Summary

A3 — Cable Schedule, Audit View
ProjectKingsford Hotel Bacolod — BMS
Canonical sourceA3-cable-schedule.yaml
How to record correctionsEdit the canonical YAML directly — add a verification: block to the affected row(s)
Totals
Total cables209
Total length (m)5,033
Field cables194
Trunk cables7
Panel power feeds8
Verification status
StatusCount% of total
verified00%
needs_correction00%
uncertain00%
unverified209100%
⚠ Known weak points
Cable lengths are estimates based on assumption A-001 (30 m average panel-to-device run, 80 m trunk per floor). Field-verified lengths typically vary by ±20% per cable. THIS IS THE SYSTEM'S WEAKEST AUTO-GENERATED QUANTITY — please verify before issuing the BOQ to the customer.
How corrections flow
1. Open A3-cable-schedule.yaml in any text editor.
2. Find the affected row by ID (column A in the Detail sheet).
3. Add a verification: block — see the 'Verification schema' sheet for the template.
4. Re-run: python3 _playbook/tools/generate-deliverables.py <project>
5. Corrections flow through B4 manhours, BOQ material costs, and final deliverables automatically.

By Panel

PanelCable countTotal length (m)
BMS-PNL-RD-MECH52780
BMS-PNL-3F26572
BMS-PNL-GF20482
BMS-PNL-2F-CASINO20440
BMS-PNL-B119418
BMS-PNL-LG-CHILLER33396
BMS-PNL-RD-CT11165
BMS-PNL-LG-PLUMB13156
TOTAL (field cables)1943409

By Floor

FloorCable countTotal length (m)
Roofdeck63945
2nd Floor53836
3rd Floor26572
Ground19470
Basement19418
Lower Ground13156
Electrical112
TOTAL1943409

By Cable Type

Cable typeCountTotal length (m)
Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)1943409

Detail (cables)

IDFromToCable typeLength (m)StatusCorrected (m)Verified byDateDrawing refNotes
C0001BMS-PNL-2F-CASINOAHU-2F-1 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0002BMS-PNL-2F-CASINOAHU-2F-1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0003BMS-PNL-2F-CASINOAHU-2F-1 (ME Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0004BMS-PNL-2F-CASINOAHU-2M.1 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0005BMS-PNL-2F-CASINOAHU-2M.1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0006BMS-PNL-2F-CASINOAHU-2M.1 (ME Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0007BMS-PNL-2F-CASINOAHU-2M.2 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0008BMS-PNL-2F-CASINOAHU-2M.2 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0009BMS-PNL-2F-CASINOAHU-2M.2 (ME Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0010BMS-PNL-B1AHU-B1-1 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0011BMS-PNL-B1AHU-B1-1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0012BMS-PNL-B1AHU-B1-1 (ME Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0013BMS-PNL-GFAHU-GF-1 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0014BMS-PNL-GFAHU-GF-1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0015BMS-PNL-GFAHU-GF-1 (ME Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0016BMS-PNL-GFAHU-GFM-1 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0017BMS-PNL-GFAHU-GFM-1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0018BMS-PNL-GFAHU-GFM-1 (ME Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0019BMS-PNL-LG-CHILLERCH-1 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0020BMS-PNL-LG-CHILLERCH-1 (ME Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0021BMS-PNL-LG-CHILLERCH-2 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0022BMS-PNL-LG-CHILLERCH-2 (ME Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0023BMS-PNL-LG-CHILLERCH-3 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0024BMS-PNL-LG-CHILLERCH-3 (ME Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0025BMS-PNL-LG-CHILLERCHW-BYPASS (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0026BMS-PNL-LG-CHILLERCHW-BYPASS (ME Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0027BMS-PNL-LG-CHILLERCHW-HDR-R (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0028BMS-PNL-LG-CHILLERCHW-HDR-S (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0029BMS-PNL-RD-CTCT-1 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0030BMS-PNL-RD-CTCT-1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0031BMS-PNL-RD-CTCT-1 (ME Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0032BMS-PNL-RD-CTCT-2 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0033BMS-PNL-RD-CTCT-2 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0034BMS-PNL-RD-CTCT-2 (ME Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0035BMS-PNL-RD-CTCT-3 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0036BMS-PNL-RD-CTCT-3 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0037BMS-PNL-RD-CTCT-3 (ME Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0038BMS-PNL-RD-CTCT-COMMON (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0039BMS-PNL-RD-CTCT-COMMON (ME Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0040BMS-PNL-LG-CHILLERCWP-1 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0041BMS-PNL-LG-CHILLERCWP-1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0042BMS-PNL-LG-CHILLERCWP-2 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0043BMS-PNL-LG-CHILLERCWP-2 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0044BMS-PNL-LG-CHILLERCWP-3 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0045BMS-PNL-LG-CHILLERCWP-3 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0046BMS-PNL-2F-CASINODOAS-2F-CASINO (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0047BMS-PNL-2F-CASINODOAS-2F-CASINO (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0048BMS-PNL-2F-CASINODOAS-2F-CASINO (ME Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0049BMS-PNL-RD-MECHDOAS-RD1 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0050BMS-PNL-RD-MECHDOAS-RD1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0051BMS-PNL-RD-MECHDOAS-RD1 (ME Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0052BMS-PNL-RD-MECHDOAS-RD2 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0053BMS-PNL-RD-MECHDOAS-RD2 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0054BMS-PNL-RD-MECHDOAS-RD2 (ME Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0055BMS-PNL-RD-MECHEF-1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0056BMS-PNL-GFEF-1.2A (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0057BMS-PNL-GFEF-1MR.1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0058BMS-PNL-GFEF-1STO.1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0059BMS-PNL-GFEF-LPG.1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0060BMS-PNL-GFEF-MRF.1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0061BMS-PNL-RD-MECHEF-RD.1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0062BMS-PNL-RD-MECHEF-RD.2 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0063BMS-PNL-RD-MECHHP-HZ-1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0064BMS-PNL-RD-MECHHP-HZ-2 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0065BMS-PNL-RD-MECHHP-HZ-3 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0066BMS-PNL-LG-PLUMBHP-LZ-1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0067BMS-PNL-LG-PLUMBHP-LZ-2 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0068BMS-PNL-LG-PLUMBHP-LZ-3 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0069BMS-PNL-LG-PLUMBHW-HEADERS (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0070BMS-PNL-RD-MECHHWT-HZ-1 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0071BMS-PNL-RD-MECHHWT-HZ-2 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0072BMS-PNL-RD-MECHHWT-HZ-3 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0073BMS-PNL-LG-PLUMBHWT-LZ-1 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0074BMS-PNL-LG-PLUMBHWT-LZ-2 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0075BMS-PNL-LG-PLUMBHWT-LZ-3 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0076BMS-PNL-2F-CASINOION-2F-1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0077BMS-PNL-2F-CASINOION-2F-2 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0078BMS-PNL-RD-MECHPAHU-01 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0079BMS-PNL-RD-MECHPAHU-01 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0080BMS-PNL-RD-MECHPAHU-01 (ME Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0081BMS-PNL-RD-MECHPAHU-02 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0082BMS-PNL-RD-MECHPAHU-02 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0083BMS-PNL-RD-MECHPAHU-02 (ME Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0084BMS-PNL-RD-MECHPAHU-03 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0085BMS-PNL-RD-MECHPAHU-03 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0086BMS-PNL-RD-MECHPAHU-03 (ME Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0087BMS-PNL-RD-MECHPAHU-04 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0088BMS-PNL-RD-MECHPAHU-04 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0089BMS-PNL-RD-MECHPAHU-04 (ME Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0090BMS-PNL-RD-MECHPAHU-05 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0091BMS-PNL-RD-MECHPAHU-05 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0092BMS-PNL-RD-MECHPAHU-05 (ME Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0093BMS-PNL-RD-MECHPAHU-06 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0094BMS-PNL-RD-MECHPAHU-06 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0095BMS-PNL-RD-MECHPAHU-06 (ME Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0096BMS-PNL-RD-MECHPAHU-07 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0097BMS-PNL-RD-MECHPAHU-07 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0098BMS-PNL-RD-MECHPAHU-07 (ME Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0099BMS-PNL-LG-CHILLERPCHWP-1 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0100BMS-PNL-LG-CHILLERPCHWP-1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0101BMS-PNL-LG-CHILLERPCHWP-2 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0102BMS-PNL-LG-CHILLERPCHWP-2 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0103BMS-PNL-LG-CHILLERPCHWP-3 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0104BMS-PNL-LG-CHILLERPCHWP-3 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0105BMS-PNL-RD-MECHRP-HZ-1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0106BMS-PNL-RD-MECHRP-HZ-2 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0107BMS-PNL-RD-MECHRP-HZ-3 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0108BMS-PNL-LG-PLUMBRP-LZ-1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0109BMS-PNL-LG-PLUMBRP-LZ-2 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0110BMS-PNL-LG-PLUMBRP-LZ-3 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0111BMS-PNL-LG-PLUMBSB-1 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0112BMS-PNL-LG-PLUMBSB-2 (BMS Contractor)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0113BMS-PNL-GFTEF-1.1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0114BMS-PNL-GFTEF-1.2 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0115BMS-PNL-GFTEF-1.3 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0116BMS-PNL-GFTEF-1.4 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0117BMS-PNL-2F-CASINOTEF-2.1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0118BMS-PNL-2F-CASINOTEF-2.3 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0119BMS-PNL-2F-CASINOTEF-2B.3 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0120BMS-PNL-3FTEF-3A.1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0121BMS-PNL-3FTEF-3A.2 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0122BMS-PNL-3FTEF-3B (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0123BMS-PNL-3FTEF-3C.1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0124BMS-PNL-3FTEF-3C.2 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0125BMS-PNL-3FTEF-3D.1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0126BMS-PNL-3FTEF-3D.10 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0127BMS-PNL-3FTEF-3D.11 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0128BMS-PNL-3FTEF-3D.12 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0129BMS-PNL-3FTEF-3D.13 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0130BMS-PNL-3FTEF-3D.14 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0131BMS-PNL-3FTEF-3D.15 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0132BMS-PNL-3FTEF-3D.16 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0133BMS-PNL-3FTEF-3D.17 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0134BMS-PNL-3FTEF-3D.18 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0135BMS-PNL-3FTEF-3D.19 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0136BMS-PNL-3FTEF-3D.2 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0137BMS-PNL-3FTEF-3D.20 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0138BMS-PNL-3FTEF-3D.3 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0139BMS-PNL-3FTEF-3D.4 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0140BMS-PNL-3FTEF-3D.5 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0141BMS-PNL-3FTEF-3D.6 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0142BMS-PNL-3FTEF-3D.7 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0143BMS-PNL-3FTEF-3D.8 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0144BMS-PNL-3FTEF-3D.9 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0145BMS-PNL-B1TEF-B.1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0146BMS-PNL-B1TEF-B.10 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0147BMS-PNL-B1TEF-B.11 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0148BMS-PNL-B1TEF-B.12 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0149BMS-PNL-B1TEF-B.13 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0150BMS-PNL-B1TEF-B.14 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0151BMS-PNL-B1TEF-B.15 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0152BMS-PNL-B1TEF-B.16 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0153BMS-PNL-B1TEF-B.2 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0154BMS-PNL-B1TEF-B.3 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0155BMS-PNL-B1TEF-B.4 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0156BMS-PNL-B1TEF-B.5 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0157BMS-PNL-B1TEF-B.6 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0158BMS-PNL-B1TEF-B.7 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0159BMS-PNL-B1TEF-B.8 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0160BMS-PNL-B1TEF-B.9 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0161BMS-PNL-GFTEF-GS.1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)35unverified
C0162BMS-PNL-GFTEF-GS.2 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)35unverified
C0163BMS-PNL-RD-MECHTEF-RD.1 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0164BMS-PNL-RD-MECHTEF-RD.2 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0165BMS-PNL-RD-MECHTEF-RD.3 (Equipment Supplier)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0166BMS-PNL-LG-CHILLERCH-1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0167BMS-PNL-LG-CHILLERCH-2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0168BMS-PNL-LG-CHILLERCH-3 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0169BMS-PNL-LG-CHILLERBTU-1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0170BMS-PNL-LG-CHILLERBTU-2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0171BMS-PNL-LG-CHILLERBTU-3 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0172BMS-PNL-LG-CHILLERBTU-4 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0173BMS-PNL-LG-CHILLERBTU-5 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0174BMS-PNL-RD-MECHDOAS-RD1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0175BMS-PNL-RD-MECHDOAS-RD2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0176BMS-PNL-2F-CASINODOAS-2F-CASINO (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0177BMS-PNL-RD-MECHPAHU-01 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0178BMS-PNL-RD-MECHPAHU-02 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0179BMS-PNL-RD-MECHPAHU-03 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0180BMS-PNL-RD-MECHPAHU-04 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0181BMS-PNL-RD-MECHPAHU-05 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0182BMS-PNL-RD-MECHPAHU-06 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0183BMS-PNL-RD-MECHPAHU-07 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
C0184BMS-PNL-GFPM-MAIN (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0185BMS-PNL-LG-CHILLERPM-CHILLER-1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0186BMS-PNL-LG-CHILLERPM-CHILLER-2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0187BMS-PNL-LG-CHILLERPM-CHILLER-3 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0188BMS-PNL-2F-CASINOPM-CASINO-FB (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0189BMS-PNL-2F-CASINOPM-KITCHEN-2F (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0190BMS-PNL-GFPM-LOBBY-GF (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)35unverified
C0191BMS-PNL-GFPM-ELEVATOR (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)35unverified
C0192BMS-PNL-3FPM-LIGHTING-GUEST (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)22unverified
C0193BMS-PNL-LG-PLUMBPM-LAUNDRY-LG (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0194BMS-PNL-RD-MECHPM-ROOFDECK-MECH (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)15unverified
T0195BMS Server Room (head-end)All BMS panels at 2nd FloorCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80unverified
T0196BMS Server Room (head-end)All BMS panels at 3rd FloorCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80unverified
T0197BMS Server Room (head-end)All BMS panels at BasementCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80unverified
T0198BMS Server Room (head-end)All BMS panels at GroundCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80unverified
T0199BMS Server Room (head-end)All BMS panels at Lower GroundCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80unverified
T0200BMS Server Room (head-end)BMS panel controllers (per topology id ?)BACnet MS/TP shielded twisted-pair trunk, 1pr × 22 AWG low-cap380unverified
T0201BMS Server Room (head-end)BMS panel controllers (per topology id ?)BACnet MS/TP shielded twisted-pair trunk, 1pr × 22 AWG low-cap700unverified
P0202Local panelboard / EE-supplied feederBMS-PNL-2F-CASINO — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18unverified
P0203Local panelboard / EE-supplied feederBMS-PNL-3F — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18unverified
P0204Local panelboard / EE-supplied feederBMS-PNL-B1 — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18unverified
P0205Local panelboard / EE-supplied feederBMS-PNL-GF — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18unverified
P0206Local panelboard / EE-supplied feederBMS-PNL-LG-CHILLER — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18unverified
P0207Local panelboard / EE-supplied feederBMS-PNL-LG-PLUMB — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18unverified
P0208Local panelboard / EE-supplied feederBMS-PNL-RD-CT — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18unverified
P0209Local panelboard / EE-supplied feederBMS-PNL-RD-MECH — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18unverified

Verification schema

How to record verification / corrections in A3-cable-schedule.yaml
Find the affected row in the YAML by ID (Detail sheet column A) and add a verification: block:
- id: C0001
from: PNL-CH-PLANT-GND
to: CH-1 (BMS Contractor)
cable_type: 4C × 1.5 mm² shielded FRLS
length_m: 30
verification: # ADDED by team
status: needs_correction # unverified | verified | needs_correction | uncertain
corrected_length_m: 42 # team's measured / confirmed value
verified_by: J. Cruz
verified_date: 2026-05-10
drawing_ref: "EE-09 grid B-2"
notes: ""
After saving, re-run: python3 _playbook/tools/generate-deliverables.py <project>
Corrections propagate to B4 manhours, BOQ, and final deliverables automatically.
Recommended verification methods (priority order):
1. Site walkthrough with measurement (most accurate; for cable lengths, after structural completion).
2. Properly-scaled architectural drawings.
3. Mechanical contractor's tray layout combined with BMS panel locations.
4. A-001 default with ±20% contingency in BOQ — last resort.