Summary

A4 — Panel Schedule Summary
Total panels13
Total physical I/O570
Total HLI subpoints49
Total network drops0
Total I/O points619
Estimated total controllers21
Estimated total power (W)525

Panel Schedule

PanelLocationSystem ScopeEquipment CountPhysical I/OHLI SubpointsNetwork DropsTotal I/ODDC ControllersNetwork GatewayTotal ControllersPower (W)Enclosure
BMS-PNL-AHU-2F2FAir Handling — Pre-cooled112401610125Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
BMS-PNL-AHU-RDRDAir Handling — Pre-cooled (Roofdeck), Air Handling — Roofdeck AHU244204620250Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
BMS-PNL-BOHAHU-2F2FAir Handling — Basement / Podium BOH112020014030375Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
BMS-PNL-BOILER-LGLGBoiler / Laundry122002210125Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
BMS-PNL-CASINO-2F2FCasino MVAC — Dedicated Outdoor Air, Casino MVAC — Smoke Sanitizer230403410125Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
BMS-PNL-CHWPLANT-2F2FChilled Water Plant412100121404100Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
BMS-PNL-CT-RDRDHeat Rejection — Cooling Tower135103610125Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
BMS-PNL-PLUMBING-LGLGPlumbing — Sanitary Hot Water418902710125Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
BMS-PNL-PLUMBING-RDRDPlumbing — Sanitary Hot Water312902110125Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
BMS-PNL-VENT-2F2FGeneral Ventilation139003910125Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
BMS-PNL-VENT-3F3FGeneral Ventilation181008130375Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
BMS-PNL-VENT-GFGFGeneral Ventilation127002710125Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
BMS-PNL-VENT-RDRDGeneral Ventilation1900910125Wall-mount IP54 metal cabinet, sized per controller count + 30% spare

Equipment per Panel

PanelEquipment Instance
BMS-PNL-AHU-2FPAHU-0.1
BMS-PNL-AHU-RDAHU-RD (with CHW mod valve)
BMS-PNL-AHU-RDPAHU-RD (×2)
BMS-PNL-BOHAHU-2FAHU-2/B.2/B.3/PP/CL/FRE/FRD
BMS-PNL-BOILER-LGSB-1 & SB-2
BMS-PNL-CASINO-2FDOAS (Casino) — 2 units
BMS-PNL-CASINO-2FSanitizer for AHU-2M.1/2M.2
BMS-PNL-CHWPLANT-2FCDWP-1 to CDWP-3
BMS-PNL-CHWPLANT-2FCH-1 to CH-3
BMS-PNL-CHWPLANT-2FCHW Supply & Return Main Header
BMS-PNL-CHWPLANT-2FCHWP-1 to CHWP-3
BMS-PNL-CT-RDCT-1 to CT-3
BMS-PNL-PLUMBING-LGHP-LZ (×3)
BMS-PNL-PLUMBING-LGHW Supply & Return Header (LG)
BMS-PNL-PLUMBING-LGHWT-LZ (×3)
BMS-PNL-PLUMBING-LGRP-LZ (×3)
BMS-PNL-PLUMBING-RDHP-HZ (×3)
BMS-PNL-PLUMBING-RDHWT-HZ (×3)
BMS-PNL-PLUMBING-RDRP-HZ (×3)
BMS-PNL-VENT-2FTEF-2.1/2.3/2B.3 + EF-2B.1/2B.2/GS.1&GS.2 + EF-2.1 to 2.4 + EF-CHRx2
BMS-PNL-VENT-3FTEF-3Ax2/3B/3Cx2/3Dx20 + others
BMS-PNL-VENT-GFTEF-1.1 to 1.4 + EF-1.2A/LPG.1/1MR.1/1STO.1/MRF.1
BMS-PNL-VENT-RDEF-RD.1/RD.2, EF-1