Summary
| A4 — Panel Schedule Summary | |
| Total panels | 8 |
| Total physical I/O | 523 |
| Total HLI subpoints | 23 |
| Total network drops | 8 |
| Total I/O points | 554 |
| Estimated total controllers | 21 |
| Estimated total power (W) | 565 |
Panel Schedule
| Panel | Location | System Scope | Equipment Count | Physical I/O | HLI Subpoints | Network Drops | Total I/O | DDC Controllers | Network Gateway | Total Controllers | Power (W) | Enclosure |
| PNL-2F | 2F / panel | Network, VENT-AHU, VENT-DOAS, VENT-EAS, VENT-FCU | 35 | 138 | 0 | 1 | 139 | 4 | 1 | 4 | 105 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| PNL-3F | 3F / panel | Network, VENT-AHU, VENT-EAS, VENT-FCU | 33 | 105 | 0 | 1 | 106 | 3 | 1 | 3 | 80 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| PNL-BOH-2F | 2F / panel | Network, VENT-AHU | 2 | 12 | 0 | 1 | 13 | 1 | 1 | 2 | 55 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| PNL-BSMT | Basement / panel | Network, PL-Boiler, VENT-AHU, VENT-EAS | 4 | 23 | 0 | 1 | 24 | 1 | 1 | 2 | 55 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| PNL-CHPLANT-GND | Plant Room / Plant Room (Basement) / panel | HVAC-Chillers, HVAC-Pumps, Network, PL-Calorifiers, PL-HeatPumps, PL-HotWater, PL-RecircPumps | 31 | 65 | 10 | 1 | 76 | 2 | 1 | 2 | 55 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| PNL-GF | GF / Main Switchgear / Sub-Distribution Board / panel | Network, Power-EE, VENT-AHU, VENT-DOAS, VENT-EAS, VENT-FCU | 47 | 126 | 13 | 1 | 140 | 4 | 1 | 4 | 105 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| PNL-HE-GF | panel | Network | 1 | 0 | 0 | 1 | 1 | 1 | 1 | 2 | 55 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| PNL-RD | Roofdeck / panel | HVAC-Chillers, HVAC-Cooling-Towers, Network, VENT-DOAS, VENT-PAHU | 8 | 54 | 0 | 1 | 55 | 2 | 1 | 2 | 55 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
Equipment per Panel
| Panel | Equipment Instance |
| PNL-2F | AHU-BALL-2F |
| PNL-2F | AHU-REST-2F |
| PNL-2F | DOAS-2F |
| PNL-2F | EAS-2F |
| PNL-2F | FCU-2F.01 |
| PNL-2F | FCU-2F.02 |
| PNL-2F | FCU-2F.03 |
| PNL-2F | FCU-2F.04 |
| PNL-2F | FCU-2F.05 |
| PNL-2F | FCU-2F.06 |
| PNL-2F | FCU-2F.07 |
| PNL-2F | FCU-2F.08 |
| PNL-2F | FCU-2F.09 |
| PNL-2F | FCU-2F.10 |
| PNL-2F | FCU-2F.11 |
| PNL-2F | FCU-2F.12 |
| PNL-2F | FCU-2F.13 |
| PNL-2F | FCU-2F.14 |
| PNL-2F | FCU-2F.15 |
| PNL-2F | FCU-2F.16 |
| PNL-2F | FCU-2F.17 |
| PNL-2F | FCU-2F.18 |
| PNL-2F | FCU-2F.19 |
| PNL-2F | FCU-2F.20 |
| PNL-2F | FCU-2F.21 |
| PNL-2F | FCU-2F.22 |
| PNL-2F | FCU-2F.23 |
| PNL-2F | FCU-2F.24 |
| PNL-2F | FCU-2F.25 |
| PNL-2F | FCU-2F.26 |
| PNL-2F | FCU-2F.27 |
| PNL-2F | FCU-2F.28 |
| PNL-2F | FCU-2F.29 |
| PNL-2F | FCU-2F.30 |
| PNL-2F | NET-PNL-2F |
| PNL-3F | AHU-AMEN-3F |
| PNL-3F | EAS-3F |
| PNL-3F | FCU-3F.01 |
| PNL-3F | FCU-3F.02 |
| PNL-3F | FCU-3F.03 |
| PNL-3F | FCU-3F.04 |
| PNL-3F | FCU-3F.05 |
| PNL-3F | FCU-3F.06 |
| PNL-3F | FCU-3F.07 |
| PNL-3F | FCU-3F.08 |
| PNL-3F | FCU-3F.09 |
| PNL-3F | FCU-3F.10 |
| PNL-3F | FCU-3F.11 |
| PNL-3F | FCU-3F.12 |
| PNL-3F | FCU-3F.13 |
| PNL-3F | FCU-3F.14 |
| PNL-3F | FCU-3F.15 |
| PNL-3F | FCU-3F.16 |
| PNL-3F | FCU-3F.17 |
| PNL-3F | FCU-3F.18 |
| PNL-3F | FCU-3F.19 |
| PNL-3F | FCU-3F.20 |
| PNL-3F | FCU-3F.21 |
| PNL-3F | FCU-3F.22 |
| PNL-3F | FCU-3F.23 |
| PNL-3F | FCU-3F.24 |
| PNL-3F | FCU-3F.25 |
| PNL-3F | FCU-3F.26 |
| PNL-3F | FCU-3F.27 |
| PNL-3F | FCU-3F.28 |
| PNL-3F | FCU-3F.29 |
| PNL-3F | FCU-3F.30 |
| PNL-3F | NET-PNL-3F |
| PNL-BOH-2F | AHU-BOH-2F |
| PNL-BOH-2F | NET-PNL-BOH-2F |
| PNL-BSMT | AHU-BOH-BSMT |
| PNL-BSMT | EAS-BSMT |
| PNL-BSMT | NET-PNL-BSMT |
| PNL-BSMT | SB-1 |
| PNL-CHPLANT-GND | BTU-CHWS-MAIN |
| PNL-CHPLANT-GND | CAL-1 |
| PNL-CHPLANT-GND | CAL-2 |
| PNL-CHPLANT-GND | CAL-3 |
| PNL-CHPLANT-GND | CAL-4 |
| PNL-CHPLANT-GND | CAL-5 |
| PNL-CHPLANT-GND | CAL-6 |
| PNL-CHPLANT-GND | CH-1 |
| PNL-CHPLANT-GND | CH-2 |
| PNL-CHPLANT-GND | CH-3 |
| PNL-CHPLANT-GND | CHWP-1.1 |
| PNL-CHPLANT-GND | CHWP-1.2 |
| PNL-CHPLANT-GND | CHWP-1.3 |
| PNL-CHPLANT-GND | CHWP-1.STBY |
| PNL-CHPLANT-GND | COWP-1 |
| PNL-CHPLANT-GND | COWP-2 |
| PNL-CHPLANT-GND | COWP-3 |
| PNL-CHPLANT-GND | HDR-CHW-BP |
| PNL-CHPLANT-GND | HDR-CHWR |
| PNL-CHPLANT-GND | HDR-CHWS |
| PNL-CHPLANT-GND | HDR-HW |
| PNL-CHPLANT-GND | HP-1 |
| PNL-CHPLANT-GND | HP-2 |
| PNL-CHPLANT-GND | HP-3 |
| PNL-CHPLANT-GND | NET-PNL-CHPLANT-GND |
| PNL-CHPLANT-GND | RP-1 |
| PNL-CHPLANT-GND | RP-2 |
| PNL-CHPLANT-GND | RP-3 |
| PNL-CHPLANT-GND | RP-4 |
| PNL-CHPLANT-GND | RP-5 |
| PNL-CHPLANT-GND | RP-6 |
| PNL-GF | AHU-LOBBY-GF |
| PNL-GF | DOAS-GF |
| PNL-GF | EAS-GF |
| PNL-GF | FCU-GF.01 |
| PNL-GF | FCU-GF.02 |
| PNL-GF | FCU-GF.03 |
| PNL-GF | FCU-GF.04 |
| PNL-GF | FCU-GF.05 |
| PNL-GF | FCU-GF.06 |
| PNL-GF | FCU-GF.07 |
| PNL-GF | FCU-GF.08 |
| PNL-GF | FCU-GF.09 |
| PNL-GF | FCU-GF.10 |
| PNL-GF | FCU-GF.11 |
| PNL-GF | FCU-GF.12 |
| PNL-GF | FCU-GF.13 |
| PNL-GF | FCU-GF.14 |
| PNL-GF | FCU-GF.15 |
| PNL-GF | FCU-GF.16 |
| PNL-GF | FCU-GF.17 |
| PNL-GF | FCU-GF.18 |
| PNL-GF | FCU-GF.19 |
| PNL-GF | FCU-GF.20 |
| PNL-GF | FCU-GF.21 |
| PNL-GF | FCU-GF.22 |
| PNL-GF | FCU-GF.23 |
| PNL-GF | FCU-GF.24 |
| PNL-GF | FCU-GF.25 |
| PNL-GF | FCU-GF.26 |
| PNL-GF | FCU-GF.27 |
| PNL-GF | FCU-GF.28 |
| PNL-GF | FCU-GF.29 |
| PNL-GF | FCU-GF.30 |
| PNL-GF | MTR-FDR-01 |
| PNL-GF | MTR-FDR-02 |
| PNL-GF | MTR-FDR-03 |
| PNL-GF | MTR-FDR-04 |
| PNL-GF | MTR-FDR-05 |
| PNL-GF | MTR-FDR-06 |
| PNL-GF | MTR-FDR-07 |
| PNL-GF | MTR-FDR-08 |
| PNL-GF | MTR-FDR-09 |
| PNL-GF | MTR-FDR-10 |
| PNL-GF | MTR-MAIN-1 |
| PNL-GF | MTR-MAIN-2 |
| PNL-GF | MTR-MAIN-3 |
| PNL-GF | NET-PNL-GF |
| PNL-HE-GF | NET-PNL-HE-GF |
| PNL-RD | CT-1 |
| PNL-RD | CT-2 |
| PNL-RD | CT-3 |
| PNL-RD | CT-COMMON |
| PNL-RD | DOAS-RD |
| PNL-RD | HDR-COW |
| PNL-RD | NET-PNL-RD |
| PNL-RD | PAHU-RD |