| Panel | Location | System Scope | Equipment Count | Physical I/O | HLI Subpoints | Network Drops | Total I/O | DDC Controllers | Network Gateway | Total Controllers | Power (W) | Enclosure |
| BMS-PNL-AHU-2F | 2F | Air Handling — Pre-cooled | 1 | 12 | 4 | 0 | 16 | 1 | 0 | 1 | 25 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| BMS-PNL-AHU-RD | RD | Air Handling — Pre-cooled (Roofdeck), Air Handling — Roofdeck AHU | 2 | 44 | 2 | 0 | 46 | 2 | 0 | 2 | 50 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| BMS-PNL-BOHAHU-2F | 2F | Air Handling — Basement / Podium BOH | 1 | 120 | 20 | 0 | 140 | 3 | 0 | 3 | 75 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| BMS-PNL-BOILER-LG | LG | Boiler / Laundry | 1 | 22 | 0 | 0 | 22 | 1 | 0 | 1 | 25 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| BMS-PNL-CASINO-2F | 2F | Casino MVAC — Dedicated Outdoor Air, Casino MVAC — Smoke Sanitizer | 2 | 30 | 4 | 0 | 34 | 1 | 0 | 1 | 25 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| BMS-PNL-CHWPLANT-2F | 2F | Chilled Water Plant | 4 | 121 | 0 | 0 | 121 | 4 | 0 | 4 | 100 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| BMS-PNL-CT-RD | RD | Heat Rejection — Cooling Tower | 1 | 35 | 1 | 0 | 36 | 1 | 0 | 1 | 25 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| BMS-PNL-PLUMBING-LG | LG | Plumbing — Sanitary Hot Water | 4 | 18 | 9 | 0 | 27 | 1 | 0 | 1 | 25 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| BMS-PNL-PLUMBING-RD | RD | Plumbing — Sanitary Hot Water | 3 | 12 | 9 | 0 | 21 | 1 | 0 | 1 | 25 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| BMS-PNL-VENT-2F | 2F | General Ventilation | 1 | 39 | 0 | 0 | 39 | 1 | 0 | 1 | 25 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| BMS-PNL-VENT-3F | 3F | General Ventilation | 1 | 81 | 0 | 0 | 81 | 3 | 0 | 3 | 75 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| BMS-PNL-VENT-GF | GF | General Ventilation | 1 | 27 | 0 | 0 | 27 | 1 | 0 | 1 | 25 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| BMS-PNL-VENT-RD | RD | General Ventilation | 1 | 9 | 0 | 0 | 9 | 1 | 0 | 1 | 25 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |