDC-LG-PLANTEquipment Supplier3003Air-source or water-source heat pump for hot water heatingHardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractor / Equipment supplierBMS reads pump status/HOA/trip via aux contacts.
HWH-HZHot Water Header Set1Roof Deck HWL AreaHWLDDC-RD-PLANTBMS Contractor3003Hot water supply/return manifolds with BMS T sensors and make-up cold water T sensorHardwiredBMS contractorField instrumentation on existing piping.
HWH-LZHot Water Header Set1Lower Ground HWL RoomHWLDDC-LG-PLANTBMS Contractor3003Hot water supply/return manifolds with BMS T sensors and make-up cold water T sensorHardwiredBMS contractorField instrumentation on existing piping.
HWT-HZCalorifier (Hot Water Storage Tank)1Roof Deck HWL AreaHWLDDC-RD-PLANTBMS Contractor1001Pressurised hot-water storage tank with internal coil, sized per design hot water demandHardwiredPlumbing contractorBMS supplies tank temperature sensor (immersion or strapped probe).
HWT-LZCalorifier (Hot Water Storage Tank)1Lower Ground HWL RoomHWLDDC-LG-PLANTBMS Contractor1001Pressurised hot-water storage tank with internal coil, sized per design hot water demandHardwiredPlumbing contractorBMS supplies tank temperature sensor (immersion or strapped probe).
MPM-AHU-2FMultifunction Power Meter (Feeder)12nd Level AHU MCCELDDC-2F-BOHBMS Contractor0112Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
MPM-AHU-GFMultifunction Power Meter (Feeder)1Ground Floor AHU MCCELDDC-GF-BOHBMS Contractor0112Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
MPM-CHILLERMultifunction Power Meter (Feeder)12nd Level Chiller MCCELDDC-2F-CHILLERBMS Contractor0112Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
MPM-LIGHT-AMultifunction Power Meter (Feeder)1Lower Ground Lighting Panel AELDDC-LG-PLANTBMS Contractor0112Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
MPM-LIGHT-BMultifunction Power Meter (Feeder)1Lower Ground Lighting Panel BELDDC-LG-PLANTBMS Contractor0112Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
MPM-MAINMultifunction Power Meter (Main)1Lower Ground Main SwitchroomELDDC-LG-PLANTBMS Contractor0112Multifunction power meter with Modbus output (Schneider PM-series, ABB M2M, Siemens SENTRON), main switchgear classModbus RTU/TCPBMS contractorMounted in main switchgear or on dedicated BMS-side panel.
PAHU-0.1Precooled Air Handling Unit1BasementVENTDDC-B1-BOHEquipment Supplier92112Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust pathHardwired (VFD via BACnet HLI)Mechanical contractor / Equipment supplierPrecool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors.
PAHU-B.1Precooled Air Handling Unit12nd Level BOHVENTDDC-2F-BOHEquipment Supplier92112Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust pathHardwired (VFD via BACnet HLI)Mechanical contractor / Equipment supplierPrecool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors.
PAHU-B.2Precooled Air Handling Unit12nd Level BOHVENTDDC-2F-BOHEquipment Supplier92112Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust pathHardwired (VFD via BACnet HLI)Mechanical contractor / Equipment supplierPrecool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors.
PAHU-B.3Precooled Air Handling Unit12nd Level BOHVENTDDC-2F-BOHEquipment Supplier92112Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust pathHardwired (VFD via BACnet HLI)Mechanical contractor / Equipment supplierPrecool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors.
PAHU-FRPrecooled Air Handling Unit12nd Level Function RoomsVENTDDC-2F-BOHEquipment Supplier92112Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust pathHardwired (VFD via BACnet HLI)Mechanical contractor / Equipment supplierPrecool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors.
PAHU-PFPrecooled Air Handling Unit12nd Level Pre-FunctionVENTDDC-2F-BOHEquipment Supplier92112Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust pathHardwired (VFD via BACnet HLI)Mechanical contractor / Equipment supplierPrecool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors.
PAHU-r.1Precooled Air Handling Unit1Roof DeckVENTDDC-RD-PLANTEquipment Supplier92112Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust pathHardwired (VFD via BACnet HLI)Mechanical contractor / Equipment supplierPrecool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors.
PAHU-r.2Precooled Air Handling Unit1Roof DeckVENTDDC-RD-PLANTEquipment Supplier92112Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust pathHardwired (VFD via BACnet HLI)Mechanical contractor / Equipment supplierPrecool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors.
PCHWP-1Primary CHW Pump12nd Level Chiller RoomACDDC-2F-CHILLEREquipment Supplier5218End-suction or split-case centrifugal with VFD, sized per design CHW flowHardwired (BMS reads VFD via BACnet HLI)Mechanical contractorVFD typically Equipment Supplier provided with BACnet card.
PCHWP-2Primary CHW Pump12nd Level Chiller RoomACDDC-2F-CHILLEREquipment Supplier5218End-suction or split-case centrifugal with VFD, sized per design CHW flowHardwired (BMS reads VFD via BACnet HLI)Mechanical contractorVFD typically Equipment Supplier provided with BACnet card.
PCHWP-3Primary CHW Pump (Standby)12nd Level Chiller RoomACDDC-2F-CHILLEREquipment Supplier4004Same as Primary CHW Pump (1 standby for N+1 redundancy)Hardwired (BMS reads VFD via BACnet HLI)Mechanical contractorStandby unit per A-CHW-001.
RP-HZRecirculating Pump1Roof Deck HWL AreaHWLDDC-RD-PLANTEquipment Supplier3003Hot water recirculating pump, fixed-speed (typical for hotwater systems)Hardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractorBMS reads aux contacts only.
RP-LZRecirculating Pump1Lower Ground HWL RoomHWLDDC-LG-PLANTEquipment Supplier3003Hot water recirculating pump, fixed-speed (typical for hotwater systems)Hardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractorBMS reads aux contacts only.
SB-1Steam Boiler1Lower Ground Boiler RoomVENTDDC-LG-PLANTEquipment Supplier88117Fire-tube steam boiler with multi-stage burner, fuel-oil fired (typical for hotel laundry)HardwiredMechanical contractor / Equipment supplierBMS supplies steam pressure, feedwater T, fluegas T+O2 sensors. Boiler equipment provides aux contacts for status/HOA/trip points.
SB-2Steam Boiler1Lower Ground Boiler RoomVENTDDC-LG-PLANTEquipment Supplier88117Fire-tube steam boiler with multi-stage burner, fuel-oil fired (typical for hotel laundry)HardwiredMechanical contractor / Equipment supplierBMS supplies steam pressure, feedwater T, fluegas T+O2 sensors. Boiler equipment provides aux contacts for status/HOA/trip points.
SCHWP-1Secondary CHW Pump12nd Level Chiller RoomACDDC-2F-CHILLEREquipment Supplier4217(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
SCHWP-2Secondary CHW Pump12nd Level Chiller RoomACDDC-2F-CHILLEREquipment Supplier4217(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
SCHWP-3Secondary CHW Pump12nd Level Chiller RoomACDDC-2F-CHILLEREquipment Supplier4217(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
TEF-1.1Exhaust Fan (Toilet)1GF Main Lobby ToiletVENTDDC-GF-BOHEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-1.2Exhaust Fan (Toilet)1GF Main Lobby ToiletVENTDDC-GF-BOHEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-1.3Exhaust Fan (Toilet)1GF Main Lobby ToiletVENTDDC-GF-BOHEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-1.4Exhaust Fan (Toilet)1GF Main Lobby ToiletVENTDDC-GF-BOHEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-2.1Exhaust Fan (Toilet)12nd Floor ToiletVENTDDC-2F-BOHEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-2.2Exhaust Fan (Toilet)12nd Floor ToiletVENTDDC-2F-BOHEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-2B.3Exhaust Fan (Toilet)12nd Floor BOH ToiletVENTDDC-2F-BOHEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-30.20Exhaust Fan (Toilet)13rd Floor ToiletVENTDDC-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3A.1Exhaust Fan (Toilet)13rd Floor Amenity ToiletVENTDDC-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3A.2Exhaust Fan (Toilet)13rd Floor Amenity ToiletVENTDDC-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3BExhaust Fan (Toilet)13rd Floor ToiletVENTDDC-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3C.1Exhaust Fan (Toilet)13rd Floor ToiletVENTDDC-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3C.2Exhaust Fan (Toilet)13rd Floor ToiletVENTDDC-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-B.1Exhaust Fan (Toilet)1Basement ToiletVENTDDC-B1-BOHEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-B.2Exhaust Fan (Toilet)1Basement ToiletVENTDDC-B1-BOHEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.