Summary
| A4 — Panel Schedule Summary | |
| Total panels | 8 |
| Total physical I/O | 622 |
| Total HLI subpoints | 102 |
| Total network drops | 29 |
| Total I/O points | 753 |
| Estimated total controllers | 19 |
| Estimated total power (W) | 620 |
Panel Schedule
| Panel | Location | System Scope | Equipment Count | Physical I/O | HLI Subpoints | Network Drops | Total I/O | DDC Controllers | Network Gateway | Total Controllers | Power (W) | Enclosure |
| BMS-PNL-2F-CASINO | 2nd Floor BOH / 2nd Floor Casino / 2nd Floor Casino MVAC Room | casino_mvac, common_area, power_metering, ventilation | 11 | 84 | 4 | 3 | 91 | 3 | 1 | 3 | 90 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| BMS-PNL-3F | 3rd Floor Amenity | power_metering, ventilation | 26 | 75 | 0 | 1 | 76 | 2 | 1 | 2 | 55 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| BMS-PNL-B1 | Basement 1 / Basement 1 BOH | common_area, ventilation | 17 | 63 | 1 | 0 | 64 | 2 | 0 | 2 | 50 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| BMS-PNL-GF | Ground Floor / Ground Floor BOH / Ground Floor Lobby / Ground Floor Mezzanine BOH / Main Switchgear Room | common_area, power_metering, ventilation | 16 | 63 | 2 | 3 | 68 | 2 | 1 | 2 | 65 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| BMS-PNL-LG-CHILLER | 2nd Level Mechanical Room | btu_metering, chilled_water, power_metering | 20 | 72 | 60 | 11 | 143 | 2 | 1 | 2 | 105 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| BMS-PNL-LG-PLUMB | Lower Ground HW Plant / Lower Ground Laundry | hot_water, power_metering, steam | 13 | 40 | 26 | 1 | 67 | 1 | 1 | 2 | 55 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| BMS-PNL-RD-CT | Roof Deck Mechanical | condenser_water | 4 | 40 | 0 | 0 | 40 | 1 | 0 | 1 | 25 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| BMS-PNL-RD-MECH | Roof Deck / Roof Deck HW Plant / Roof Deck Mechanical | hot_water, power_metering, ventilation | 25 | 185 | 9 | 10 | 204 | 5 | 1 | 5 | 175 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
Equipment per Panel
| Panel | Equipment Instance |
| BMS-PNL-2F-CASINO | AHU-2F-1 |
| BMS-PNL-2F-CASINO | AHU-2M.1 |
| BMS-PNL-2F-CASINO | AHU-2M.2 |
| BMS-PNL-2F-CASINO | DOAS-2F-CASINO |
| BMS-PNL-2F-CASINO | ION-2F-1 |
| BMS-PNL-2F-CASINO | ION-2F-2 |
| BMS-PNL-2F-CASINO | PM-CASINO-FB |
| BMS-PNL-2F-CASINO | PM-KITCHEN-2F |
| BMS-PNL-2F-CASINO | TEF-2.1 |
| BMS-PNL-2F-CASINO | TEF-2.3 |
| BMS-PNL-2F-CASINO | TEF-2B.3 |
| BMS-PNL-3F | PM-LIGHTING-GUEST |
| BMS-PNL-3F | TEF-3A.1 |
| BMS-PNL-3F | TEF-3A.2 |
| BMS-PNL-3F | TEF-3B |
| BMS-PNL-3F | TEF-3C.1 |
| BMS-PNL-3F | TEF-3C.2 |
| BMS-PNL-3F | TEF-3D.1 |
| BMS-PNL-3F | TEF-3D.10 |
| BMS-PNL-3F | TEF-3D.11 |
| BMS-PNL-3F | TEF-3D.12 |
| BMS-PNL-3F | TEF-3D.13 |
| BMS-PNL-3F | TEF-3D.14 |
| BMS-PNL-3F | TEF-3D.15 |
| BMS-PNL-3F | TEF-3D.16 |
| BMS-PNL-3F | TEF-3D.17 |
| BMS-PNL-3F | TEF-3D.18 |
| BMS-PNL-3F | TEF-3D.19 |
| BMS-PNL-3F | TEF-3D.2 |
| BMS-PNL-3F | TEF-3D.20 |
| BMS-PNL-3F | TEF-3D.3 |
| BMS-PNL-3F | TEF-3D.4 |
| BMS-PNL-3F | TEF-3D.5 |
| BMS-PNL-3F | TEF-3D.6 |
| BMS-PNL-3F | TEF-3D.7 |
| BMS-PNL-3F | TEF-3D.8 |
| BMS-PNL-3F | TEF-3D.9 |
| BMS-PNL-B1 | AHU-B1-1 |
| BMS-PNL-B1 | TEF-B.1 |
| BMS-PNL-B1 | TEF-B.10 |
| BMS-PNL-B1 | TEF-B.11 |
| BMS-PNL-B1 | TEF-B.12 |
| BMS-PNL-B1 | TEF-B.13 |
| BMS-PNL-B1 | TEF-B.14 |
| BMS-PNL-B1 | TEF-B.15 |
| BMS-PNL-B1 | TEF-B.16 |
| BMS-PNL-B1 | TEF-B.2 |
| BMS-PNL-B1 | TEF-B.3 |
| BMS-PNL-B1 | TEF-B.4 |
| BMS-PNL-B1 | TEF-B.5 |
| BMS-PNL-B1 | TEF-B.6 |
| BMS-PNL-B1 | TEF-B.7 |
| BMS-PNL-B1 | TEF-B.8 |
| BMS-PNL-B1 | TEF-B.9 |
| BMS-PNL-GF | AHU-GF-1 |
| BMS-PNL-GF | AHU-GFM-1 |
| BMS-PNL-GF | EF-1.2A |
| BMS-PNL-GF | EF-1MR.1 |
| BMS-PNL-GF | EF-1STO.1 |
| BMS-PNL-GF | EF-LPG.1 |
| BMS-PNL-GF | EF-MRF.1 |
| BMS-PNL-GF | PM-ELEVATOR |
| BMS-PNL-GF | PM-LOBBY-GF |
| BMS-PNL-GF | PM-MAIN |
| BMS-PNL-GF | TEF-1.1 |
| BMS-PNL-GF | TEF-1.2 |
| BMS-PNL-GF | TEF-1.3 |
| BMS-PNL-GF | TEF-1.4 |
| BMS-PNL-GF | TEF-GS.1 |
| BMS-PNL-GF | TEF-GS.2 |
| BMS-PNL-LG-CHILLER | BTU-1 |
| BMS-PNL-LG-CHILLER | BTU-2 |
| BMS-PNL-LG-CHILLER | BTU-3 |
| BMS-PNL-LG-CHILLER | BTU-4 |
| BMS-PNL-LG-CHILLER | BTU-5 |
| BMS-PNL-LG-CHILLER | CH-1 |
| BMS-PNL-LG-CHILLER | CH-2 |
| BMS-PNL-LG-CHILLER | CH-3 |
| BMS-PNL-LG-CHILLER | CHW-BYPASS |
| BMS-PNL-LG-CHILLER | CHW-HDR-R |
| BMS-PNL-LG-CHILLER | CHW-HDR-S |
| BMS-PNL-LG-CHILLER | CWP-1 |
| BMS-PNL-LG-CHILLER | CWP-2 |
| BMS-PNL-LG-CHILLER | CWP-3 |
| BMS-PNL-LG-CHILLER | PCHWP-1 |
| BMS-PNL-LG-CHILLER | PCHWP-2 |
| BMS-PNL-LG-CHILLER | PCHWP-3 |
| BMS-PNL-LG-CHILLER | PM-CHILLER-1 |
| BMS-PNL-LG-CHILLER | PM-CHILLER-2 |
| BMS-PNL-LG-CHILLER | PM-CHILLER-3 |
| BMS-PNL-LG-PLUMB | HP-LZ-1 |
| BMS-PNL-LG-PLUMB | HP-LZ-2 |
| BMS-PNL-LG-PLUMB | HP-LZ-3 |
| BMS-PNL-LG-PLUMB | HW-HEADERS |
| BMS-PNL-LG-PLUMB | HWT-LZ-1 |
| BMS-PNL-LG-PLUMB | HWT-LZ-2 |
| BMS-PNL-LG-PLUMB | HWT-LZ-3 |
| BMS-PNL-LG-PLUMB | PM-LAUNDRY-LG |
| BMS-PNL-LG-PLUMB | RP-LZ-1 |
| BMS-PNL-LG-PLUMB | RP-LZ-2 |
| BMS-PNL-LG-PLUMB | RP-LZ-3 |
| BMS-PNL-LG-PLUMB | SB-1 |
| BMS-PNL-LG-PLUMB | SB-2 |
| BMS-PNL-RD-CT | CT-1 |
| BMS-PNL-RD-CT | CT-2 |
| BMS-PNL-RD-CT | CT-3 |
| BMS-PNL-RD-CT | CT-COMMON |
| BMS-PNL-RD-MECH | DOAS-RD1 |
| BMS-PNL-RD-MECH | DOAS-RD2 |
| BMS-PNL-RD-MECH | EF-1 |
| BMS-PNL-RD-MECH | EF-RD.1 |
| BMS-PNL-RD-MECH | EF-RD.2 |
| BMS-PNL-RD-MECH | HP-HZ-1 |
| BMS-PNL-RD-MECH | HP-HZ-2 |
| BMS-PNL-RD-MECH | HP-HZ-3 |
| BMS-PNL-RD-MECH | HWT-HZ-1 |
| BMS-PNL-RD-MECH | HWT-HZ-2 |
| BMS-PNL-RD-MECH | HWT-HZ-3 |
| BMS-PNL-RD-MECH | PAHU-01 |
| BMS-PNL-RD-MECH | PAHU-02 |
| BMS-PNL-RD-MECH | PAHU-03 |
| BMS-PNL-RD-MECH | PAHU-04 |
| BMS-PNL-RD-MECH | PAHU-05 |
| BMS-PNL-RD-MECH | PAHU-06 |
| BMS-PNL-RD-MECH | PAHU-07 |
| BMS-PNL-RD-MECH | PM-ROOFDECK-MECH |
| BMS-PNL-RD-MECH | RP-HZ-1 |
| BMS-PNL-RD-MECH | RP-HZ-2 |
| BMS-PNL-RD-MECH | RP-HZ-3 |
| BMS-PNL-RD-MECH | TEF-RD.1 |
| BMS-PNL-RD-MECH | TEF-RD.2 |
| BMS-PNL-RD-MECH | TEF-RD.3 |