Summary

A3 — Cable Schedule Summary
Total field cable runs29
Total field cable length (m)473
Total trunk cable length (m)400
Total power feed length (m)234
GRAND TOTAL cable length (m)1107
By cable type (m)
4C × 1.5 mm² FRLS (equipment aux contacts — status / H-O-A / trip)305
4C × 1.5 mm² shielded FRLS (BMS sensor signal)168

Field Cables

IDFromToEquipment ClassSystemLocationCable TypeConductors RequiredConductors SpecifiedLength (m)I/O Points CarriedNotes
C0001BMS-PNL-BOHAHU-2FAHU-2/B.2/B.3/PP/CL/FRE/FRD (BMS Contractor)AHU (Chilled-Water-Served)Air Handling — Basement / Podium BOH2F4C × 1.5 mm² shielded FRLS (BMS sensor signal)12612612100100 I/O points carried, 126C cable; length 12 m (typical_range:plant_room_same_room)
C0002BMS-PNL-BOHAHU-2FAHU-2/B.2/B.3/PP/CL/FRE/FRD (ME Contractor)AHU (Chilled-Water-Served)Air Handling — Basement / Podium BOH2F4C × 1.5 mm² FRLS (equipment aux contacts — status / H-O-A / trip)2324122020 I/O points carried, 24C cable; length 12 m (typical_range:plant_room_same_room)
C0003BMS-PNL-AHU-RDAHU-RD (with CHW mod valve) (BMS Contractor)AHU (Chilled-Water-Served)Air Handling — Roofdeck AHURD4C × 1.5 mm² shielded FRLS (BMS sensor signal)2525162020 I/O points carried, 25C cable; length 16 m (measured)
C0004BMS-PNL-AHU-RDAHU-RD (with CHW mod valve) (ME Contractor)AHU (Chilled-Water-Served)Air Handling — Roofdeck AHURD4C × 1.5 mm² FRLS (equipment aux contacts — status / H-O-A / trip)1416141212 I/O points carried, 16C cable; length 14 m (measured)
C0005BMS-PNL-CHWPLANT-2FCDWP-1 to CDWP-3 (ME Contractor)Condenser Water PumpChilled Water Plant2F4C × 1.5 mm² FRLS (equipment aux contacts — status / H-O-A / trip)1316121212 I/O points carried, 16C cable; length 12 m (typical_range:plant_room_same_room)
C0006BMS-PNL-CHWPLANT-2FCH-1 to CH-3 (BMS Contractor)Chiller (Package Water-Cooled)Chilled Water Plant2F4C × 1.5 mm² shielded FRLS (BMS sensor signal)3434142727 I/O points carried, 34C cable; length 14 m (measured)
C0007BMS-PNL-CHWPLANT-2FCH-1 to CH-3 (ME Contractor)Chiller (Package Water-Cooled)Chilled Water Plant2F4C × 1.5 mm² FRLS (equipment aux contacts — status / H-O-A / trip)6262125454 I/O points carried, 62C cable; length 12 m (measured)
C0008BMS-PNL-CHWPLANT-2FCHW Supply & Return Main Header (BMS Contractor)CHW Supply Main HeaderChilled Water Plant2F4C × 1.5 mm² shielded FRLS (BMS sensor signal)912877 I/O points carried, 12C cable; length 8 m (measured)
C0009BMS-PNL-CHWPLANT-2FCHWP-1 to CHWP-3 (ME Contractor)Primary CHW PumpChilled Water Plant2F4C × 1.5 mm² FRLS (equipment aux contacts — status / H-O-A / trip)2424102121 I/O points carried, 24C cable; length 10 m (measured)
C0010BMS-PNL-CT-RDCT-1 to CT-3 (BMS Contractor)Cooling TowerHeat Rejection — Cooling TowerRD4C × 1.5 mm² shielded FRLS (BMS sensor signal)3030182424 I/O points carried, 30C cable; length 18 m (measured)
C0011BMS-PNL-CT-RDCT-1 to CT-3 (ME Contractor)Cooling TowerHeat Rejection — Cooling TowerRD4C × 1.5 mm² FRLS (equipment aux contacts — status / H-O-A / trip)1212161111 I/O points carried, 12C cable; length 16 m (measured)
C0012BMS-PNL-CASINO-2FDOAS (Casino) — 2 units (BMS Contractor)DOAS UnitCasino MVAC — Dedicated Outdoor Air2F4C × 1.5 mm² shielded FRLS (BMS sensor signal)2828262222 I/O points carried, 28C cable; length 26 m (measured)
C0013BMS-PNL-CASINO-2FDOAS (Casino) — 2 units (ME Contractor)DOAS UnitCasino MVAC — Dedicated Outdoor Air2F4C × 1.5 mm² FRLS (equipment aux contacts — status / H-O-A / trip)562444 I/O points carried, 6C cable; length 24 m (measured)
C0014BMS-PNL-VENT-RDEF-RD.1/RD.2, EF-1 (ME Contractor)Exhaust Fan (General)General VentilationRD4C × 1.5 mm² FRLS (equipment aux contacts — status / H-O-A / trip)10121499 I/O points carried, 12C cable; length 14 m (measured)
C0015BMS-PNL-PLUMBING-LGHW Supply & Return Header (LG) (BMS Contractor)CHW Supply Main HeaderPlumbing — Sanitary Hot WaterLG4C × 1.5 mm² shielded FRLS (BMS sensor signal)881066 I/O points carried, 8C cable; length 10 m (measured)
C0016BMS-PNL-PLUMBING-RDHWT-HZ (×3) (BMS Contractor)Calorifier (Hot Water Storage Tank)Plumbing — Sanitary Hot WaterRD4C × 1.5 mm² shielded FRLS (BMS sensor signal)441233 I/O points carried, 4C cable; length 12 m (measured)
C0017BMS-PNL-PLUMBING-LGHWT-LZ (×3) (BMS Contractor)Calorifier (Hot Water Storage Tank)Plumbing — Sanitary Hot WaterLG4C × 1.5 mm² shielded FRLS (BMS sensor signal)441433 I/O points carried, 4C cable; length 14 m (measured)
C0018BMS-PNL-AHU-2FPAHU-0.1 (BMS Contractor)Precooled Air Handling UnitAir Handling — Pre-cooled2F4C × 1.5 mm² shielded FRLS (BMS sensor signal)10121288 I/O points carried, 12C cable; length 12 m (typical_range:plant_room_same_room)
C0019BMS-PNL-AHU-2FPAHU-0.1 (ME Contractor)Precooled Air Handling UnitAir Handling — Pre-cooled2F4C × 1.5 mm² FRLS (equipment aux contacts — status / H-O-A / trip)561244 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
C0020BMS-PNL-AHU-RDPAHU-RD (×2) (BMS Contractor)Precooled Air Handling UnitAir Handling — Pre-cooled (Roofdeck)RD4C × 1.5 mm² shielded FRLS (BMS sensor signal)561444 I/O points carried, 6C cable; length 14 m (measured)
C0021BMS-PNL-AHU-RDPAHU-RD (×2) (ME Contractor)Precooled Air Handling UnitAir Handling — Pre-cooled (Roofdeck)RD4C × 1.5 mm² FRLS (equipment aux contacts — status / H-O-A / trip)9121288 I/O points carried, 12C cable; length 12 m (measured)
C0022BMS-PNL-PLUMBING-RDRP-HZ (×3) (ME Contractor)Recirculating PumpPlumbing — Sanitary Hot WaterRD4C × 1.5 mm² FRLS (equipment aux contacts — status / H-O-A / trip)10121299 I/O points carried, 12C cable; length 12 m (typical_range:plant_room_same_room)
C0023BMS-PNL-PLUMBING-LGRP-LZ (×3) (ME Contractor)Recirculating PumpPlumbing — Sanitary Hot WaterLG4C × 1.5 mm² FRLS (equipment aux contacts — status / H-O-A / trip)10121299 I/O points carried, 12C cable; length 12 m (typical_range:plant_room_same_room)
C0024BMS-PNL-BOILER-LGSB-1 & SB-2 (BMS Contractor)Steam BoilerBoiler / LaundryLG4C × 1.5 mm² shielded FRLS (BMS sensor signal)881266 I/O points carried, 8C cable; length 12 m (measured)
C0025BMS-PNL-BOILER-LGSB-1 & SB-2 (ME Contractor)Steam BoilerBoiler / LaundryLG4C × 1.5 mm² FRLS (equipment aux contacts — status / H-O-A / trip)1820101616 I/O points carried, 20C cable; length 10 m (measured)
C0026BMS-PNL-CASINO-2FSanitizer for AHU-2M.1/2M.2 (Equipment Supplier)Ozone Generator (UV-light or Corona)Casino MVAC — Smoke Sanitizer2F4C × 1.5 mm² FRLS (equipment aux contacts — status / H-O-A / trip)562844 I/O points carried, 6C cable; length 28 m (typical_range:casino_floor_field)
C0027BMS-PNL-VENT-GFTEF-1.1 to 1.4 + EF-1.2A/LPG.1/1MR.1/1STO.1/MRF.1 (ME Contractor)Exhaust Fan (General)General VentilationGF4C × 1.5 mm² FRLS (equipment aux contacts — status / H-O-A / trip)3131352727 I/O points carried, 31C cable; length 35 m (typical_range:guestroom_corridor)
C0028BMS-PNL-VENT-2FTEF-2.1/2.3/2B.3 + EF-2B.1/2B.2/GS.1&GS.2 + EF-2.1 to 2.4 + EF-CHRx2 (ME Contractor)Exhaust Fan (General)General Ventilation2F4C × 1.5 mm² FRLS (equipment aux contacts — status / H-O-A / trip)4545353939 I/O points carried, 45C cable; length 35 m (typical_range:guestroom_corridor)
C0029BMS-PNL-VENT-3FTEF-3Ax2/3B/3Cx2/3Dx20 + others (ME Contractor)Exhaust Fan (General)General Ventilation3F4C × 1.5 mm² FRLS (equipment aux contacts — status / H-O-A / trip)9393358181 I/O points carried, 93C cable; length 35 m (typical_range:guestroom_corridor)

Trunks

IDFromToCable TypeLength (m)Notes
T0030BMS Server Room (head-end)All BMS panels at 2nd FloorCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80Network trunk for 2nd Floor — fiber to floor switch + Cat6 distribution to floor's BMS panels
T0031BMS Server Room (head-end)BMS panel controllers (per topology id mstp_main_backbone)BACnet MS/TP shielded twisted-pair trunk, 1pr × 22 AWG low-cap320Daisy-chain across the 13 BMS field panels. Path: Boiler-LG → Plumbing-LG → CHWPlant-2F → BOH-AHU-2F → AHU-2F → Casino-2F → Vent-GF → Vent-2F → Vent-3F → Vent-RD → AHU-RD → CT-RD → Plumbing-RD. Routed via riser shaft per EE-24 + horizontal corridor tray on each floor (per ECE auxiliary plans).

Panel Power Feeds

IDFromToCable TypeLength (m)Notes
P0032Local panelboard / EE-supplied feederBMS-PNL-AHU-2F — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:bms_panel_power_feed)
P0033Local panelboard / EE-supplied feederBMS-PNL-AHU-RD — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:bms_panel_power_feed)
P0034Local panelboard / EE-supplied feederBMS-PNL-BOHAHU-2F — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:bms_panel_power_feed)
P0035Local panelboard / EE-supplied feederBMS-PNL-BOILER-LG — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:bms_panel_power_feed)
P0036Local panelboard / EE-supplied feederBMS-PNL-CASINO-2F — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:bms_panel_power_feed)
P0037Local panelboard / EE-supplied feederBMS-PNL-CHWPLANT-2F — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:bms_panel_power_feed)
P0038Local panelboard / EE-supplied feederBMS-PNL-CT-RD — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:bms_panel_power_feed)
P0039Local panelboard / EE-supplied feederBMS-PNL-PLUMBING-LG — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:bms_panel_power_feed)
P0040Local panelboard / EE-supplied feederBMS-PNL-PLUMBING-RD — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:bms_panel_power_feed)
P0041Local panelboard / EE-supplied feederBMS-PNL-VENT-2F — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:bms_panel_power_feed)
P0042Local panelboard / EE-supplied feederBMS-PNL-VENT-3F — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:bms_panel_power_feed)
P0043Local panelboard / EE-supplied feederBMS-PNL-VENT-GF — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:bms_panel_power_feed)
P0044Local panelboard / EE-supplied feederBMS-PNL-VENT-RD — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:bms_panel_power_feed)