Summary

A2 — Equipment Takeoff, Audit View
ProjectKingsford Hotel Bacolod — BMS
Canonical sourceA2-equipment-takeoff.yaml
How to record correctionsEdit the canonical YAML directly — add a verification: block to the affected row(s)
Totals
Total equipment instances132
Equipment classes23
Locations17
Verification status
StatusCount% of total
verified00%
needs_correction00%
uncertain00%
unverified132100%
⚠ Known weak points
Verify quantities and locations against mechanical / electrical drawings. The 'Make/Model' field is a generic class default — supplier RFQ refines.
How corrections flow
Edit A2-equipment-takeoff.yaml — add a verification: block to the affected row when location or count is confirmed/corrected.

By Class

Equipment classCount
Exhaust Fan (Toilet)53
Multifunction Power Meter (Feeder)10
Exhaust Fan (General)8
Precooled Air Handling Unit7
Heat Pump6
Calorifier (Hot Water Storage Tank)6
Recirculating Pump6
BTU Meter5
AHU (Chilled-Water-Served)4
Chiller (Package Water-Cooled)3
Cooling Tower3
Condenser Water Pump3
DOAS Unit3
Primary CHW Pump3
AHU (Modulating CHW-served)2
Ozone Generator (UV-light or Corona)2
Steam Boiler2
CHW Bypass Header1
CHW Return Main Header1
CHW Supply Main Header1
Cooling Tower (Common)1
Hot Water Header Set1
Multifunction Power Meter (Main)1
TOTAL132

By Location

LocationCount
3rd Floor Amenity26
2nd Level Mechanical Room20
Basement 116
Roof Deck Mechanical14
Lower Ground HW Plant10
Ground Floor Lobby9
Roof Deck HW Plant9
Roof Deck6
2nd Floor BOH5
Ground Floor4
2nd Floor Casino MVAC Room3
2nd Floor Casino3
Lower Ground Laundry3
Basement 1 BOH1
Ground Floor BOH1
Ground Floor Mezzanine BOH1
Main Switchgear Room1

Detail

IDClassLocationPanelPrimary C/OStatusVerified byDateDrawing refNotes
AHU-2F-1AHU (Chilled-Water-Served)2nd Floor BOHBMS-PNL-2F-CASINOBMS Contractorunverified
AHU-2M.1AHU (Modulating CHW-served)2nd Floor Casino MVAC RoomBMS-PNL-2F-CASINOBMS Contractorunverified
AHU-2M.2AHU (Modulating CHW-served)2nd Floor Casino MVAC RoomBMS-PNL-2F-CASINOBMS Contractorunverified
AHU-B1-1AHU (Chilled-Water-Served)Basement 1 BOHBMS-PNL-B1BMS Contractorunverified
AHU-GF-1AHU (Chilled-Water-Served)Ground Floor BOHBMS-PNL-GFBMS Contractorunverified
AHU-GFM-1AHU (Chilled-Water-Served)Ground Floor Mezzanine BOHBMS-PNL-GFBMS Contractorunverified
BTU-1BTU Meter2nd Level Mechanical RoomBMS-PNL-LG-CHILLERBMS Contractorunverified
BTU-2BTU Meter2nd Level Mechanical RoomBMS-PNL-LG-CHILLERBMS Contractorunverified
BTU-3BTU Meter2nd Level Mechanical RoomBMS-PNL-LG-CHILLERBMS Contractorunverified
BTU-4BTU Meter2nd Level Mechanical RoomBMS-PNL-LG-CHILLERBMS Contractorunverified
BTU-5BTU Meter2nd Level Mechanical RoomBMS-PNL-LG-CHILLERBMS Contractorunverified
CH-1Chiller (Package Water-Cooled)2nd Level Mechanical RoomBMS-PNL-LG-CHILLEREquipment Supplierunverified
CH-2Chiller (Package Water-Cooled)2nd Level Mechanical RoomBMS-PNL-LG-CHILLEREquipment Supplierunverified
CH-3Chiller (Package Water-Cooled)2nd Level Mechanical RoomBMS-PNL-LG-CHILLEREquipment Supplierunverified
CHW-BYPASSCHW Bypass Header2nd Level Mechanical RoomBMS-PNL-LG-CHILLERBMS Contractorunverified
CHW-HDR-RCHW Return Main Header2nd Level Mechanical RoomBMS-PNL-LG-CHILLERBMS Contractorunverified
CHW-HDR-SCHW Supply Main Header2nd Level Mechanical RoomBMS-PNL-LG-CHILLERBMS Contractorunverified
CT-1Cooling TowerRoof Deck MechanicalBMS-PNL-RD-CTBMS Contractorunverified
CT-2Cooling TowerRoof Deck MechanicalBMS-PNL-RD-CTBMS Contractorunverified
CT-3Cooling TowerRoof Deck MechanicalBMS-PNL-RD-CTBMS Contractorunverified
CT-COMMONCooling Tower (Common)Roof Deck MechanicalBMS-PNL-RD-CTBMS Contractorunverified
CWP-1Condenser Water Pump2nd Level Mechanical RoomBMS-PNL-LG-CHILLEREquipment Supplierunverified
CWP-2Condenser Water Pump2nd Level Mechanical RoomBMS-PNL-LG-CHILLEREquipment Supplierunverified
CWP-3Condenser Water Pump2nd Level Mechanical RoomBMS-PNL-LG-CHILLEREquipment Supplierunverified
DOAS-2F-CASINODOAS Unit2nd Floor Casino MVAC RoomBMS-PNL-2F-CASINOBMS Contractorunverified
DOAS-RD1DOAS UnitRoof Deck MechanicalBMS-PNL-RD-MECHBMS Contractorunverified
DOAS-RD2DOAS UnitRoof Deck MechanicalBMS-PNL-RD-MECHBMS Contractorunverified
EF-1Exhaust Fan (General)Roof DeckBMS-PNL-RD-MECHEquipment Supplierunverified
EF-1.2AExhaust Fan (General)Ground Floor LobbyBMS-PNL-GFEquipment Supplierunverified
EF-1MR.1Exhaust Fan (General)Ground Floor LobbyBMS-PNL-GFEquipment Supplierunverified
EF-1STO.1Exhaust Fan (General)Ground Floor LobbyBMS-PNL-GFEquipment Supplierunverified
EF-LPG.1Exhaust Fan (General)Ground Floor LobbyBMS-PNL-GFEquipment Supplierunverified
EF-MRF.1Exhaust Fan (General)Ground Floor LobbyBMS-PNL-GFEquipment Supplierunverified
EF-RD.1Exhaust Fan (General)Roof DeckBMS-PNL-RD-MECHEquipment Supplierunverified
EF-RD.2Exhaust Fan (General)Roof DeckBMS-PNL-RD-MECHEquipment Supplierunverified
HP-HZ-1Heat PumpRoof Deck HW PlantBMS-PNL-RD-MECHEquipment Supplierunverified
HP-HZ-2Heat PumpRoof Deck HW PlantBMS-PNL-RD-MECHEquipment Supplierunverified
HP-HZ-3Heat PumpRoof Deck HW PlantBMS-PNL-RD-MECHEquipment Supplierunverified
HP-LZ-1Heat PumpLower Ground HW PlantBMS-PNL-LG-PLUMBEquipment Supplierunverified
HP-LZ-2Heat PumpLower Ground HW PlantBMS-PNL-LG-PLUMBEquipment Supplierunverified
HP-LZ-3Heat PumpLower Ground HW PlantBMS-PNL-LG-PLUMBEquipment Supplierunverified
HW-HEADERSHot Water Header SetLower Ground HW PlantBMS-PNL-LG-PLUMBBMS Contractorunverified
HWT-HZ-1Calorifier (Hot Water Storage Tank)Roof Deck HW PlantBMS-PNL-RD-MECHBMS Contractorunverified
HWT-HZ-2Calorifier (Hot Water Storage Tank)Roof Deck HW PlantBMS-PNL-RD-MECHBMS Contractorunverified
HWT-HZ-3Calorifier (Hot Water Storage Tank)Roof Deck HW PlantBMS-PNL-RD-MECHBMS Contractorunverified
HWT-LZ-1Calorifier (Hot Water Storage Tank)Lower Ground HW PlantBMS-PNL-LG-PLUMBBMS Contractorunverified
HWT-LZ-2Calorifier (Hot Water Storage Tank)Lower Ground HW PlantBMS-PNL-LG-PLUMBBMS Contractorunverified
HWT-LZ-3Calorifier (Hot Water Storage Tank)Lower Ground HW PlantBMS-PNL-LG-PLUMBBMS Contractorunverified
ION-2F-1Ozone Generator (UV-light or Corona)2nd Floor CasinoBMS-PNL-2F-CASINOEquipment Supplierunverified
ION-2F-2Ozone Generator (UV-light or Corona)2nd Floor CasinoBMS-PNL-2F-CASINOEquipment Supplierunverified
PAHU-01Precooled Air Handling UnitRoof Deck MechanicalBMS-PNL-RD-MECHBMS Contractorunverified
PAHU-02Precooled Air Handling UnitRoof Deck MechanicalBMS-PNL-RD-MECHBMS Contractorunverified
PAHU-03Precooled Air Handling UnitRoof Deck MechanicalBMS-PNL-RD-MECHBMS Contractorunverified
PAHU-04Precooled Air Handling UnitRoof Deck MechanicalBMS-PNL-RD-MECHBMS Contractorunverified
PAHU-05Precooled Air Handling UnitRoof Deck MechanicalBMS-PNL-RD-MECHBMS Contractorunverified
PAHU-06Precooled Air Handling UnitRoof Deck MechanicalBMS-PNL-RD-MECHBMS Contractorunverified
PAHU-07Precooled Air Handling UnitRoof Deck MechanicalBMS-PNL-RD-MECHBMS Contractorunverified
PCHWP-1Primary CHW Pump2nd Level Mechanical RoomBMS-PNL-LG-CHILLEREquipment Supplierunverified
PCHWP-2Primary CHW Pump2nd Level Mechanical RoomBMS-PNL-LG-CHILLEREquipment Supplierunverified
PCHWP-3Primary CHW Pump2nd Level Mechanical RoomBMS-PNL-LG-CHILLEREquipment Supplierunverified
PM-CASINO-FBMultifunction Power Meter (Feeder)2nd Floor CasinoBMS-PNL-2F-CASINOBMS Contractorunverified
PM-CHILLER-1Multifunction Power Meter (Feeder)2nd Level Mechanical RoomBMS-PNL-LG-CHILLERBMS Contractorunverified
PM-CHILLER-2Multifunction Power Meter (Feeder)2nd Level Mechanical RoomBMS-PNL-LG-CHILLERBMS Contractorunverified
PM-CHILLER-3Multifunction Power Meter (Feeder)2nd Level Mechanical RoomBMS-PNL-LG-CHILLERBMS Contractorunverified
PM-ELEVATORMultifunction Power Meter (Feeder)Ground FloorBMS-PNL-GFBMS Contractorunverified
PM-KITCHEN-2FMultifunction Power Meter (Feeder)2nd Floor BOHBMS-PNL-2F-CASINOBMS Contractorunverified
PM-LAUNDRY-LGMultifunction Power Meter (Feeder)Lower Ground LaundryBMS-PNL-LG-PLUMBBMS Contractorunverified
PM-LIGHTING-GUESTMultifunction Power Meter (Feeder)3rd Floor AmenityBMS-PNL-3FBMS Contractorunverified
PM-LOBBY-GFMultifunction Power Meter (Feeder)Ground FloorBMS-PNL-GFBMS Contractorunverified
PM-MAINMultifunction Power Meter (Main)Main Switchgear RoomBMS-PNL-GFBMS Contractorunverified
PM-ROOFDECK-MECHMultifunction Power Meter (Feeder)Roof Deck MechanicalBMS-PNL-RD-MECHBMS Contractorunverified
RP-HZ-1Recirculating PumpRoof Deck HW PlantBMS-PNL-RD-MECHEquipment Supplierunverified
RP-HZ-2Recirculating PumpRoof Deck HW PlantBMS-PNL-RD-MECHEquipment Supplierunverified
RP-HZ-3Recirculating PumpRoof Deck HW PlantBMS-PNL-RD-MECHEquipment Supplierunverified
RP-LZ-1Recirculating PumpLower Ground HW PlantBMS-PNL-LG-PLUMBEquipment Supplierunverified
RP-LZ-2Recirculating PumpLower Ground HW PlantBMS-PNL-LG-PLUMBEquipment Supplierunverified
RP-LZ-3Recirculating PumpLower Ground HW PlantBMS-PNL-LG-PLUMBEquipment Supplierunverified
SB-1Steam BoilerLower Ground LaundryBMS-PNL-LG-PLUMBEquipment Supplierunverified
SB-2Steam BoilerLower Ground LaundryBMS-PNL-LG-PLUMBEquipment Supplierunverified
TEF-1.1Exhaust Fan (Toilet)Ground Floor LobbyBMS-PNL-GFEquipment Supplierunverified
TEF-1.2Exhaust Fan (Toilet)Ground Floor LobbyBMS-PNL-GFEquipment Supplierunverified
TEF-1.3Exhaust Fan (Toilet)Ground Floor LobbyBMS-PNL-GFEquipment Supplierunverified
TEF-1.4Exhaust Fan (Toilet)Ground Floor LobbyBMS-PNL-GFEquipment Supplierunverified
TEF-2.1Exhaust Fan (Toilet)2nd Floor BOHBMS-PNL-2F-CASINOEquipment Supplierunverified
TEF-2.3Exhaust Fan (Toilet)2nd Floor BOHBMS-PNL-2F-CASINOEquipment Supplierunverified
TEF-2B.3Exhaust Fan (Toilet)2nd Floor BOHBMS-PNL-2F-CASINOEquipment Supplierunverified
TEF-3A.1Exhaust Fan (Toilet)3rd Floor AmenityBMS-PNL-3FEquipment Supplierunverified
TEF-3A.2Exhaust Fan (Toilet)3rd Floor AmenityBMS-PNL-3FEquipment Supplierunverified
TEF-3BExhaust Fan (Toilet)3rd Floor AmenityBMS-PNL-3FEquipment Supplierunverified
TEF-3C.1Exhaust Fan (Toilet)3rd Floor AmenityBMS-PNL-3FEquipment Supplierunverified
TEF-3C.2Exhaust Fan (Toilet)3rd Floor AmenityBMS-PNL-3FEquipment Supplierunverified
TEF-3D.1Exhaust Fan (Toilet)3rd Floor AmenityBMS-PNL-3FEquipment Supplierunverified
TEF-3D.10Exhaust Fan (Toilet)3rd Floor AmenityBMS-PNL-3FEquipment Supplierunverified
TEF-3D.11Exhaust Fan (Toilet)3rd Floor AmenityBMS-PNL-3FEquipment Supplierunverified
TEF-3D.12Exhaust Fan (Toilet)3rd Floor AmenityBMS-PNL-3FEquipment Supplierunverified
TEF-3D.13Exhaust Fan (Toilet)3rd Floor AmenityBMS-PNL-3FEquipment Supplierunverified
TEF-3D.14Exhaust Fan (Toilet)3rd Floor AmenityBMS-PNL-3FEquipment Supplierunverified
TEF-3D.15Exhaust Fan (Toilet)3rd Floor AmenityBMS-PNL-3FEquipment Supplierunverified
TEF-3D.16Exhaust Fan (Toilet)3rd Floor AmenityBMS-PNL-3FEquipment Supplierunverified
TEF-3D.17Exhaust Fan (Toilet)3rd Floor AmenityBMS-PNL-3FEquipment Supplierunverified
TEF-3D.18Exhaust Fan (Toilet)3rd Floor AmenityBMS-PNL-3FEquipment Supplierunverified
TEF-3D.19Exhaust Fan (Toilet)3rd Floor AmenityBMS-PNL-3FEquipment Supplierunverified
TEF-3D.2Exhaust Fan (Toilet)3rd Floor AmenityBMS-PNL-3FEquipment Supplierunverified
TEF-3D.20Exhaust Fan (Toilet)3rd Floor AmenityBMS-PNL-3FEquipment Supplierunverified
TEF-3D.3Exhaust Fan (Toilet)3rd Floor AmenityBMS-PNL-3FEquipment Supplierunverified
TEF-3D.4Exhaust Fan (Toilet)3rd Floor AmenityBMS-PNL-3FEquipment Supplierunverified
TEF-3D.5Exhaust Fan (Toilet)3rd Floor AmenityBMS-PNL-3FEquipment Supplierunverified
TEF-3D.6Exhaust Fan (Toilet)3rd Floor AmenityBMS-PNL-3FEquipment Supplierunverified
TEF-3D.7Exhaust Fan (Toilet)3rd Floor AmenityBMS-PNL-3FEquipment Supplierunverified
TEF-3D.8Exhaust Fan (Toilet)3rd Floor AmenityBMS-PNL-3FEquipment Supplierunverified
TEF-3D.9Exhaust Fan (Toilet)3rd Floor AmenityBMS-PNL-3FEquipment Supplierunverified
TEF-B.1Exhaust Fan (Toilet)Basement 1BMS-PNL-B1Equipment Supplierunverified
TEF-B.10Exhaust Fan (Toilet)Basement 1BMS-PNL-B1Equipment Supplierunverified
TEF-B.11Exhaust Fan (Toilet)Basement 1BMS-PNL-B1Equipment Supplierunverified
TEF-B.12Exhaust Fan (Toilet)Basement 1BMS-PNL-B1Equipment Supplierunverified
TEF-B.13Exhaust Fan (Toilet)Basement 1BMS-PNL-B1Equipment Supplierunverified
TEF-B.14Exhaust Fan (Toilet)Basement 1BMS-PNL-B1Equipment Supplierunverified
TEF-B.15Exhaust Fan (Toilet)Basement 1BMS-PNL-B1Equipment Supplierunverified
TEF-B.16Exhaust Fan (Toilet)Basement 1BMS-PNL-B1Equipment Supplierunverified
TEF-B.2Exhaust Fan (Toilet)Basement 1BMS-PNL-B1Equipment Supplierunverified
TEF-B.3Exhaust Fan (Toilet)Basement 1BMS-PNL-B1Equipment Supplierunverified
TEF-B.4Exhaust Fan (Toilet)Basement 1BMS-PNL-B1Equipment Supplierunverified
TEF-B.5Exhaust Fan (Toilet)Basement 1BMS-PNL-B1Equipment Supplierunverified
TEF-B.6Exhaust Fan (Toilet)Basement 1BMS-PNL-B1Equipment Supplierunverified
TEF-B.7Exhaust Fan (Toilet)Basement 1BMS-PNL-B1Equipment Supplierunverified
TEF-B.8Exhaust Fan (Toilet)Basement 1BMS-PNL-B1Equipment Supplierunverified
TEF-B.9Exhaust Fan (Toilet)Basement 1BMS-PNL-B1Equipment Supplierunverified
TEF-GS.1Exhaust Fan (Toilet)Ground FloorBMS-PNL-GFEquipment Supplierunverified
TEF-GS.2Exhaust Fan (Toilet)Ground FloorBMS-PNL-GFEquipment Supplierunverified
TEF-RD.1Exhaust Fan (Toilet)Roof DeckBMS-PNL-RD-MECHEquipment Supplierunverified
TEF-RD.2Exhaust Fan (Toilet)Roof DeckBMS-PNL-RD-MECHEquipment Supplierunverified
TEF-RD.3Exhaust Fan (Toilet)Roof DeckBMS-PNL-RD-MECHEquipment Supplierunverified

Verification schema

How to record verification / corrections in A2-equipment-takeoff.yaml
Find the affected row in the YAML by ID (Detail sheet column A) and add a verification: block:
- id: AHU-01
verification: # ADDED by team
status: needs_correction # unverified | verified | needs_correction | uncertain
corrected_location: 3rd Floor Mech Room # team's measured / confirmed value
verified_by: J. Cruz
verified_date: 2026-05-10
drawing_ref: "EE-09 grid B-2"
notes: ""
After saving, re-run: python3 _playbook/tools/generate-deliverables.py <project>
Corrections propagate to B4 manhours, BOQ, and final deliverables automatically.
Recommended verification methods (priority order):
1. Site walkthrough with measurement (most accurate; for cable lengths, after structural completion).
2. Properly-scaled architectural drawings.
3. Mechanical contractor's tray layout combined with BMS panel locations.
4. A-001 default with ±20% contingency in BOQ — last resort.