Summary

A1 — Consolidated I/O List Summary
ProjectKingsford Hotel Bacolod — BMS
Total I/O rows744
By type
DI286
AI200
HLI141
AO58
Network42
DO17
By C/O
Equipment Supplier490
BMS Contractor183
ME Contractor67
EE Contractor4
By system
AC365
VENT343
HWL20
EL12
FDAS4
By panel
DDC-2F-BOH203
DDC-2F-CHILLER146
DDC-RD-PLANT126
DDC-GF-BOH63
DDC-2M-CASINO60
DDC-B1-BOH60
DDC-LG-PLANT50
DDC-3F36

All IO Points

IDSystemEquipment ClassEquipment InstanceLocationPoint DescriptionTypeField DeviceC/ODoO RefPanelSourceNotes
P-0001ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomEntering Chilled Water TemperatureAITemperature SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0002ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomLeaving Chilled Water TemperatureAITemperature SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0003ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomIsolation Motorized Valve Status CHW Return & SupplyDIElectric Valve ActuatorME ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0004ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomEntering Condenser Water TemperatureAITemperature SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0005ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomLeaving Condenser Water TemperatureAITemperature SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0006ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomIsolation Motorized Valve Status COW Return & SupplyDIElectric Valve ActuatorME ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0007ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomChilled Water Return Flow MeteringAIFlow SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0008ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomChilled Water Supply Flow MeteringAIFlow SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0009ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomCondenser Water Supply Flow MeteringAIFlow SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0010ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomNetwork drop (BACnet/IP — chiller plant manager gateway)NetworkChiller PLC + BACnet gatewayEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0011ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomChiller Compressor Pump On/Off StatusHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0012ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomChiller Compressor Hand/Off/Auto StatusHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0013ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomChiller Compressor Trip Alarm StatusHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0014ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomMotor Load CurrentHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0015ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomMotor Consumption — KW / BTU MeterHLIChiller PLC + BTU meterEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0016ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomWinding TemperatureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0017ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomEvaporator Approach Delta TemperatureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0018ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomEvaporator Approach Delta PressureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0019ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomEvaporator Refrigerant PressureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0020ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomEvaporator Refrigerant TemperatureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0021ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomCondenser Refrigerant PressureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0022ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomCondenser Refrigerant TemperatureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0023ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomCondenser Approach Delta TemperatureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0024ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomCondenser Approach Delta PressureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0025ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomOil Sump PressureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0026ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomOil Sump TemperatureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0027ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomOil Pump Status (ON/OFF)HLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0028ACChiller (Package Water-Cooled)CH-12nd Level Chiller RoomOil Pump Trip StatusHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0029ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomEntering Chilled Water TemperatureAITemperature SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0030ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomLeaving Chilled Water TemperatureAITemperature SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0031ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomIsolation Motorized Valve Status CHW Return & SupplyDIElectric Valve ActuatorME ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0032ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomEntering Condenser Water TemperatureAITemperature SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0033ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomLeaving Condenser Water TemperatureAITemperature SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0034ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomIsolation Motorized Valve Status COW Return & SupplyDIElectric Valve ActuatorME ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0035ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomChilled Water Return Flow MeteringAIFlow SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0036ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomChilled Water Supply Flow MeteringAIFlow SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0037ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomCondenser Water Supply Flow MeteringAIFlow SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0038ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomNetwork drop (BACnet/IP — chiller plant manager gateway)NetworkChiller PLC + BACnet gatewayEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0039ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomChiller Compressor Pump On/Off StatusHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0040ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomChiller Compressor Hand/Off/Auto StatusHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0041ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomChiller Compressor Trip Alarm StatusHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0042ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomMotor Load CurrentHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0043ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomMotor Consumption — KW / BTU MeterHLIChiller PLC + BTU meterEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0044ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomWinding TemperatureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0045ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomEvaporator Approach Delta TemperatureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0046ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomEvaporator Approach Delta PressureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0047ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomEvaporator Refrigerant PressureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0048ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomEvaporator Refrigerant TemperatureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0049ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomCondenser Refrigerant PressureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0050ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomCondenser Refrigerant TemperatureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0051ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomCondenser Approach Delta TemperatureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0052ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomCondenser Approach Delta PressureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0053ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomOil Sump PressureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0054ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomOil Sump TemperatureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0055ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomOil Pump Status (ON/OFF)HLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0056ACChiller (Package Water-Cooled)CH-22nd Level Chiller RoomOil Pump Trip StatusHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0057ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomEntering Chilled Water TemperatureAITemperature SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0058ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomLeaving Chilled Water TemperatureAITemperature SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0059ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomIsolation Motorized Valve Status CHW Return & SupplyDIElectric Valve ActuatorME ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0060ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomEntering Condenser Water TemperatureAITemperature SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0061ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomLeaving Condenser Water TemperatureAITemperature SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0062ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomIsolation Motorized Valve Status COW Return & SupplyDIElectric Valve ActuatorME ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0063ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomChilled Water Return Flow MeteringAIFlow SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0064ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomChilled Water Supply Flow MeteringAIFlow SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0065ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomCondenser Water Supply Flow MeteringAIFlow SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0066ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomNetwork drop (BACnet/IP — chiller plant manager gateway)NetworkChiller PLC + BACnet gatewayEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0067ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomChiller Compressor Pump On/Off StatusHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0068ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomChiller Compressor Hand/Off/Auto StatusHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0069ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomChiller Compressor Trip Alarm StatusHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0070ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomMotor Load CurrentHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0071ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomMotor Consumption — KW / BTU MeterHLIChiller PLC + BTU meterEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0072ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomWinding TemperatureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0073ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomEvaporator Approach Delta TemperatureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0074ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomEvaporator Approach Delta PressureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0075ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomEvaporator Refrigerant PressureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0076ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomEvaporator Refrigerant TemperatureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0077ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomCondenser Refrigerant PressureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0078ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomCondenser Refrigerant TemperatureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0079ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomCondenser Approach Delta TemperatureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0080ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomCondenser Approach Delta PressureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0081ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomOil Sump PressureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0082ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomOil Sump TemperatureHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0083ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomOil Pump Status (ON/OFF)HLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0084ACChiller (Package Water-Cooled)CH-32nd Level Chiller RoomOil Pump Trip StatusHLIChiller PLCEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0085ACPrimary CHW PumpPCHWP-12nd Level Chiller RoomPump On/Off StatusDIAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0086ACPrimary CHW PumpPCHWP-12nd Level Chiller RoomPump Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0087ACPrimary CHW PumpPCHWP-12nd Level Chiller RoomPump Trip AlarmDIAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0088ACPrimary CHW PumpPCHWP-12nd Level Chiller RoomPump Start/Stop CommandDOAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0089ACPrimary CHW PumpPCHWP-12nd Level Chiller RoomChilled Water Supply PressureAIPressure SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0090ACPrimary CHW PumpPCHWP-12nd Level Chiller RoomVFD Speed (HLI)HLIVFDEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0091ACPrimary CHW PumpPCHWP-12nd Level Chiller RoomVFD Speed Command (HLI)HLIVFDEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0092ACPrimary CHW PumpPCHWP-12nd Level Chiller RoomNetwork drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0093ACPrimary CHW PumpPCHWP-22nd Level Chiller RoomPump On/Off StatusDIAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0094ACPrimary CHW PumpPCHWP-22nd Level Chiller RoomPump Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0095ACPrimary CHW PumpPCHWP-22nd Level Chiller RoomPump Trip AlarmDIAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0096ACPrimary CHW PumpPCHWP-22nd Level Chiller RoomPump Start/Stop CommandDOAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0097ACPrimary CHW PumpPCHWP-22nd Level Chiller RoomChilled Water Supply PressureAIPressure SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0098ACPrimary CHW PumpPCHWP-22nd Level Chiller RoomVFD Speed (HLI)HLIVFDEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0099ACPrimary CHW PumpPCHWP-22nd Level Chiller RoomVFD Speed Command (HLI)HLIVFDEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0100ACPrimary CHW PumpPCHWP-22nd Level Chiller RoomNetwork drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0101ACPrimary CHW Pump (Standby)PCHWP-32nd Level Chiller RoomPump On/Off StatusDIAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0102ACPrimary CHW Pump (Standby)PCHWP-32nd Level Chiller RoomPump Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0103ACPrimary CHW Pump (Standby)PCHWP-32nd Level Chiller RoomPump Trip AlarmDIAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0104ACPrimary CHW Pump (Standby)PCHWP-32nd Level Chiller RoomPump Start/Stop CommandDOAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0105ACSecondary CHW PumpSCHWP-12nd Level Chiller RoomPump On/Off StatusDIAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0106ACSecondary CHW PumpSCHWP-12nd Level Chiller RoomPump Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0107ACSecondary CHW PumpSCHWP-12nd Level Chiller RoomPump Trip AlarmDIAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0108ACSecondary CHW PumpSCHWP-12nd Level Chiller RoomPump Start/Stop CommandDOAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0109ACSecondary CHW PumpSCHWP-12nd Level Chiller RoomVFD Speed (HLI)HLIVFDEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0110ACSecondary CHW PumpSCHWP-12nd Level Chiller RoomVFD Speed Command (HLI)HLIVFDEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0111ACSecondary CHW PumpSCHWP-12nd Level Chiller RoomNetwork drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0112ACSecondary CHW PumpSCHWP-22nd Level Chiller RoomPump On/Off StatusDIAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0113ACSecondary CHW PumpSCHWP-22nd Level Chiller RoomPump Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0114ACSecondary CHW PumpSCHWP-22nd Level Chiller RoomPump Trip AlarmDIAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0115ACSecondary CHW PumpSCHWP-22nd Level Chiller RoomPump Start/Stop CommandDOAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0116ACSecondary CHW PumpSCHWP-22nd Level Chiller RoomVFD Speed (HLI)HLIVFDEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0117ACSecondary CHW PumpSCHWP-22nd Level Chiller RoomVFD Speed Command (HLI)HLIVFDEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0118ACSecondary CHW PumpSCHWP-22nd Level Chiller RoomNetwork drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0119ACSecondary CHW PumpSCHWP-32nd Level Chiller RoomPump On/Off StatusDIAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0120ACSecondary CHW PumpSCHWP-32nd Level Chiller RoomPump Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0121ACSecondary CHW PumpSCHWP-32nd Level Chiller RoomPump Trip AlarmDIAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0122ACSecondary CHW PumpSCHWP-32nd Level Chiller RoomPump Start/Stop CommandDOAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0123ACSecondary CHW PumpSCHWP-32nd Level Chiller RoomVFD Speed (HLI)HLIVFDEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0124ACSecondary CHW PumpSCHWP-32nd Level Chiller RoomVFD Speed Command (HLI)HLIVFDEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0125ACSecondary CHW PumpSCHWP-32nd Level Chiller RoomNetwork drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0126ACCondenser Water PumpCOWP-12nd Level Chiller RoomPump On/Off StatusDIAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0127ACCondenser Water PumpCOWP-12nd Level Chiller RoomPump Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0128ACCondenser Water PumpCOWP-12nd Level Chiller RoomPump Trip AlarmDIAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0129ACCondenser Water PumpCOWP-12nd Level Chiller RoomPump Start/Stop CommandDOAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0130ACCondenser Water PumpCOWP-22nd Level Chiller RoomPump On/Off StatusDIAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0131ACCondenser Water PumpCOWP-22nd Level Chiller RoomPump Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0132ACCondenser Water PumpCOWP-22nd Level Chiller RoomPump Trip AlarmDIAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0133ACCondenser Water PumpCOWP-22nd Level Chiller RoomPump Start/Stop CommandDOAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0134ACCondenser Water PumpCOWP-32nd Level Chiller RoomPump On/Off StatusDIAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0135ACCondenser Water PumpCOWP-32nd Level Chiller RoomPump Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0136ACCondenser Water PumpCOWP-32nd Level Chiller RoomPump Trip AlarmDIAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0137ACCondenser Water PumpCOWP-32nd Level Chiller RoomPump Start/Stop CommandDOAuxiliary ContactEquipment SupplierDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0138ACCHW Supply Main HeaderCHW-SUP-HDR2nd Level Chiller RoomCHW Supply Main Header PressureAIPressure SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0139ACCHW Supply Main HeaderCHW-SUP-HDR2nd Level Chiller RoomCHW Supply Main Header TemperatureAITemperature SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0140ACCHW Return Main HeaderCHW-RET-HDR2nd Level Chiller RoomCHW Return Main Header PressureAIPressure SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0141ACCHW Return Main HeaderCHW-RET-HDR2nd Level Chiller RoomCHW Return Main Header TemperatureAITemperature SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0142ACCHW Bypass HeaderCHW-DIFF2nd Level Chiller RoomCHW Differential PressureAIDiff. Pressure SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0143ACCHW Bypass HeaderCHW-DIFF2nd Level Chiller RoomCHW Differential TemperatureAIDiff. Pressure SensorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0144ACCHW Bypass HeaderCHW-DIFF2nd Level Chiller RoomIsolation Motorized Valve Status CHW BypassDIElectric Valve ActuatorBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0145ACCondenser Water HeaderCW-HDRRoof Deck CT AreaCondenser Water Supply Header TemperatureAITemperature SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0146ACCondenser Water HeaderCW-HDRRoof Deck CT AreaCondenser Water Return Header TemperatureAITemperature SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0147ACCooling TowerCT-1Roof DeckFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0148ACCooling TowerCT-1Roof DeckFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0149ACCooling TowerCT-1Roof DeckFan Start/Stop CommandDOAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0150ACCooling TowerCT-1Roof DeckLevel Alarm Low (CT Basin)DILevel Sensor / ElectrodeBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0151ACCooling TowerCT-1Roof DeckLevel Alarm High (CT Basin)DILevel Sensor / ElectrodeBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0152ACCooling TowerCT-1Roof DeckIsolation Motorized Valve Status COW Return & SupplyDIElectric Valve ActuatorME ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0153ACCooling TowerCT-1Roof DeckBlowdown Corrosion/Scale MonitoringAIpH Sensor / Conductivity SensorME ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0154ACCooling TowerCT-1Roof DeckMotorized Blowdown Valve StatusDIElectric Valve ActuatorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0155ACCooling TowerCT-1Roof DeckMotorized Blowdown Valve ControlDOElectric Valve ActuatorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0156ACCooling TowerCT-2Roof DeckFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0157ACCooling TowerCT-2Roof DeckFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0158ACCooling TowerCT-2Roof DeckFan Start/Stop CommandDOAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0159ACCooling TowerCT-2Roof DeckLevel Alarm Low (CT Basin)DILevel Sensor / ElectrodeBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0160ACCooling TowerCT-2Roof DeckLevel Alarm High (CT Basin)DILevel Sensor / ElectrodeBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0161ACCooling TowerCT-2Roof DeckIsolation Motorized Valve Status COW Return & SupplyDIElectric Valve ActuatorME ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0162ACCooling TowerCT-2Roof DeckBlowdown Corrosion/Scale MonitoringAIpH Sensor / Conductivity SensorME ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0163ACCooling TowerCT-2Roof DeckMotorized Blowdown Valve StatusDIElectric Valve ActuatorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0164ACCooling TowerCT-2Roof DeckMotorized Blowdown Valve ControlDOElectric Valve ActuatorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0165ACCooling TowerCT-3Roof DeckFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0166ACCooling TowerCT-3Roof DeckFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0167ACCooling TowerCT-3Roof DeckFan Start/Stop CommandDOAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0168ACCooling TowerCT-3Roof DeckLevel Alarm Low (CT Basin)DILevel Sensor / ElectrodeBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0169ACCooling TowerCT-3Roof DeckLevel Alarm High (CT Basin)DILevel Sensor / ElectrodeBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0170ACCooling TowerCT-3Roof DeckIsolation Motorized Valve Status COW Return & SupplyDIElectric Valve ActuatorME ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0171ACCooling TowerCT-3Roof DeckBlowdown Corrosion/Scale MonitoringAIpH Sensor / Conductivity SensorME ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0172ACCooling TowerCT-3Roof DeckMotorized Blowdown Valve StatusDIElectric Valve ActuatorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0173ACCooling TowerCT-3Roof DeckMotorized Blowdown Valve ControlDOElectric Valve ActuatorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0174ACCooling Tower (Common)CT-COMMONRoof DeckOutside Air Temperature MonitoringAITemperature SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0175ACCooling Tower (Common)CT-COMMONRoof DeckOutside Air Humidity MonitoringAIHumidity SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0176ACCooling Tower (Common)CT-COMMONRoof DeckWater Temp Monitoring (Condenser Return Header)AITemperature SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0177ACCooling Tower (Common)CT-COMMONRoof DeckWater Temp Monitoring (Condenser Supply Header)AITemperature SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0178VENTSteam BoilerSB-1Lower Ground Boiler RoomSupply Steam PressureAIPressure SensorBMS ContractorDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0179VENTSteam BoilerSB-1Lower Ground Boiler RoomLow Water LevelDILevel SensorEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0180VENTSteam BoilerSB-1Lower Ground Boiler RoomHigh Water LevelDILevel SensorEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0181VENTSteam BoilerSB-1Lower Ground Boiler RoomBurner PowerHLIBurner ControllerEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0182VENTSteam BoilerSB-1Lower Ground Boiler RoomSmall Fire Control SignalHLIBurner ControllerEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0183VENTSteam BoilerSB-1Lower Ground Boiler RoomBig Fire Control SignalHLIBurner ControllerEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0184VENTSteam BoilerSB-1Lower Ground Boiler RoomWaterfeed Pump StatusHLIBurner ControllerEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0185VENTSteam BoilerSB-1Lower Ground Boiler RoomBurner StatusHLIBurner ControllerEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0186VENTSteam BoilerSB-1Lower Ground Boiler RoomBurner Fire Running StatusHLIBurner ControllerEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0187VENTSteam BoilerSB-1Lower Ground Boiler RoomBlower Motor StatusHLIBurner ControllerEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0188VENTSteam BoilerSB-1Lower Ground Boiler RoomFuel Oil Pump StatusHLIBurner ControllerEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0189VENTSteam BoilerSB-1Lower Ground Boiler RoomMotorized Valve Status Blowdown WaterDIElectric Valve ActuatorBMS ContractorDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0190VENTSteam BoilerSB-1Lower Ground Boiler RoomMotorized Valve Control Blowdown WaterDOElectric Valve ActuatorBMS ContractorDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0191VENTSteam BoilerSB-1Lower Ground Boiler RoomFeedwater Supply TemperatureAITemperature SensorBMS ContractorDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0192VENTSteam BoilerSB-1Lower Ground Boiler RoomFluegas TemperatureAITemperature SensorBMS ContractorDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0193VENTSteam BoilerSB-1Lower Ground Boiler RoomFluegas Oxygen LevelAIOxygen SensorBMS ContractorDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0194VENTSteam BoilerSB-1Lower Ground Boiler RoomNetwork drop (BACnet MS/TP — Burner Controller)NetworkBurner Controller gatewayEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0195VENTSteam BoilerSB-2Lower Ground Boiler RoomSupply Steam PressureAIPressure SensorBMS ContractorDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0196VENTSteam BoilerSB-2Lower Ground Boiler RoomLow Water LevelDILevel SensorEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0197VENTSteam BoilerSB-2Lower Ground Boiler RoomHigh Water LevelDILevel SensorEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0198VENTSteam BoilerSB-2Lower Ground Boiler RoomBurner PowerHLIBurner ControllerEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0199VENTSteam BoilerSB-2Lower Ground Boiler RoomSmall Fire Control SignalHLIBurner ControllerEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0200VENTSteam BoilerSB-2Lower Ground Boiler RoomBig Fire Control SignalHLIBurner ControllerEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0201VENTSteam BoilerSB-2Lower Ground Boiler RoomWaterfeed Pump StatusHLIBurner ControllerEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0202VENTSteam BoilerSB-2Lower Ground Boiler RoomBurner StatusHLIBurner ControllerEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0203VENTSteam BoilerSB-2Lower Ground Boiler RoomBurner Fire Running StatusHLIBurner ControllerEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0204VENTSteam BoilerSB-2Lower Ground Boiler RoomBlower Motor StatusHLIBurner ControllerEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0205VENTSteam BoilerSB-2Lower Ground Boiler RoomFuel Oil Pump StatusHLIBurner ControllerEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0206VENTSteam BoilerSB-2Lower Ground Boiler RoomMotorized Valve Status Blowdown WaterDIElectric Valve ActuatorBMS ContractorDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0207VENTSteam BoilerSB-2Lower Ground Boiler RoomMotorized Valve Control Blowdown WaterDOElectric Valve ActuatorBMS ContractorDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0208VENTSteam BoilerSB-2Lower Ground Boiler RoomFeedwater Supply TemperatureAITemperature SensorBMS ContractorDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0209VENTSteam BoilerSB-2Lower Ground Boiler RoomFluegas TemperatureAITemperature SensorBMS ContractorDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0210VENTSteam BoilerSB-2Lower Ground Boiler RoomFluegas Oxygen LevelAIOxygen SensorBMS ContractorDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0211VENTSteam BoilerSB-2Lower Ground Boiler RoomNetwork drop (BACnet MS/TP — Burner Controller)NetworkBurner Controller gatewayEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0212HWLCalorifier (Hot Water Storage Tank)HWT-LZLower Ground HWL RoomTank TemperatureAITemperature SensorBMS ContractorDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0213HWLCalorifier (Hot Water Storage Tank)HWT-HZRoof Deck HWL AreaTank TemperatureAITemperature SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0214HWLHot Water Header SetHWH-LZLower Ground HWL RoomHot Water Supply Header TemperatureAITemperature SensorBMS ContractorDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0215HWLHot Water Header SetHWH-LZLower Ground HWL RoomMake-Up Cold Water Header TemperatureAITemperature SensorBMS ContractorDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0216HWLHot Water Header SetHWH-LZLower Ground HWL RoomHot Water Return Header TemperatureAITemperature SensorBMS ContractorDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0217HWLHot Water Header SetHWH-HZRoof Deck HWL AreaHot Water Supply Header TemperatureAITemperature SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0218HWLHot Water Header SetHWH-HZRoof Deck HWL AreaMake-Up Cold Water Header TemperatureAITemperature SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0219HWLHot Water Header SetHWH-HZRoof Deck HWL AreaHot Water Return Header TemperatureAITemperature SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0220HWLHeat PumpHP-LZLower Ground HWL RoomPump Motor StatusDIAuxiliary ContactEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0221HWLHeat PumpHP-LZLower Ground HWL RoomPump Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0222HWLHeat PumpHP-LZLower Ground HWL RoomPump Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0223HWLHeat PumpHP-HZRoof Deck HWL AreaPump Motor StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0224HWLHeat PumpHP-HZRoof Deck HWL AreaPump Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0225HWLHeat PumpHP-HZRoof Deck HWL AreaPump Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0226HWLRecirculating PumpRP-LZLower Ground HWL RoomPump Motor StatusDIAuxiliary ContactEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0227HWLRecirculating PumpRP-LZLower Ground HWL RoomPump Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0228HWLRecirculating PumpRP-LZLower Ground HWL RoomPump Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0229HWLRecirculating PumpRP-HZRoof Deck HWL AreaPump Motor StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0230HWLRecirculating PumpRP-HZRoof Deck HWL AreaPump Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0231HWLRecirculating PumpRP-HZRoof Deck HWL AreaPump Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0232VENTDOAS UnitDOAS-RD.1Roof DeckTemperature Monitoring (Outside — Supply Air)AITemperature SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0233VENTDOAS UnitDOAS-RD.1Roof DeckFlow Monitoring (Outside — Supply Air)AIFlow SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0234VENTDOAS UnitDOAS-RD.1Roof DeckHumidity Monitoring (Outdoor — Supply Air)AIHumidity SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0235VENTDOAS UnitDOAS-RD.1Roof DeckOutdoor Supply Air Motorized Damper StatusAIDamper ControllerME ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0236VENTDOAS UnitDOAS-RD.1Roof DeckOutdoor Supply Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerME ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0237VENTDOAS UnitDOAS-RD.1Roof DeckRecovery Wheel Motor StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0238VENTDOAS UnitDOAS-RD.1Roof DeckRecovery Wheel Motor Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0239VENTDOAS UnitDOAS-RD.1Roof DeckSupply Fan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0240VENTDOAS UnitDOAS-RD.1Roof DeckSupply Fan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0241VENTDOAS UnitDOAS-RD.1Roof DeckSupply Fan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0242VENTDOAS UnitDOAS-RD.1Roof DeckSupply Fan Variable Speed Monitoring (HLI)HLIVFDEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0243VENTDOAS UnitDOAS-RD.1Roof DeckSupply Fan Control (On/Off/Modulating) (HLI)HLIVFDEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0244VENTDOAS UnitDOAS-RD.1Roof DeckTemperature Monitoring (Indoor — Mixed Air)AITemperature SensorEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0245VENTDOAS UnitDOAS-RD.1Roof DeckHumidity Monitoring (Indoor — Mixed Air)AIHumidity SensorEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0246VENTDOAS UnitDOAS-RD.1Roof DeckCHWS / Cooling Coil Valve StatusAIElectric Valve ActuatorME ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0247VENTDOAS UnitDOAS-RD.1Roof DeckCHWS Valve Control (On/Off/Modulating)AOElectric Valve ActuatorME ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0248VENTDOAS UnitDOAS-RD.1Roof DeckTemperature Monitoring (Indoor — Supply Air)AITemperature SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0249VENTDOAS UnitDOAS-RD.1Roof DeckHumidity Monitoring (Indoor — Exhaust Air)AIHumidity SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0250VENTDOAS UnitDOAS-RD.1Roof DeckTemperature Monitoring (Indoor — Exhaust Air)AITemperature SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0251VENTDOAS UnitDOAS-RD.1Roof DeckExhaust Fan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0252VENTDOAS UnitDOAS-RD.1Roof DeckExhaust Fan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0253VENTDOAS UnitDOAS-RD.1Roof DeckExhaust Fan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0254VENTDOAS UnitDOAS-RD.1Roof DeckExhaust Fan Variable Speed Monitoring (HLI)HLIVFDEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0255VENTDOAS UnitDOAS-RD.1Roof DeckExhaust Fan Control (On/Off/Modulating) (HLI)HLIVFDEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0256VENTDOAS UnitDOAS-RD.1Roof DeckNetwork drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0257VENTDOAS UnitDOAS-RD.2Roof DeckTemperature Monitoring (Outside — Supply Air)AITemperature SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0258VENTDOAS UnitDOAS-RD.2Roof DeckFlow Monitoring (Outside — Supply Air)AIFlow SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0259VENTDOAS UnitDOAS-RD.2Roof DeckHumidity Monitoring (Outdoor — Supply Air)AIHumidity SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0260VENTDOAS UnitDOAS-RD.2Roof DeckOutdoor Supply Air Motorized Damper StatusAIDamper ControllerME ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0261VENTDOAS UnitDOAS-RD.2Roof DeckOutdoor Supply Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerME ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0262VENTDOAS UnitDOAS-RD.2Roof DeckRecovery Wheel Motor StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0263VENTDOAS UnitDOAS-RD.2Roof DeckRecovery Wheel Motor Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0264VENTDOAS UnitDOAS-RD.2Roof DeckSupply Fan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0265VENTDOAS UnitDOAS-RD.2Roof DeckSupply Fan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0266VENTDOAS UnitDOAS-RD.2Roof DeckSupply Fan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0267VENTDOAS UnitDOAS-RD.2Roof DeckSupply Fan Variable Speed Monitoring (HLI)HLIVFDEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0268VENTDOAS UnitDOAS-RD.2Roof DeckSupply Fan Control (On/Off/Modulating) (HLI)HLIVFDEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0269VENTDOAS UnitDOAS-RD.2Roof DeckTemperature Monitoring (Indoor — Mixed Air)AITemperature SensorEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0270VENTDOAS UnitDOAS-RD.2Roof DeckHumidity Monitoring (Indoor — Mixed Air)AIHumidity SensorEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0271VENTDOAS UnitDOAS-RD.2Roof DeckCHWS / Cooling Coil Valve StatusAIElectric Valve ActuatorME ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0272VENTDOAS UnitDOAS-RD.2Roof DeckCHWS Valve Control (On/Off/Modulating)AOElectric Valve ActuatorME ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0273VENTDOAS UnitDOAS-RD.2Roof DeckTemperature Monitoring (Indoor — Supply Air)AITemperature SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0274VENTDOAS UnitDOAS-RD.2Roof DeckHumidity Monitoring (Indoor — Exhaust Air)AIHumidity SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0275VENTDOAS UnitDOAS-RD.2Roof DeckTemperature Monitoring (Indoor — Exhaust Air)AITemperature SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0276VENTDOAS UnitDOAS-RD.2Roof DeckExhaust Fan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0277VENTDOAS UnitDOAS-RD.2Roof DeckExhaust Fan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0278VENTDOAS UnitDOAS-RD.2Roof DeckExhaust Fan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0279VENTDOAS UnitDOAS-RD.2Roof DeckExhaust Fan Variable Speed Monitoring (HLI)HLIVFDEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0280VENTDOAS UnitDOAS-RD.2Roof DeckExhaust Fan Control (On/Off/Modulating) (HLI)HLIVFDEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0281VENTDOAS UnitDOAS-RD.2Roof DeckNetwork drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0282VENTPrecooled Air Handling UnitPAHU-r.1Roof DeckOutdoor Supply Air Motorized Damper StatusAIDamper ControllerEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0283VENTPrecooled Air Handling UnitPAHU-r.1Roof DeckOutdoor Supply Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0284VENTPrecooled Air Handling UnitPAHU-r.1Roof DeckTemperature Monitoring (Outside — Supply Air)AITemperature SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0285VENTPrecooled Air Handling UnitPAHU-r.1Roof DeckFlow Monitoring (Outside — Supply Air)AIFlow SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0286VENTPrecooled Air Handling UnitPAHU-r.1Roof DeckCHWS Valve Control (On/Off/Modulating)AOElectric Valve ActuatorME ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0287VENTPrecooled Air Handling UnitPAHU-r.1Roof DeckFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0288VENTPrecooled Air Handling UnitPAHU-r.1Roof DeckFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0289VENTPrecooled Air Handling UnitPAHU-r.1Roof DeckFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0290VENTPrecooled Air Handling UnitPAHU-r.1Roof DeckTemperature Monitoring (Indoor — Supply Air)AITemperature SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0291VENTPrecooled Air Handling UnitPAHU-r.1Roof DeckVariable Speed Monitoring (HLI)HLIVFDEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0292VENTPrecooled Air Handling UnitPAHU-r.1Roof DeckFan Control (On/Off/Modulating) (HLI)HLIVFDEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0293VENTPrecooled Air Handling UnitPAHU-r.1Roof DeckNetwork drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0294VENTPrecooled Air Handling UnitPAHU-r.2Roof DeckOutdoor Supply Air Motorized Damper StatusAIDamper ControllerEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0295VENTPrecooled Air Handling UnitPAHU-r.2Roof DeckOutdoor Supply Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0296VENTPrecooled Air Handling UnitPAHU-r.2Roof DeckTemperature Monitoring (Outside — Supply Air)AITemperature SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0297VENTPrecooled Air Handling UnitPAHU-r.2Roof DeckFlow Monitoring (Outside — Supply Air)AIFlow SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0298VENTPrecooled Air Handling UnitPAHU-r.2Roof DeckCHWS Valve Control (On/Off/Modulating)AOElectric Valve ActuatorME ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0299VENTPrecooled Air Handling UnitPAHU-r.2Roof DeckFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0300VENTPrecooled Air Handling UnitPAHU-r.2Roof DeckFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0301VENTPrecooled Air Handling UnitPAHU-r.2Roof DeckFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0302VENTPrecooled Air Handling UnitPAHU-r.2Roof DeckTemperature Monitoring (Indoor — Supply Air)AITemperature SensorBMS ContractorDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0303VENTPrecooled Air Handling UnitPAHU-r.2Roof DeckVariable Speed Monitoring (HLI)HLIVFDEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0304VENTPrecooled Air Handling UnitPAHU-r.2Roof DeckFan Control (On/Off/Modulating) (HLI)HLIVFDEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0305VENTPrecooled Air Handling UnitPAHU-r.2Roof DeckNetwork drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0306VENTDOAS Unit (Casino — with CO/VOC)DOAS-2M2nd Mezzanine (Casino)Temperature Monitoring (Outside — Supply Air)AITemperature SensorBMS ContractorDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0307VENTDOAS Unit (Casino — with CO/VOC)DOAS-2M2nd Mezzanine (Casino)Flow Monitoring (Outside — Supply Air)AIFlow SensorBMS ContractorDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0308VENTDOAS Unit (Casino — with CO/VOC)DOAS-2M2nd Mezzanine (Casino)Humidity Monitoring (Outdoor — Supply Air)AIHumidity SensorBMS ContractorDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0309VENTDOAS Unit (Casino — with CO/VOC)DOAS-2M2nd Mezzanine (Casino)Outdoor Supply Air Motorized Damper StatusAIDamper ControllerME ContractorDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0310VENTDOAS Unit (Casino — with CO/VOC)DOAS-2M2nd Mezzanine (Casino)Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerME ContractorDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0311VENTDOAS Unit (Casino — with CO/VOC)DOAS-2M2nd Mezzanine (Casino)Recovery Wheel Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0312VENTDOAS Unit (Casino — with CO/VOC)DOAS-2M2nd Mezzanine (Casino)Recovery Wheel Motor Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0313VENTDOAS Unit (Casino — with CO/VOC)DOAS-2M2nd Mezzanine (Casino)Supply Fan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0314VENTDOAS Unit (Casino — with CO/VOC)DOAS-2M2nd Mezzanine (Casino)Supply Fan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0315VENTDOAS Unit (Casino — with CO/VOC)DOAS-2M2nd Mezzanine (Casino)Supply Fan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0316VENTDOAS Unit (Casino — with CO/VOC)DOAS-2M2nd Mezzanine (Casino)Supply Fan Variable Speed Monitoring (HLI)HLIVFDEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0317VENTDOAS Unit (Casino — with CO/VOC)DOAS-2M2nd Mezzanine (Casino)Supply Fan Control (On/Off/Modulating) (HLI)HLIVFDEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0318VENTDOAS Unit (Casino — with CO/VOC)DOAS-2M2nd Mezzanine (Casino)Temperature Monitoring (Indoor — Mixed Air)AITemperature SensorEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0319VENTDOAS Unit (Casino — with CO/VOC)DOAS-2M2nd Mezzanine (Casino)Humidity Monitoring (Indoor — Mixed Air)AIHumidity SensorEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0320VENTDOAS Unit (Casino — with CO/VOC)DOAS-2M2nd Mezzanine (Casino)CHWS Valve Control (On/Off/Modulating)AOElectric Valve ActuatorME ContractorDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0321VENTDOAS Unit (Casino — with CO/VOC)DOAS-2M2nd Mezzanine (Casino)Carbon Dioxide (CO2) Sensor at Return DuctAICO2 SensorBMS ContractorDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0322VENTDOAS Unit (Casino — with CO/VOC)DOAS-2M2nd Mezzanine (Casino)Carbon Monoxide (CO) Sensor at Return Duct (Casino)AICO SensorBMS ContractorDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0323VENTDOAS Unit (Casino — with CO/VOC)DOAS-2M2nd Mezzanine (Casino)Exhaust Fan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0324VENTDOAS Unit (Casino — with CO/VOC)DOAS-2M2nd Mezzanine (Casino)Exhaust Fan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0325VENTDOAS Unit (Casino — with CO/VOC)DOAS-2M2nd Mezzanine (Casino)Exhaust Fan Variable Speed Monitoring (HLI)HLIVFDEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0326VENTDOAS Unit (Casino — with CO/VOC)DOAS-2M2nd Mezzanine (Casino)Exhaust Fan Control (On/Off/Modulating) (HLI)HLIVFDEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0327VENTDOAS Unit (Casino — with CO/VOC)DOAS-2M2nd Mezzanine (Casino)Network drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0328ACAHU (Chilled-Water-Served)AHU-2M.12nd Mezzanine (Casino)Indoor Return Air Motorized Damper StatusAIDamper ControllerME ContractorDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0329ACAHU (Chilled-Water-Served)AHU-2M.12nd Mezzanine (Casino)Indoor Return Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerME ContractorDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0330ACAHU (Chilled-Water-Served)AHU-2M.12nd Mezzanine (Casino)Indoor Return Air CO2 LevelAICO2 SensorBMS ContractorDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0331ACAHU (Chilled-Water-Served)AHU-2M.12nd Mezzanine (Casino)Temperature Monitoring (Indoor — Return Air)AITemperature SensorBMS ContractorDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0332ACAHU (Chilled-Water-Served)AHU-2M.12nd Mezzanine (Casino)Temperature Monitoring (Indoor — Mixed Air)AITemperature SensorBMS ContractorDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0333ACAHU (Chilled-Water-Served)AHU-2M.12nd Mezzanine (Casino)Outdoor Supply Air Motorized Damper StatusAIDamper ControllerEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0334ACAHU (Chilled-Water-Served)AHU-2M.12nd Mezzanine (Casino)Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0335ACAHU (Chilled-Water-Served)AHU-2M.12nd Mezzanine (Casino)Temperature Monitoring (Outside — Supply Air)AITemperature SensorBMS ContractorDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0336ACAHU (Chilled-Water-Served)AHU-2M.12nd Mezzanine (Casino)Temperature Monitoring (Indoor — Supply Air)AITemperature SensorBMS ContractorDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0337ACAHU (Chilled-Water-Served)AHU-2M.12nd Mezzanine (Casino)CHWS Valve Control (On/Off/Modulating)AOElectric Valve ActuatorME ContractorDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0338ACAHU (Chilled-Water-Served)AHU-2M.12nd Mezzanine (Casino)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0339ACAHU (Chilled-Water-Served)AHU-2M.12nd Mezzanine (Casino)Fan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0340ACAHU (Chilled-Water-Served)AHU-2M.12nd Mezzanine (Casino)Fan Variable Speed Monitoring (HLI)HLIVFDEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0341ACAHU (Chilled-Water-Served)AHU-2M.12nd Mezzanine (Casino)Fan Control On/Off/Modulating (HLI)HLIVFDEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0342ACAHU (Chilled-Water-Served)AHU-2M.12nd Mezzanine (Casino)Network drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0343ACAHU (Chilled-Water-Served)AHU-2M.22nd Mezzanine (Casino)Indoor Return Air Motorized Damper StatusAIDamper ControllerME ContractorDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0344ACAHU (Chilled-Water-Served)AHU-2M.22nd Mezzanine (Casino)Indoor Return Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerME ContractorDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0345ACAHU (Chilled-Water-Served)AHU-2M.22nd Mezzanine (Casino)Indoor Return Air CO2 LevelAICO2 SensorBMS ContractorDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0346ACAHU (Chilled-Water-Served)AHU-2M.22nd Mezzanine (Casino)Temperature Monitoring (Indoor — Return Air)AITemperature SensorBMS ContractorDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0347ACAHU (Chilled-Water-Served)AHU-2M.22nd Mezzanine (Casino)Temperature Monitoring (Indoor — Mixed Air)AITemperature SensorBMS ContractorDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0348ACAHU (Chilled-Water-Served)AHU-2M.22nd Mezzanine (Casino)Outdoor Supply Air Motorized Damper StatusAIDamper ControllerEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0349ACAHU (Chilled-Water-Served)AHU-2M.22nd Mezzanine (Casino)Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0350ACAHU (Chilled-Water-Served)AHU-2M.22nd Mezzanine (Casino)Temperature Monitoring (Outside — Supply Air)AITemperature SensorBMS ContractorDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0351ACAHU (Chilled-Water-Served)AHU-2M.22nd Mezzanine (Casino)Temperature Monitoring (Indoor — Supply Air)AITemperature SensorBMS ContractorDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0352ACAHU (Chilled-Water-Served)AHU-2M.22nd Mezzanine (Casino)CHWS Valve Control (On/Off/Modulating)AOElectric Valve ActuatorME ContractorDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0353ACAHU (Chilled-Water-Served)AHU-2M.22nd Mezzanine (Casino)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0354ACAHU (Chilled-Water-Served)AHU-2M.22nd Mezzanine (Casino)Fan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0355ACAHU (Chilled-Water-Served)AHU-2M.22nd Mezzanine (Casino)Fan Variable Speed Monitoring (HLI)HLIVFDEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0356ACAHU (Chilled-Water-Served)AHU-2M.22nd Mezzanine (Casino)Fan Control On/Off/Modulating (HLI)HLIVFDEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0357ACAHU (Chilled-Water-Served)AHU-2M.22nd Mezzanine (Casino)Network drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0358ACAir Ionizer (Casino)AIR-ION-2M.12nd Mezzanine (Casino)VOC Monitoring (Return Duct)AIVOC SensorBMS ContractorDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0359ACAir Ionizer (Casino)AIR-ION-2M.12nd Mezzanine (Casino)Air Ionizer Equipment StatusDIAuxiliary Contact / ModbusEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0360ACAir Ionizer (Casino)AIR-ION-2M.12nd Mezzanine (Casino)Air Ionizer Equipment Trip StatusDIAuxiliary Contact / ModbusEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0361ACAir Ionizer (Casino)AIR-ION-2M.12nd Mezzanine (Casino)Network drop (Modbus / BACnet MS-TP — Ionizer Controller)NetworkIonizer ControllerEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0362ACAir Ionizer (Casino)AIR-ION-2M.22nd Mezzanine (Casino)VOC Monitoring (Return Duct)AIVOC SensorBMS ContractorDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0363ACAir Ionizer (Casino)AIR-ION-2M.22nd Mezzanine (Casino)Air Ionizer Equipment StatusDIAuxiliary Contact / ModbusEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0364ACAir Ionizer (Casino)AIR-ION-2M.22nd Mezzanine (Casino)Air Ionizer Equipment Trip StatusDIAuxiliary Contact / ModbusEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0365ACAir Ionizer (Casino)AIR-ION-2M.22nd Mezzanine (Casino)Network drop (Modbus / BACnet MS-TP — Ionizer Controller)NetworkIonizer ControllerEquipment SupplierDDC-2M-CASINOBMS-01/02 + MC Standards ME/PL
P-0366ACAHU (Chilled-Water-Served)AHU-B.12nd Level BOHIndoor Return Air Motorized Damper StatusAIDamper ControllerME ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0367ACAHU (Chilled-Water-Served)AHU-B.12nd Level BOHIndoor Return Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerME ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0368ACAHU (Chilled-Water-Served)AHU-B.12nd Level BOHIndoor Return Air CO2 LevelAICO2 SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0369ACAHU (Chilled-Water-Served)AHU-B.12nd Level BOHTemperature Monitoring (Indoor — Return Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0370ACAHU (Chilled-Water-Served)AHU-B.12nd Level BOHTemperature Monitoring (Indoor — Mixed Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0371ACAHU (Chilled-Water-Served)AHU-B.12nd Level BOHOutdoor Supply Air Motorized Damper StatusAIDamper ControllerEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0372ACAHU (Chilled-Water-Served)AHU-B.12nd Level BOHOutdoor Supply Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0373ACAHU (Chilled-Water-Served)AHU-B.12nd Level BOHTemperature Monitoring (Outside — Supply Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0374ACAHU (Chilled-Water-Served)AHU-B.12nd Level BOHTemperature Monitoring (Indoor — Supply Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0375ACAHU (Chilled-Water-Served)AHU-B.12nd Level BOHCHWS Valve Control (On/Off/Modulating)AOElectric Valve ActuatorME ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0376ACAHU (Chilled-Water-Served)AHU-B.12nd Level BOHFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0377ACAHU (Chilled-Water-Served)AHU-B.12nd Level BOHFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0378ACAHU (Chilled-Water-Served)AHU-B.12nd Level BOHFan Variable Speed Monitoring (HLI)HLIVFDEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0379ACAHU (Chilled-Water-Served)AHU-B.12nd Level BOHFan Control On/Off/Modulating (HLI)HLIVFDEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0380ACAHU (Chilled-Water-Served)AHU-B.12nd Level BOHNetwork drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0381ACAHU (Chilled-Water-Served)AHU-B.22nd Level BOHIndoor Return Air Motorized Damper StatusAIDamper ControllerME ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0382ACAHU (Chilled-Water-Served)AHU-B.22nd Level BOHIndoor Return Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerME ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0383ACAHU (Chilled-Water-Served)AHU-B.22nd Level BOHIndoor Return Air CO2 LevelAICO2 SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0384ACAHU (Chilled-Water-Served)AHU-B.22nd Level BOHTemperature Monitoring (Indoor — Return Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0385ACAHU (Chilled-Water-Served)AHU-B.22nd Level BOHTemperature Monitoring (Indoor — Mixed Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0386ACAHU (Chilled-Water-Served)AHU-B.22nd Level BOHOutdoor Supply Air Motorized Damper StatusAIDamper ControllerEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0387ACAHU (Chilled-Water-Served)AHU-B.22nd Level BOHOutdoor Supply Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0388ACAHU (Chilled-Water-Served)AHU-B.22nd Level BOHTemperature Monitoring (Outside — Supply Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0389ACAHU (Chilled-Water-Served)AHU-B.22nd Level BOHTemperature Monitoring (Indoor — Supply Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0390ACAHU (Chilled-Water-Served)AHU-B.22nd Level BOHCHWS Valve Control (On/Off/Modulating)AOElectric Valve ActuatorME ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0391ACAHU (Chilled-Water-Served)AHU-B.22nd Level BOHFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0392ACAHU (Chilled-Water-Served)AHU-B.22nd Level BOHFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0393ACAHU (Chilled-Water-Served)AHU-B.22nd Level BOHFan Variable Speed Monitoring (HLI)HLIVFDEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0394ACAHU (Chilled-Water-Served)AHU-B.22nd Level BOHFan Control On/Off/Modulating (HLI)HLIVFDEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0395ACAHU (Chilled-Water-Served)AHU-B.22nd Level BOHNetwork drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0396ACAHU (Chilled-Water-Served)AHU-B.32nd Level BOHIndoor Return Air Motorized Damper StatusAIDamper ControllerME ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0397ACAHU (Chilled-Water-Served)AHU-B.32nd Level BOHIndoor Return Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerME ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0398ACAHU (Chilled-Water-Served)AHU-B.32nd Level BOHIndoor Return Air CO2 LevelAICO2 SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0399ACAHU (Chilled-Water-Served)AHU-B.32nd Level BOHTemperature Monitoring (Indoor — Return Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0400ACAHU (Chilled-Water-Served)AHU-B.32nd Level BOHTemperature Monitoring (Indoor — Mixed Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0401ACAHU (Chilled-Water-Served)AHU-B.32nd Level BOHOutdoor Supply Air Motorized Damper StatusAIDamper ControllerEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0402ACAHU (Chilled-Water-Served)AHU-B.32nd Level BOHOutdoor Supply Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0403ACAHU (Chilled-Water-Served)AHU-B.32nd Level BOHTemperature Monitoring (Outside — Supply Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0404ACAHU (Chilled-Water-Served)AHU-B.32nd Level BOHTemperature Monitoring (Indoor — Supply Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0405ACAHU (Chilled-Water-Served)AHU-B.32nd Level BOHCHWS Valve Control (On/Off/Modulating)AOElectric Valve ActuatorME ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0406ACAHU (Chilled-Water-Served)AHU-B.32nd Level BOHFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0407ACAHU (Chilled-Water-Served)AHU-B.32nd Level BOHFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0408ACAHU (Chilled-Water-Served)AHU-B.32nd Level BOHFan Variable Speed Monitoring (HLI)HLIVFDEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0409ACAHU (Chilled-Water-Served)AHU-B.32nd Level BOHFan Control On/Off/Modulating (HLI)HLIVFDEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0410ACAHU (Chilled-Water-Served)AHU-B.32nd Level BOHNetwork drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0411ACAHU (Chilled-Water-Served)AHU-PF2nd Level Pre-FunctionIndoor Return Air Motorized Damper StatusAIDamper ControllerME ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0412ACAHU (Chilled-Water-Served)AHU-PF2nd Level Pre-FunctionIndoor Return Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerME ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0413ACAHU (Chilled-Water-Served)AHU-PF2nd Level Pre-FunctionIndoor Return Air CO2 LevelAICO2 SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0414ACAHU (Chilled-Water-Served)AHU-PF2nd Level Pre-FunctionTemperature Monitoring (Indoor — Return Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0415ACAHU (Chilled-Water-Served)AHU-PF2nd Level Pre-FunctionTemperature Monitoring (Indoor — Mixed Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0416ACAHU (Chilled-Water-Served)AHU-PF2nd Level Pre-FunctionOutdoor Supply Air Motorized Damper StatusAIDamper ControllerEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0417ACAHU (Chilled-Water-Served)AHU-PF2nd Level Pre-FunctionOutdoor Supply Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0418ACAHU (Chilled-Water-Served)AHU-PF2nd Level Pre-FunctionTemperature Monitoring (Outside — Supply Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0419ACAHU (Chilled-Water-Served)AHU-PF2nd Level Pre-FunctionTemperature Monitoring (Indoor — Supply Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0420ACAHU (Chilled-Water-Served)AHU-PF2nd Level Pre-FunctionCHWS Valve Control (On/Off/Modulating)AOElectric Valve ActuatorME ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0421ACAHU (Chilled-Water-Served)AHU-PF2nd Level Pre-FunctionFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0422ACAHU (Chilled-Water-Served)AHU-PF2nd Level Pre-FunctionFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0423ACAHU (Chilled-Water-Served)AHU-PF2nd Level Pre-FunctionFan Variable Speed Monitoring (HLI)HLIVFDEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0424ACAHU (Chilled-Water-Served)AHU-PF2nd Level Pre-FunctionFan Control On/Off/Modulating (HLI)HLIVFDEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0425ACAHU (Chilled-Water-Served)AHU-PF2nd Level Pre-FunctionNetwork drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0426ACAHU (Chilled-Water-Served)AHU-EL2nd Level Executive LoungeIndoor Return Air Motorized Damper StatusAIDamper ControllerME ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0427ACAHU (Chilled-Water-Served)AHU-EL2nd Level Executive LoungeIndoor Return Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerME ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0428ACAHU (Chilled-Water-Served)AHU-EL2nd Level Executive LoungeIndoor Return Air CO2 LevelAICO2 SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0429ACAHU (Chilled-Water-Served)AHU-EL2nd Level Executive LoungeTemperature Monitoring (Indoor — Return Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0430ACAHU (Chilled-Water-Served)AHU-EL2nd Level Executive LoungeTemperature Monitoring (Indoor — Mixed Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0431ACAHU (Chilled-Water-Served)AHU-EL2nd Level Executive LoungeOutdoor Supply Air Motorized Damper StatusAIDamper ControllerEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0432ACAHU (Chilled-Water-Served)AHU-EL2nd Level Executive LoungeOutdoor Supply Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0433ACAHU (Chilled-Water-Served)AHU-EL2nd Level Executive LoungeTemperature Monitoring (Outside — Supply Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0434ACAHU (Chilled-Water-Served)AHU-EL2nd Level Executive LoungeTemperature Monitoring (Indoor — Supply Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0435ACAHU (Chilled-Water-Served)AHU-EL2nd Level Executive LoungeCHWS Valve Control (On/Off/Modulating)AOElectric Valve ActuatorME ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0436ACAHU (Chilled-Water-Served)AHU-EL2nd Level Executive LoungeFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0437ACAHU (Chilled-Water-Served)AHU-EL2nd Level Executive LoungeFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0438ACAHU (Chilled-Water-Served)AHU-EL2nd Level Executive LoungeFan Variable Speed Monitoring (HLI)HLIVFDEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0439ACAHU (Chilled-Water-Served)AHU-EL2nd Level Executive LoungeFan Control On/Off/Modulating (HLI)HLIVFDEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0440ACAHU (Chilled-Water-Served)AHU-EL2nd Level Executive LoungeNetwork drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0441ACAHU (Chilled-Water-Served)AHU-FR22nd Level Function Room 2Indoor Return Air Motorized Damper StatusAIDamper ControllerME ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0442ACAHU (Chilled-Water-Served)AHU-FR22nd Level Function Room 2Indoor Return Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerME ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0443ACAHU (Chilled-Water-Served)AHU-FR22nd Level Function Room 2Indoor Return Air CO2 LevelAICO2 SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0444ACAHU (Chilled-Water-Served)AHU-FR22nd Level Function Room 2Temperature Monitoring (Indoor — Return Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0445ACAHU (Chilled-Water-Served)AHU-FR22nd Level Function Room 2Temperature Monitoring (Indoor — Mixed Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0446ACAHU (Chilled-Water-Served)AHU-FR22nd Level Function Room 2Outdoor Supply Air Motorized Damper StatusAIDamper ControllerEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0447ACAHU (Chilled-Water-Served)AHU-FR22nd Level Function Room 2Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0448ACAHU (Chilled-Water-Served)AHU-FR22nd Level Function Room 2Temperature Monitoring (Outside — Supply Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0449ACAHU (Chilled-Water-Served)AHU-FR22nd Level Function Room 2Temperature Monitoring (Indoor — Supply Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0450ACAHU (Chilled-Water-Served)AHU-FR22nd Level Function Room 2CHWS Valve Control (On/Off/Modulating)AOElectric Valve ActuatorME ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0451ACAHU (Chilled-Water-Served)AHU-FR22nd Level Function Room 2Fan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0452ACAHU (Chilled-Water-Served)AHU-FR22nd Level Function Room 2Fan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0453ACAHU (Chilled-Water-Served)AHU-FR22nd Level Function Room 2Fan Variable Speed Monitoring (HLI)HLIVFDEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0454ACAHU (Chilled-Water-Served)AHU-FR22nd Level Function Room 2Fan Control On/Off/Modulating (HLI)HLIVFDEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0455ACAHU (Chilled-Water-Served)AHU-FR22nd Level Function Room 2Network drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0456ACAHU (Chilled-Water-Served)AHU-FR32nd Level Function Room 3Indoor Return Air Motorized Damper StatusAIDamper ControllerME ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0457ACAHU (Chilled-Water-Served)AHU-FR32nd Level Function Room 3Indoor Return Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerME ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0458ACAHU (Chilled-Water-Served)AHU-FR32nd Level Function Room 3Indoor Return Air CO2 LevelAICO2 SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0459ACAHU (Chilled-Water-Served)AHU-FR32nd Level Function Room 3Temperature Monitoring (Indoor — Return Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0460ACAHU (Chilled-Water-Served)AHU-FR32nd Level Function Room 3Temperature Monitoring (Indoor — Mixed Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0461ACAHU (Chilled-Water-Served)AHU-FR32nd Level Function Room 3Outdoor Supply Air Motorized Damper StatusAIDamper ControllerEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0462ACAHU (Chilled-Water-Served)AHU-FR32nd Level Function Room 3Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0463ACAHU (Chilled-Water-Served)AHU-FR32nd Level Function Room 3Temperature Monitoring (Outside — Supply Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0464ACAHU (Chilled-Water-Served)AHU-FR32nd Level Function Room 3Temperature Monitoring (Indoor — Supply Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0465ACAHU (Chilled-Water-Served)AHU-FR32nd Level Function Room 3CHWS Valve Control (On/Off/Modulating)AOElectric Valve ActuatorME ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0466ACAHU (Chilled-Water-Served)AHU-FR32nd Level Function Room 3Fan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0467ACAHU (Chilled-Water-Served)AHU-FR32nd Level Function Room 3Fan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0468ACAHU (Chilled-Water-Served)AHU-FR32nd Level Function Room 3Fan Variable Speed Monitoring (HLI)HLIVFDEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0469ACAHU (Chilled-Water-Served)AHU-FR32nd Level Function Room 3Fan Control On/Off/Modulating (HLI)HLIVFDEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0470ACAHU (Chilled-Water-Served)AHU-FR32nd Level Function Room 3Network drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0471VENTPrecooled Air Handling UnitPAHU-B.12nd Level BOHOutdoor Supply Air Motorized Damper StatusAIDamper ControllerEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0472VENTPrecooled Air Handling UnitPAHU-B.12nd Level BOHOutdoor Supply Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0473VENTPrecooled Air Handling UnitPAHU-B.12nd Level BOHTemperature Monitoring (Outside — Supply Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0474VENTPrecooled Air Handling UnitPAHU-B.12nd Level BOHFlow Monitoring (Outside — Supply Air)AIFlow SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0475VENTPrecooled Air Handling UnitPAHU-B.12nd Level BOHCHWS Valve Control (On/Off/Modulating)AOElectric Valve ActuatorME ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0476VENTPrecooled Air Handling UnitPAHU-B.12nd Level BOHFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0477VENTPrecooled Air Handling UnitPAHU-B.12nd Level BOHFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0478VENTPrecooled Air Handling UnitPAHU-B.12nd Level BOHFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0479VENTPrecooled Air Handling UnitPAHU-B.12nd Level BOHTemperature Monitoring (Indoor — Supply Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0480VENTPrecooled Air Handling UnitPAHU-B.12nd Level BOHVariable Speed Monitoring (HLI)HLIVFDEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0481VENTPrecooled Air Handling UnitPAHU-B.12nd Level BOHFan Control (On/Off/Modulating) (HLI)HLIVFDEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0482VENTPrecooled Air Handling UnitPAHU-B.12nd Level BOHNetwork drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0483VENTPrecooled Air Handling UnitPAHU-B.22nd Level BOHOutdoor Supply Air Motorized Damper StatusAIDamper ControllerEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0484VENTPrecooled Air Handling UnitPAHU-B.22nd Level BOHOutdoor Supply Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0485VENTPrecooled Air Handling UnitPAHU-B.22nd Level BOHTemperature Monitoring (Outside — Supply Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0486VENTPrecooled Air Handling UnitPAHU-B.22nd Level BOHFlow Monitoring (Outside — Supply Air)AIFlow SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0487VENTPrecooled Air Handling UnitPAHU-B.22nd Level BOHCHWS Valve Control (On/Off/Modulating)AOElectric Valve ActuatorME ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0488VENTPrecooled Air Handling UnitPAHU-B.22nd Level BOHFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0489VENTPrecooled Air Handling UnitPAHU-B.22nd Level BOHFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0490VENTPrecooled Air Handling UnitPAHU-B.22nd Level BOHFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0491VENTPrecooled Air Handling UnitPAHU-B.22nd Level BOHTemperature Monitoring (Indoor — Supply Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0492VENTPrecooled Air Handling UnitPAHU-B.22nd Level BOHVariable Speed Monitoring (HLI)HLIVFDEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0493VENTPrecooled Air Handling UnitPAHU-B.22nd Level BOHFan Control (On/Off/Modulating) (HLI)HLIVFDEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0494VENTPrecooled Air Handling UnitPAHU-B.22nd Level BOHNetwork drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0495VENTPrecooled Air Handling UnitPAHU-B.32nd Level BOHOutdoor Supply Air Motorized Damper StatusAIDamper ControllerEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0496VENTPrecooled Air Handling UnitPAHU-B.32nd Level BOHOutdoor Supply Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0497VENTPrecooled Air Handling UnitPAHU-B.32nd Level BOHTemperature Monitoring (Outside — Supply Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0498VENTPrecooled Air Handling UnitPAHU-B.32nd Level BOHFlow Monitoring (Outside — Supply Air)AIFlow SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0499VENTPrecooled Air Handling UnitPAHU-B.32nd Level BOHCHWS Valve Control (On/Off/Modulating)AOElectric Valve ActuatorME ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0500VENTPrecooled Air Handling UnitPAHU-B.32nd Level BOHFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0501VENTPrecooled Air Handling UnitPAHU-B.32nd Level BOHFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0502VENTPrecooled Air Handling UnitPAHU-B.32nd Level BOHFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0503VENTPrecooled Air Handling UnitPAHU-B.32nd Level BOHTemperature Monitoring (Indoor — Supply Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0504VENTPrecooled Air Handling UnitPAHU-B.32nd Level BOHVariable Speed Monitoring (HLI)HLIVFDEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0505VENTPrecooled Air Handling UnitPAHU-B.32nd Level BOHFan Control (On/Off/Modulating) (HLI)HLIVFDEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0506VENTPrecooled Air Handling UnitPAHU-B.32nd Level BOHNetwork drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0507VENTPrecooled Air Handling UnitPAHU-PF2nd Level Pre-FunctionOutdoor Supply Air Motorized Damper StatusAIDamper ControllerEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0508VENTPrecooled Air Handling UnitPAHU-PF2nd Level Pre-FunctionOutdoor Supply Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0509VENTPrecooled Air Handling UnitPAHU-PF2nd Level Pre-FunctionTemperature Monitoring (Outside — Supply Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0510VENTPrecooled Air Handling UnitPAHU-PF2nd Level Pre-FunctionFlow Monitoring (Outside — Supply Air)AIFlow SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0511VENTPrecooled Air Handling UnitPAHU-PF2nd Level Pre-FunctionCHWS Valve Control (On/Off/Modulating)AOElectric Valve ActuatorME ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0512VENTPrecooled Air Handling UnitPAHU-PF2nd Level Pre-FunctionFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0513VENTPrecooled Air Handling UnitPAHU-PF2nd Level Pre-FunctionFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0514VENTPrecooled Air Handling UnitPAHU-PF2nd Level Pre-FunctionFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0515VENTPrecooled Air Handling UnitPAHU-PF2nd Level Pre-FunctionTemperature Monitoring (Indoor — Supply Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0516VENTPrecooled Air Handling UnitPAHU-PF2nd Level Pre-FunctionVariable Speed Monitoring (HLI)HLIVFDEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0517VENTPrecooled Air Handling UnitPAHU-PF2nd Level Pre-FunctionFan Control (On/Off/Modulating) (HLI)HLIVFDEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0518VENTPrecooled Air Handling UnitPAHU-PF2nd Level Pre-FunctionNetwork drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0519VENTPrecooled Air Handling UnitPAHU-FR2nd Level Function RoomsOutdoor Supply Air Motorized Damper StatusAIDamper ControllerEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0520VENTPrecooled Air Handling UnitPAHU-FR2nd Level Function RoomsOutdoor Supply Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0521VENTPrecooled Air Handling UnitPAHU-FR2nd Level Function RoomsTemperature Monitoring (Outside — Supply Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0522VENTPrecooled Air Handling UnitPAHU-FR2nd Level Function RoomsFlow Monitoring (Outside — Supply Air)AIFlow SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0523VENTPrecooled Air Handling UnitPAHU-FR2nd Level Function RoomsCHWS Valve Control (On/Off/Modulating)AOElectric Valve ActuatorME ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0524VENTPrecooled Air Handling UnitPAHU-FR2nd Level Function RoomsFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0525VENTPrecooled Air Handling UnitPAHU-FR2nd Level Function RoomsFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0526VENTPrecooled Air Handling UnitPAHU-FR2nd Level Function RoomsFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0527VENTPrecooled Air Handling UnitPAHU-FR2nd Level Function RoomsTemperature Monitoring (Indoor — Supply Air)AITemperature SensorBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0528VENTPrecooled Air Handling UnitPAHU-FR2nd Level Function RoomsVariable Speed Monitoring (HLI)HLIVFDEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0529VENTPrecooled Air Handling UnitPAHU-FR2nd Level Function RoomsFan Control (On/Off/Modulating) (HLI)HLIVFDEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0530VENTPrecooled Air Handling UnitPAHU-FR2nd Level Function RoomsNetwork drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0531ACAHU (Chilled-Water-Served)AHU-1.1Ground Floor BOHIndoor Return Air Motorized Damper StatusAIDamper ControllerME ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0532ACAHU (Chilled-Water-Served)AHU-1.1Ground Floor BOHIndoor Return Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerME ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0533ACAHU (Chilled-Water-Served)AHU-1.1Ground Floor BOHIndoor Return Air CO2 LevelAICO2 SensorBMS ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0534ACAHU (Chilled-Water-Served)AHU-1.1Ground Floor BOHTemperature Monitoring (Indoor — Return Air)AITemperature SensorBMS ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0535ACAHU (Chilled-Water-Served)AHU-1.1Ground Floor BOHTemperature Monitoring (Indoor — Mixed Air)AITemperature SensorBMS ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0536ACAHU (Chilled-Water-Served)AHU-1.1Ground Floor BOHOutdoor Supply Air Motorized Damper StatusAIDamper ControllerEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0537ACAHU (Chilled-Water-Served)AHU-1.1Ground Floor BOHOutdoor Supply Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0538ACAHU (Chilled-Water-Served)AHU-1.1Ground Floor BOHTemperature Monitoring (Outside — Supply Air)AITemperature SensorBMS ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0539ACAHU (Chilled-Water-Served)AHU-1.1Ground Floor BOHTemperature Monitoring (Indoor — Supply Air)AITemperature SensorBMS ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0540ACAHU (Chilled-Water-Served)AHU-1.1Ground Floor BOHCHWS Valve Control (On/Off/Modulating)AOElectric Valve ActuatorME ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0541ACAHU (Chilled-Water-Served)AHU-1.1Ground Floor BOHFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0542ACAHU (Chilled-Water-Served)AHU-1.1Ground Floor BOHFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0543ACAHU (Chilled-Water-Served)AHU-1.1Ground Floor BOHFan Variable Speed Monitoring (HLI)HLIVFDEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0544ACAHU (Chilled-Water-Served)AHU-1.1Ground Floor BOHFan Control On/Off/Modulating (HLI)HLIVFDEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0545ACAHU (Chilled-Water-Served)AHU-1.1Ground Floor BOHNetwork drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0546ACAHU (Chilled-Water-Served)AHU-1.2Ground Floor BOHIndoor Return Air Motorized Damper StatusAIDamper ControllerME ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0547ACAHU (Chilled-Water-Served)AHU-1.2Ground Floor BOHIndoor Return Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerME ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0548ACAHU (Chilled-Water-Served)AHU-1.2Ground Floor BOHIndoor Return Air CO2 LevelAICO2 SensorBMS ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0549ACAHU (Chilled-Water-Served)AHU-1.2Ground Floor BOHTemperature Monitoring (Indoor — Return Air)AITemperature SensorBMS ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0550ACAHU (Chilled-Water-Served)AHU-1.2Ground Floor BOHTemperature Monitoring (Indoor — Mixed Air)AITemperature SensorBMS ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0551ACAHU (Chilled-Water-Served)AHU-1.2Ground Floor BOHOutdoor Supply Air Motorized Damper StatusAIDamper ControllerEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0552ACAHU (Chilled-Water-Served)AHU-1.2Ground Floor BOHOutdoor Supply Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0553ACAHU (Chilled-Water-Served)AHU-1.2Ground Floor BOHTemperature Monitoring (Outside — Supply Air)AITemperature SensorBMS ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0554ACAHU (Chilled-Water-Served)AHU-1.2Ground Floor BOHTemperature Monitoring (Indoor — Supply Air)AITemperature SensorBMS ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0555ACAHU (Chilled-Water-Served)AHU-1.2Ground Floor BOHCHWS Valve Control (On/Off/Modulating)AOElectric Valve ActuatorME ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0556ACAHU (Chilled-Water-Served)AHU-1.2Ground Floor BOHFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0557ACAHU (Chilled-Water-Served)AHU-1.2Ground Floor BOHFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0558ACAHU (Chilled-Water-Served)AHU-1.2Ground Floor BOHFan Variable Speed Monitoring (HLI)HLIVFDEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0559ACAHU (Chilled-Water-Served)AHU-1.2Ground Floor BOHFan Control On/Off/Modulating (HLI)HLIVFDEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0560ACAHU (Chilled-Water-Served)AHU-1.2Ground Floor BOHNetwork drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0561ACAHU (Chilled-Water-Served)AHU-1.3Ground Floor BOHIndoor Return Air Motorized Damper StatusAIDamper ControllerME ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0562ACAHU (Chilled-Water-Served)AHU-1.3Ground Floor BOHIndoor Return Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerME ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0563ACAHU (Chilled-Water-Served)AHU-1.3Ground Floor BOHIndoor Return Air CO2 LevelAICO2 SensorBMS ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0564ACAHU (Chilled-Water-Served)AHU-1.3Ground Floor BOHTemperature Monitoring (Indoor — Return Air)AITemperature SensorBMS ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0565ACAHU (Chilled-Water-Served)AHU-1.3Ground Floor BOHTemperature Monitoring (Indoor — Mixed Air)AITemperature SensorBMS ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0566ACAHU (Chilled-Water-Served)AHU-1.3Ground Floor BOHOutdoor Supply Air Motorized Damper StatusAIDamper ControllerEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0567ACAHU (Chilled-Water-Served)AHU-1.3Ground Floor BOHOutdoor Supply Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0568ACAHU (Chilled-Water-Served)AHU-1.3Ground Floor BOHTemperature Monitoring (Outside — Supply Air)AITemperature SensorBMS ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0569ACAHU (Chilled-Water-Served)AHU-1.3Ground Floor BOHTemperature Monitoring (Indoor — Supply Air)AITemperature SensorBMS ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0570ACAHU (Chilled-Water-Served)AHU-1.3Ground Floor BOHCHWS Valve Control (On/Off/Modulating)AOElectric Valve ActuatorME ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0571ACAHU (Chilled-Water-Served)AHU-1.3Ground Floor BOHFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0572ACAHU (Chilled-Water-Served)AHU-1.3Ground Floor BOHFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0573ACAHU (Chilled-Water-Served)AHU-1.3Ground Floor BOHFan Variable Speed Monitoring (HLI)HLIVFDEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0574ACAHU (Chilled-Water-Served)AHU-1.3Ground Floor BOHFan Control On/Off/Modulating (HLI)HLIVFDEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0575ACAHU (Chilled-Water-Served)AHU-1.3Ground Floor BOHNetwork drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0576VENTPrecooled Air Handling UnitPAHU-0.1BasementOutdoor Supply Air Motorized Damper StatusAIDamper ControllerEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0577VENTPrecooled Air Handling UnitPAHU-0.1BasementOutdoor Supply Air Motorized Damper Control (On/Off/Modulating)AODamper ControllerEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0578VENTPrecooled Air Handling UnitPAHU-0.1BasementTemperature Monitoring (Outside — Supply Air)AITemperature SensorBMS ContractorDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0579VENTPrecooled Air Handling UnitPAHU-0.1BasementFlow Monitoring (Outside — Supply Air)AIFlow SensorBMS ContractorDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0580VENTPrecooled Air Handling UnitPAHU-0.1BasementCHWS Valve Control (On/Off/Modulating)AOElectric Valve ActuatorME ContractorDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0581VENTPrecooled Air Handling UnitPAHU-0.1BasementFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0582VENTPrecooled Air Handling UnitPAHU-0.1BasementFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0583VENTPrecooled Air Handling UnitPAHU-0.1BasementFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0584VENTPrecooled Air Handling UnitPAHU-0.1BasementTemperature Monitoring (Indoor — Supply Air)AITemperature SensorBMS ContractorDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0585VENTPrecooled Air Handling UnitPAHU-0.1BasementVariable Speed Monitoring (HLI)HLIVFDEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0586VENTPrecooled Air Handling UnitPAHU-0.1BasementFan Control (On/Off/Modulating) (HLI)HLIVFDEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0587VENTPrecooled Air Handling UnitPAHU-0.1BasementNetwork drop (BACnet MS/TP — VFD)NetworkVFD BACnet cardEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0588VENTExhaust Fan (Toilet)TEF-1.1GF Main Lobby ToiletFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0589VENTExhaust Fan (Toilet)TEF-1.1GF Main Lobby ToiletFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0590VENTExhaust Fan (Toilet)TEF-1.1GF Main Lobby ToiletFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0591VENTExhaust Fan (Toilet)TEF-1.2GF Main Lobby ToiletFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0592VENTExhaust Fan (Toilet)TEF-1.2GF Main Lobby ToiletFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0593VENTExhaust Fan (Toilet)TEF-1.2GF Main Lobby ToiletFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0594VENTExhaust Fan (Toilet)TEF-1.3GF Main Lobby ToiletFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0595VENTExhaust Fan (Toilet)TEF-1.3GF Main Lobby ToiletFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0596VENTExhaust Fan (Toilet)TEF-1.3GF Main Lobby ToiletFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0597VENTExhaust Fan (Toilet)TEF-1.4GF Main Lobby ToiletFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0598VENTExhaust Fan (Toilet)TEF-1.4GF Main Lobby ToiletFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0599VENTExhaust Fan (Toilet)TEF-1.4GF Main Lobby ToiletFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0600VENTExhaust Fan (Toilet)TEF-2.12nd Floor ToiletFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0601VENTExhaust Fan (Toilet)TEF-2.12nd Floor ToiletFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0602VENTExhaust Fan (Toilet)TEF-2.12nd Floor ToiletFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0603VENTExhaust Fan (Toilet)TEF-2.22nd Floor ToiletFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0604VENTExhaust Fan (Toilet)TEF-2.22nd Floor ToiletFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0605VENTExhaust Fan (Toilet)TEF-2.22nd Floor ToiletFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0606VENTExhaust Fan (Toilet)TEF-2B.32nd Floor BOH ToiletFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0607VENTExhaust Fan (Toilet)TEF-2B.32nd Floor BOH ToiletFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0608VENTExhaust Fan (Toilet)TEF-2B.32nd Floor BOH ToiletFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0609VENTExhaust Fan (General)EF-2B.12nd Floor BOHFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0610VENTExhaust Fan (General)EF-2B.12nd Floor BOHFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0611VENTExhaust Fan (General)EF-2B.12nd Floor BOHFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0612VENTExhaust Fan (General)EF-2B.22nd Floor BOHFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0613VENTExhaust Fan (General)EF-2B.22nd Floor BOHFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0614VENTExhaust Fan (General)EF-2B.22nd Floor BOHFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0615VENTExhaust Fan (General)EF-GS.12nd Floor General ServiceFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0616VENTExhaust Fan (General)EF-GS.12nd Floor General ServiceFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0617VENTExhaust Fan (General)EF-GS.12nd Floor General ServiceFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0618VENTExhaust Fan (General)EF-GS.22nd Floor General ServiceFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0619VENTExhaust Fan (General)EF-GS.22nd Floor General ServiceFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0620VENTExhaust Fan (General)EF-GS.22nd Floor General ServiceFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0621VENTExhaust Fan (General)EF-2.12nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0622VENTExhaust Fan (General)EF-2.12nd FloorFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0623VENTExhaust Fan (General)EF-2.12nd FloorFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0624VENTExhaust Fan (General)EF-2.22nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0625VENTExhaust Fan (General)EF-2.22nd FloorFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0626VENTExhaust Fan (General)EF-2.22nd FloorFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0627VENTExhaust Fan (General)EF-2.32nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0628VENTExhaust Fan (General)EF-2.32nd FloorFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0629VENTExhaust Fan (General)EF-2.32nd FloorFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0630VENTExhaust Fan (General)EF-2.42nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0631VENTExhaust Fan (General)EF-2.42nd FloorFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0632VENTExhaust Fan (General)EF-2.42nd FloorFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0633VENTExhaust Fan (General)EF-OHRv22nd Floor OHRFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0634VENTExhaust Fan (General)EF-OHRv22nd Floor OHRFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0635VENTExhaust Fan (General)EF-OHRv22nd Floor OHRFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0636VENTExhaust Fan (Toilet)TEF-3A.13rd Floor Amenity ToiletFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0637VENTExhaust Fan (Toilet)TEF-3A.13rd Floor Amenity ToiletFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0638VENTExhaust Fan (Toilet)TEF-3A.13rd Floor Amenity ToiletFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0639VENTExhaust Fan (Toilet)TEF-3A.23rd Floor Amenity ToiletFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0640VENTExhaust Fan (Toilet)TEF-3A.23rd Floor Amenity ToiletFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0641VENTExhaust Fan (Toilet)TEF-3A.23rd Floor Amenity ToiletFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0642VENTExhaust Fan (Toilet)TEF-3B3rd Floor ToiletFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0643VENTExhaust Fan (Toilet)TEF-3B3rd Floor ToiletFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0644VENTExhaust Fan (Toilet)TEF-3B3rd Floor ToiletFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0645VENTExhaust Fan (Toilet)TEF-3C.13rd Floor ToiletFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0646VENTExhaust Fan (Toilet)TEF-3C.13rd Floor ToiletFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0647VENTExhaust Fan (Toilet)TEF-3C.13rd Floor ToiletFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0648VENTExhaust Fan (Toilet)TEF-3C.23rd Floor ToiletFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0649VENTExhaust Fan (Toilet)TEF-3C.23rd Floor ToiletFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0650VENTExhaust Fan (Toilet)TEF-3C.23rd Floor ToiletFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0651VENTExhaust Fan (Toilet)TEF-30.203rd Floor ToiletFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0652VENTExhaust Fan (Toilet)TEF-30.203rd Floor ToiletFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0653VENTExhaust Fan (Toilet)TEF-30.203rd Floor ToiletFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0654VENTExhaust Fan (General)EF-3.13rd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0655VENTExhaust Fan (General)EF-3.13rd FloorFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0656VENTExhaust Fan (General)EF-3.13rd FloorFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0657VENTExhaust Fan (General)EF-3.23rd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0658VENTExhaust Fan (General)EF-3.23rd FloorFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0659VENTExhaust Fan (General)EF-3.23rd FloorFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0660VENTExhaust Fan (General)EF-3.33rd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0661VENTExhaust Fan (General)EF-3.33rd FloorFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0662VENTExhaust Fan (General)EF-3.33rd FloorFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0663VENTExhaust Fan (General)EF-3.43rd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0664VENTExhaust Fan (General)EF-3.43rd FloorFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0665VENTExhaust Fan (General)EF-3.43rd FloorFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0666VENTExhaust Fan (General)EF-3B-G3rd Floor BOHFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0667VENTExhaust Fan (General)EF-3B-G3rd Floor BOHFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0668VENTExhaust Fan (General)EF-3B-G3rd Floor BOHFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0669VENTExhaust Fan (General)EF-3C.1-G3rd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0670VENTExhaust Fan (General)EF-3C.1-G3rd FloorFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0671VENTExhaust Fan (General)EF-3C.1-G3rd FloorFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-3FBMS-01/02 + MC Standards ME/PL
P-0672VENTExhaust Fan (Toilet)TEF-B.1Basement ToiletFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0673VENTExhaust Fan (Toilet)TEF-B.1Basement ToiletFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0674VENTExhaust Fan (Toilet)TEF-B.1Basement ToiletFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0675VENTExhaust Fan (Toilet)TEF-B.2Basement ToiletFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0676VENTExhaust Fan (Toilet)TEF-B.2Basement ToiletFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0677VENTExhaust Fan (Toilet)TEF-B.2Basement ToiletFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0678VENTExhaust Fan (General)EF-B.1BasementFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0679VENTExhaust Fan (General)EF-B.1BasementFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0680VENTExhaust Fan (General)EF-B.1BasementFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0681VENTExhaust Fan (General)EF-B.2BasementFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0682VENTExhaust Fan (General)EF-B.2BasementFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0683VENTExhaust Fan (General)EF-B.2BasementFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0684VENTExhaust Fan (General)EF-BS.1Basement ServiceFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0685VENTExhaust Fan (General)EF-BS.1Basement ServiceFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0686VENTExhaust Fan (General)EF-BS.1Basement ServiceFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0687VENTExhaust Fan (General)EF-BS.2Basement ServiceFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0688VENTExhaust Fan (General)EF-BS.2Basement ServiceFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0689VENTExhaust Fan (General)EF-BS.2Basement ServiceFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0690VENTExhaust Fan (General)EF-GL.1Basement Garbage LobbyFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0691VENTExhaust Fan (General)EF-GL.1Basement Garbage LobbyFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0692VENTExhaust Fan (General)EF-GL.1Basement Garbage LobbyFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0693VENTExhaust Fan (General)EF-GL.2Basement Garbage LobbyFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0694VENTExhaust Fan (General)EF-GL.2Basement Garbage LobbyFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0695VENTExhaust Fan (General)EF-GL.2Basement Garbage LobbyFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0696VENTExhaust Fan (General)EF-FOST.1Basement FOST RoomFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0697VENTExhaust Fan (General)EF-FOST.1Basement FOST RoomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0698VENTExhaust Fan (General)EF-FOST.1Basement FOST RoomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0699VENTExhaust Fan (General)EF-BR.1Basement Battery RoomFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0700VENTExhaust Fan (General)EF-BR.1Basement Battery RoomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0701VENTExhaust Fan (General)EF-BR.1Basement Battery RoomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0702VENTExhaust Fan (General)EF-BR.2Basement Battery RoomFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0703VENTExhaust Fan (General)EF-BR.2Basement Battery RoomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0704VENTExhaust Fan (General)EF-BR.2Basement Battery RoomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0705VENTExhaust Fan (General)EF-WS.1Basement Wash ServiceFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0706VENTExhaust Fan (General)EF-WS.1Basement Wash ServiceFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0707VENTExhaust Fan (General)EF-WS.1Basement Wash ServiceFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0708VENTExhaust Fan (General)EF-MP.1Basement Mech / PumpFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0709VENTExhaust Fan (General)EF-MP.1Basement Mech / PumpFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0710VENTExhaust Fan (General)EF-MP.1Basement Mech / PumpFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0711VENTExhaust Fan (General)EF-PR.1Basement Pump RoomFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0712VENTExhaust Fan (General)EF-PR.1Basement Pump RoomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0713VENTExhaust Fan (General)EF-PR.1Basement Pump RoomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0714VENTExhaust Fan (General)EF-PR.3Basement Pump RoomFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0715VENTExhaust Fan (General)EF-PR.3Basement Pump RoomFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0716VENTExhaust Fan (General)EF-PR.3Basement Pump RoomFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0717VENTExhaust Fan (General)EF-MFR.1Basement Main Fire RiserFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0718VENTExhaust Fan (General)EF-MFR.1Basement Main Fire RiserFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0719VENTExhaust Fan (General)EF-MFR.1Basement Main Fire RiserFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-B1-BOHBMS-01/02 + MC Standards ME/PL
P-0720VENTExhaust Fan (General)EF-RD.1Roof DeckFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0721VENTExhaust Fan (General)EF-RD.1Roof DeckFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0722VENTExhaust Fan (General)EF-RD.1Roof DeckFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0723VENTExhaust Fan (General)EF-RO.2Roof DeckFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0724VENTExhaust Fan (General)EF-RO.2Roof DeckFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0725VENTExhaust Fan (General)EF-RO.2Roof DeckFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0726VENTExhaust Fan (General)EF-1Roof DeckFan Motor StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0727VENTExhaust Fan (General)EF-1Roof DeckFan Motor Hand/Off/Auto StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0728VENTExhaust Fan (General)EF-1Roof DeckFan Trip Alarm StatusDIAuxiliary ContactEquipment SupplierDDC-RD-PLANTBMS-01/02 + MC Standards ME/PL
P-0729ELMultifunction Power Meter (Main)MPM-MAINLower Ground Main SwitchroomMultifunction power meter — voltage / current / kW / kWh / power factor / harmonicsHLIMultifunction Power MeterBMS ContractorDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0730ELMultifunction Power Meter (Main)MPM-MAINLower Ground Main SwitchroomNetwork drop (Modbus TCP — Power Meter)NetworkMultifunction Power MeterBMS ContractorDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0731ELMultifunction Power Meter (Feeder)MPM-CHILLER2nd Level Chiller MCCMultifunction power meter — voltage / current / kW / kWh / power factorHLIMultifunction Power MeterBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0732ELMultifunction Power Meter (Feeder)MPM-CHILLER2nd Level Chiller MCCNetwork drop (Modbus TCP — Power Meter)NetworkMultifunction Power MeterBMS ContractorDDC-2F-CHILLERBMS-01/02 + MC Standards ME/PL
P-0733ELMultifunction Power Meter (Feeder)MPM-AHU-2F2nd Level AHU MCCMultifunction power meter — voltage / current / kW / kWh / power factorHLIMultifunction Power MeterBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0734ELMultifunction Power Meter (Feeder)MPM-AHU-2F2nd Level AHU MCCNetwork drop (Modbus TCP — Power Meter)NetworkMultifunction Power MeterBMS ContractorDDC-2F-BOHBMS-01/02 + MC Standards ME/PL
P-0735ELMultifunction Power Meter (Feeder)MPM-AHU-GFGround Floor AHU MCCMultifunction power meter — voltage / current / kW / kWh / power factorHLIMultifunction Power MeterBMS ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0736ELMultifunction Power Meter (Feeder)MPM-AHU-GFGround Floor AHU MCCNetwork drop (Modbus TCP — Power Meter)NetworkMultifunction Power MeterBMS ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0737ELMultifunction Power Meter (Feeder)MPM-LIGHT-ALower Ground Lighting Panel AMultifunction power meter — voltage / current / kW / kWh / power factorHLIMultifunction Power MeterBMS ContractorDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0738ELMultifunction Power Meter (Feeder)MPM-LIGHT-ALower Ground Lighting Panel ANetwork drop (Modbus TCP — Power Meter)NetworkMultifunction Power MeterBMS ContractorDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0739ELMultifunction Power Meter (Feeder)MPM-LIGHT-BLower Ground Lighting Panel BMultifunction power meter — voltage / current / kW / kWh / power factorHLIMultifunction Power MeterBMS ContractorDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0740ELMultifunction Power Meter (Feeder)MPM-LIGHT-BLower Ground Lighting Panel BNetwork drop (Modbus TCP — Power Meter)NetworkMultifunction Power MeterBMS ContractorDDC-LG-PLANTBMS-01/02 + MC Standards ME/PL
P-0741FDASFACP GatewayFACP-GWGround Floor Fire Command CenterFire Alarm Common AlarmHLIFACP BACnet GatewayEE ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0742FDASFACP GatewayFACP-GWGround Floor Fire Command CenterFire Alarm Common TroubleHLIFACP BACnet GatewayEE ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0743FDASFACP GatewayFACP-GWGround Floor Fire Command CenterFire Alarm System StatusHLIFACP BACnet GatewayEE ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL
P-0744FDASFACP GatewayFACP-GWGround Floor Fire Command CenterNetwork drop (BACnet/IP — FACP Gateway)NetworkFACP BACnet GatewayEE ContractorDDC-GF-BOHBMS-01/02 + MC Standards ME/PL