Summary

A4 — Panel Schedule Summary
Total panels8
Total physical I/O622
Total HLI subpoints102
Total network drops29
Total I/O points753
Estimated total controllers19
Estimated total power (W)620

Panel Schedule

PanelLocationSystem ScopeEquipment CountPhysical I/OHLI SubpointsNetwork DropsTotal I/ODDC ControllersNetwork GatewayTotal ControllersPower (W)Enclosure
BMS-PNL-2F-CASINO2nd Floor BOH / 2nd Floor Casino / 2nd Floor Casino MVAC Roomcasino_mvac, common_area, power_metering, ventilation1184439131390Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
BMS-PNL-3F3rd Floor Amenitypower_metering, ventilation2675017621255Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
BMS-PNL-B1Basement 1 / Basement 1 BOHcommon_area, ventilation1763106420250Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
BMS-PNL-GFGround Floor / Ground Floor BOH / Ground Floor Lobby / Ground Floor Mezzanine BOH / Main Switchgear Roomcommon_area, power_metering, ventilation1663236821265Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
BMS-PNL-LG-CHILLER2nd Level Mechanical Roombtu_metering, chilled_water, power_metering20726011143212105Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
BMS-PNL-LG-PLUMBLower Ground HW Plant / Lower Ground Laundryhot_water, power_metering, steam13402616711255Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
BMS-PNL-RD-CTRoof Deck Mechanicalcondenser_water440004010125Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
BMS-PNL-RD-MECHRoof Deck / Roof Deck HW Plant / Roof Deck Mechanicalhot_water, power_metering, ventilation25185910204515175Wall-mount IP54 metal cabinet, sized per controller count + 30% spare

Equipment per Panel

PanelEquipment Instance
BMS-PNL-2F-CASINOAHU-2F-1
BMS-PNL-2F-CASINOAHU-2M.1
BMS-PNL-2F-CASINOAHU-2M.2
BMS-PNL-2F-CASINODOAS-2F-CASINO
BMS-PNL-2F-CASINOION-2F-1
BMS-PNL-2F-CASINOION-2F-2
BMS-PNL-2F-CASINOPM-CASINO-FB
BMS-PNL-2F-CASINOPM-KITCHEN-2F
BMS-PNL-2F-CASINOTEF-2.1
BMS-PNL-2F-CASINOTEF-2.3
BMS-PNL-2F-CASINOTEF-2B.3
BMS-PNL-3FPM-LIGHTING-GUEST
BMS-PNL-3FTEF-3A.1
BMS-PNL-3FTEF-3A.2
BMS-PNL-3FTEF-3B
BMS-PNL-3FTEF-3C.1
BMS-PNL-3FTEF-3C.2
BMS-PNL-3FTEF-3D.1
BMS-PNL-3FTEF-3D.10
BMS-PNL-3FTEF-3D.11
BMS-PNL-3FTEF-3D.12
BMS-PNL-3FTEF-3D.13
BMS-PNL-3FTEF-3D.14
BMS-PNL-3FTEF-3D.15
BMS-PNL-3FTEF-3D.16
BMS-PNL-3FTEF-3D.17
BMS-PNL-3FTEF-3D.18
BMS-PNL-3FTEF-3D.19
BMS-PNL-3FTEF-3D.2
BMS-PNL-3FTEF-3D.20
BMS-PNL-3FTEF-3D.3
BMS-PNL-3FTEF-3D.4
BMS-PNL-3FTEF-3D.5
BMS-PNL-3FTEF-3D.6
BMS-PNL-3FTEF-3D.7
BMS-PNL-3FTEF-3D.8
BMS-PNL-3FTEF-3D.9
BMS-PNL-B1AHU-B1-1
BMS-PNL-B1TEF-B.1
BMS-PNL-B1TEF-B.10
BMS-PNL-B1TEF-B.11
BMS-PNL-B1TEF-B.12
BMS-PNL-B1TEF-B.13
BMS-PNL-B1TEF-B.14
BMS-PNL-B1TEF-B.15
BMS-PNL-B1TEF-B.16
BMS-PNL-B1TEF-B.2
BMS-PNL-B1TEF-B.3
BMS-PNL-B1TEF-B.4
BMS-PNL-B1TEF-B.5
BMS-PNL-B1TEF-B.6
BMS-PNL-B1TEF-B.7
BMS-PNL-B1TEF-B.8
BMS-PNL-B1TEF-B.9
BMS-PNL-GFAHU-GF-1
BMS-PNL-GFAHU-GFM-1
BMS-PNL-GFEF-1.2A
BMS-PNL-GFEF-1MR.1
BMS-PNL-GFEF-1STO.1
BMS-PNL-GFEF-LPG.1
BMS-PNL-GFEF-MRF.1
BMS-PNL-GFPM-ELEVATOR
BMS-PNL-GFPM-LOBBY-GF
BMS-PNL-GFPM-MAIN
BMS-PNL-GFTEF-1.1
BMS-PNL-GFTEF-1.2
BMS-PNL-GFTEF-1.3
BMS-PNL-GFTEF-1.4
BMS-PNL-GFTEF-GS.1
BMS-PNL-GFTEF-GS.2
BMS-PNL-LG-CHILLERBTU-1
BMS-PNL-LG-CHILLERBTU-2
BMS-PNL-LG-CHILLERBTU-3
BMS-PNL-LG-CHILLERBTU-4
BMS-PNL-LG-CHILLERBTU-5
BMS-PNL-LG-CHILLERCH-1
BMS-PNL-LG-CHILLERCH-2
BMS-PNL-LG-CHILLERCH-3
BMS-PNL-LG-CHILLERCHW-BYPASS
BMS-PNL-LG-CHILLERCHW-HDR-R
BMS-PNL-LG-CHILLERCHW-HDR-S
BMS-PNL-LG-CHILLERCWP-1
BMS-PNL-LG-CHILLERCWP-2
BMS-PNL-LG-CHILLERCWP-3
BMS-PNL-LG-CHILLERPCHWP-1
BMS-PNL-LG-CHILLERPCHWP-2
BMS-PNL-LG-CHILLERPCHWP-3
BMS-PNL-LG-CHILLERPM-CHILLER-1
BMS-PNL-LG-CHILLERPM-CHILLER-2
BMS-PNL-LG-CHILLERPM-CHILLER-3
BMS-PNL-LG-PLUMBHP-LZ-1
BMS-PNL-LG-PLUMBHP-LZ-2
BMS-PNL-LG-PLUMBHP-LZ-3
BMS-PNL-LG-PLUMBHW-HEADERS
BMS-PNL-LG-PLUMBHWT-LZ-1
BMS-PNL-LG-PLUMBHWT-LZ-2
BMS-PNL-LG-PLUMBHWT-LZ-3
BMS-PNL-LG-PLUMBPM-LAUNDRY-LG
BMS-PNL-LG-PLUMBRP-LZ-1
BMS-PNL-LG-PLUMBRP-LZ-2
BMS-PNL-LG-PLUMBRP-LZ-3
BMS-PNL-LG-PLUMBSB-1
BMS-PNL-LG-PLUMBSB-2
BMS-PNL-RD-CTCT-1
BMS-PNL-RD-CTCT-2
BMS-PNL-RD-CTCT-3
BMS-PNL-RD-CTCT-COMMON
BMS-PNL-RD-MECHDOAS-RD1
BMS-PNL-RD-MECHDOAS-RD2
BMS-PNL-RD-MECHEF-1
BMS-PNL-RD-MECHEF-RD.1
BMS-PNL-RD-MECHEF-RD.2
BMS-PNL-RD-MECHHP-HZ-1
BMS-PNL-RD-MECHHP-HZ-2
BMS-PNL-RD-MECHHP-HZ-3
BMS-PNL-RD-MECHHWT-HZ-1
BMS-PNL-RD-MECHHWT-HZ-2
BMS-PNL-RD-MECHHWT-HZ-3
BMS-PNL-RD-MECHPAHU-01
BMS-PNL-RD-MECHPAHU-02
BMS-PNL-RD-MECHPAHU-03
BMS-PNL-RD-MECHPAHU-04
BMS-PNL-RD-MECHPAHU-05
BMS-PNL-RD-MECHPAHU-06
BMS-PNL-RD-MECHPAHU-07
BMS-PNL-RD-MECHPM-ROOFDECK-MECH
BMS-PNL-RD-MECHRP-HZ-1
BMS-PNL-RD-MECHRP-HZ-2
BMS-PNL-RD-MECHRP-HZ-3
BMS-PNL-RD-MECHTEF-RD.1
BMS-PNL-RD-MECHTEF-RD.2
BMS-PNL-RD-MECHTEF-RD.3