| ID | System | Equipment Class | Equipment Instance | Location | Point Description | Type | Field Device | C/O | DoO Ref | Panel | Source | Notes |
| P0001 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | Compressor on/off status | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0002 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | Compressor H/O/A status | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0003 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | Compressor trip alarm | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0004 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | Motor load current | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0005 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | Motor consumption (kW) | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0006 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | Motor winding temperature | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0007 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | Oil sump pressure | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0008 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | Oil sump temperature | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0009 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | Oil pump on/off status | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0010 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | Oil pump trip | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0011 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | Evaporator approach delta-T | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0012 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | Evaporator approach delta-P | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0013 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | Evaporator refrigerant pressure | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0014 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | Evaporator refrigerant temperature | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0015 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | Condenser refrigerant pressure | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0016 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | Condenser refrigerant temperature | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0017 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | Condenser approach delta-T | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0018 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | Condenser approach delta-P | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0019 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | Entering CHW temperature | AI | Temperature Sensor (immersion) | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0020 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | Leaving CHW temperature | AI | Temperature Sensor (immersion) | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0021 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | Entering condenser water temperature | AI | Temperature Sensor (immersion) | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0022 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | Leaving condenser water temperature | AI | Temperature Sensor (immersion) | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0023 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | Chiller native BACnet/IP gateway | Network | BACnet/IP | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0024 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | CHW Supply isolation valve status | DI | Auxiliary Contact | ME Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0025 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | CHW Return isolation valve status | DI | Auxiliary Contact | ME Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0026 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | Condenser Water Supply isolation valve status | DI | Auxiliary Contact | ME Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0027 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | Condenser Water Return isolation valve status | DI | Auxiliary Contact | ME Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0028 | chilled_water | Chiller (Package Water-Cooled) | CH-1 | 2nd Level Mechanical Room | Start permissive | DO | Relay output | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0029 | chilled_water | Primary CHW Pump | PCHWP-1 | 2nd Level Mechanical Room | Pump motor on/off status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0030 | chilled_water | Primary CHW Pump | PCHWP-1 | 2nd Level Mechanical Room | Pump motor H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0031 | chilled_water | Primary CHW Pump | PCHWP-1 | 2nd Level Mechanical Room | Pump motor trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0032 | chilled_water | Primary CHW Pump | PCHWP-1 | 2nd Level Mechanical Room | VFD speed feedback | AI | VFD analog output / 4-20 mA | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0033 | chilled_water | Primary CHW Pump | PCHWP-1 | 2nd Level Mechanical Room | VFD speed command | AO | 0-10V / 4-20 mA out | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0034 | chilled_water | Primary CHW Pump | PCHWP-1 | 2nd Level Mechanical Room | CHW supply pressure (per pump) | AI | Pressure Transmitter | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0035 | chilled_water | Primary CHW Pump | PCHWP-1 | 2nd Level Mechanical Room | VFD network HLI (run hours, fault, kWh) | HLI | BACnet/Modbus card | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0036 | chilled_water | Primary CHW Pump | PCHWP-1 | 2nd Level Mechanical Room | Pump start command | DO | Relay output | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0037 | chilled_water | Condenser Water Pump | CWP-1 | 2nd Level Mechanical Room | Pump motor on/off status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0038 | chilled_water | Condenser Water Pump | CWP-1 | 2nd Level Mechanical Room | Pump motor H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0039 | chilled_water | Condenser Water Pump | CWP-1 | 2nd Level Mechanical Room | Pump motor trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0040 | chilled_water | Condenser Water Pump | CWP-1 | 2nd Level Mechanical Room | Pump start command | DO | Relay output | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0041 | chilled_water | Condenser Water Pump | CWP-1 | 2nd Level Mechanical Room | Pump VFD speed feedback | AI | VFD analog output | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0042 | chilled_water | Condenser Water Pump | CWP-1 | 2nd Level Mechanical Room | VFD network HLI | HLI | BACnet/Modbus card | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0043 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | Compressor on/off status | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0044 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | Compressor H/O/A status | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0045 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | Compressor trip alarm | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0046 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | Motor load current | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0047 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | Motor consumption (kW) | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0048 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | Motor winding temperature | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0049 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | Oil sump pressure | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0050 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | Oil sump temperature | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0051 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | Oil pump on/off status | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0052 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | Oil pump trip | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0053 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | Evaporator approach delta-T | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0054 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | Evaporator approach delta-P | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0055 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | Evaporator refrigerant pressure | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0056 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | Evaporator refrigerant temperature | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0057 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | Condenser refrigerant pressure | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0058 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | Condenser refrigerant temperature | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0059 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | Condenser approach delta-T | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0060 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | Condenser approach delta-P | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0061 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | Entering CHW temperature | AI | Temperature Sensor (immersion) | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0062 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | Leaving CHW temperature | AI | Temperature Sensor (immersion) | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0063 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | Entering condenser water temperature | AI | Temperature Sensor (immersion) | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0064 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | Leaving condenser water temperature | AI | Temperature Sensor (immersion) | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0065 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | Chiller native BACnet/IP gateway | Network | BACnet/IP | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0066 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | CHW Supply isolation valve status | DI | Auxiliary Contact | ME Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0067 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | CHW Return isolation valve status | DI | Auxiliary Contact | ME Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0068 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | Condenser Water Supply isolation valve status | DI | Auxiliary Contact | ME Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0069 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | Condenser Water Return isolation valve status | DI | Auxiliary Contact | ME Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0070 | chilled_water | Chiller (Package Water-Cooled) | CH-2 | 2nd Level Mechanical Room | Start permissive | DO | Relay output | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0071 | chilled_water | Primary CHW Pump | PCHWP-2 | 2nd Level Mechanical Room | Pump motor on/off status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0072 | chilled_water | Primary CHW Pump | PCHWP-2 | 2nd Level Mechanical Room | Pump motor H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0073 | chilled_water | Primary CHW Pump | PCHWP-2 | 2nd Level Mechanical Room | Pump motor trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0074 | chilled_water | Primary CHW Pump | PCHWP-2 | 2nd Level Mechanical Room | VFD speed feedback | AI | VFD analog output / 4-20 mA | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0075 | chilled_water | Primary CHW Pump | PCHWP-2 | 2nd Level Mechanical Room | VFD speed command | AO | 0-10V / 4-20 mA out | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0076 | chilled_water | Primary CHW Pump | PCHWP-2 | 2nd Level Mechanical Room | CHW supply pressure (per pump) | AI | Pressure Transmitter | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0077 | chilled_water | Primary CHW Pump | PCHWP-2 | 2nd Level Mechanical Room | VFD network HLI (run hours, fault, kWh) | HLI | BACnet/Modbus card | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0078 | chilled_water | Primary CHW Pump | PCHWP-2 | 2nd Level Mechanical Room | Pump start command | DO | Relay output | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0079 | chilled_water | Condenser Water Pump | CWP-2 | 2nd Level Mechanical Room | Pump motor on/off status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0080 | chilled_water | Condenser Water Pump | CWP-2 | 2nd Level Mechanical Room | Pump motor H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0081 | chilled_water | Condenser Water Pump | CWP-2 | 2nd Level Mechanical Room | Pump motor trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0082 | chilled_water | Condenser Water Pump | CWP-2 | 2nd Level Mechanical Room | Pump start command | DO | Relay output | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0083 | chilled_water | Condenser Water Pump | CWP-2 | 2nd Level Mechanical Room | Pump VFD speed feedback | AI | VFD analog output | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0084 | chilled_water | Condenser Water Pump | CWP-2 | 2nd Level Mechanical Room | VFD network HLI | HLI | BACnet/Modbus card | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0085 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | Compressor on/off status | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0086 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | Compressor H/O/A status | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0087 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | Compressor trip alarm | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0088 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | Motor load current | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0089 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | Motor consumption (kW) | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0090 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | Motor winding temperature | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0091 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | Oil sump pressure | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0092 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | Oil sump temperature | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0093 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | Oil pump on/off status | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0094 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | Oil pump trip | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0095 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | Evaporator approach delta-T | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0096 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | Evaporator approach delta-P | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0097 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | Evaporator refrigerant pressure | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0098 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | Evaporator refrigerant temperature | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0099 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | Condenser refrigerant pressure | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0100 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | Condenser refrigerant temperature | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0101 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | Condenser approach delta-T | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0102 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | Condenser approach delta-P | HLI | — | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0103 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | Entering CHW temperature | AI | Temperature Sensor (immersion) | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0104 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | Leaving CHW temperature | AI | Temperature Sensor (immersion) | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0105 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | Entering condenser water temperature | AI | Temperature Sensor (immersion) | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0106 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | Leaving condenser water temperature | AI | Temperature Sensor (immersion) | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0107 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | Chiller native BACnet/IP gateway | Network | BACnet/IP | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0108 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | CHW Supply isolation valve status | DI | Auxiliary Contact | ME Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0109 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | CHW Return isolation valve status | DI | Auxiliary Contact | ME Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0110 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | Condenser Water Supply isolation valve status | DI | Auxiliary Contact | ME Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0111 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | Condenser Water Return isolation valve status | DI | Auxiliary Contact | ME Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0112 | chilled_water | Chiller (Package Water-Cooled) | CH-3 | 2nd Level Mechanical Room | Start permissive | DO | Relay output | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0113 | chilled_water | Primary CHW Pump | PCHWP-3 | 2nd Level Mechanical Room | Pump motor on/off status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0114 | chilled_water | Primary CHW Pump | PCHWP-3 | 2nd Level Mechanical Room | Pump motor H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0115 | chilled_water | Primary CHW Pump | PCHWP-3 | 2nd Level Mechanical Room | Pump motor trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0116 | chilled_water | Primary CHW Pump | PCHWP-3 | 2nd Level Mechanical Room | VFD speed feedback | AI | VFD analog output / 4-20 mA | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0117 | chilled_water | Primary CHW Pump | PCHWP-3 | 2nd Level Mechanical Room | VFD speed command | AO | 0-10V / 4-20 mA out | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0118 | chilled_water | Primary CHW Pump | PCHWP-3 | 2nd Level Mechanical Room | CHW supply pressure (per pump) | AI | Pressure Transmitter | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0119 | chilled_water | Primary CHW Pump | PCHWP-3 | 2nd Level Mechanical Room | VFD network HLI (run hours, fault, kWh) | HLI | BACnet/Modbus card | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0120 | chilled_water | Primary CHW Pump | PCHWP-3 | 2nd Level Mechanical Room | Pump start command | DO | Relay output | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0121 | chilled_water | Condenser Water Pump | CWP-3 | 2nd Level Mechanical Room | Pump motor on/off status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0122 | chilled_water | Condenser Water Pump | CWP-3 | 2nd Level Mechanical Room | Pump motor H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0123 | chilled_water | Condenser Water Pump | CWP-3 | 2nd Level Mechanical Room | Pump motor trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0124 | chilled_water | Condenser Water Pump | CWP-3 | 2nd Level Mechanical Room | Pump start command | DO | Relay output | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0125 | chilled_water | Condenser Water Pump | CWP-3 | 2nd Level Mechanical Room | Pump VFD speed feedback | AI | VFD analog output | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0126 | chilled_water | Condenser Water Pump | CWP-3 | 2nd Level Mechanical Room | VFD network HLI | HLI | BACnet/Modbus card | Equipment Supplier | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0127 | chilled_water | CHW Supply Main Header | CHW-HDR-S | 2nd Level Mechanical Room | CHW supply header temperature | AI | Temperature Sensor | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0128 | chilled_water | CHW Supply Main Header | CHW-HDR-S | 2nd Level Mechanical Room | CHW supply header pressure | AI | Pressure Transmitter | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0129 | chilled_water | CHW Return Main Header | CHW-HDR-R | 2nd Level Mechanical Room | CHW return header temperature | AI | Temperature Sensor | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0130 | chilled_water | CHW Return Main Header | CHW-HDR-R | 2nd Level Mechanical Room | CHW return header pressure | AI | Pressure Transmitter | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0131 | chilled_water | CHW Bypass Header | CHW-BYPASS | 2nd Level Mechanical Room | CHW differential pressure | AI | Diff. Pressure Sensor | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0132 | chilled_water | CHW Bypass Header | CHW-BYPASS | 2nd Level Mechanical Room | CHW differential temperature | AI | Diff. Temp Sensor | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0133 | chilled_water | CHW Bypass Header | CHW-BYPASS | 2nd Level Mechanical Room | Bypass motorized valve command | AO | Electric Valve Actuator | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0134 | chilled_water | CHW Bypass Header | CHW-BYPASS | 2nd Level Mechanical Room | Bypass motorized valve feedback | AI | Position Feedback | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0135 | chilled_water | CHW Bypass Header | CHW-BYPASS | 2nd Level Mechanical Room | Bypass valve status | DI | Auxiliary Contact | ME Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0136 | condenser_water | Cooling Tower | CT-1 | Roof Deck Mechanical | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0137 | condenser_water | Cooling Tower | CT-1 | Roof Deck Mechanical | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0138 | condenser_water | Cooling Tower | CT-1 | Roof Deck Mechanical | Fan start command | DO | Relay output | BMS Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0139 | condenser_water | Cooling Tower | CT-1 | Roof Deck Mechanical | Fan VFD speed command | AO | 0-10V / 4-20 mA | BMS Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0140 | condenser_water | Cooling Tower | CT-1 | Roof Deck Mechanical | Fan VFD speed feedback | AI | VFD analog output | Equipment Supplier | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0141 | condenser_water | Cooling Tower | CT-1 | Roof Deck Mechanical | Basin level low alarm | DI | Level Electrode | BMS Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0142 | condenser_water | Cooling Tower | CT-1 | Roof Deck Mechanical | Basin level high alarm | DI | Level Electrode | BMS Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0143 | condenser_water | Cooling Tower | CT-1 | Roof Deck Mechanical | Outside air temperature (local) | AI | OA Temperature Sensor | BMS Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0144 | condenser_water | Cooling Tower | CT-1 | Roof Deck Mechanical | Outside air humidity (local) | AI | OA Humidity Sensor | BMS Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0145 | condenser_water | Cooling Tower | CT-1 | Roof Deck Mechanical | CT supply isolation valve status | DI | Auxiliary Contact | ME Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0146 | condenser_water | Cooling Tower | CT-1 | Roof Deck Mechanical | CT return isolation valve status | DI | Auxiliary Contact | ME Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0147 | condenser_water | Cooling Tower | CT-1 | Roof Deck Mechanical | Motorized blowdown valve control | DO | Electric Valve Actuator | BMS Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0148 | condenser_water | Cooling Tower | CT-2 | Roof Deck Mechanical | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0149 | condenser_water | Cooling Tower | CT-2 | Roof Deck Mechanical | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0150 | condenser_water | Cooling Tower | CT-2 | Roof Deck Mechanical | Fan start command | DO | Relay output | BMS Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0151 | condenser_water | Cooling Tower | CT-2 | Roof Deck Mechanical | Fan VFD speed command | AO | 0-10V / 4-20 mA | BMS Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0152 | condenser_water | Cooling Tower | CT-2 | Roof Deck Mechanical | Fan VFD speed feedback | AI | VFD analog output | Equipment Supplier | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0153 | condenser_water | Cooling Tower | CT-2 | Roof Deck Mechanical | Basin level low alarm | DI | Level Electrode | BMS Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0154 | condenser_water | Cooling Tower | CT-2 | Roof Deck Mechanical | Basin level high alarm | DI | Level Electrode | BMS Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0155 | condenser_water | Cooling Tower | CT-2 | Roof Deck Mechanical | Outside air temperature (local) | AI | OA Temperature Sensor | BMS Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0156 | condenser_water | Cooling Tower | CT-2 | Roof Deck Mechanical | Outside air humidity (local) | AI | OA Humidity Sensor | BMS Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0157 | condenser_water | Cooling Tower | CT-2 | Roof Deck Mechanical | CT supply isolation valve status | DI | Auxiliary Contact | ME Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0158 | condenser_water | Cooling Tower | CT-2 | Roof Deck Mechanical | CT return isolation valve status | DI | Auxiliary Contact | ME Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0159 | condenser_water | Cooling Tower | CT-2 | Roof Deck Mechanical | Motorized blowdown valve control | DO | Electric Valve Actuator | BMS Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0160 | condenser_water | Cooling Tower | CT-3 | Roof Deck Mechanical | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0161 | condenser_water | Cooling Tower | CT-3 | Roof Deck Mechanical | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0162 | condenser_water | Cooling Tower | CT-3 | Roof Deck Mechanical | Fan start command | DO | Relay output | BMS Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0163 | condenser_water | Cooling Tower | CT-3 | Roof Deck Mechanical | Fan VFD speed command | AO | 0-10V / 4-20 mA | BMS Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0164 | condenser_water | Cooling Tower | CT-3 | Roof Deck Mechanical | Fan VFD speed feedback | AI | VFD analog output | Equipment Supplier | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0165 | condenser_water | Cooling Tower | CT-3 | Roof Deck Mechanical | Basin level low alarm | DI | Level Electrode | BMS Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0166 | condenser_water | Cooling Tower | CT-3 | Roof Deck Mechanical | Basin level high alarm | DI | Level Electrode | BMS Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0167 | condenser_water | Cooling Tower | CT-3 | Roof Deck Mechanical | Outside air temperature (local) | AI | OA Temperature Sensor | BMS Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0168 | condenser_water | Cooling Tower | CT-3 | Roof Deck Mechanical | Outside air humidity (local) | AI | OA Humidity Sensor | BMS Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0169 | condenser_water | Cooling Tower | CT-3 | Roof Deck Mechanical | CT supply isolation valve status | DI | Auxiliary Contact | ME Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0170 | condenser_water | Cooling Tower | CT-3 | Roof Deck Mechanical | CT return isolation valve status | DI | Auxiliary Contact | ME Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0171 | condenser_water | Cooling Tower | CT-3 | Roof Deck Mechanical | Motorized blowdown valve control | DO | Electric Valve Actuator | BMS Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0172 | condenser_water | Cooling Tower (Common) | CT-COMMON | Roof Deck Mechanical | Condenser supply header temperature | AI | Temperature Sensor | BMS Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0173 | condenser_water | Cooling Tower (Common) | CT-COMMON | Roof Deck Mechanical | Condenser return header temperature | AI | Temperature Sensor | BMS Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0174 | condenser_water | Cooling Tower (Common) | CT-COMMON | Roof Deck Mechanical | Condenser water pH (corrosion) | AI | pH Sensor | ME Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0175 | condenser_water | Cooling Tower (Common) | CT-COMMON | Roof Deck Mechanical | Condenser water conductivity (scale) | AI | Conductivity Sensor | ME Contractor | | BMS-PNL-RD-CT | BMS Points list (TUEC) + ME/PL Points list | |
| P0176 | btu_metering | BTU Meter | BTU-1 | 2nd Level Mechanical Room | BTU meter (energy reading) | Network | Modbus RTU/TCP | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0177 | btu_metering | BTU Meter | BTU-2 | 2nd Level Mechanical Room | BTU meter (energy reading) | Network | Modbus RTU/TCP | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0178 | btu_metering | BTU Meter | BTU-3 | 2nd Level Mechanical Room | BTU meter (energy reading) | Network | Modbus RTU/TCP | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0179 | btu_metering | BTU Meter | BTU-4 | 2nd Level Mechanical Room | BTU meter (energy reading) | Network | Modbus RTU/TCP | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0180 | btu_metering | BTU Meter | BTU-5 | 2nd Level Mechanical Room | BTU meter (energy reading) | Network | Modbus RTU/TCP | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0181 | ventilation | DOAS Unit | DOAS-RD1 | Roof Deck Mechanical | Outside SA temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0182 | ventilation | DOAS Unit | DOAS-RD1 | Roof Deck Mechanical | Outside SA flow | AI | Air Flow Station | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0183 | ventilation | DOAS Unit | DOAS-RD1 | Roof Deck Mechanical | Outside SA humidity | AI | Duct RH Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0184 | ventilation | DOAS Unit | DOAS-RD1 | Roof Deck Mechanical | OA motorized damper status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0185 | ventilation | DOAS Unit | DOAS-RD1 | Roof Deck Mechanical | OA motorized damper command | AO | Damper Actuator | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0186 | ventilation | DOAS Unit | DOAS-RD1 | Roof Deck Mechanical | Recovery wheel motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0187 | ventilation | DOAS Unit | DOAS-RD1 | Roof Deck Mechanical | Recovery wheel trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0188 | ventilation | DOAS Unit | DOAS-RD1 | Roof Deck Mechanical | Supply fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0189 | ventilation | DOAS Unit | DOAS-RD1 | Roof Deck Mechanical | Supply fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0190 | ventilation | DOAS Unit | DOAS-RD1 | Roof Deck Mechanical | Supply fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0191 | ventilation | DOAS Unit | DOAS-RD1 | Roof Deck Mechanical | Supply fan VFD speed feedback | AI | VFD analog output | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0192 | ventilation | DOAS Unit | DOAS-RD1 | Roof Deck Mechanical | Supply fan VFD speed command | AO | 0-10V / 4-20 mA | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0193 | ventilation | DOAS Unit | DOAS-RD1 | Roof Deck Mechanical | Mixed air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0194 | ventilation | DOAS Unit | DOAS-RD1 | Roof Deck Mechanical | Mixed air humidity | AI | Duct RH Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0195 | ventilation | DOAS Unit | DOAS-RD1 | Roof Deck Mechanical | CHWS / cooling-coil valve status | DI | Auxiliary Contact | ME Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0196 | ventilation | DOAS Unit | DOAS-RD1 | Roof Deck Mechanical | CHWS / cooling-coil valve command | AO | Electric Valve Actuator | ME Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0197 | ventilation | DOAS Unit | DOAS-RD1 | Roof Deck Mechanical | Indoor supply air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0198 | ventilation | DOAS Unit | DOAS-RD1 | Roof Deck Mechanical | Indoor exhaust air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0199 | ventilation | DOAS Unit | DOAS-RD1 | Roof Deck Mechanical | Indoor exhaust air humidity | AI | Duct RH Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0200 | ventilation | DOAS Unit | DOAS-RD1 | Roof Deck Mechanical | Exhaust fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0201 | ventilation | DOAS Unit | DOAS-RD1 | Roof Deck Mechanical | Exhaust fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0202 | ventilation | DOAS Unit | DOAS-RD1 | Roof Deck Mechanical | Exhaust fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0203 | ventilation | DOAS Unit | DOAS-RD1 | Roof Deck Mechanical | Exhaust fan VFD speed feedback | AI | VFD analog output | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0204 | ventilation | DOAS Unit | DOAS-RD1 | Roof Deck Mechanical | Exhaust fan VFD speed command | AO | 0-10V / 4-20 mA | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0205 | ventilation | DOAS Unit | DOAS-RD1 | Roof Deck Mechanical | DOAS network HLI (VFDs, kWh) | HLI | BACnet/Modbus card | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0206 | ventilation | DOAS Unit | DOAS-RD1 | Roof Deck Mechanical | DOAS network drop | Network | BACnet/IP | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0207 | ventilation | DOAS Unit | DOAS-RD2 | Roof Deck Mechanical | Outside SA temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0208 | ventilation | DOAS Unit | DOAS-RD2 | Roof Deck Mechanical | Outside SA flow | AI | Air Flow Station | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0209 | ventilation | DOAS Unit | DOAS-RD2 | Roof Deck Mechanical | Outside SA humidity | AI | Duct RH Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0210 | ventilation | DOAS Unit | DOAS-RD2 | Roof Deck Mechanical | OA motorized damper status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0211 | ventilation | DOAS Unit | DOAS-RD2 | Roof Deck Mechanical | OA motorized damper command | AO | Damper Actuator | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0212 | ventilation | DOAS Unit | DOAS-RD2 | Roof Deck Mechanical | Recovery wheel motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0213 | ventilation | DOAS Unit | DOAS-RD2 | Roof Deck Mechanical | Recovery wheel trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0214 | ventilation | DOAS Unit | DOAS-RD2 | Roof Deck Mechanical | Supply fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0215 | ventilation | DOAS Unit | DOAS-RD2 | Roof Deck Mechanical | Supply fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0216 | ventilation | DOAS Unit | DOAS-RD2 | Roof Deck Mechanical | Supply fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0217 | ventilation | DOAS Unit | DOAS-RD2 | Roof Deck Mechanical | Supply fan VFD speed feedback | AI | VFD analog output | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0218 | ventilation | DOAS Unit | DOAS-RD2 | Roof Deck Mechanical | Supply fan VFD speed command | AO | 0-10V / 4-20 mA | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0219 | ventilation | DOAS Unit | DOAS-RD2 | Roof Deck Mechanical | Mixed air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0220 | ventilation | DOAS Unit | DOAS-RD2 | Roof Deck Mechanical | Mixed air humidity | AI | Duct RH Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0221 | ventilation | DOAS Unit | DOAS-RD2 | Roof Deck Mechanical | CHWS / cooling-coil valve status | DI | Auxiliary Contact | ME Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0222 | ventilation | DOAS Unit | DOAS-RD2 | Roof Deck Mechanical | CHWS / cooling-coil valve command | AO | Electric Valve Actuator | ME Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0223 | ventilation | DOAS Unit | DOAS-RD2 | Roof Deck Mechanical | Indoor supply air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0224 | ventilation | DOAS Unit | DOAS-RD2 | Roof Deck Mechanical | Indoor exhaust air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0225 | ventilation | DOAS Unit | DOAS-RD2 | Roof Deck Mechanical | Indoor exhaust air humidity | AI | Duct RH Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0226 | ventilation | DOAS Unit | DOAS-RD2 | Roof Deck Mechanical | Exhaust fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0227 | ventilation | DOAS Unit | DOAS-RD2 | Roof Deck Mechanical | Exhaust fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0228 | ventilation | DOAS Unit | DOAS-RD2 | Roof Deck Mechanical | Exhaust fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0229 | ventilation | DOAS Unit | DOAS-RD2 | Roof Deck Mechanical | Exhaust fan VFD speed feedback | AI | VFD analog output | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0230 | ventilation | DOAS Unit | DOAS-RD2 | Roof Deck Mechanical | Exhaust fan VFD speed command | AO | 0-10V / 4-20 mA | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0231 | ventilation | DOAS Unit | DOAS-RD2 | Roof Deck Mechanical | DOAS network HLI (VFDs, kWh) | HLI | BACnet/Modbus card | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0232 | ventilation | DOAS Unit | DOAS-RD2 | Roof Deck Mechanical | DOAS network drop | Network | BACnet/IP | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0233 | ventilation | DOAS Unit | DOAS-2F-CASINO | 2nd Floor Casino MVAC Room | Outside SA temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0234 | ventilation | DOAS Unit | DOAS-2F-CASINO | 2nd Floor Casino MVAC Room | Outside SA flow | AI | Air Flow Station | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0235 | ventilation | DOAS Unit | DOAS-2F-CASINO | 2nd Floor Casino MVAC Room | Outside SA humidity | AI | Duct RH Sensor | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0236 | ventilation | DOAS Unit | DOAS-2F-CASINO | 2nd Floor Casino MVAC Room | OA motorized damper status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0237 | ventilation | DOAS Unit | DOAS-2F-CASINO | 2nd Floor Casino MVAC Room | OA motorized damper command | AO | Damper Actuator | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0238 | ventilation | DOAS Unit | DOAS-2F-CASINO | 2nd Floor Casino MVAC Room | Recovery wheel motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0239 | ventilation | DOAS Unit | DOAS-2F-CASINO | 2nd Floor Casino MVAC Room | Recovery wheel trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0240 | ventilation | DOAS Unit | DOAS-2F-CASINO | 2nd Floor Casino MVAC Room | Supply fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0241 | ventilation | DOAS Unit | DOAS-2F-CASINO | 2nd Floor Casino MVAC Room | Supply fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0242 | ventilation | DOAS Unit | DOAS-2F-CASINO | 2nd Floor Casino MVAC Room | Supply fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0243 | ventilation | DOAS Unit | DOAS-2F-CASINO | 2nd Floor Casino MVAC Room | Supply fan VFD speed feedback | AI | VFD analog output | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0244 | ventilation | DOAS Unit | DOAS-2F-CASINO | 2nd Floor Casino MVAC Room | Supply fan VFD speed command | AO | 0-10V / 4-20 mA | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0245 | ventilation | DOAS Unit | DOAS-2F-CASINO | 2nd Floor Casino MVAC Room | Mixed air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0246 | ventilation | DOAS Unit | DOAS-2F-CASINO | 2nd Floor Casino MVAC Room | Mixed air humidity | AI | Duct RH Sensor | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0247 | ventilation | DOAS Unit | DOAS-2F-CASINO | 2nd Floor Casino MVAC Room | CHWS / cooling-coil valve status | DI | Auxiliary Contact | ME Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0248 | ventilation | DOAS Unit | DOAS-2F-CASINO | 2nd Floor Casino MVAC Room | CHWS / cooling-coil valve command | AO | Electric Valve Actuator | ME Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0249 | ventilation | DOAS Unit | DOAS-2F-CASINO | 2nd Floor Casino MVAC Room | Indoor supply air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0250 | ventilation | DOAS Unit | DOAS-2F-CASINO | 2nd Floor Casino MVAC Room | Indoor exhaust air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0251 | ventilation | DOAS Unit | DOAS-2F-CASINO | 2nd Floor Casino MVAC Room | Indoor exhaust air humidity | AI | Duct RH Sensor | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0252 | ventilation | DOAS Unit | DOAS-2F-CASINO | 2nd Floor Casino MVAC Room | Exhaust fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0253 | ventilation | DOAS Unit | DOAS-2F-CASINO | 2nd Floor Casino MVAC Room | Exhaust fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0254 | ventilation | DOAS Unit | DOAS-2F-CASINO | 2nd Floor Casino MVAC Room | Exhaust fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0255 | ventilation | DOAS Unit | DOAS-2F-CASINO | 2nd Floor Casino MVAC Room | Exhaust fan VFD speed feedback | AI | VFD analog output | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0256 | ventilation | DOAS Unit | DOAS-2F-CASINO | 2nd Floor Casino MVAC Room | Exhaust fan VFD speed command | AO | 0-10V / 4-20 mA | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0257 | ventilation | DOAS Unit | DOAS-2F-CASINO | 2nd Floor Casino MVAC Room | DOAS network HLI (VFDs, kWh) | HLI | BACnet/Modbus card | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0258 | ventilation | DOAS Unit | DOAS-2F-CASINO | 2nd Floor Casino MVAC Room | DOAS network drop | Network | BACnet/IP | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0259 | ventilation | Precooled Air Handling Unit | PAHU-01 | Roof Deck Mechanical | Outside SA temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0260 | ventilation | Precooled Air Handling Unit | PAHU-01 | Roof Deck Mechanical | Outside SA flow | AI | Air Flow Station | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0261 | ventilation | Precooled Air Handling Unit | PAHU-01 | Roof Deck Mechanical | OA motorized damper status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0262 | ventilation | Precooled Air Handling Unit | PAHU-01 | Roof Deck Mechanical | OA motorized damper command | AO | Damper Actuator | ME Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0263 | ventilation | Precooled Air Handling Unit | PAHU-01 | Roof Deck Mechanical | CHWS / cooling-coil valve command | AO | Electric Valve Actuator | ME Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0264 | ventilation | Precooled Air Handling Unit | PAHU-01 | Roof Deck Mechanical | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0265 | ventilation | Precooled Air Handling Unit | PAHU-01 | Roof Deck Mechanical | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0266 | ventilation | Precooled Air Handling Unit | PAHU-01 | Roof Deck Mechanical | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0267 | ventilation | Precooled Air Handling Unit | PAHU-01 | Roof Deck Mechanical | Fan VFD speed feedback | AI | VFD analog output | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0268 | ventilation | Precooled Air Handling Unit | PAHU-01 | Roof Deck Mechanical | Fan VFD speed command | AO | 0-10V / 4-20 mA | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0269 | ventilation | Precooled Air Handling Unit | PAHU-01 | Roof Deck Mechanical | Indoor supply air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0270 | ventilation | Precooled Air Handling Unit | PAHU-01 | Roof Deck Mechanical | Mixed air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0271 | ventilation | Precooled Air Handling Unit | PAHU-01 | Roof Deck Mechanical | Mixed air humidity | AI | Duct RH Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0272 | ventilation | Precooled Air Handling Unit | PAHU-01 | Roof Deck Mechanical | Filter differential pressure (high) | DI | Diff. Pressure Switch | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0273 | ventilation | Precooled Air Handling Unit | PAHU-01 | Roof Deck Mechanical | PAHU network HLI | HLI | BACnet/Modbus card | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0274 | ventilation | Precooled Air Handling Unit | PAHU-01 | Roof Deck Mechanical | PAHU network drop | Network | BACnet/IP | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0275 | ventilation | Precooled Air Handling Unit | PAHU-02 | Roof Deck Mechanical | Outside SA temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0276 | ventilation | Precooled Air Handling Unit | PAHU-02 | Roof Deck Mechanical | Outside SA flow | AI | Air Flow Station | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0277 | ventilation | Precooled Air Handling Unit | PAHU-02 | Roof Deck Mechanical | OA motorized damper status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0278 | ventilation | Precooled Air Handling Unit | PAHU-02 | Roof Deck Mechanical | OA motorized damper command | AO | Damper Actuator | ME Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0279 | ventilation | Precooled Air Handling Unit | PAHU-02 | Roof Deck Mechanical | CHWS / cooling-coil valve command | AO | Electric Valve Actuator | ME Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0280 | ventilation | Precooled Air Handling Unit | PAHU-02 | Roof Deck Mechanical | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0281 | ventilation | Precooled Air Handling Unit | PAHU-02 | Roof Deck Mechanical | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0282 | ventilation | Precooled Air Handling Unit | PAHU-02 | Roof Deck Mechanical | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0283 | ventilation | Precooled Air Handling Unit | PAHU-02 | Roof Deck Mechanical | Fan VFD speed feedback | AI | VFD analog output | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0284 | ventilation | Precooled Air Handling Unit | PAHU-02 | Roof Deck Mechanical | Fan VFD speed command | AO | 0-10V / 4-20 mA | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0285 | ventilation | Precooled Air Handling Unit | PAHU-02 | Roof Deck Mechanical | Indoor supply air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0286 | ventilation | Precooled Air Handling Unit | PAHU-02 | Roof Deck Mechanical | Mixed air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0287 | ventilation | Precooled Air Handling Unit | PAHU-02 | Roof Deck Mechanical | Mixed air humidity | AI | Duct RH Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0288 | ventilation | Precooled Air Handling Unit | PAHU-02 | Roof Deck Mechanical | Filter differential pressure (high) | DI | Diff. Pressure Switch | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0289 | ventilation | Precooled Air Handling Unit | PAHU-02 | Roof Deck Mechanical | PAHU network HLI | HLI | BACnet/Modbus card | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0290 | ventilation | Precooled Air Handling Unit | PAHU-02 | Roof Deck Mechanical | PAHU network drop | Network | BACnet/IP | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0291 | ventilation | Precooled Air Handling Unit | PAHU-03 | Roof Deck Mechanical | Outside SA temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0292 | ventilation | Precooled Air Handling Unit | PAHU-03 | Roof Deck Mechanical | Outside SA flow | AI | Air Flow Station | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0293 | ventilation | Precooled Air Handling Unit | PAHU-03 | Roof Deck Mechanical | OA motorized damper status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0294 | ventilation | Precooled Air Handling Unit | PAHU-03 | Roof Deck Mechanical | OA motorized damper command | AO | Damper Actuator | ME Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0295 | ventilation | Precooled Air Handling Unit | PAHU-03 | Roof Deck Mechanical | CHWS / cooling-coil valve command | AO | Electric Valve Actuator | ME Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0296 | ventilation | Precooled Air Handling Unit | PAHU-03 | Roof Deck Mechanical | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0297 | ventilation | Precooled Air Handling Unit | PAHU-03 | Roof Deck Mechanical | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0298 | ventilation | Precooled Air Handling Unit | PAHU-03 | Roof Deck Mechanical | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0299 | ventilation | Precooled Air Handling Unit | PAHU-03 | Roof Deck Mechanical | Fan VFD speed feedback | AI | VFD analog output | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0300 | ventilation | Precooled Air Handling Unit | PAHU-03 | Roof Deck Mechanical | Fan VFD speed command | AO | 0-10V / 4-20 mA | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0301 | ventilation | Precooled Air Handling Unit | PAHU-03 | Roof Deck Mechanical | Indoor supply air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0302 | ventilation | Precooled Air Handling Unit | PAHU-03 | Roof Deck Mechanical | Mixed air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0303 | ventilation | Precooled Air Handling Unit | PAHU-03 | Roof Deck Mechanical | Mixed air humidity | AI | Duct RH Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0304 | ventilation | Precooled Air Handling Unit | PAHU-03 | Roof Deck Mechanical | Filter differential pressure (high) | DI | Diff. Pressure Switch | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0305 | ventilation | Precooled Air Handling Unit | PAHU-03 | Roof Deck Mechanical | PAHU network HLI | HLI | BACnet/Modbus card | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0306 | ventilation | Precooled Air Handling Unit | PAHU-03 | Roof Deck Mechanical | PAHU network drop | Network | BACnet/IP | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0307 | ventilation | Precooled Air Handling Unit | PAHU-04 | Roof Deck Mechanical | Outside SA temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0308 | ventilation | Precooled Air Handling Unit | PAHU-04 | Roof Deck Mechanical | Outside SA flow | AI | Air Flow Station | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0309 | ventilation | Precooled Air Handling Unit | PAHU-04 | Roof Deck Mechanical | OA motorized damper status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0310 | ventilation | Precooled Air Handling Unit | PAHU-04 | Roof Deck Mechanical | OA motorized damper command | AO | Damper Actuator | ME Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0311 | ventilation | Precooled Air Handling Unit | PAHU-04 | Roof Deck Mechanical | CHWS / cooling-coil valve command | AO | Electric Valve Actuator | ME Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0312 | ventilation | Precooled Air Handling Unit | PAHU-04 | Roof Deck Mechanical | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0313 | ventilation | Precooled Air Handling Unit | PAHU-04 | Roof Deck Mechanical | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0314 | ventilation | Precooled Air Handling Unit | PAHU-04 | Roof Deck Mechanical | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0315 | ventilation | Precooled Air Handling Unit | PAHU-04 | Roof Deck Mechanical | Fan VFD speed feedback | AI | VFD analog output | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0316 | ventilation | Precooled Air Handling Unit | PAHU-04 | Roof Deck Mechanical | Fan VFD speed command | AO | 0-10V / 4-20 mA | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0317 | ventilation | Precooled Air Handling Unit | PAHU-04 | Roof Deck Mechanical | Indoor supply air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0318 | ventilation | Precooled Air Handling Unit | PAHU-04 | Roof Deck Mechanical | Mixed air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0319 | ventilation | Precooled Air Handling Unit | PAHU-04 | Roof Deck Mechanical | Mixed air humidity | AI | Duct RH Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0320 | ventilation | Precooled Air Handling Unit | PAHU-04 | Roof Deck Mechanical | Filter differential pressure (high) | DI | Diff. Pressure Switch | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0321 | ventilation | Precooled Air Handling Unit | PAHU-04 | Roof Deck Mechanical | PAHU network HLI | HLI | BACnet/Modbus card | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0322 | ventilation | Precooled Air Handling Unit | PAHU-04 | Roof Deck Mechanical | PAHU network drop | Network | BACnet/IP | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0323 | ventilation | Precooled Air Handling Unit | PAHU-05 | Roof Deck Mechanical | Outside SA temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0324 | ventilation | Precooled Air Handling Unit | PAHU-05 | Roof Deck Mechanical | Outside SA flow | AI | Air Flow Station | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0325 | ventilation | Precooled Air Handling Unit | PAHU-05 | Roof Deck Mechanical | OA motorized damper status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0326 | ventilation | Precooled Air Handling Unit | PAHU-05 | Roof Deck Mechanical | OA motorized damper command | AO | Damper Actuator | ME Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0327 | ventilation | Precooled Air Handling Unit | PAHU-05 | Roof Deck Mechanical | CHWS / cooling-coil valve command | AO | Electric Valve Actuator | ME Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0328 | ventilation | Precooled Air Handling Unit | PAHU-05 | Roof Deck Mechanical | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0329 | ventilation | Precooled Air Handling Unit | PAHU-05 | Roof Deck Mechanical | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0330 | ventilation | Precooled Air Handling Unit | PAHU-05 | Roof Deck Mechanical | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0331 | ventilation | Precooled Air Handling Unit | PAHU-05 | Roof Deck Mechanical | Fan VFD speed feedback | AI | VFD analog output | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0332 | ventilation | Precooled Air Handling Unit | PAHU-05 | Roof Deck Mechanical | Fan VFD speed command | AO | 0-10V / 4-20 mA | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0333 | ventilation | Precooled Air Handling Unit | PAHU-05 | Roof Deck Mechanical | Indoor supply air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0334 | ventilation | Precooled Air Handling Unit | PAHU-05 | Roof Deck Mechanical | Mixed air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0335 | ventilation | Precooled Air Handling Unit | PAHU-05 | Roof Deck Mechanical | Mixed air humidity | AI | Duct RH Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0336 | ventilation | Precooled Air Handling Unit | PAHU-05 | Roof Deck Mechanical | Filter differential pressure (high) | DI | Diff. Pressure Switch | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0337 | ventilation | Precooled Air Handling Unit | PAHU-05 | Roof Deck Mechanical | PAHU network HLI | HLI | BACnet/Modbus card | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0338 | ventilation | Precooled Air Handling Unit | PAHU-05 | Roof Deck Mechanical | PAHU network drop | Network | BACnet/IP | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0339 | ventilation | Precooled Air Handling Unit | PAHU-06 | Roof Deck Mechanical | Outside SA temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0340 | ventilation | Precooled Air Handling Unit | PAHU-06 | Roof Deck Mechanical | Outside SA flow | AI | Air Flow Station | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0341 | ventilation | Precooled Air Handling Unit | PAHU-06 | Roof Deck Mechanical | OA motorized damper status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0342 | ventilation | Precooled Air Handling Unit | PAHU-06 | Roof Deck Mechanical | OA motorized damper command | AO | Damper Actuator | ME Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0343 | ventilation | Precooled Air Handling Unit | PAHU-06 | Roof Deck Mechanical | CHWS / cooling-coil valve command | AO | Electric Valve Actuator | ME Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0344 | ventilation | Precooled Air Handling Unit | PAHU-06 | Roof Deck Mechanical | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0345 | ventilation | Precooled Air Handling Unit | PAHU-06 | Roof Deck Mechanical | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0346 | ventilation | Precooled Air Handling Unit | PAHU-06 | Roof Deck Mechanical | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0347 | ventilation | Precooled Air Handling Unit | PAHU-06 | Roof Deck Mechanical | Fan VFD speed feedback | AI | VFD analog output | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0348 | ventilation | Precooled Air Handling Unit | PAHU-06 | Roof Deck Mechanical | Fan VFD speed command | AO | 0-10V / 4-20 mA | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0349 | ventilation | Precooled Air Handling Unit | PAHU-06 | Roof Deck Mechanical | Indoor supply air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0350 | ventilation | Precooled Air Handling Unit | PAHU-06 | Roof Deck Mechanical | Mixed air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0351 | ventilation | Precooled Air Handling Unit | PAHU-06 | Roof Deck Mechanical | Mixed air humidity | AI | Duct RH Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0352 | ventilation | Precooled Air Handling Unit | PAHU-06 | Roof Deck Mechanical | Filter differential pressure (high) | DI | Diff. Pressure Switch | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0353 | ventilation | Precooled Air Handling Unit | PAHU-06 | Roof Deck Mechanical | PAHU network HLI | HLI | BACnet/Modbus card | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0354 | ventilation | Precooled Air Handling Unit | PAHU-06 | Roof Deck Mechanical | PAHU network drop | Network | BACnet/IP | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0355 | ventilation | Precooled Air Handling Unit | PAHU-07 | Roof Deck Mechanical | Outside SA temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0356 | ventilation | Precooled Air Handling Unit | PAHU-07 | Roof Deck Mechanical | Outside SA flow | AI | Air Flow Station | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0357 | ventilation | Precooled Air Handling Unit | PAHU-07 | Roof Deck Mechanical | OA motorized damper status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0358 | ventilation | Precooled Air Handling Unit | PAHU-07 | Roof Deck Mechanical | OA motorized damper command | AO | Damper Actuator | ME Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0359 | ventilation | Precooled Air Handling Unit | PAHU-07 | Roof Deck Mechanical | CHWS / cooling-coil valve command | AO | Electric Valve Actuator | ME Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0360 | ventilation | Precooled Air Handling Unit | PAHU-07 | Roof Deck Mechanical | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0361 | ventilation | Precooled Air Handling Unit | PAHU-07 | Roof Deck Mechanical | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0362 | ventilation | Precooled Air Handling Unit | PAHU-07 | Roof Deck Mechanical | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0363 | ventilation | Precooled Air Handling Unit | PAHU-07 | Roof Deck Mechanical | Fan VFD speed feedback | AI | VFD analog output | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0364 | ventilation | Precooled Air Handling Unit | PAHU-07 | Roof Deck Mechanical | Fan VFD speed command | AO | 0-10V / 4-20 mA | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0365 | ventilation | Precooled Air Handling Unit | PAHU-07 | Roof Deck Mechanical | Indoor supply air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0366 | ventilation | Precooled Air Handling Unit | PAHU-07 | Roof Deck Mechanical | Mixed air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0367 | ventilation | Precooled Air Handling Unit | PAHU-07 | Roof Deck Mechanical | Mixed air humidity | AI | Duct RH Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0368 | ventilation | Precooled Air Handling Unit | PAHU-07 | Roof Deck Mechanical | Filter differential pressure (high) | DI | Diff. Pressure Switch | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0369 | ventilation | Precooled Air Handling Unit | PAHU-07 | Roof Deck Mechanical | PAHU network HLI | HLI | BACnet/Modbus card | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0370 | ventilation | Precooled Air Handling Unit | PAHU-07 | Roof Deck Mechanical | PAHU network drop | Network | BACnet/IP | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0371 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor Casino MVAC Room | Return air motorized damper status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0372 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor Casino MVAC Room | Return air motorized damper command | AO | Damper Actuator | ME Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0373 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor Casino MVAC Room | Return air CO2 (DCV) | AI | CO2 Sensor | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0374 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor Casino MVAC Room | Return air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0375 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor Casino MVAC Room | Mixed air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0376 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor Casino MVAC Room | Supply air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0377 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor Casino MVAC Room | CHWS valve command | AO | Electric Valve Actuator | ME Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0378 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor Casino MVAC Room | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0379 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor Casino MVAC Room | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0380 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor Casino MVAC Room | Fan VFD speed command | AO | 0-10V / 4-20 mA | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0381 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor Casino MVAC Room | Fan VFD speed feedback | AI | VFD analog output | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0382 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor Casino MVAC Room | OA motorized damper status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0383 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor Casino MVAC Room | OA motorized damper command | AO | Damper Actuator | ME Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0384 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor Casino MVAC Room | Outside SA temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0385 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor Casino MVAC Room | Filter differential pressure | DI | Diff. Pressure Switch | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0386 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor Casino MVAC Room | AHU network HLI | HLI | BACnet/Modbus card | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0387 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor Casino MVAC Room | Casino return-air CO sensor | AI | CO Sensor | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0388 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor Casino MVAC Room | Return air motorized damper status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0389 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor Casino MVAC Room | Return air motorized damper command | AO | Damper Actuator | ME Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0390 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor Casino MVAC Room | Return air CO2 (DCV) | AI | CO2 Sensor | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0391 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor Casino MVAC Room | Return air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0392 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor Casino MVAC Room | Mixed air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0393 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor Casino MVAC Room | Supply air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0394 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor Casino MVAC Room | CHWS valve command | AO | Electric Valve Actuator | ME Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0395 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor Casino MVAC Room | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0396 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor Casino MVAC Room | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0397 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor Casino MVAC Room | Fan VFD speed command | AO | 0-10V / 4-20 mA | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0398 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor Casino MVAC Room | Fan VFD speed feedback | AI | VFD analog output | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0399 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor Casino MVAC Room | OA motorized damper status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0400 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor Casino MVAC Room | OA motorized damper command | AO | Damper Actuator | ME Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0401 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor Casino MVAC Room | Outside SA temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0402 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor Casino MVAC Room | Filter differential pressure | DI | Diff. Pressure Switch | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0403 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor Casino MVAC Room | AHU network HLI | HLI | BACnet/Modbus card | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0404 | casino_mvac | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor Casino MVAC Room | Casino return-air CO sensor | AI | CO Sensor | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0405 | common_area | AHU (Chilled-Water-Served) | AHU-GF-1 | Ground Floor BOH | Return air motorized damper status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0406 | common_area | AHU (Chilled-Water-Served) | AHU-GF-1 | Ground Floor BOH | Return air motorized damper command | AO | Damper Actuator | ME Contractor | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0407 | common_area | AHU (Chilled-Water-Served) | AHU-GF-1 | Ground Floor BOH | Return air CO2 (DCV) | AI | CO2 Sensor | BMS Contractor | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0408 | common_area | AHU (Chilled-Water-Served) | AHU-GF-1 | Ground Floor BOH | Return air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0409 | common_area | AHU (Chilled-Water-Served) | AHU-GF-1 | Ground Floor BOH | Mixed air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0410 | common_area | AHU (Chilled-Water-Served) | AHU-GF-1 | Ground Floor BOH | Supply air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0411 | common_area | AHU (Chilled-Water-Served) | AHU-GF-1 | Ground Floor BOH | CHWS valve command | AO | Electric Valve Actuator | ME Contractor | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0412 | common_area | AHU (Chilled-Water-Served) | AHU-GF-1 | Ground Floor BOH | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0413 | common_area | AHU (Chilled-Water-Served) | AHU-GF-1 | Ground Floor BOH | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0414 | common_area | AHU (Chilled-Water-Served) | AHU-GF-1 | Ground Floor BOH | Fan VFD speed command | AO | 0-10V / 4-20 mA | BMS Contractor | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0415 | common_area | AHU (Chilled-Water-Served) | AHU-GF-1 | Ground Floor BOH | Fan VFD speed feedback | AI | VFD analog output | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0416 | common_area | AHU (Chilled-Water-Served) | AHU-GF-1 | Ground Floor BOH | OA motorized damper status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0417 | common_area | AHU (Chilled-Water-Served) | AHU-GF-1 | Ground Floor BOH | OA motorized damper command | AO | Damper Actuator | ME Contractor | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0418 | common_area | AHU (Chilled-Water-Served) | AHU-GF-1 | Ground Floor BOH | Outside SA temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0419 | common_area | AHU (Chilled-Water-Served) | AHU-GF-1 | Ground Floor BOH | Filter differential pressure | DI | Diff. Pressure Switch | BMS Contractor | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0420 | common_area | AHU (Chilled-Water-Served) | AHU-GF-1 | Ground Floor BOH | AHU network HLI | HLI | BACnet/Modbus card | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0421 | common_area | AHU (Chilled-Water-Served) | AHU-GFM-1 | Ground Floor Mezzanine BOH | Return air motorized damper status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0422 | common_area | AHU (Chilled-Water-Served) | AHU-GFM-1 | Ground Floor Mezzanine BOH | Return air motorized damper command | AO | Damper Actuator | ME Contractor | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0423 | common_area | AHU (Chilled-Water-Served) | AHU-GFM-1 | Ground Floor Mezzanine BOH | Return air CO2 (DCV) | AI | CO2 Sensor | BMS Contractor | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0424 | common_area | AHU (Chilled-Water-Served) | AHU-GFM-1 | Ground Floor Mezzanine BOH | Return air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0425 | common_area | AHU (Chilled-Water-Served) | AHU-GFM-1 | Ground Floor Mezzanine BOH | Mixed air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0426 | common_area | AHU (Chilled-Water-Served) | AHU-GFM-1 | Ground Floor Mezzanine BOH | Supply air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0427 | common_area | AHU (Chilled-Water-Served) | AHU-GFM-1 | Ground Floor Mezzanine BOH | CHWS valve command | AO | Electric Valve Actuator | ME Contractor | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0428 | common_area | AHU (Chilled-Water-Served) | AHU-GFM-1 | Ground Floor Mezzanine BOH | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0429 | common_area | AHU (Chilled-Water-Served) | AHU-GFM-1 | Ground Floor Mezzanine BOH | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0430 | common_area | AHU (Chilled-Water-Served) | AHU-GFM-1 | Ground Floor Mezzanine BOH | Fan VFD speed command | AO | 0-10V / 4-20 mA | BMS Contractor | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0431 | common_area | AHU (Chilled-Water-Served) | AHU-GFM-1 | Ground Floor Mezzanine BOH | Fan VFD speed feedback | AI | VFD analog output | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0432 | common_area | AHU (Chilled-Water-Served) | AHU-GFM-1 | Ground Floor Mezzanine BOH | OA motorized damper status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0433 | common_area | AHU (Chilled-Water-Served) | AHU-GFM-1 | Ground Floor Mezzanine BOH | OA motorized damper command | AO | Damper Actuator | ME Contractor | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0434 | common_area | AHU (Chilled-Water-Served) | AHU-GFM-1 | Ground Floor Mezzanine BOH | Outside SA temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0435 | common_area | AHU (Chilled-Water-Served) | AHU-GFM-1 | Ground Floor Mezzanine BOH | Filter differential pressure | DI | Diff. Pressure Switch | BMS Contractor | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0436 | common_area | AHU (Chilled-Water-Served) | AHU-GFM-1 | Ground Floor Mezzanine BOH | AHU network HLI | HLI | BACnet/Modbus card | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0437 | common_area | AHU (Chilled-Water-Served) | AHU-2F-1 | 2nd Floor BOH | Return air motorized damper status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0438 | common_area | AHU (Chilled-Water-Served) | AHU-2F-1 | 2nd Floor BOH | Return air motorized damper command | AO | Damper Actuator | ME Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0439 | common_area | AHU (Chilled-Water-Served) | AHU-2F-1 | 2nd Floor BOH | Return air CO2 (DCV) | AI | CO2 Sensor | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0440 | common_area | AHU (Chilled-Water-Served) | AHU-2F-1 | 2nd Floor BOH | Return air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0441 | common_area | AHU (Chilled-Water-Served) | AHU-2F-1 | 2nd Floor BOH | Mixed air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0442 | common_area | AHU (Chilled-Water-Served) | AHU-2F-1 | 2nd Floor BOH | Supply air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0443 | common_area | AHU (Chilled-Water-Served) | AHU-2F-1 | 2nd Floor BOH | CHWS valve command | AO | Electric Valve Actuator | ME Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0444 | common_area | AHU (Chilled-Water-Served) | AHU-2F-1 | 2nd Floor BOH | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0445 | common_area | AHU (Chilled-Water-Served) | AHU-2F-1 | 2nd Floor BOH | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0446 | common_area | AHU (Chilled-Water-Served) | AHU-2F-1 | 2nd Floor BOH | Fan VFD speed command | AO | 0-10V / 4-20 mA | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0447 | common_area | AHU (Chilled-Water-Served) | AHU-2F-1 | 2nd Floor BOH | Fan VFD speed feedback | AI | VFD analog output | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0448 | common_area | AHU (Chilled-Water-Served) | AHU-2F-1 | 2nd Floor BOH | OA motorized damper status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0449 | common_area | AHU (Chilled-Water-Served) | AHU-2F-1 | 2nd Floor BOH | OA motorized damper command | AO | Damper Actuator | ME Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0450 | common_area | AHU (Chilled-Water-Served) | AHU-2F-1 | 2nd Floor BOH | Outside SA temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0451 | common_area | AHU (Chilled-Water-Served) | AHU-2F-1 | 2nd Floor BOH | Filter differential pressure | DI | Diff. Pressure Switch | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0452 | common_area | AHU (Chilled-Water-Served) | AHU-2F-1 | 2nd Floor BOH | AHU network HLI | HLI | BACnet/Modbus card | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0453 | common_area | AHU (Chilled-Water-Served) | AHU-B1-1 | Basement 1 BOH | Return air motorized damper status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0454 | common_area | AHU (Chilled-Water-Served) | AHU-B1-1 | Basement 1 BOH | Return air motorized damper command | AO | Damper Actuator | ME Contractor | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0455 | common_area | AHU (Chilled-Water-Served) | AHU-B1-1 | Basement 1 BOH | Return air CO2 (DCV) | AI | CO2 Sensor | BMS Contractor | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0456 | common_area | AHU (Chilled-Water-Served) | AHU-B1-1 | Basement 1 BOH | Return air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0457 | common_area | AHU (Chilled-Water-Served) | AHU-B1-1 | Basement 1 BOH | Mixed air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0458 | common_area | AHU (Chilled-Water-Served) | AHU-B1-1 | Basement 1 BOH | Supply air temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0459 | common_area | AHU (Chilled-Water-Served) | AHU-B1-1 | Basement 1 BOH | CHWS valve command | AO | Electric Valve Actuator | ME Contractor | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0460 | common_area | AHU (Chilled-Water-Served) | AHU-B1-1 | Basement 1 BOH | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0461 | common_area | AHU (Chilled-Water-Served) | AHU-B1-1 | Basement 1 BOH | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0462 | common_area | AHU (Chilled-Water-Served) | AHU-B1-1 | Basement 1 BOH | Fan VFD speed command | AO | 0-10V / 4-20 mA | BMS Contractor | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0463 | common_area | AHU (Chilled-Water-Served) | AHU-B1-1 | Basement 1 BOH | Fan VFD speed feedback | AI | VFD analog output | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0464 | common_area | AHU (Chilled-Water-Served) | AHU-B1-1 | Basement 1 BOH | OA motorized damper status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0465 | common_area | AHU (Chilled-Water-Served) | AHU-B1-1 | Basement 1 BOH | OA motorized damper command | AO | Damper Actuator | ME Contractor | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0466 | common_area | AHU (Chilled-Water-Served) | AHU-B1-1 | Basement 1 BOH | Outside SA temperature | AI | Duct Temp Sensor | BMS Contractor | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0467 | common_area | AHU (Chilled-Water-Served) | AHU-B1-1 | Basement 1 BOH | Filter differential pressure | DI | Diff. Pressure Switch | BMS Contractor | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0468 | common_area | AHU (Chilled-Water-Served) | AHU-B1-1 | Basement 1 BOH | AHU network HLI | HLI | BACnet/Modbus card | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0469 | casino_mvac | Ozone Generator (UV-light or Corona) | ION-2F-1 | 2nd Floor Casino | Ionizer run status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0470 | casino_mvac | Ozone Generator (UV-light or Corona) | ION-2F-1 | 2nd Floor Casino | Ionizer fault status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0471 | casino_mvac | Ozone Generator (UV-light or Corona) | ION-2F-2 | 2nd Floor Casino | Ionizer run status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0472 | casino_mvac | Ozone Generator (UV-light or Corona) | ION-2F-2 | 2nd Floor Casino | Ionizer fault status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0473 | ventilation | Exhaust Fan (Toilet) | TEF-2.1 | 2nd Floor BOH | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0474 | ventilation | Exhaust Fan (Toilet) | TEF-2.1 | 2nd Floor BOH | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0475 | ventilation | Exhaust Fan (Toilet) | TEF-2.1 | 2nd Floor BOH | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0476 | ventilation | Exhaust Fan (Toilet) | TEF-2.3 | 2nd Floor BOH | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0477 | ventilation | Exhaust Fan (Toilet) | TEF-2.3 | 2nd Floor BOH | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0478 | ventilation | Exhaust Fan (Toilet) | TEF-2.3 | 2nd Floor BOH | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0479 | ventilation | Exhaust Fan (Toilet) | TEF-2B.3 | 2nd Floor BOH | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0480 | ventilation | Exhaust Fan (Toilet) | TEF-2B.3 | 2nd Floor BOH | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0481 | ventilation | Exhaust Fan (Toilet) | TEF-2B.3 | 2nd Floor BOH | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0482 | ventilation | Exhaust Fan (Toilet) | TEF-GS.1 | Ground Floor | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0483 | ventilation | Exhaust Fan (Toilet) | TEF-GS.1 | Ground Floor | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0484 | ventilation | Exhaust Fan (Toilet) | TEF-GS.1 | Ground Floor | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0485 | ventilation | Exhaust Fan (Toilet) | TEF-GS.2 | Ground Floor | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0486 | ventilation | Exhaust Fan (Toilet) | TEF-GS.2 | Ground Floor | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0487 | ventilation | Exhaust Fan (Toilet) | TEF-GS.2 | Ground Floor | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0488 | ventilation | Exhaust Fan (Toilet) | TEF-1.1 | Ground Floor Lobby | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0489 | ventilation | Exhaust Fan (Toilet) | TEF-1.1 | Ground Floor Lobby | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0490 | ventilation | Exhaust Fan (Toilet) | TEF-1.1 | Ground Floor Lobby | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0491 | ventilation | Exhaust Fan (Toilet) | TEF-1.2 | Ground Floor Lobby | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0492 | ventilation | Exhaust Fan (Toilet) | TEF-1.2 | Ground Floor Lobby | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0493 | ventilation | Exhaust Fan (Toilet) | TEF-1.2 | Ground Floor Lobby | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0494 | ventilation | Exhaust Fan (Toilet) | TEF-1.3 | Ground Floor Lobby | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0495 | ventilation | Exhaust Fan (Toilet) | TEF-1.3 | Ground Floor Lobby | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0496 | ventilation | Exhaust Fan (Toilet) | TEF-1.3 | Ground Floor Lobby | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0497 | ventilation | Exhaust Fan (Toilet) | TEF-1.4 | Ground Floor Lobby | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0498 | ventilation | Exhaust Fan (Toilet) | TEF-1.4 | Ground Floor Lobby | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0499 | ventilation | Exhaust Fan (Toilet) | TEF-1.4 | Ground Floor Lobby | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0500 | ventilation | Exhaust Fan (Toilet) | TEF-3A.1 | 3rd Floor Amenity | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0501 | ventilation | Exhaust Fan (Toilet) | TEF-3A.1 | 3rd Floor Amenity | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0502 | ventilation | Exhaust Fan (Toilet) | TEF-3A.1 | 3rd Floor Amenity | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0503 | ventilation | Exhaust Fan (Toilet) | TEF-3A.2 | 3rd Floor Amenity | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0504 | ventilation | Exhaust Fan (Toilet) | TEF-3A.2 | 3rd Floor Amenity | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0505 | ventilation | Exhaust Fan (Toilet) | TEF-3A.2 | 3rd Floor Amenity | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0506 | ventilation | Exhaust Fan (Toilet) | TEF-3B | 3rd Floor Amenity | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0507 | ventilation | Exhaust Fan (Toilet) | TEF-3B | 3rd Floor Amenity | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0508 | ventilation | Exhaust Fan (Toilet) | TEF-3B | 3rd Floor Amenity | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0509 | ventilation | Exhaust Fan (Toilet) | TEF-3C.1 | 3rd Floor Amenity | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0510 | ventilation | Exhaust Fan (Toilet) | TEF-3C.1 | 3rd Floor Amenity | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0511 | ventilation | Exhaust Fan (Toilet) | TEF-3C.1 | 3rd Floor Amenity | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0512 | ventilation | Exhaust Fan (Toilet) | TEF-3C.2 | 3rd Floor Amenity | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0513 | ventilation | Exhaust Fan (Toilet) | TEF-3C.2 | 3rd Floor Amenity | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0514 | ventilation | Exhaust Fan (Toilet) | TEF-3C.2 | 3rd Floor Amenity | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0515 | ventilation | Exhaust Fan (Toilet) | TEF-3D.1 | 3rd Floor Amenity | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0516 | ventilation | Exhaust Fan (Toilet) | TEF-3D.1 | 3rd Floor Amenity | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0517 | ventilation | Exhaust Fan (Toilet) | TEF-3D.1 | 3rd Floor Amenity | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0518 | ventilation | Exhaust Fan (Toilet) | TEF-3D.2 | 3rd Floor Amenity | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0519 | ventilation | Exhaust Fan (Toilet) | TEF-3D.2 | 3rd Floor Amenity | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0520 | ventilation | Exhaust Fan (Toilet) | TEF-3D.2 | 3rd Floor Amenity | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0521 | ventilation | Exhaust Fan (Toilet) | TEF-3D.3 | 3rd Floor Amenity | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0522 | ventilation | Exhaust Fan (Toilet) | TEF-3D.3 | 3rd Floor Amenity | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0523 | ventilation | Exhaust Fan (Toilet) | TEF-3D.3 | 3rd Floor Amenity | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0524 | ventilation | Exhaust Fan (Toilet) | TEF-3D.4 | 3rd Floor Amenity | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0525 | ventilation | Exhaust Fan (Toilet) | TEF-3D.4 | 3rd Floor Amenity | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0526 | ventilation | Exhaust Fan (Toilet) | TEF-3D.4 | 3rd Floor Amenity | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0527 | ventilation | Exhaust Fan (Toilet) | TEF-3D.5 | 3rd Floor Amenity | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0528 | ventilation | Exhaust Fan (Toilet) | TEF-3D.5 | 3rd Floor Amenity | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0529 | ventilation | Exhaust Fan (Toilet) | TEF-3D.5 | 3rd Floor Amenity | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0530 | ventilation | Exhaust Fan (Toilet) | TEF-3D.6 | 3rd Floor Amenity | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0531 | ventilation | Exhaust Fan (Toilet) | TEF-3D.6 | 3rd Floor Amenity | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0532 | ventilation | Exhaust Fan (Toilet) | TEF-3D.6 | 3rd Floor Amenity | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0533 | ventilation | Exhaust Fan (Toilet) | TEF-3D.7 | 3rd Floor Amenity | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0534 | ventilation | Exhaust Fan (Toilet) | TEF-3D.7 | 3rd Floor Amenity | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0535 | ventilation | Exhaust Fan (Toilet) | TEF-3D.7 | 3rd Floor Amenity | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0536 | ventilation | Exhaust Fan (Toilet) | TEF-3D.8 | 3rd Floor Amenity | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0537 | ventilation | Exhaust Fan (Toilet) | TEF-3D.8 | 3rd Floor Amenity | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0538 | ventilation | Exhaust Fan (Toilet) | TEF-3D.8 | 3rd Floor Amenity | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0539 | ventilation | Exhaust Fan (Toilet) | TEF-3D.9 | 3rd Floor Amenity | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0540 | ventilation | Exhaust Fan (Toilet) | TEF-3D.9 | 3rd Floor Amenity | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0541 | ventilation | Exhaust Fan (Toilet) | TEF-3D.9 | 3rd Floor Amenity | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0542 | ventilation | Exhaust Fan (Toilet) | TEF-3D.10 | 3rd Floor Amenity | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0543 | ventilation | Exhaust Fan (Toilet) | TEF-3D.10 | 3rd Floor Amenity | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0544 | ventilation | Exhaust Fan (Toilet) | TEF-3D.10 | 3rd Floor Amenity | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0545 | ventilation | Exhaust Fan (Toilet) | TEF-3D.11 | 3rd Floor Amenity | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0546 | ventilation | Exhaust Fan (Toilet) | TEF-3D.11 | 3rd Floor Amenity | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0547 | ventilation | Exhaust Fan (Toilet) | TEF-3D.11 | 3rd Floor Amenity | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0548 | ventilation | Exhaust Fan (Toilet) | TEF-3D.12 | 3rd Floor Amenity | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0549 | ventilation | Exhaust Fan (Toilet) | TEF-3D.12 | 3rd Floor Amenity | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0550 | ventilation | Exhaust Fan (Toilet) | TEF-3D.12 | 3rd Floor Amenity | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0551 | ventilation | Exhaust Fan (Toilet) | TEF-3D.13 | 3rd Floor Amenity | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0552 | ventilation | Exhaust Fan (Toilet) | TEF-3D.13 | 3rd Floor Amenity | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0553 | ventilation | Exhaust Fan (Toilet) | TEF-3D.13 | 3rd Floor Amenity | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0554 | ventilation | Exhaust Fan (Toilet) | TEF-3D.14 | 3rd Floor Amenity | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0555 | ventilation | Exhaust Fan (Toilet) | TEF-3D.14 | 3rd Floor Amenity | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0556 | ventilation | Exhaust Fan (Toilet) | TEF-3D.14 | 3rd Floor Amenity | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0557 | ventilation | Exhaust Fan (Toilet) | TEF-3D.15 | 3rd Floor Amenity | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0558 | ventilation | Exhaust Fan (Toilet) | TEF-3D.15 | 3rd Floor Amenity | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0559 | ventilation | Exhaust Fan (Toilet) | TEF-3D.15 | 3rd Floor Amenity | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0560 | ventilation | Exhaust Fan (Toilet) | TEF-3D.16 | 3rd Floor Amenity | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0561 | ventilation | Exhaust Fan (Toilet) | TEF-3D.16 | 3rd Floor Amenity | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0562 | ventilation | Exhaust Fan (Toilet) | TEF-3D.16 | 3rd Floor Amenity | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0563 | ventilation | Exhaust Fan (Toilet) | TEF-3D.17 | 3rd Floor Amenity | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0564 | ventilation | Exhaust Fan (Toilet) | TEF-3D.17 | 3rd Floor Amenity | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0565 | ventilation | Exhaust Fan (Toilet) | TEF-3D.17 | 3rd Floor Amenity | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0566 | ventilation | Exhaust Fan (Toilet) | TEF-3D.18 | 3rd Floor Amenity | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0567 | ventilation | Exhaust Fan (Toilet) | TEF-3D.18 | 3rd Floor Amenity | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0568 | ventilation | Exhaust Fan (Toilet) | TEF-3D.18 | 3rd Floor Amenity | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0569 | ventilation | Exhaust Fan (Toilet) | TEF-3D.19 | 3rd Floor Amenity | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0570 | ventilation | Exhaust Fan (Toilet) | TEF-3D.19 | 3rd Floor Amenity | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0571 | ventilation | Exhaust Fan (Toilet) | TEF-3D.19 | 3rd Floor Amenity | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0572 | ventilation | Exhaust Fan (Toilet) | TEF-3D.20 | 3rd Floor Amenity | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0573 | ventilation | Exhaust Fan (Toilet) | TEF-3D.20 | 3rd Floor Amenity | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0574 | ventilation | Exhaust Fan (Toilet) | TEF-3D.20 | 3rd Floor Amenity | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0575 | ventilation | Exhaust Fan (Toilet) | TEF-B.1 | Basement 1 | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0576 | ventilation | Exhaust Fan (Toilet) | TEF-B.1 | Basement 1 | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0577 | ventilation | Exhaust Fan (Toilet) | TEF-B.1 | Basement 1 | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0578 | ventilation | Exhaust Fan (Toilet) | TEF-B.2 | Basement 1 | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0579 | ventilation | Exhaust Fan (Toilet) | TEF-B.2 | Basement 1 | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0580 | ventilation | Exhaust Fan (Toilet) | TEF-B.2 | Basement 1 | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0581 | ventilation | Exhaust Fan (Toilet) | TEF-B.3 | Basement 1 | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0582 | ventilation | Exhaust Fan (Toilet) | TEF-B.3 | Basement 1 | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0583 | ventilation | Exhaust Fan (Toilet) | TEF-B.3 | Basement 1 | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0584 | ventilation | Exhaust Fan (Toilet) | TEF-B.4 | Basement 1 | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0585 | ventilation | Exhaust Fan (Toilet) | TEF-B.4 | Basement 1 | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0586 | ventilation | Exhaust Fan (Toilet) | TEF-B.4 | Basement 1 | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0587 | ventilation | Exhaust Fan (Toilet) | TEF-B.5 | Basement 1 | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0588 | ventilation | Exhaust Fan (Toilet) | TEF-B.5 | Basement 1 | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0589 | ventilation | Exhaust Fan (Toilet) | TEF-B.5 | Basement 1 | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0590 | ventilation | Exhaust Fan (Toilet) | TEF-B.6 | Basement 1 | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0591 | ventilation | Exhaust Fan (Toilet) | TEF-B.6 | Basement 1 | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0592 | ventilation | Exhaust Fan (Toilet) | TEF-B.6 | Basement 1 | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0593 | ventilation | Exhaust Fan (Toilet) | TEF-B.7 | Basement 1 | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0594 | ventilation | Exhaust Fan (Toilet) | TEF-B.7 | Basement 1 | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0595 | ventilation | Exhaust Fan (Toilet) | TEF-B.7 | Basement 1 | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0596 | ventilation | Exhaust Fan (Toilet) | TEF-B.8 | Basement 1 | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0597 | ventilation | Exhaust Fan (Toilet) | TEF-B.8 | Basement 1 | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0598 | ventilation | Exhaust Fan (Toilet) | TEF-B.8 | Basement 1 | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0599 | ventilation | Exhaust Fan (Toilet) | TEF-B.9 | Basement 1 | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0600 | ventilation | Exhaust Fan (Toilet) | TEF-B.9 | Basement 1 | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0601 | ventilation | Exhaust Fan (Toilet) | TEF-B.9 | Basement 1 | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0602 | ventilation | Exhaust Fan (Toilet) | TEF-B.10 | Basement 1 | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0603 | ventilation | Exhaust Fan (Toilet) | TEF-B.10 | Basement 1 | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0604 | ventilation | Exhaust Fan (Toilet) | TEF-B.10 | Basement 1 | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0605 | ventilation | Exhaust Fan (Toilet) | TEF-B.11 | Basement 1 | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0606 | ventilation | Exhaust Fan (Toilet) | TEF-B.11 | Basement 1 | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0607 | ventilation | Exhaust Fan (Toilet) | TEF-B.11 | Basement 1 | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0608 | ventilation | Exhaust Fan (Toilet) | TEF-B.12 | Basement 1 | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0609 | ventilation | Exhaust Fan (Toilet) | TEF-B.12 | Basement 1 | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0610 | ventilation | Exhaust Fan (Toilet) | TEF-B.12 | Basement 1 | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0611 | ventilation | Exhaust Fan (Toilet) | TEF-B.13 | Basement 1 | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0612 | ventilation | Exhaust Fan (Toilet) | TEF-B.13 | Basement 1 | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0613 | ventilation | Exhaust Fan (Toilet) | TEF-B.13 | Basement 1 | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0614 | ventilation | Exhaust Fan (Toilet) | TEF-B.14 | Basement 1 | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0615 | ventilation | Exhaust Fan (Toilet) | TEF-B.14 | Basement 1 | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0616 | ventilation | Exhaust Fan (Toilet) | TEF-B.14 | Basement 1 | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0617 | ventilation | Exhaust Fan (Toilet) | TEF-B.15 | Basement 1 | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0618 | ventilation | Exhaust Fan (Toilet) | TEF-B.15 | Basement 1 | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0619 | ventilation | Exhaust Fan (Toilet) | TEF-B.15 | Basement 1 | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0620 | ventilation | Exhaust Fan (Toilet) | TEF-B.16 | Basement 1 | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0621 | ventilation | Exhaust Fan (Toilet) | TEF-B.16 | Basement 1 | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0622 | ventilation | Exhaust Fan (Toilet) | TEF-B.16 | Basement 1 | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-B1 | BMS Points list (TUEC) + ME/PL Points list | |
| P0623 | ventilation | Exhaust Fan (Toilet) | TEF-RD.1 | Roof Deck | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0624 | ventilation | Exhaust Fan (Toilet) | TEF-RD.1 | Roof Deck | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0625 | ventilation | Exhaust Fan (Toilet) | TEF-RD.1 | Roof Deck | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0626 | ventilation | Exhaust Fan (Toilet) | TEF-RD.2 | Roof Deck | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0627 | ventilation | Exhaust Fan (Toilet) | TEF-RD.2 | Roof Deck | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0628 | ventilation | Exhaust Fan (Toilet) | TEF-RD.2 | Roof Deck | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0629 | ventilation | Exhaust Fan (Toilet) | TEF-RD.3 | Roof Deck | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0630 | ventilation | Exhaust Fan (Toilet) | TEF-RD.3 | Roof Deck | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0631 | ventilation | Exhaust Fan (Toilet) | TEF-RD.3 | Roof Deck | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0632 | ventilation | Exhaust Fan (General) | EF-1.2A | Ground Floor Lobby | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0633 | ventilation | Exhaust Fan (General) | EF-1.2A | Ground Floor Lobby | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0634 | ventilation | Exhaust Fan (General) | EF-1.2A | Ground Floor Lobby | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0635 | ventilation | Exhaust Fan (General) | EF-LPG.1 | Ground Floor Lobby | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0636 | ventilation | Exhaust Fan (General) | EF-LPG.1 | Ground Floor Lobby | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0637 | ventilation | Exhaust Fan (General) | EF-LPG.1 | Ground Floor Lobby | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0638 | ventilation | Exhaust Fan (General) | EF-1MR.1 | Ground Floor Lobby | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0639 | ventilation | Exhaust Fan (General) | EF-1MR.1 | Ground Floor Lobby | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0640 | ventilation | Exhaust Fan (General) | EF-1MR.1 | Ground Floor Lobby | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0641 | ventilation | Exhaust Fan (General) | EF-1STO.1 | Ground Floor Lobby | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0642 | ventilation | Exhaust Fan (General) | EF-1STO.1 | Ground Floor Lobby | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0643 | ventilation | Exhaust Fan (General) | EF-1STO.1 | Ground Floor Lobby | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0644 | ventilation | Exhaust Fan (General) | EF-MRF.1 | Ground Floor Lobby | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0645 | ventilation | Exhaust Fan (General) | EF-MRF.1 | Ground Floor Lobby | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0646 | ventilation | Exhaust Fan (General) | EF-MRF.1 | Ground Floor Lobby | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0647 | ventilation | Exhaust Fan (General) | EF-RD.1 | Roof Deck | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0648 | ventilation | Exhaust Fan (General) | EF-RD.1 | Roof Deck | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0649 | ventilation | Exhaust Fan (General) | EF-RD.1 | Roof Deck | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0650 | ventilation | Exhaust Fan (General) | EF-RD.2 | Roof Deck | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0651 | ventilation | Exhaust Fan (General) | EF-RD.2 | Roof Deck | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0652 | ventilation | Exhaust Fan (General) | EF-RD.2 | Roof Deck | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0653 | ventilation | Exhaust Fan (General) | EF-1 | Roof Deck | Fan motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0654 | ventilation | Exhaust Fan (General) | EF-1 | Roof Deck | Fan H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0655 | ventilation | Exhaust Fan (General) | EF-1 | Roof Deck | Fan trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0656 | hot_water | Calorifier (Hot Water Storage Tank) | HWT-LZ-1 | Lower Ground HW Plant | Tank temperature | AI | Temperature Sensor | BMS Contractor | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0657 | hot_water | Heat Pump | HP-LZ-1 | Lower Ground HW Plant | Pump motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0658 | hot_water | Heat Pump | HP-LZ-1 | Lower Ground HW Plant | Pump motor H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0659 | hot_water | Heat Pump | HP-LZ-1 | Lower Ground HW Plant | Pump motor trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0660 | hot_water | Recirculating Pump | RP-LZ-1 | Lower Ground HW Plant | Pump motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0661 | hot_water | Recirculating Pump | RP-LZ-1 | Lower Ground HW Plant | Pump motor H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0662 | hot_water | Recirculating Pump | RP-LZ-1 | Lower Ground HW Plant | Pump motor trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0663 | hot_water | Calorifier (Hot Water Storage Tank) | HWT-LZ-2 | Lower Ground HW Plant | Tank temperature | AI | Temperature Sensor | BMS Contractor | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0664 | hot_water | Heat Pump | HP-LZ-2 | Lower Ground HW Plant | Pump motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0665 | hot_water | Heat Pump | HP-LZ-2 | Lower Ground HW Plant | Pump motor H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0666 | hot_water | Heat Pump | HP-LZ-2 | Lower Ground HW Plant | Pump motor trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0667 | hot_water | Recirculating Pump | RP-LZ-2 | Lower Ground HW Plant | Pump motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0668 | hot_water | Recirculating Pump | RP-LZ-2 | Lower Ground HW Plant | Pump motor H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0669 | hot_water | Recirculating Pump | RP-LZ-2 | Lower Ground HW Plant | Pump motor trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0670 | hot_water | Calorifier (Hot Water Storage Tank) | HWT-LZ-3 | Lower Ground HW Plant | Tank temperature | AI | Temperature Sensor | BMS Contractor | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0671 | hot_water | Heat Pump | HP-LZ-3 | Lower Ground HW Plant | Pump motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0672 | hot_water | Heat Pump | HP-LZ-3 | Lower Ground HW Plant | Pump motor H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0673 | hot_water | Heat Pump | HP-LZ-3 | Lower Ground HW Plant | Pump motor trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0674 | hot_water | Recirculating Pump | RP-LZ-3 | Lower Ground HW Plant | Pump motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0675 | hot_water | Recirculating Pump | RP-LZ-3 | Lower Ground HW Plant | Pump motor H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0676 | hot_water | Recirculating Pump | RP-LZ-3 | Lower Ground HW Plant | Pump motor trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0677 | hot_water | Calorifier (Hot Water Storage Tank) | HWT-HZ-1 | Roof Deck HW Plant | Tank temperature | AI | Temperature Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0678 | hot_water | Heat Pump | HP-HZ-1 | Roof Deck HW Plant | Pump motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0679 | hot_water | Heat Pump | HP-HZ-1 | Roof Deck HW Plant | Pump motor H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0680 | hot_water | Heat Pump | HP-HZ-1 | Roof Deck HW Plant | Pump motor trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0681 | hot_water | Recirculating Pump | RP-HZ-1 | Roof Deck HW Plant | Pump motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0682 | hot_water | Recirculating Pump | RP-HZ-1 | Roof Deck HW Plant | Pump motor H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0683 | hot_water | Recirculating Pump | RP-HZ-1 | Roof Deck HW Plant | Pump motor trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0684 | hot_water | Calorifier (Hot Water Storage Tank) | HWT-HZ-2 | Roof Deck HW Plant | Tank temperature | AI | Temperature Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0685 | hot_water | Heat Pump | HP-HZ-2 | Roof Deck HW Plant | Pump motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0686 | hot_water | Heat Pump | HP-HZ-2 | Roof Deck HW Plant | Pump motor H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0687 | hot_water | Heat Pump | HP-HZ-2 | Roof Deck HW Plant | Pump motor trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0688 | hot_water | Recirculating Pump | RP-HZ-2 | Roof Deck HW Plant | Pump motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0689 | hot_water | Recirculating Pump | RP-HZ-2 | Roof Deck HW Plant | Pump motor H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0690 | hot_water | Recirculating Pump | RP-HZ-2 | Roof Deck HW Plant | Pump motor trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0691 | hot_water | Calorifier (Hot Water Storage Tank) | HWT-HZ-3 | Roof Deck HW Plant | Tank temperature | AI | Temperature Sensor | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0692 | hot_water | Heat Pump | HP-HZ-3 | Roof Deck HW Plant | Pump motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0693 | hot_water | Heat Pump | HP-HZ-3 | Roof Deck HW Plant | Pump motor H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0694 | hot_water | Heat Pump | HP-HZ-3 | Roof Deck HW Plant | Pump motor trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0695 | hot_water | Recirculating Pump | RP-HZ-3 | Roof Deck HW Plant | Pump motor status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0696 | hot_water | Recirculating Pump | RP-HZ-3 | Roof Deck HW Plant | Pump motor H/O/A status | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0697 | hot_water | Recirculating Pump | RP-HZ-3 | Roof Deck HW Plant | Pump motor trip alarm | DI | Auxiliary Contact | Equipment Supplier | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |
| P0698 | hot_water | Hot Water Header Set | HW-HEADERS | Lower Ground HW Plant | HW supply header temperature | AI | Temperature Sensor | BMS Contractor | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0699 | hot_water | Hot Water Header Set | HW-HEADERS | Lower Ground HW Plant | Make-up cold water header temperature | AI | Temperature Sensor | BMS Contractor | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0700 | hot_water | Hot Water Header Set | HW-HEADERS | Lower Ground HW Plant | HW return temperature | AI | Temperature Sensor | BMS Contractor | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0701 | steam | Steam Boiler | SB-1 | Lower Ground Laundry | Supply steam pressure | AI | Pressure Transmitter | BMS Contractor | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0702 | steam | Steam Boiler | SB-1 | Lower Ground Laundry | Low water level alarm | HLI | Equipment Supplier level sensor | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0703 | steam | Steam Boiler | SB-1 | Lower Ground Laundry | High water level alarm | HLI | Equipment Supplier level sensor | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0704 | steam | Steam Boiler | SB-1 | Lower Ground Laundry | Burner power | HLI | — | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0705 | steam | Steam Boiler | SB-1 | Lower Ground Laundry | Small-fire control signal | HLI | — | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0706 | steam | Steam Boiler | SB-1 | Lower Ground Laundry | Big-fire control signal | HLI | — | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0707 | steam | Steam Boiler | SB-1 | Lower Ground Laundry | Burner status | HLI | — | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0708 | steam | Steam Boiler | SB-1 | Lower Ground Laundry | Burner-fire running status | HLI | — | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0709 | steam | Steam Boiler | SB-1 | Lower Ground Laundry | Blower motor status | HLI | — | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0710 | steam | Steam Boiler | SB-1 | Lower Ground Laundry | Fuel-oil pump status | HLI | — | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0711 | steam | Steam Boiler | SB-1 | Lower Ground Laundry | Waterfeed pump status | HLI | — | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0712 | steam | Steam Boiler | SB-1 | Lower Ground Laundry | Burner trip alarm | HLI | — | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0713 | steam | Steam Boiler | SB-1 | Lower Ground Laundry | Blower trip alarm | HLI | — | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0714 | steam | Steam Boiler | SB-1 | Lower Ground Laundry | Oil pump trip alarm | HLI | — | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0715 | steam | Steam Boiler | SB-1 | Lower Ground Laundry | Motorized blowdown valve command | AO | Electric Valve Actuator | BMS Contractor | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0716 | steam | Steam Boiler | SB-1 | Lower Ground Laundry | Motorized blowdown valve status | DI | Auxiliary Contact | BMS Contractor | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0717 | steam | Steam Boiler | SB-1 | Lower Ground Laundry | Feedwater supply temperature | AI | Temperature Sensor | BMS Contractor | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0718 | steam | Steam Boiler | SB-1 | Lower Ground Laundry | Fluegas temperature | AI | Temperature Sensor (high-temp) | BMS Contractor | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0719 | steam | Steam Boiler | SB-1 | Lower Ground Laundry | Fluegas oxygen level | AI | Oxygen Sensor | BMS Contractor | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0720 | steam | Steam Boiler | SB-1 | Lower Ground Laundry | Steam supply pressure (high alarm) | AI | Pressure Transmitter | BMS Contractor | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0721 | steam | Steam Boiler | SB-1 | Lower Ground Laundry | Boiler firing-rate command | AO | 0-10V / 4-20 mA | BMS Contractor | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0722 | steam | Steam Boiler | SB-2 | Lower Ground Laundry | Supply steam pressure | AI | Pressure Transmitter | BMS Contractor | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0723 | steam | Steam Boiler | SB-2 | Lower Ground Laundry | Low water level alarm | HLI | Equipment Supplier level sensor | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0724 | steam | Steam Boiler | SB-2 | Lower Ground Laundry | High water level alarm | HLI | Equipment Supplier level sensor | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0725 | steam | Steam Boiler | SB-2 | Lower Ground Laundry | Burner power | HLI | — | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0726 | steam | Steam Boiler | SB-2 | Lower Ground Laundry | Small-fire control signal | HLI | — | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0727 | steam | Steam Boiler | SB-2 | Lower Ground Laundry | Big-fire control signal | HLI | — | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0728 | steam | Steam Boiler | SB-2 | Lower Ground Laundry | Burner status | HLI | — | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0729 | steam | Steam Boiler | SB-2 | Lower Ground Laundry | Burner-fire running status | HLI | — | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0730 | steam | Steam Boiler | SB-2 | Lower Ground Laundry | Blower motor status | HLI | — | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0731 | steam | Steam Boiler | SB-2 | Lower Ground Laundry | Fuel-oil pump status | HLI | — | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0732 | steam | Steam Boiler | SB-2 | Lower Ground Laundry | Waterfeed pump status | HLI | — | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0733 | steam | Steam Boiler | SB-2 | Lower Ground Laundry | Burner trip alarm | HLI | — | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0734 | steam | Steam Boiler | SB-2 | Lower Ground Laundry | Blower trip alarm | HLI | — | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0735 | steam | Steam Boiler | SB-2 | Lower Ground Laundry | Oil pump trip alarm | HLI | — | Equipment Supplier | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0736 | steam | Steam Boiler | SB-2 | Lower Ground Laundry | Motorized blowdown valve command | AO | Electric Valve Actuator | BMS Contractor | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0737 | steam | Steam Boiler | SB-2 | Lower Ground Laundry | Motorized blowdown valve status | DI | Auxiliary Contact | BMS Contractor | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0738 | steam | Steam Boiler | SB-2 | Lower Ground Laundry | Feedwater supply temperature | AI | Temperature Sensor | BMS Contractor | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0739 | steam | Steam Boiler | SB-2 | Lower Ground Laundry | Fluegas temperature | AI | Temperature Sensor (high-temp) | BMS Contractor | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0740 | steam | Steam Boiler | SB-2 | Lower Ground Laundry | Fluegas oxygen level | AI | Oxygen Sensor | BMS Contractor | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0741 | steam | Steam Boiler | SB-2 | Lower Ground Laundry | Steam supply pressure (high alarm) | AI | Pressure Transmitter | BMS Contractor | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0742 | steam | Steam Boiler | SB-2 | Lower Ground Laundry | Boiler firing-rate command | AO | 0-10V / 4-20 mA | BMS Contractor | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0743 | power_metering | Multifunction Power Meter (Main) | PM-MAIN | Main Switchgear Room | Main power meter (kW, kWh, V, A, PF, kVAR) | Network | Modbus RTU/TCP | BMS Contractor | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0744 | power_metering | Multifunction Power Meter (Feeder) | PM-CHILLER-1 | 2nd Level Mechanical Room | Feeder power meter (kW, kWh, V, A) | Network | Modbus RTU/TCP | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0745 | power_metering | Multifunction Power Meter (Feeder) | PM-CHILLER-2 | 2nd Level Mechanical Room | Feeder power meter (kW, kWh, V, A) | Network | Modbus RTU/TCP | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0746 | power_metering | Multifunction Power Meter (Feeder) | PM-CHILLER-3 | 2nd Level Mechanical Room | Feeder power meter (kW, kWh, V, A) | Network | Modbus RTU/TCP | BMS Contractor | | BMS-PNL-LG-CHILLER | BMS Points list (TUEC) + ME/PL Points list | |
| P0747 | power_metering | Multifunction Power Meter (Feeder) | PM-CASINO-FB | 2nd Floor Casino | Feeder power meter (kW, kWh, V, A) | Network | Modbus RTU/TCP | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0748 | power_metering | Multifunction Power Meter (Feeder) | PM-KITCHEN-2F | 2nd Floor BOH | Feeder power meter (kW, kWh, V, A) | Network | Modbus RTU/TCP | BMS Contractor | | BMS-PNL-2F-CASINO | BMS Points list (TUEC) + ME/PL Points list | |
| P0749 | power_metering | Multifunction Power Meter (Feeder) | PM-LOBBY-GF | Ground Floor | Feeder power meter (kW, kWh, V, A) | Network | Modbus RTU/TCP | BMS Contractor | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0750 | power_metering | Multifunction Power Meter (Feeder) | PM-ELEVATOR | Ground Floor | Feeder power meter (kW, kWh, V, A) | Network | Modbus RTU/TCP | BMS Contractor | | BMS-PNL-GF | BMS Points list (TUEC) + ME/PL Points list | |
| P0751 | power_metering | Multifunction Power Meter (Feeder) | PM-LIGHTING-GUEST | 3rd Floor Amenity | Feeder power meter (kW, kWh, V, A) | Network | Modbus RTU/TCP | BMS Contractor | | BMS-PNL-3F | BMS Points list (TUEC) + ME/PL Points list | |
| P0752 | power_metering | Multifunction Power Meter (Feeder) | PM-LAUNDRY-LG | Lower Ground Laundry | Feeder power meter (kW, kWh, V, A) | Network | Modbus RTU/TCP | BMS Contractor | | BMS-PNL-LG-PLUMB | BMS Points list (TUEC) + ME/PL Points list | |
| P0753 | power_metering | Multifunction Power Meter (Feeder) | PM-ROOFDECK-MECH | Roof Deck Mechanical | Feeder power meter (kW, kWh, V, A) | Network | Modbus RTU/TCP | BMS Contractor | | BMS-PNL-RD-MECH | BMS Points list (TUEC) + ME/PL Points list | |