| ID | Equipment Class | Quantity | Location | System | Panel | Primary C/O | Physical I/O | HLI Subpoints | Network Drops | Total I/O | Make/Model Assumed | Network Type | Typical Supplier | Notes |
| AHU-2F-1 | AHU (Chilled-Water-Served) | 1 | 2nd Floor BOH | common_area | BMS-PNL-2F-CASINO | BMS Contractor | 15 | 1 | 0 | 16 | Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers | Hardwired (VFD via BACnet HLI) | Mechanical contractor | BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier. |
| AHU-2M.1 | AHU (Modulating CHW-served) | 1 | 2nd Floor Casino MVAC Room | casino_mvac | BMS-PNL-2F-CASINO | BMS Contractor | 16 | 1 | 0 | 17 | Modulating CHW-served AHU with VFD, modulating valve and dampers (position feedback) | Hardwired (VFD via BACnet HLI) | Mechanical contractor | Casino-spec AHU — modulating actuators with position feedback; CO/CO2 monitoring at return duct. |
| AHU-2M.2 | AHU (Modulating CHW-served) | 1 | 2nd Floor Casino MVAC Room | casino_mvac | BMS-PNL-2F-CASINO | BMS Contractor | 16 | 1 | 0 | 17 | Modulating CHW-served AHU with VFD, modulating valve and dampers (position feedback) | Hardwired (VFD via BACnet HLI) | Mechanical contractor | Casino-spec AHU — modulating actuators with position feedback; CO/CO2 monitoring at return duct. |
| AHU-B1-1 | AHU (Chilled-Water-Served) | 1 | Basement 1 BOH | common_area | BMS-PNL-B1 | BMS Contractor | 15 | 1 | 0 | 16 | Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers | Hardwired (VFD via BACnet HLI) | Mechanical contractor | BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier. |
| AHU-GF-1 | AHU (Chilled-Water-Served) | 1 | Ground Floor BOH | common_area | BMS-PNL-GF | BMS Contractor | 15 | 1 | 0 | 16 | Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers | Hardwired (VFD via BACnet HLI) | Mechanical contractor | BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier. |
| AHU-GFM-1 | AHU (Chilled-Water-Served) | 1 | Ground Floor Mezzanine BOH | common_area | BMS-PNL-GF | BMS Contractor | 15 | 1 | 0 | 16 | Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers | Hardwired (VFD via BACnet HLI) | Mechanical contractor | BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier. |
| BTU-1 | BTU Meter | 1 | 2nd Level Mechanical Room | btu_metering | BMS-PNL-LG-CHILLER | BMS Contractor | 0 | 0 | 1 | 1 | Ultrasonic or insertion-type BTU meter with Modbus output (Onicon, Aichi, Kamstrup) | Modbus RTU/TCP | BMS contractor | System-level energy submeter. |
| BTU-2 | BTU Meter | 1 | 2nd Level Mechanical Room | btu_metering | BMS-PNL-LG-CHILLER | BMS Contractor | 0 | 0 | 1 | 1 | Ultrasonic or insertion-type BTU meter with Modbus output (Onicon, Aichi, Kamstrup) | Modbus RTU/TCP | BMS contractor | System-level energy submeter. |
| BTU-3 | BTU Meter | 1 | 2nd Level Mechanical Room | btu_metering | BMS-PNL-LG-CHILLER | BMS Contractor | 0 | 0 | 1 | 1 | Ultrasonic or insertion-type BTU meter with Modbus output (Onicon, Aichi, Kamstrup) | Modbus RTU/TCP | BMS contractor | System-level energy submeter. |
| BTU-4 | BTU Meter | 1 | 2nd Level Mechanical Room | btu_metering | BMS-PNL-LG-CHILLER | BMS Contractor | 0 | 0 | 1 | 1 | Ultrasonic or insertion-type BTU meter with Modbus output (Onicon, Aichi, Kamstrup) | Modbus RTU/TCP | BMS contractor | System-level energy submeter. |
| BTU-5 | BTU Meter | 1 | 2nd Level Mechanical Room | btu_metering | BMS-PNL-LG-CHILLER | BMS Contractor | 0 | 0 | 1 | 1 | Ultrasonic or insertion-type BTU meter with Modbus output (Onicon, Aichi, Kamstrup) | Modbus RTU/TCP | BMS contractor | System-level energy submeter. |
| CH-1 | Chiller (Package Water-Cooled) | 1 | 2nd Level Mechanical Room | chilled_water | BMS-PNL-LG-CHILLER | Equipment Supplier | 9 | 18 | 1 | 28 | Tier-1 BACnet IP chiller (Trane/York/Carrier/Daikin), water-cooled centrifugal or screw, sized per design cooling load | BACnet/IP | Mechanical contractor / Equipment supplier | BMS reads via chiller's native BACnet gateway. BMS supplies external T-sensors on entering/leaving CHW & CW pipes. |
| CH-2 | Chiller (Package Water-Cooled) | 1 | 2nd Level Mechanical Room | chilled_water | BMS-PNL-LG-CHILLER | Equipment Supplier | 9 | 18 | 1 | 28 | Tier-1 BACnet IP chiller (Trane/York/Carrier/Daikin), water-cooled centrifugal or screw, sized per design cooling load | BACnet/IP | Mechanical contractor / Equipment supplier | BMS reads via chiller's native BACnet gateway. BMS supplies external T-sensors on entering/leaving CHW & CW pipes. |
| CH-3 | Chiller (Package Water-Cooled) | 1 | 2nd Level Mechanical Room | chilled_water | BMS-PNL-LG-CHILLER | Equipment Supplier | 9 | 18 | 1 | 28 | Tier-1 BACnet IP chiller (Trane/York/Carrier/Daikin), water-cooled centrifugal or screw, sized per design cooling load | BACnet/IP | Mechanical contractor / Equipment supplier | BMS reads via chiller's native BACnet gateway. BMS supplies external T-sensors on entering/leaving CHW & CW pipes. |
| CHW-BYPASS | CHW Bypass Header | 1 | 2nd Level Mechanical Room | chilled_water | BMS-PNL-LG-CHILLER | BMS Contractor | 5 | 0 | 0 | 5 | BMS dP/dT sensors + motorized bypass valve (BMS-supplied) | Hardwired | BMS contractor | BMS controls bypass valve to maintain CHW differential. |
| CHW-HDR-R | CHW Return Main Header | 1 | 2nd Level Mechanical Room | chilled_water | BMS-PNL-LG-CHILLER | BMS Contractor | 2 | 0 | 0 | 2 | BMS T+P sensors on CHW return manifold | Hardwired | BMS contractor | Field instrumentation only. |
| CHW-HDR-S | CHW Supply Main Header | 1 | 2nd Level Mechanical Room | chilled_water | BMS-PNL-LG-CHILLER | BMS Contractor | 2 | 0 | 0 | 2 | BMS T+P sensors on CHW supply manifold | Hardwired | BMS contractor | Field instrumentation only. |
| CT-1 | Cooling Tower | 1 | Roof Deck Mechanical | condenser_water | BMS-PNL-RD-CT | BMS Contractor | 12 | 0 | 0 | 12 | Induced-draft counterflow open cooling tower (Marley/BAC/EVAPCO), sized per condenser water flow | Hardwired | Mechanical contractor / Equipment supplier | BMS supplies basin level sensors and condenser water header T-sensors. |
| CT-2 | Cooling Tower | 1 | Roof Deck Mechanical | condenser_water | BMS-PNL-RD-CT | BMS Contractor | 12 | 0 | 0 | 12 | Induced-draft counterflow open cooling tower (Marley/BAC/EVAPCO), sized per condenser water flow | Hardwired | Mechanical contractor / Equipment supplier | BMS supplies basin level sensors and condenser water header T-sensors. |
| CT-3 | Cooling Tower | 1 | Roof Deck Mechanical | condenser_water | BMS-PNL-RD-CT | BMS Contractor | 12 | 0 | 0 | 12 | Induced-draft counterflow open cooling tower (Marley/BAC/EVAPCO), sized per condenser water flow | Hardwired | Mechanical contractor / Equipment supplier | BMS supplies basin level sensors and condenser water header T-sensors. |
| CT-COMMON | Cooling Tower (Common) | 1 | Roof Deck Mechanical | condenser_water | BMS-PNL-RD-CT | BMS Contractor | 4 | 0 | 0 | 4 | Common BMS sensors at cooling tower area (OA T/RH, condenser headers) | Hardwired | BMS contractor | Field instrumentation only — no equipment per se. |
| CWP-1 | Condenser Water Pump | 1 | 2nd Level Mechanical Room | chilled_water | BMS-PNL-LG-CHILLER | Equipment Supplier | 5 | 1 | 0 | 6 | End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious) | Hardwired | Mechanical contractor | BMS reads aux contacts; commands start via DO. |
| CWP-2 | Condenser Water Pump | 1 | 2nd Level Mechanical Room | chilled_water | BMS-PNL-LG-CHILLER | Equipment Supplier | 5 | 1 | 0 | 6 | End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious) | Hardwired | Mechanical contractor | BMS reads aux contacts; commands start via DO. |
| CWP-3 | Condenser Water Pump | 1 | 2nd Level Mechanical Room | chilled_water | BMS-PNL-LG-CHILLER | Equipment Supplier | 5 | 1 | 0 | 6 | End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious) | Hardwired | Mechanical contractor | BMS reads aux contacts; commands start via DO. |
| DOAS-2F-CASINO | DOAS Unit | 1 | 2nd Floor Casino MVAC Room | ventilation | BMS-PNL-2F-CASINO | BMS Contractor | 24 | 1 | 1 | 26 | Dedicated Outdoor Air System with energy recovery wheel, supply + exhaust fans, CHW coil | BACnet/IP | Mechanical contractor / Equipment supplier | Native BACnet controller typical. BMS supplies external sensors (OA T/RH/Flow, indoor T/RH, exhaust T) and modulating valve actuator. |
| DOAS-RD1 | DOAS Unit | 1 | Roof Deck Mechanical | ventilation | BMS-PNL-RD-MECH | BMS Contractor | 24 | 1 | 1 | 26 | Dedicated Outdoor Air System with energy recovery wheel, supply + exhaust fans, CHW coil | BACnet/IP | Mechanical contractor / Equipment supplier | Native BACnet controller typical. BMS supplies external sensors (OA T/RH/Flow, indoor T/RH, exhaust T) and modulating valve actuator. |
| DOAS-RD2 | DOAS Unit | 1 | Roof Deck Mechanical | ventilation | BMS-PNL-RD-MECH | BMS Contractor | 24 | 1 | 1 | 26 | Dedicated Outdoor Air System with energy recovery wheel, supply + exhaust fans, CHW coil | BACnet/IP | Mechanical contractor / Equipment supplier | Native BACnet controller typical. BMS supplies external sensors (OA T/RH/Flow, indoor T/RH, exhaust T) and modulating valve actuator. |
| EF-1 | Exhaust Fan (General) | 1 | Roof Deck | ventilation | BMS-PNL-RD-MECH | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line, ceiling, or roof-mounted general exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| EF-1.2A | Exhaust Fan (General) | 1 | Ground Floor Lobby | ventilation | BMS-PNL-GF | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line, ceiling, or roof-mounted general exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| EF-1MR.1 | Exhaust Fan (General) | 1 | Ground Floor Lobby | ventilation | BMS-PNL-GF | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line, ceiling, or roof-mounted general exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| EF-1STO.1 | Exhaust Fan (General) | 1 | Ground Floor Lobby | ventilation | BMS-PNL-GF | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line, ceiling, or roof-mounted general exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| EF-LPG.1 | Exhaust Fan (General) | 1 | Ground Floor Lobby | ventilation | BMS-PNL-GF | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line, ceiling, or roof-mounted general exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| EF-MRF.1 | Exhaust Fan (General) | 1 | Ground Floor Lobby | ventilation | BMS-PNL-GF | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line, ceiling, or roof-mounted general exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| EF-RD.1 | Exhaust Fan (General) | 1 | Roof Deck | ventilation | BMS-PNL-RD-MECH | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line, ceiling, or roof-mounted general exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| EF-RD.2 | Exhaust Fan (General) | 1 | Roof Deck | ventilation | BMS-PNL-RD-MECH | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line, ceiling, or roof-mounted general exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| HP-HZ-1 | Heat Pump | 1 | Roof Deck HW Plant | hot_water | BMS-PNL-RD-MECH | Equipment Supplier | 3 | 0 | 0 | 3 | Air-source or water-source heat pump for hot water heating | Hardwired (LZ) or HLI (HZ — per A-PL-001) | Plumbing contractor / Equipment supplier | BMS reads pump status/HOA/trip via aux contacts. |
| HP-HZ-2 | Heat Pump | 1 | Roof Deck HW Plant | hot_water | BMS-PNL-RD-MECH | Equipment Supplier | 3 | 0 | 0 | 3 | Air-source or water-source heat pump for hot water heating | Hardwired (LZ) or HLI (HZ — per A-PL-001) | Plumbing contractor / Equipment supplier | BMS reads pump status/HOA/trip via aux contacts. |
| HP-HZ-3 | Heat Pump | 1 | Roof Deck HW Plant | hot_water | BMS-PNL-RD-MECH | Equipment Supplier | 3 | 0 | 0 | 3 | Air-source or water-source heat pump for hot water heating | Hardwired (LZ) or HLI (HZ — per A-PL-001) | Plumbing contractor / Equipment supplier | BMS reads pump status/HOA/trip via aux contacts. |
| HP-LZ-1 | Heat Pump | 1 | Lower Ground HW Plant | hot_water | BMS-PNL-LG-PLUMB | Equipment Supplier | 3 | 0 | 0 | 3 | Air-source or water-source heat pump for hot water heating | Hardwired (LZ) or HLI (HZ — per A-PL-001) | Plumbing contractor / Equipment supplier | BMS reads pump status/HOA/trip via aux contacts. |
| HP-LZ-2 | Heat Pump | 1 | Lower Ground HW Plant | hot_water | BMS-PNL-LG-PLUMB | Equipment Supplier | 3 | 0 | 0 | 3 | Air-source or water-source heat pump for hot water heating | Hardwired (LZ) or HLI (HZ — per A-PL-001) | Plumbing contractor / Equipment supplier | BMS reads pump status/HOA/trip via aux contacts. |
| HP-LZ-3 | Heat Pump | 1 | Lower Ground HW Plant | hot_water | BMS-PNL-LG-PLUMB | Equipment Supplier | 3 | 0 | 0 | 3 | Air-source or water-source heat pump for hot water heating | Hardwired (LZ) or HLI (HZ — per A-PL-001) | Plumbing contractor / Equipment supplier | BMS reads pump status/HOA/trip via aux contacts. |
| HW-HEADERS | Hot Water Header Set | 1 | Lower Ground HW Plant | hot_water | BMS-PNL-LG-PLUMB | BMS Contractor | 3 | 0 | 0 | 3 | Hot water supply/return manifolds with BMS T sensors and make-up cold water T sensor | Hardwired | BMS contractor | Field instrumentation on existing piping. |
| HWT-HZ-1 | Calorifier (Hot Water Storage Tank) | 1 | Roof Deck HW Plant | hot_water | BMS-PNL-RD-MECH | BMS Contractor | 1 | 0 | 0 | 1 | Pressurised hot-water storage tank with internal coil, sized per design hot water demand | Hardwired | Plumbing contractor | BMS supplies tank temperature sensor (immersion or strapped probe). |
| HWT-HZ-2 | Calorifier (Hot Water Storage Tank) | 1 | Roof Deck HW Plant | hot_water | BMS-PNL-RD-MECH | BMS Contractor | 1 | 0 | 0 | 1 | Pressurised hot-water storage tank with internal coil, sized per design hot water demand | Hardwired | Plumbing contractor | BMS supplies tank temperature sensor (immersion or strapped probe). |
| HWT-HZ-3 | Calorifier (Hot Water Storage Tank) | 1 | Roof Deck HW Plant | hot_water | BMS-PNL-RD-MECH | BMS Contractor | 1 | 0 | 0 | 1 | Pressurised hot-water storage tank with internal coil, sized per design hot water demand | Hardwired | Plumbing contractor | BMS supplies tank temperature sensor (immersion or strapped probe). |
| HWT-LZ-1 | Calorifier (Hot Water Storage Tank) | 1 | Lower Ground HW Plant | hot_water | BMS-PNL-LG-PLUMB | BMS Contractor | 1 | 0 | 0 | 1 | Pressurised hot-water storage tank with internal coil, sized per design hot water demand | Hardwired | Plumbing contractor | BMS supplies tank temperature sensor (immersion or strapped probe). |
| HWT-LZ-2 | Calorifier (Hot Water Storage Tank) | 1 | Lower Ground HW Plant | hot_water | BMS-PNL-LG-PLUMB | BMS Contractor | 1 | 0 | 0 | 1 | Pressurised hot-water storage tank with internal coil, sized per design hot water demand | Hardwired | Plumbing contractor | BMS supplies tank temperature sensor (immersion or strapped probe). |
| HWT-LZ-3 | Calorifier (Hot Water Storage Tank) | 1 | Lower Ground HW Plant | hot_water | BMS-PNL-LG-PLUMB | BMS Contractor | 1 | 0 | 0 | 1 | Pressurised hot-water storage tank with internal coil, sized per design hot water demand | Hardwired | Plumbing contractor | BMS supplies tank temperature sensor (immersion or strapped probe). |
| ION-2F-1 | Ozone Generator (UV-light or Corona) | 1 | 2nd Floor Casino | casino_mvac | BMS-PNL-2F-CASINO | Equipment Supplier | 2 | 0 | 0 | 2 | UV-light or corona-discharge ozone generator (paired with Casino AHU) | Hardwired | Equipment supplier | Casino-specific air-treatment device. BMS monitors status/trip and reads VOC sensor (BMS-supplied). |
| ION-2F-2 | Ozone Generator (UV-light or Corona) | 1 | 2nd Floor Casino | casino_mvac | BMS-PNL-2F-CASINO | Equipment Supplier | 2 | 0 | 0 | 2 | UV-light or corona-discharge ozone generator (paired with Casino AHU) | Hardwired | Equipment supplier | Casino-specific air-treatment device. BMS monitors status/trip and reads VOC sensor (BMS-supplied). |
| PAHU-01 | Precooled Air Handling Unit | 1 | Roof Deck Mechanical | ventilation | BMS-PNL-RD-MECH | BMS Contractor | 14 | 1 | 1 | 16 | Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust path | Hardwired (VFD via BACnet HLI) | Mechanical contractor / Equipment supplier | Precool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors. |
| PAHU-02 | Precooled Air Handling Unit | 1 | Roof Deck Mechanical | ventilation | BMS-PNL-RD-MECH | BMS Contractor | 14 | 1 | 1 | 16 | Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust path | Hardwired (VFD via BACnet HLI) | Mechanical contractor / Equipment supplier | Precool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors. |
| PAHU-03 | Precooled Air Handling Unit | 1 | Roof Deck Mechanical | ventilation | BMS-PNL-RD-MECH | BMS Contractor | 14 | 1 | 1 | 16 | Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust path | Hardwired (VFD via BACnet HLI) | Mechanical contractor / Equipment supplier | Precool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors. |
| PAHU-04 | Precooled Air Handling Unit | 1 | Roof Deck Mechanical | ventilation | BMS-PNL-RD-MECH | BMS Contractor | 14 | 1 | 1 | 16 | Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust path | Hardwired (VFD via BACnet HLI) | Mechanical contractor / Equipment supplier | Precool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors. |
| PAHU-05 | Precooled Air Handling Unit | 1 | Roof Deck Mechanical | ventilation | BMS-PNL-RD-MECH | BMS Contractor | 14 | 1 | 1 | 16 | Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust path | Hardwired (VFD via BACnet HLI) | Mechanical contractor / Equipment supplier | Precool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors. |
| PAHU-06 | Precooled Air Handling Unit | 1 | Roof Deck Mechanical | ventilation | BMS-PNL-RD-MECH | BMS Contractor | 14 | 1 | 1 | 16 | Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust path | Hardwired (VFD via BACnet HLI) | Mechanical contractor / Equipment supplier | Precool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors. |
| PAHU-07 | Precooled Air Handling Unit | 1 | Roof Deck Mechanical | ventilation | BMS-PNL-RD-MECH | BMS Contractor | 14 | 1 | 1 | 16 | Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust path | Hardwired (VFD via BACnet HLI) | Mechanical contractor / Equipment supplier | Precool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors. |
| PCHWP-1 | Primary CHW Pump | 1 | 2nd Level Mechanical Room | chilled_water | BMS-PNL-LG-CHILLER | Equipment Supplier | 7 | 1 | 0 | 8 | End-suction or split-case centrifugal with VFD, sized per design CHW flow | Hardwired (BMS reads VFD via BACnet HLI) | Mechanical contractor | VFD typically Equipment Supplier provided with BACnet card. |
| PCHWP-2 | Primary CHW Pump | 1 | 2nd Level Mechanical Room | chilled_water | BMS-PNL-LG-CHILLER | Equipment Supplier | 7 | 1 | 0 | 8 | End-suction or split-case centrifugal with VFD, sized per design CHW flow | Hardwired (BMS reads VFD via BACnet HLI) | Mechanical contractor | VFD typically Equipment Supplier provided with BACnet card. |
| PCHWP-3 | Primary CHW Pump | 1 | 2nd Level Mechanical Room | chilled_water | BMS-PNL-LG-CHILLER | Equipment Supplier | 7 | 1 | 0 | 8 | End-suction or split-case centrifugal with VFD, sized per design CHW flow | Hardwired (BMS reads VFD via BACnet HLI) | Mechanical contractor | VFD typically Equipment Supplier provided with BACnet card. |
| PM-CASINO-FB | Multifunction Power Meter (Feeder) | 1 | 2nd Floor Casino | power_metering | BMS-PNL-2F-CASINO | BMS Contractor | 0 | 0 | 1 | 1 | Multifunction power meter with Modbus output, sub-feeder class (smaller form factor) | Modbus RTU | BMS contractor | Daisy-chained on Modbus bus(es) back to BMS gateway. |
| PM-CHILLER-1 | Multifunction Power Meter (Feeder) | 1 | 2nd Level Mechanical Room | power_metering | BMS-PNL-LG-CHILLER | BMS Contractor | 0 | 0 | 1 | 1 | Multifunction power meter with Modbus output, sub-feeder class (smaller form factor) | Modbus RTU | BMS contractor | Daisy-chained on Modbus bus(es) back to BMS gateway. |
| PM-CHILLER-2 | Multifunction Power Meter (Feeder) | 1 | 2nd Level Mechanical Room | power_metering | BMS-PNL-LG-CHILLER | BMS Contractor | 0 | 0 | 1 | 1 | Multifunction power meter with Modbus output, sub-feeder class (smaller form factor) | Modbus RTU | BMS contractor | Daisy-chained on Modbus bus(es) back to BMS gateway. |
| PM-CHILLER-3 | Multifunction Power Meter (Feeder) | 1 | 2nd Level Mechanical Room | power_metering | BMS-PNL-LG-CHILLER | BMS Contractor | 0 | 0 | 1 | 1 | Multifunction power meter with Modbus output, sub-feeder class (smaller form factor) | Modbus RTU | BMS contractor | Daisy-chained on Modbus bus(es) back to BMS gateway. |
| PM-ELEVATOR | Multifunction Power Meter (Feeder) | 1 | Ground Floor | power_metering | BMS-PNL-GF | BMS Contractor | 0 | 0 | 1 | 1 | Multifunction power meter with Modbus output, sub-feeder class (smaller form factor) | Modbus RTU | BMS contractor | Daisy-chained on Modbus bus(es) back to BMS gateway. |
| PM-KITCHEN-2F | Multifunction Power Meter (Feeder) | 1 | 2nd Floor BOH | power_metering | BMS-PNL-2F-CASINO | BMS Contractor | 0 | 0 | 1 | 1 | Multifunction power meter with Modbus output, sub-feeder class (smaller form factor) | Modbus RTU | BMS contractor | Daisy-chained on Modbus bus(es) back to BMS gateway. |
| PM-LAUNDRY-LG | Multifunction Power Meter (Feeder) | 1 | Lower Ground Laundry | power_metering | BMS-PNL-LG-PLUMB | BMS Contractor | 0 | 0 | 1 | 1 | Multifunction power meter with Modbus output, sub-feeder class (smaller form factor) | Modbus RTU | BMS contractor | Daisy-chained on Modbus bus(es) back to BMS gateway. |
| PM-LIGHTING-GUEST | Multifunction Power Meter (Feeder) | 1 | 3rd Floor Amenity | power_metering | BMS-PNL-3F | BMS Contractor | 0 | 0 | 1 | 1 | Multifunction power meter with Modbus output, sub-feeder class (smaller form factor) | Modbus RTU | BMS contractor | Daisy-chained on Modbus bus(es) back to BMS gateway. |
| PM-LOBBY-GF | Multifunction Power Meter (Feeder) | 1 | Ground Floor | power_metering | BMS-PNL-GF | BMS Contractor | 0 | 0 | 1 | 1 | Multifunction power meter with Modbus output, sub-feeder class (smaller form factor) | Modbus RTU | BMS contractor | Daisy-chained on Modbus bus(es) back to BMS gateway. |
| PM-MAIN | Multifunction Power Meter (Main) | 1 | Main Switchgear Room | power_metering | BMS-PNL-GF | BMS Contractor | 0 | 0 | 1 | 1 | Multifunction power meter with Modbus output (Schneider PM-series, ABB M2M, Siemens SENTRON), main switchgear class | Modbus RTU/TCP | BMS contractor | Mounted in main switchgear or on dedicated BMS-side panel. |
| PM-ROOFDECK-MECH | Multifunction Power Meter (Feeder) | 1 | Roof Deck Mechanical | power_metering | BMS-PNL-RD-MECH | BMS Contractor | 0 | 0 | 1 | 1 | Multifunction power meter with Modbus output, sub-feeder class (smaller form factor) | Modbus RTU | BMS contractor | Daisy-chained on Modbus bus(es) back to BMS gateway. |
| RP-HZ-1 | Recirculating Pump | 1 | Roof Deck HW Plant | hot_water | BMS-PNL-RD-MECH | Equipment Supplier | 3 | 0 | 0 | 3 | Hot water recirculating pump, fixed-speed (typical for hotwater systems) | Hardwired (LZ) or HLI (HZ — per A-PL-001) | Plumbing contractor | BMS reads aux contacts only. |
| RP-HZ-2 | Recirculating Pump | 1 | Roof Deck HW Plant | hot_water | BMS-PNL-RD-MECH | Equipment Supplier | 3 | 0 | 0 | 3 | Hot water recirculating pump, fixed-speed (typical for hotwater systems) | Hardwired (LZ) or HLI (HZ — per A-PL-001) | Plumbing contractor | BMS reads aux contacts only. |
| RP-HZ-3 | Recirculating Pump | 1 | Roof Deck HW Plant | hot_water | BMS-PNL-RD-MECH | Equipment Supplier | 3 | 0 | 0 | 3 | Hot water recirculating pump, fixed-speed (typical for hotwater systems) | Hardwired (LZ) or HLI (HZ — per A-PL-001) | Plumbing contractor | BMS reads aux contacts only. |
| RP-LZ-1 | Recirculating Pump | 1 | Lower Ground HW Plant | hot_water | BMS-PNL-LG-PLUMB | Equipment Supplier | 3 | 0 | 0 | 3 | Hot water recirculating pump, fixed-speed (typical for hotwater systems) | Hardwired (LZ) or HLI (HZ — per A-PL-001) | Plumbing contractor | BMS reads aux contacts only. |
| RP-LZ-2 | Recirculating Pump | 1 | Lower Ground HW Plant | hot_water | BMS-PNL-LG-PLUMB | Equipment Supplier | 3 | 0 | 0 | 3 | Hot water recirculating pump, fixed-speed (typical for hotwater systems) | Hardwired (LZ) or HLI (HZ — per A-PL-001) | Plumbing contractor | BMS reads aux contacts only. |
| RP-LZ-3 | Recirculating Pump | 1 | Lower Ground HW Plant | hot_water | BMS-PNL-LG-PLUMB | Equipment Supplier | 3 | 0 | 0 | 3 | Hot water recirculating pump, fixed-speed (typical for hotwater systems) | Hardwired (LZ) or HLI (HZ — per A-PL-001) | Plumbing contractor | BMS reads aux contacts only. |
| SB-1 | Steam Boiler | 1 | Lower Ground Laundry | steam | BMS-PNL-LG-PLUMB | Equipment Supplier | 8 | 13 | 0 | 21 | Fire-tube steam boiler with multi-stage burner, fuel-oil fired (typical for hotel laundry) | Hardwired | Mechanical contractor / Equipment supplier | BMS supplies steam pressure, feedwater T, fluegas T+O2 sensors. Boiler equipment provides aux contacts for status/HOA/trip points. |
| SB-2 | Steam Boiler | 1 | Lower Ground Laundry | steam | BMS-PNL-LG-PLUMB | Equipment Supplier | 8 | 13 | 0 | 21 | Fire-tube steam boiler with multi-stage burner, fuel-oil fired (typical for hotel laundry) | Hardwired | Mechanical contractor / Equipment supplier | BMS supplies steam pressure, feedwater T, fluegas T+O2 sensors. Boiler equipment provides aux contacts for status/HOA/trip points. |
| TEF-1.1 | Exhaust Fan (Toilet) | 1 | Ground Floor Lobby | ventilation | BMS-PNL-GF | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-1.2 | Exhaust Fan (Toilet) | 1 | Ground Floor Lobby | ventilation | BMS-PNL-GF | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-1.3 | Exhaust Fan (Toilet) | 1 | Ground Floor Lobby | ventilation | BMS-PNL-GF | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-1.4 | Exhaust Fan (Toilet) | 1 | Ground Floor Lobby | ventilation | BMS-PNL-GF | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-2.1 | Exhaust Fan (Toilet) | 1 | 2nd Floor BOH | ventilation | BMS-PNL-2F-CASINO | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-2.3 | Exhaust Fan (Toilet) | 1 | 2nd Floor BOH | ventilation | BMS-PNL-2F-CASINO | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-2B.3 | Exhaust Fan (Toilet) | 1 | 2nd Floor BOH | ventilation | BMS-PNL-2F-CASINO | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-3A.1 | Exhaust Fan (Toilet) | 1 | 3rd Floor Amenity | ventilation | BMS-PNL-3F | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-3A.2 | Exhaust Fan (Toilet) | 1 | 3rd Floor Amenity | ventilation | BMS-PNL-3F | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-3B | Exhaust Fan (Toilet) | 1 | 3rd Floor Amenity | ventilation | BMS-PNL-3F | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-3C.1 | Exhaust Fan (Toilet) | 1 | 3rd Floor Amenity | ventilation | BMS-PNL-3F | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-3C.2 | Exhaust Fan (Toilet) | 1 | 3rd Floor Amenity | ventilation | BMS-PNL-3F | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-3D.1 | Exhaust Fan (Toilet) | 1 | 3rd Floor Amenity | ventilation | BMS-PNL-3F | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-3D.10 | Exhaust Fan (Toilet) | 1 | 3rd Floor Amenity | ventilation | BMS-PNL-3F | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-3D.11 | Exhaust Fan (Toilet) | 1 | 3rd Floor Amenity | ventilation | BMS-PNL-3F | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-3D.12 | Exhaust Fan (Toilet) | 1 | 3rd Floor Amenity | ventilation | BMS-PNL-3F | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-3D.13 | Exhaust Fan (Toilet) | 1 | 3rd Floor Amenity | ventilation | BMS-PNL-3F | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-3D.14 | Exhaust Fan (Toilet) | 1 | 3rd Floor Amenity | ventilation | BMS-PNL-3F | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-3D.15 | Exhaust Fan (Toilet) | 1 | 3rd Floor Amenity | ventilation | BMS-PNL-3F | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-3D.16 | Exhaust Fan (Toilet) | 1 | 3rd Floor Amenity | ventilation | BMS-PNL-3F | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-3D.17 | Exhaust Fan (Toilet) | 1 | 3rd Floor Amenity | ventilation | BMS-PNL-3F | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-3D.18 | Exhaust Fan (Toilet) | 1 | 3rd Floor Amenity | ventilation | BMS-PNL-3F | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-3D.19 | Exhaust Fan (Toilet) | 1 | 3rd Floor Amenity | ventilation | BMS-PNL-3F | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-3D.2 | Exhaust Fan (Toilet) | 1 | 3rd Floor Amenity | ventilation | BMS-PNL-3F | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-3D.20 | Exhaust Fan (Toilet) | 1 | 3rd Floor Amenity | ventilation | BMS-PNL-3F | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-3D.3 | Exhaust Fan (Toilet) | 1 | 3rd Floor Amenity | ventilation | BMS-PNL-3F | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-3D.4 | Exhaust Fan (Toilet) | 1 | 3rd Floor Amenity | ventilation | BMS-PNL-3F | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-3D.5 | Exhaust Fan (Toilet) | 1 | 3rd Floor Amenity | ventilation | BMS-PNL-3F | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-3D.6 | Exhaust Fan (Toilet) | 1 | 3rd Floor Amenity | ventilation | BMS-PNL-3F | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-3D.7 | Exhaust Fan (Toilet) | 1 | 3rd Floor Amenity | ventilation | BMS-PNL-3F | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-3D.8 | Exhaust Fan (Toilet) | 1 | 3rd Floor Amenity | ventilation | BMS-PNL-3F | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-3D.9 | Exhaust Fan (Toilet) | 1 | 3rd Floor Amenity | ventilation | BMS-PNL-3F | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-B.1 | Exhaust Fan (Toilet) | 1 | Basement 1 | ventilation | BMS-PNL-B1 | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-B.10 | Exhaust Fan (Toilet) | 1 | Basement 1 | ventilation | BMS-PNL-B1 | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-B.11 | Exhaust Fan (Toilet) | 1 | Basement 1 | ventilation | BMS-PNL-B1 | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-B.12 | Exhaust Fan (Toilet) | 1 | Basement 1 | ventilation | BMS-PNL-B1 | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-B.13 | Exhaust Fan (Toilet) | 1 | Basement 1 | ventilation | BMS-PNL-B1 | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-B.14 | Exhaust Fan (Toilet) | 1 | Basement 1 | ventilation | BMS-PNL-B1 | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-B.15 | Exhaust Fan (Toilet) | 1 | Basement 1 | ventilation | BMS-PNL-B1 | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-B.16 | Exhaust Fan (Toilet) | 1 | Basement 1 | ventilation | BMS-PNL-B1 | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-B.2 | Exhaust Fan (Toilet) | 1 | Basement 1 | ventilation | BMS-PNL-B1 | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-B.3 | Exhaust Fan (Toilet) | 1 | Basement 1 | ventilation | BMS-PNL-B1 | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-B.4 | Exhaust Fan (Toilet) | 1 | Basement 1 | ventilation | BMS-PNL-B1 | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-B.5 | Exhaust Fan (Toilet) | 1 | Basement 1 | ventilation | BMS-PNL-B1 | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-B.6 | Exhaust Fan (Toilet) | 1 | Basement 1 | ventilation | BMS-PNL-B1 | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-B.7 | Exhaust Fan (Toilet) | 1 | Basement 1 | ventilation | BMS-PNL-B1 | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-B.8 | Exhaust Fan (Toilet) | 1 | Basement 1 | ventilation | BMS-PNL-B1 | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-B.9 | Exhaust Fan (Toilet) | 1 | Basement 1 | ventilation | BMS-PNL-B1 | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-GS.1 | Exhaust Fan (Toilet) | 1 | Ground Floor | ventilation | BMS-PNL-GF | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-GS.2 | Exhaust Fan (Toilet) | 1 | Ground Floor | ventilation | BMS-PNL-GF | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-RD.1 | Exhaust Fan (Toilet) | 1 | Roof Deck | ventilation | BMS-PNL-RD-MECH | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-RD.2 | Exhaust Fan (Toilet) | 1 | Roof Deck | ventilation | BMS-PNL-RD-MECH | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |
| TEF-RD.3 | Exhaust Fan (Toilet) | 1 | Roof Deck | ventilation | BMS-PNL-RD-MECH | Equipment Supplier | 3 | 0 | 0 | 3 | Constant-speed in-line or roof-mounted toilet exhaust fan | Hardwired | Mechanical contractor | BMS reads aux contacts only — no control points. |