| ID | From | To | Cable type | Length (m) | Status | Corrected (m) | Verified by | Date | Drawing ref | Notes |
| C0001 | PNL-3F | AHU-AMEN-3F (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — sensors) | 35 | unverified | | | | | |
| C0002 | PNL-3F | AHU-AMEN-3F (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 35 | unverified | | | | | |
| C0003 | PNL-3F | AHU-AMEN-3F (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 35 | unverified | | | | | |
| C0004 | PNL-2F | AHU-BALL-2F (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — sensors) | 35 | unverified | | | | | |
| C0005 | PNL-2F | AHU-BALL-2F (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 35 | unverified | | | | | |
| C0006 | PNL-2F | AHU-BALL-2F (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 35 | unverified | | | | | |
| C0007 | PNL-BOH-2F | AHU-BOH-2F (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — sensors) | 32 | unverified | | | | | |
| C0008 | PNL-BOH-2F | AHU-BOH-2F (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 32 | unverified | | | | | |
| C0009 | PNL-BOH-2F | AHU-BOH-2F (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 32 | unverified | | | | | |
| C0010 | PNL-BSMT | AHU-BOH-BSMT (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — sensors) | 32 | unverified | | | | | |
| C0011 | PNL-BSMT | AHU-BOH-BSMT (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 32 | unverified | | | | | |
| C0012 | PNL-BSMT | AHU-BOH-BSMT (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 32 | unverified | | | | | |
| C0013 | PNL-GF | AHU-LOBBY-GF (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — sensors) | 35 | unverified | | | | | |
| C0014 | PNL-GF | AHU-LOBBY-GF (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 35 | unverified | | | | | |
| C0015 | PNL-GF | AHU-LOBBY-GF (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 35 | unverified | | | | | |
| C0016 | PNL-2F | AHU-REST-2F (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — sensors) | 35 | unverified | | | | | |
| C0017 | PNL-2F | AHU-REST-2F (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 35 | unverified | | | | | |
| C0018 | PNL-2F | AHU-REST-2F (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 35 | unverified | | | | | |
| C0019 | PNL-CHPLANT-GND | CAL-1 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — sensors) | 12 | unverified | | | | | |
| C0020 | PNL-CHPLANT-GND | CAL-2 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — sensors) | 12 | unverified | | | | | |
| C0021 | PNL-CHPLANT-GND | CAL-3 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — sensors) | 12 | unverified | | | | | |
| C0022 | PNL-CHPLANT-GND | CAL-4 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — sensors) | 12 | unverified | | | | | |
| C0023 | PNL-CHPLANT-GND | CAL-5 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — sensors) | 12 | unverified | | | | | |
| C0024 | PNL-CHPLANT-GND | CAL-6 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — sensors) | 12 | unverified | | | | | |
| C0025 | PNL-CHPLANT-GND | CHWP-1.1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 12 | unverified | | | | | |
| C0026 | PNL-CHPLANT-GND | CHWP-1.2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 12 | unverified | | | | | |
| C0027 | PNL-CHPLANT-GND | CHWP-1.3 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 12 | unverified | | | | | |
| C0028 | PNL-CHPLANT-GND | CHWP-1.STBY (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 12 | unverified | | | | | |
| C0029 | PNL-CHPLANT-GND | COWP-1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 12 | unverified | | | | | |
| C0030 | PNL-CHPLANT-GND | COWP-2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 12 | unverified | | | | | |
| C0031 | PNL-CHPLANT-GND | COWP-3 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 12 | unverified | | | | | |
| C0032 | PNL-RD | CT-1 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — sensors) | 18 | unverified | | | | | |
| C0033 | PNL-RD | CT-1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 18 | unverified | | | | | |
| C0034 | PNL-RD | CT-2 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — sensors) | 18 | unverified | | | | | |
| C0035 | PNL-RD | CT-2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 18 | unverified | | | | | |
| C0036 | PNL-RD | CT-3 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — sensors) | 18 | unverified | | | | | |
| C0037 | PNL-RD | CT-3 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 18 | unverified | | | | | |
| C0038 | PNL-RD | CT-COMMON (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — sensors) | 18 | unverified | | | | | |
| C0039 | PNL-2F | DOAS-2F (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — sensors) | 35 | unverified | | | | | |
| C0040 | PNL-2F | DOAS-2F (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 35 | unverified | | | | | |
| C0041 | PNL-2F | DOAS-2F (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 35 | unverified | | | | | |
| C0042 | PNL-GF | DOAS-GF (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — sensors) | 35 | unverified | | | | | |
| C0043 | PNL-GF | DOAS-GF (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 35 | unverified | | | | | |
| C0044 | PNL-GF | DOAS-GF (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 35 | unverified | | | | | |
| C0045 | PNL-RD | DOAS-RD (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — sensors) | 18 | unverified | | | | | |
| C0046 | PNL-RD | DOAS-RD (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 18 | unverified | | | | | |
| C0047 | PNL-RD | DOAS-RD (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 18 | unverified | | | | | |
| C0048 | PNL-2F | EAS-2F (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 35 | unverified | | | | | |
| C0049 | PNL-3F | EAS-3F (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 35 | unverified | | | | | |
| C0050 | PNL-BSMT | EAS-BSMT (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 32 | unverified | | | | | |
| C0051 | PNL-GF | EAS-GF (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 35 | unverified | | | | | |
| C0052 | PNL-2F | FCU-2F.01 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0053 | PNL-2F | FCU-2F.01 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0054 | PNL-2F | FCU-2F.02 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0055 | PNL-2F | FCU-2F.02 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0056 | PNL-2F | FCU-2F.03 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0057 | PNL-2F | FCU-2F.03 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0058 | PNL-2F | FCU-2F.04 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0059 | PNL-2F | FCU-2F.04 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0060 | PNL-2F | FCU-2F.05 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0061 | PNL-2F | FCU-2F.05 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0062 | PNL-2F | FCU-2F.06 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0063 | PNL-2F | FCU-2F.06 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0064 | PNL-2F | FCU-2F.07 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0065 | PNL-2F | FCU-2F.07 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0066 | PNL-2F | FCU-2F.08 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0067 | PNL-2F | FCU-2F.08 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0068 | PNL-2F | FCU-2F.09 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0069 | PNL-2F | FCU-2F.09 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0070 | PNL-2F | FCU-2F.10 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0071 | PNL-2F | FCU-2F.10 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0072 | PNL-2F | FCU-2F.11 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0073 | PNL-2F | FCU-2F.11 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0074 | PNL-2F | FCU-2F.12 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0075 | PNL-2F | FCU-2F.12 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0076 | PNL-2F | FCU-2F.13 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0077 | PNL-2F | FCU-2F.13 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0078 | PNL-2F | FCU-2F.14 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0079 | PNL-2F | FCU-2F.14 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0080 | PNL-2F | FCU-2F.15 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0081 | PNL-2F | FCU-2F.15 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0082 | PNL-2F | FCU-2F.16 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0083 | PNL-2F | FCU-2F.16 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0084 | PNL-2F | FCU-2F.17 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0085 | PNL-2F | FCU-2F.17 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0086 | PNL-2F | FCU-2F.18 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0087 | PNL-2F | FCU-2F.18 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0088 | PNL-2F | FCU-2F.19 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0089 | PNL-2F | FCU-2F.19 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0090 | PNL-2F | FCU-2F.20 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0091 | PNL-2F | FCU-2F.20 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0092 | PNL-2F | FCU-2F.21 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0093 | PNL-2F | FCU-2F.21 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0094 | PNL-2F | FCU-2F.22 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0095 | PNL-2F | FCU-2F.22 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0096 | PNL-2F | FCU-2F.23 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0097 | PNL-2F | FCU-2F.23 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0098 | PNL-2F | FCU-2F.24 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0099 | PNL-2F | FCU-2F.24 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0100 | PNL-2F | FCU-2F.25 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0101 | PNL-2F | FCU-2F.25 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0102 | PNL-2F | FCU-2F.26 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0103 | PNL-2F | FCU-2F.26 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0104 | PNL-2F | FCU-2F.27 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0105 | PNL-2F | FCU-2F.27 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0106 | PNL-2F | FCU-2F.28 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0107 | PNL-2F | FCU-2F.28 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0108 | PNL-2F | FCU-2F.29 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0109 | PNL-2F | FCU-2F.29 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0110 | PNL-2F | FCU-2F.30 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0111 | PNL-2F | FCU-2F.30 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0112 | PNL-3F | FCU-3F.01 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0113 | PNL-3F | FCU-3F.01 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0114 | PNL-3F | FCU-3F.02 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0115 | PNL-3F | FCU-3F.02 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0116 | PNL-3F | FCU-3F.03 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0117 | PNL-3F | FCU-3F.03 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0118 | PNL-3F | FCU-3F.04 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0119 | PNL-3F | FCU-3F.04 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0120 | PNL-3F | FCU-3F.05 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0121 | PNL-3F | FCU-3F.05 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0122 | PNL-3F | FCU-3F.06 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0123 | PNL-3F | FCU-3F.06 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0124 | PNL-3F | FCU-3F.07 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0125 | PNL-3F | FCU-3F.07 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0126 | PNL-3F | FCU-3F.08 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0127 | PNL-3F | FCU-3F.08 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0128 | PNL-3F | FCU-3F.09 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0129 | PNL-3F | FCU-3F.09 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0130 | PNL-3F | FCU-3F.10 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0131 | PNL-3F | FCU-3F.10 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0132 | PNL-3F | FCU-3F.11 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0133 | PNL-3F | FCU-3F.11 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0134 | PNL-3F | FCU-3F.12 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0135 | PNL-3F | FCU-3F.12 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0136 | PNL-3F | FCU-3F.13 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0137 | PNL-3F | FCU-3F.13 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0138 | PNL-3F | FCU-3F.14 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0139 | PNL-3F | FCU-3F.14 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0140 | PNL-3F | FCU-3F.15 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0141 | PNL-3F | FCU-3F.15 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0142 | PNL-3F | FCU-3F.16 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0143 | PNL-3F | FCU-3F.16 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0144 | PNL-3F | FCU-3F.17 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0145 | PNL-3F | FCU-3F.17 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0146 | PNL-3F | FCU-3F.18 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0147 | PNL-3F | FCU-3F.18 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0148 | PNL-3F | FCU-3F.19 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0149 | PNL-3F | FCU-3F.19 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0150 | PNL-3F | FCU-3F.20 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0151 | PNL-3F | FCU-3F.20 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0152 | PNL-3F | FCU-3F.21 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0153 | PNL-3F | FCU-3F.21 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0154 | PNL-3F | FCU-3F.22 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0155 | PNL-3F | FCU-3F.22 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0156 | PNL-3F | FCU-3F.23 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0157 | PNL-3F | FCU-3F.23 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0158 | PNL-3F | FCU-3F.24 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0159 | PNL-3F | FCU-3F.24 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0160 | PNL-3F | FCU-3F.25 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0161 | PNL-3F | FCU-3F.25 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0162 | PNL-3F | FCU-3F.26 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0163 | PNL-3F | FCU-3F.26 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0164 | PNL-3F | FCU-3F.27 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0165 | PNL-3F | FCU-3F.27 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0166 | PNL-3F | FCU-3F.28 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0167 | PNL-3F | FCU-3F.28 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0168 | PNL-3F | FCU-3F.29 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0169 | PNL-3F | FCU-3F.29 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0170 | PNL-3F | FCU-3F.30 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0171 | PNL-3F | FCU-3F.30 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0172 | PNL-GF | FCU-GF.01 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0173 | PNL-GF | FCU-GF.01 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0174 | PNL-GF | FCU-GF.02 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0175 | PNL-GF | FCU-GF.02 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0176 | PNL-GF | FCU-GF.03 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0177 | PNL-GF | FCU-GF.03 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0178 | PNL-GF | FCU-GF.04 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0179 | PNL-GF | FCU-GF.04 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0180 | PNL-GF | FCU-GF.05 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0181 | PNL-GF | FCU-GF.05 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0182 | PNL-GF | FCU-GF.06 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0183 | PNL-GF | FCU-GF.06 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0184 | PNL-GF | FCU-GF.07 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0185 | PNL-GF | FCU-GF.07 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0186 | PNL-GF | FCU-GF.08 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0187 | PNL-GF | FCU-GF.08 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0188 | PNL-GF | FCU-GF.09 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0189 | PNL-GF | FCU-GF.09 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0190 | PNL-GF | FCU-GF.10 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0191 | PNL-GF | FCU-GF.10 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0192 | PNL-GF | FCU-GF.11 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0193 | PNL-GF | FCU-GF.11 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0194 | PNL-GF | FCU-GF.12 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0195 | PNL-GF | FCU-GF.12 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0196 | PNL-GF | FCU-GF.13 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0197 | PNL-GF | FCU-GF.13 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0198 | PNL-GF | FCU-GF.14 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0199 | PNL-GF | FCU-GF.14 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0200 | PNL-GF | FCU-GF.15 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0201 | PNL-GF | FCU-GF.15 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0202 | PNL-GF | FCU-GF.16 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0203 | PNL-GF | FCU-GF.16 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0204 | PNL-GF | FCU-GF.17 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0205 | PNL-GF | FCU-GF.17 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0206 | PNL-GF | FCU-GF.18 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0207 | PNL-GF | FCU-GF.18 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0208 | PNL-GF | FCU-GF.19 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0209 | PNL-GF | FCU-GF.19 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0210 | PNL-GF | FCU-GF.20 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0211 | PNL-GF | FCU-GF.20 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0212 | PNL-GF | FCU-GF.21 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0213 | PNL-GF | FCU-GF.21 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0214 | PNL-GF | FCU-GF.22 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0215 | PNL-GF | FCU-GF.22 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0216 | PNL-GF | FCU-GF.23 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0217 | PNL-GF | FCU-GF.23 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0218 | PNL-GF | FCU-GF.24 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0219 | PNL-GF | FCU-GF.24 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0220 | PNL-GF | FCU-GF.25 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0221 | PNL-GF | FCU-GF.25 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0222 | PNL-GF | FCU-GF.26 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0223 | PNL-GF | FCU-GF.26 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0224 | PNL-GF | FCU-GF.27 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0225 | PNL-GF | FCU-GF.27 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0226 | PNL-GF | FCU-GF.28 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0227 | PNL-GF | FCU-GF.28 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0228 | PNL-GF | FCU-GF.29 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0229 | PNL-GF | FCU-GF.29 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0230 | PNL-GF | FCU-GF.30 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 28 | unverified | | | | | |
| C0231 | PNL-GF | FCU-GF.30 (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 28 | unverified | | | | | |
| C0232 | PNL-CHPLANT-GND | HDR-CHW-BP (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — sensors) | 12 | unverified | | | | | |
| C0233 | PNL-CHPLANT-GND | HDR-CHWR (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — sensors) | 12 | unverified | | | | | |
| C0234 | PNL-CHPLANT-GND | HDR-CHWS (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — sensors) | 12 | unverified | | | | | |
| C0235 | PNL-RD | HDR-COW (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — sensors) | 18 | unverified | | | | | |
| C0236 | PNL-CHPLANT-GND | HDR-HW (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — sensors) | 12 | unverified | | | | | |
| C0237 | PNL-CHPLANT-GND | HP-1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 12 | unverified | | | | | |
| C0238 | PNL-CHPLANT-GND | HP-2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 12 | unverified | | | | | |
| C0239 | PNL-CHPLANT-GND | HP-3 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 12 | unverified | | | | | |
| C0240 | PNL-RD | PAHU-RD (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — sensors) | 18 | unverified | | | | | |
| C0241 | PNL-RD | PAHU-RD (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 18 | unverified | | | | | |
| C0242 | PNL-RD | PAHU-RD (ME Contractor) | 4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control) | 18 | unverified | | | | | |
| C0243 | PNL-CHPLANT-GND | RP-1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 12 | unverified | | | | | |
| C0244 | PNL-CHPLANT-GND | RP-2 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 12 | unverified | | | | | |
| C0245 | PNL-CHPLANT-GND | RP-3 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 12 | unverified | | | | | |
| C0246 | PNL-CHPLANT-GND | RP-4 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 12 | unverified | | | | | |
| C0247 | PNL-CHPLANT-GND | RP-5 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 12 | unverified | | | | | |
| C0248 | PNL-CHPLANT-GND | RP-6 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 12 | unverified | | | | | |
| C0249 | PNL-BSMT | SB-1 (BMS Contractor) | 4C × 1.5 mm² shielded FRLS (BMS signal — sensors) | 32 | unverified | | | | | |
| C0250 | PNL-BSMT | SB-1 (Equipment Supplier) | 4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip) | 32 | unverified | | | | | |
| C0251 | PNL-RD | NET-PNL-RD (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 18 | unverified | | | | | |
| C0252 | PNL-3F | NET-PNL-3F (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 35 | unverified | | | | | |
| C0253 | PNL-2F | NET-PNL-2F (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 35 | unverified | | | | | |
| C0254 | PNL-GF | NET-PNL-GF (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 35 | unverified | | | | | |
| C0255 | PNL-BSMT | NET-PNL-BSMT (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 35 | unverified | | | | | |
| C0256 | PNL-CHPLANT-GND | NET-PNL-CHPLANT-GND (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 12 | unverified | | | | | |
| C0257 | PNL-BOH-2F | NET-PNL-BOH-2F (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 32 | unverified | | | | | |
| C0258 | PNL-HE-GF | NET-PNL-HE-GF (Network) | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) | 35 | unverified | | | | | |
| T0259 | BMS Server Room (head-end) | All BMS panels at 2nd Floor | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk | 80 | unverified | | | | | |
| T0260 | BMS Server Room (head-end) | All BMS panels at Basement | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk | 80 | unverified | | | | | |
| T0261 | BMS Server Room (head-end) | All BMS panels at Roofdeck | Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk | 80 | unverified | | | | | |
| T0262 | BMS Server Room (head-end) | BMS panel controllers (per topology id mstp_main_backbone) | BACnet MS/TP shielded twisted-pair trunk, 1pr × 22 AWG low-cap | 245 | unverified | | | | | |
| P0263 | Local panelboard / EE-supplied feeder | PNL-2F — BMS panel 240V power feed | 3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed) | 12 | unverified | | | | | |
| P0264 | Local panelboard / EE-supplied feeder | PNL-3F — BMS panel 240V power feed | 3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed) | 12 | unverified | | | | | |
| P0265 | Local panelboard / EE-supplied feeder | PNL-BOH-2F — BMS panel 240V power feed | 3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed) | 12 | unverified | | | | | |
| P0266 | Local panelboard / EE-supplied feeder | PNL-BSMT — BMS panel 240V power feed | 3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed) | 12 | unverified | | | | | |
| P0267 | Local panelboard / EE-supplied feeder | PNL-CHPLANT-GND — BMS panel 240V power feed | 3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed) | 12 | unverified | | | | | |
| P0268 | Local panelboard / EE-supplied feeder | PNL-GF — BMS panel 240V power feed | 3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed) | 12 | unverified | | | | | |
| P0269 | Local panelboard / EE-supplied feeder | PNL-HE-GF — BMS panel 240V power feed | 3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed) | 12 | unverified | | | | | |
| P0270 | Local panelboard / EE-supplied feeder | PNL-RD — BMS panel 240V power feed | 3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed) | 12 | unverified | | | | | |