Summary

A3 — Cable Schedule Summary
Total field cable runs258
Total field cable length (m)6864
Total trunk cable length (m)485
Total power feed length (m)96
GRAND TOTAL cable length (m)7445
By cable type (m)
4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)3245
4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)2830
4C × 1.5 mm² shielded FRLS (BMS signal — sensors)552
Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)237

Field Cables

IDFromToEquipment ClassSystemLocationCable TypeConductors RequiredConductors SpecifiedLength (m)I/O Points CarriedNotes
C0001PNL-3FAHU-AMEN-3F (BMS Contractor)AHU (Chilled-Water-Served)VENT-AHU3F4C × 1.5 mm² shielded FRLS (BMS signal — sensors)563544 I/O points carried, 6C cable; length 35 m (typical_range:same_floor_corridor_field)
C0002PNL-3FAHU-AMEN-3F (Equipment Supplier)AHU (Chilled-Water-Served)VENT-AHU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)443544 I/O points carried, 4C cable; length 35 m (typical_range:same_floor_corridor_field)
C0003PNL-3FAHU-AMEN-3F (ME Contractor)AHU (Chilled-Water-Served)VENT-AHU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)563544 I/O points carried, 6C cable; length 35 m (typical_range:same_floor_corridor_field)
C0004PNL-2FAHU-BALL-2F (BMS Contractor)AHU (Chilled-Water-Served)VENT-AHU2F4C × 1.5 mm² shielded FRLS (BMS signal — sensors)563544 I/O points carried, 6C cable; length 35 m (typical_range:same_floor_corridor_field)
C0005PNL-2FAHU-BALL-2F (Equipment Supplier)AHU (Chilled-Water-Served)VENT-AHU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)443544 I/O points carried, 4C cable; length 35 m (typical_range:same_floor_corridor_field)
C0006PNL-2FAHU-BALL-2F (ME Contractor)AHU (Chilled-Water-Served)VENT-AHU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)563544 I/O points carried, 6C cable; length 35 m (typical_range:same_floor_corridor_field)
C0007PNL-BOH-2FAHU-BOH-2F (BMS Contractor)AHU (Chilled-Water-Served)VENT-AHU2F4C × 1.5 mm² shielded FRLS (BMS signal — sensors)563244 I/O points carried, 6C cable; length 32 m (typical_range:boh_corridor_field)
C0008PNL-BOH-2FAHU-BOH-2F (Equipment Supplier)AHU (Chilled-Water-Served)VENT-AHU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)443244 I/O points carried, 4C cable; length 32 m (typical_range:boh_corridor_field)
C0009PNL-BOH-2FAHU-BOH-2F (ME Contractor)AHU (Chilled-Water-Served)VENT-AHU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)563244 I/O points carried, 6C cable; length 32 m (typical_range:boh_corridor_field)
C0010PNL-BSMTAHU-BOH-BSMT (BMS Contractor)AHU (Chilled-Water-Served)VENT-AHUBasement4C × 1.5 mm² shielded FRLS (BMS signal — sensors)563244 I/O points carried, 6C cable; length 32 m (typical_range:boh_corridor_field)
C0011PNL-BSMTAHU-BOH-BSMT (Equipment Supplier)AHU (Chilled-Water-Served)VENT-AHUBasement4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)443244 I/O points carried, 4C cable; length 32 m (typical_range:boh_corridor_field)
C0012PNL-BSMTAHU-BOH-BSMT (ME Contractor)AHU (Chilled-Water-Served)VENT-AHUBasement4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)563244 I/O points carried, 6C cable; length 32 m (typical_range:boh_corridor_field)
C0013PNL-GFAHU-LOBBY-GF (BMS Contractor)AHU (Chilled-Water-Served)VENT-AHUGF4C × 1.5 mm² shielded FRLS (BMS signal — sensors)563544 I/O points carried, 6C cable; length 35 m (typical_range:same_floor_corridor_field)
C0014PNL-GFAHU-LOBBY-GF (Equipment Supplier)AHU (Chilled-Water-Served)VENT-AHUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)443544 I/O points carried, 4C cable; length 35 m (typical_range:same_floor_corridor_field)
C0015PNL-GFAHU-LOBBY-GF (ME Contractor)AHU (Chilled-Water-Served)VENT-AHUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)563544 I/O points carried, 6C cable; length 35 m (typical_range:same_floor_corridor_field)
C0016PNL-2FAHU-REST-2F (BMS Contractor)AHU (Chilled-Water-Served)VENT-AHU2F4C × 1.5 mm² shielded FRLS (BMS signal — sensors)563544 I/O points carried, 6C cable; length 35 m (typical_range:same_floor_corridor_field)
C0017PNL-2FAHU-REST-2F (Equipment Supplier)AHU (Chilled-Water-Served)VENT-AHU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)443544 I/O points carried, 4C cable; length 35 m (typical_range:same_floor_corridor_field)
C0018PNL-2FAHU-REST-2F (ME Contractor)AHU (Chilled-Water-Served)VENT-AHU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)563544 I/O points carried, 6C cable; length 35 m (typical_range:same_floor_corridor_field)
C0019PNL-CHPLANT-GNDCAL-1 (BMS Contractor)Calorifier (Hot Water Storage Tank)PL-CalorifiersPlant Room4C × 1.5 mm² shielded FRLS (BMS signal — sensors)141211 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0020PNL-CHPLANT-GNDCAL-2 (BMS Contractor)Calorifier (Hot Water Storage Tank)PL-CalorifiersPlant Room4C × 1.5 mm² shielded FRLS (BMS signal — sensors)141211 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0021PNL-CHPLANT-GNDCAL-3 (BMS Contractor)Calorifier (Hot Water Storage Tank)PL-CalorifiersPlant Room4C × 1.5 mm² shielded FRLS (BMS signal — sensors)141211 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0022PNL-CHPLANT-GNDCAL-4 (BMS Contractor)Calorifier (Hot Water Storage Tank)PL-CalorifiersPlant Room4C × 1.5 mm² shielded FRLS (BMS signal — sensors)141211 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0023PNL-CHPLANT-GNDCAL-5 (BMS Contractor)Calorifier (Hot Water Storage Tank)PL-CalorifiersPlant Room4C × 1.5 mm² shielded FRLS (BMS signal — sensors)141211 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0024PNL-CHPLANT-GNDCAL-6 (BMS Contractor)Calorifier (Hot Water Storage Tank)PL-CalorifiersPlant Room4C × 1.5 mm² shielded FRLS (BMS signal — sensors)141211 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0025PNL-CHPLANT-GNDCHWP-1.1 (Equipment Supplier)Primary CHW PumpHVAC-PumpsPlant Room4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)341233 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0026PNL-CHPLANT-GNDCHWP-1.2 (Equipment Supplier)Primary CHW PumpHVAC-PumpsPlant Room4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)341233 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0027PNL-CHPLANT-GNDCHWP-1.3 (Equipment Supplier)Primary CHW PumpHVAC-PumpsPlant Room4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)341233 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0028PNL-CHPLANT-GNDCHWP-1.STBY (Equipment Supplier)Primary CHW Pump (Standby)HVAC-PumpsPlant Room4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)241222 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0029PNL-CHPLANT-GNDCOWP-1 (Equipment Supplier)Condenser Water PumpHVAC-PumpsPlant Room4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)441244 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0030PNL-CHPLANT-GNDCOWP-2 (Equipment Supplier)Condenser Water PumpHVAC-PumpsPlant Room4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)441244 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0031PNL-CHPLANT-GNDCOWP-3 (Equipment Supplier)Condenser Water PumpHVAC-PumpsPlant Room4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)441244 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0032PNL-RDCT-1 (BMS Contractor)Cooling TowerHVAC-Cooling-TowersRoofdeck4C × 1.5 mm² shielded FRLS (BMS signal — sensors)141811 I/O points carried, 4C cable; length 18 m (typical_range:roofdeck_same_area)
C0033PNL-RDCT-1 (Equipment Supplier)Cooling TowerHVAC-Cooling-TowersRoofdeck4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)561855 I/O points carried, 6C cable; length 18 m (typical_range:roofdeck_same_area)
C0034PNL-RDCT-2 (BMS Contractor)Cooling TowerHVAC-Cooling-TowersRoofdeck4C × 1.5 mm² shielded FRLS (BMS signal — sensors)141811 I/O points carried, 4C cable; length 18 m (typical_range:roofdeck_same_area)
C0035PNL-RDCT-2 (Equipment Supplier)Cooling TowerHVAC-Cooling-TowersRoofdeck4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)561855 I/O points carried, 6C cable; length 18 m (typical_range:roofdeck_same_area)
C0036PNL-RDCT-3 (BMS Contractor)Cooling TowerHVAC-Cooling-TowersRoofdeck4C × 1.5 mm² shielded FRLS (BMS signal — sensors)141811 I/O points carried, 4C cable; length 18 m (typical_range:roofdeck_same_area)
C0037PNL-RDCT-3 (Equipment Supplier)Cooling TowerHVAC-Cooling-TowersRoofdeck4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)561855 I/O points carried, 6C cable; length 18 m (typical_range:roofdeck_same_area)
C0038PNL-RDCT-COMMON (BMS Contractor)Cooling Tower (Common)HVAC-Cooling-TowersRoofdeck4C × 1.5 mm² shielded FRLS (BMS signal — sensors)241822 I/O points carried, 4C cable; length 18 m (typical_range:roofdeck_same_area)
C0039PNL-2FDOAS-2F (BMS Contractor)DOAS UnitVENT-DOAS2F4C × 1.5 mm² shielded FRLS (BMS signal — sensors)663555 I/O points carried, 6C cable; length 35 m (typical_range:same_floor_corridor_field)
C0040PNL-2FDOAS-2F (Equipment Supplier)DOAS UnitVENT-DOAS2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)1416351212 I/O points carried, 16C cable; length 35 m (typical_range:same_floor_corridor_field)
C0041PNL-2FDOAS-2F (ME Contractor)DOAS UnitVENT-DOAS2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)443544 I/O points carried, 4C cable; length 35 m (typical_range:same_floor_corridor_field)
C0042PNL-GFDOAS-GF (BMS Contractor)DOAS UnitVENT-DOASGF4C × 1.5 mm² shielded FRLS (BMS signal — sensors)663555 I/O points carried, 6C cable; length 35 m (typical_range:same_floor_corridor_field)
C0043PNL-GFDOAS-GF (Equipment Supplier)DOAS UnitVENT-DOASGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)1416351212 I/O points carried, 16C cable; length 35 m (typical_range:same_floor_corridor_field)
C0044PNL-GFDOAS-GF (ME Contractor)DOAS UnitVENT-DOASGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)443544 I/O points carried, 4C cable; length 35 m (typical_range:same_floor_corridor_field)
C0045PNL-RDDOAS-RD (BMS Contractor)DOAS UnitVENT-DOASRoofdeck4C × 1.5 mm² shielded FRLS (BMS signal — sensors)661855 I/O points carried, 6C cable; length 18 m (typical_range:roofdeck_same_area)
C0046PNL-RDDOAS-RD (Equipment Supplier)DOAS UnitVENT-DOASRoofdeck4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)1416181212 I/O points carried, 16C cable; length 18 m (typical_range:roofdeck_same_area)
C0047PNL-RDDOAS-RD (ME Contractor)DOAS UnitVENT-DOASRoofdeck4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)441844 I/O points carried, 4C cable; length 18 m (typical_range:roofdeck_same_area)
C0048PNL-2FEAS-2F (Equipment Supplier)Exhaust Fan (General)VENT-EAS2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)343533 I/O points carried, 4C cable; length 35 m (typical_range:same_floor_corridor_field)
C0049PNL-3FEAS-3F (Equipment Supplier)Exhaust Fan (General)VENT-EAS3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)343533 I/O points carried, 4C cable; length 35 m (typical_range:same_floor_corridor_field)
C0050PNL-BSMTEAS-BSMT (Equipment Supplier)Exhaust Fan (General)VENT-EASBasement4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)343233 I/O points carried, 4C cable; length 32 m (typical_range:boh_corridor_field)
C0051PNL-GFEAS-GF (Equipment Supplier)Exhaust Fan (General)VENT-EASGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)343533 I/O points carried, 4C cable; length 35 m (typical_range:same_floor_corridor_field)
C0052PNL-2FFCU-2F.01 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0053PNL-2FFCU-2F.01 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0054PNL-2FFCU-2F.02 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0055PNL-2FFCU-2F.02 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0056PNL-2FFCU-2F.03 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0057PNL-2FFCU-2F.03 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0058PNL-2FFCU-2F.04 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0059PNL-2FFCU-2F.04 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0060PNL-2FFCU-2F.05 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0061PNL-2FFCU-2F.05 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0062PNL-2FFCU-2F.06 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0063PNL-2FFCU-2F.06 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0064PNL-2FFCU-2F.07 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0065PNL-2FFCU-2F.07 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0066PNL-2FFCU-2F.08 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0067PNL-2FFCU-2F.08 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0068PNL-2FFCU-2F.09 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0069PNL-2FFCU-2F.09 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0070PNL-2FFCU-2F.10 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0071PNL-2FFCU-2F.10 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0072PNL-2FFCU-2F.11 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0073PNL-2FFCU-2F.11 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0074PNL-2FFCU-2F.12 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0075PNL-2FFCU-2F.12 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0076PNL-2FFCU-2F.13 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0077PNL-2FFCU-2F.13 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0078PNL-2FFCU-2F.14 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0079PNL-2FFCU-2F.14 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0080PNL-2FFCU-2F.15 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0081PNL-2FFCU-2F.15 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0082PNL-2FFCU-2F.16 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0083PNL-2FFCU-2F.16 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0084PNL-2FFCU-2F.17 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0085PNL-2FFCU-2F.17 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0086PNL-2FFCU-2F.18 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0087PNL-2FFCU-2F.18 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0088PNL-2FFCU-2F.19 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0089PNL-2FFCU-2F.19 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0090PNL-2FFCU-2F.20 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0091PNL-2FFCU-2F.20 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0092PNL-2FFCU-2F.21 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0093PNL-2FFCU-2F.21 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0094PNL-2FFCU-2F.22 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0095PNL-2FFCU-2F.22 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0096PNL-2FFCU-2F.23 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0097PNL-2FFCU-2F.23 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0098PNL-2FFCU-2F.24 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0099PNL-2FFCU-2F.24 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0100PNL-2FFCU-2F.25 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0101PNL-2FFCU-2F.25 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0102PNL-2FFCU-2F.26 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0103PNL-2FFCU-2F.26 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0104PNL-2FFCU-2F.27 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0105PNL-2FFCU-2F.27 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0106PNL-2FFCU-2F.28 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0107PNL-2FFCU-2F.28 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0108PNL-2FFCU-2F.29 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0109PNL-2FFCU-2F.29 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0110PNL-2FFCU-2F.30 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0111PNL-2FFCU-2F.30 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU2F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0112PNL-3FFCU-3F.01 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0113PNL-3FFCU-3F.01 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0114PNL-3FFCU-3F.02 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0115PNL-3FFCU-3F.02 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0116PNL-3FFCU-3F.03 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0117PNL-3FFCU-3F.03 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0118PNL-3FFCU-3F.04 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0119PNL-3FFCU-3F.04 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0120PNL-3FFCU-3F.05 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0121PNL-3FFCU-3F.05 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0122PNL-3FFCU-3F.06 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0123PNL-3FFCU-3F.06 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0124PNL-3FFCU-3F.07 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0125PNL-3FFCU-3F.07 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0126PNL-3FFCU-3F.08 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0127PNL-3FFCU-3F.08 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0128PNL-3FFCU-3F.09 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0129PNL-3FFCU-3F.09 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0130PNL-3FFCU-3F.10 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0131PNL-3FFCU-3F.10 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0132PNL-3FFCU-3F.11 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0133PNL-3FFCU-3F.11 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0134PNL-3FFCU-3F.12 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0135PNL-3FFCU-3F.12 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0136PNL-3FFCU-3F.13 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0137PNL-3FFCU-3F.13 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0138PNL-3FFCU-3F.14 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0139PNL-3FFCU-3F.14 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0140PNL-3FFCU-3F.15 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0141PNL-3FFCU-3F.15 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0142PNL-3FFCU-3F.16 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0143PNL-3FFCU-3F.16 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0144PNL-3FFCU-3F.17 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0145PNL-3FFCU-3F.17 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0146PNL-3FFCU-3F.18 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0147PNL-3FFCU-3F.18 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0148PNL-3FFCU-3F.19 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0149PNL-3FFCU-3F.19 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0150PNL-3FFCU-3F.20 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0151PNL-3FFCU-3F.20 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0152PNL-3FFCU-3F.21 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0153PNL-3FFCU-3F.21 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0154PNL-3FFCU-3F.22 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0155PNL-3FFCU-3F.22 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0156PNL-3FFCU-3F.23 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0157PNL-3FFCU-3F.23 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0158PNL-3FFCU-3F.24 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0159PNL-3FFCU-3F.24 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0160PNL-3FFCU-3F.25 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0161PNL-3FFCU-3F.25 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0162PNL-3FFCU-3F.26 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0163PNL-3FFCU-3F.26 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0164PNL-3FFCU-3F.27 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0165PNL-3FFCU-3F.27 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0166PNL-3FFCU-3F.28 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0167PNL-3FFCU-3F.28 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0168PNL-3FFCU-3F.29 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0169PNL-3FFCU-3F.29 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0170PNL-3FFCU-3F.30 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0171PNL-3FFCU-3F.30 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCU3F4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0172PNL-GFFCU-GF.01 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0173PNL-GFFCU-GF.01 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0174PNL-GFFCU-GF.02 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0175PNL-GFFCU-GF.02 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0176PNL-GFFCU-GF.03 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0177PNL-GFFCU-GF.03 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0178PNL-GFFCU-GF.04 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0179PNL-GFFCU-GF.04 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0180PNL-GFFCU-GF.05 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0181PNL-GFFCU-GF.05 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0182PNL-GFFCU-GF.06 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0183PNL-GFFCU-GF.06 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0184PNL-GFFCU-GF.07 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0185PNL-GFFCU-GF.07 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0186PNL-GFFCU-GF.08 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0187PNL-GFFCU-GF.08 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0188PNL-GFFCU-GF.09 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0189PNL-GFFCU-GF.09 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0190PNL-GFFCU-GF.10 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0191PNL-GFFCU-GF.10 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0192PNL-GFFCU-GF.11 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0193PNL-GFFCU-GF.11 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0194PNL-GFFCU-GF.12 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0195PNL-GFFCU-GF.12 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0196PNL-GFFCU-GF.13 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0197PNL-GFFCU-GF.13 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0198PNL-GFFCU-GF.14 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0199PNL-GFFCU-GF.14 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0200PNL-GFFCU-GF.15 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0201PNL-GFFCU-GF.15 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0202PNL-GFFCU-GF.16 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0203PNL-GFFCU-GF.16 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0204PNL-GFFCU-GF.17 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0205PNL-GFFCU-GF.17 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0206PNL-GFFCU-GF.18 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0207PNL-GFFCU-GF.18 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0208PNL-GFFCU-GF.19 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0209PNL-GFFCU-GF.19 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0210PNL-GFFCU-GF.20 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0211PNL-GFFCU-GF.20 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0212PNL-GFFCU-GF.21 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0213PNL-GFFCU-GF.21 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0214PNL-GFFCU-GF.22 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0215PNL-GFFCU-GF.22 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0216PNL-GFFCU-GF.23 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0217PNL-GFFCU-GF.23 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0218PNL-GFFCU-GF.24 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0219PNL-GFFCU-GF.24 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0220PNL-GFFCU-GF.25 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0221PNL-GFFCU-GF.25 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0222PNL-GFFCU-GF.26 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0223PNL-GFFCU-GF.26 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0224PNL-GFFCU-GF.27 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0225PNL-GFFCU-GF.27 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0226PNL-GFFCU-GF.28 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0227PNL-GFFCU-GF.28 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0228PNL-GFFCU-GF.29 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0229PNL-GFFCU-GF.29 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0230PNL-GFFCU-GF.30 (Equipment Supplier)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)242822 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0231PNL-GFFCU-GF.30 (ME Contractor)FCU (guestroom/zone, hardwired)VENT-FCUGF4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)142811 I/O points carried, 4C cable; length 28 m (typical_range:guestroom_zone_field)
C0232PNL-CHPLANT-GNDHDR-CHW-BP (BMS Contractor)CHW Bypass HeaderHVAC-ChillersPlant Room4C × 1.5 mm² shielded FRLS (BMS signal — sensors)341233 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0233PNL-CHPLANT-GNDHDR-CHWR (BMS Contractor)CHW Return Main HeaderHVAC-ChillersPlant Room4C × 1.5 mm² shielded FRLS (BMS signal — sensors)441233 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0234PNL-CHPLANT-GNDHDR-CHWS (BMS Contractor)CHW Supply Main HeaderHVAC-ChillersPlant Room4C × 1.5 mm² shielded FRLS (BMS signal — sensors)441233 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0235PNL-RDHDR-COW (BMS Contractor)Condenser Water HeaderHVAC-ChillersRoofdeck4C × 1.5 mm² shielded FRLS (BMS signal — sensors)441833 I/O points carried, 4C cable; length 18 m (typical_range:roofdeck_same_area)
C0236PNL-CHPLANT-GNDHDR-HW (BMS Contractor)Hot Water Header SetPL-HotWaterPlant Room4C × 1.5 mm² shielded FRLS (BMS signal — sensors)881266 I/O points carried, 8C cable; length 12 m (typical_range:plant_room_same_room)
C0237PNL-CHPLANT-GNDHP-1 (Equipment Supplier)Heat PumpPL-HeatPumpsPlant Room4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)341233 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0238PNL-CHPLANT-GNDHP-2 (Equipment Supplier)Heat PumpPL-HeatPumpsPlant Room4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)341233 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0239PNL-CHPLANT-GNDHP-3 (Equipment Supplier)Heat PumpPL-HeatPumpsPlant Room4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)341233 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0240PNL-RDPAHU-RD (BMS Contractor)Precooled Air Handling UnitVENT-PAHURoofdeck4C × 1.5 mm² shielded FRLS (BMS signal — sensors)441833 I/O points carried, 4C cable; length 18 m (typical_range:roofdeck_same_area)
C0241PNL-RDPAHU-RD (Equipment Supplier)Precooled Air Handling UnitVENT-PAHURoofdeck4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)561855 I/O points carried, 6C cable; length 18 m (typical_range:roofdeck_same_area)
C0242PNL-RDPAHU-RD (ME Contractor)Precooled Air Handling UnitVENT-PAHURoofdeck4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)241822 I/O points carried, 4C cable; length 18 m (typical_range:roofdeck_same_area)
C0243PNL-CHPLANT-GNDRP-1 (Equipment Supplier)Recirculating PumpPL-RecircPumpsPlant Room4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)241222 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0244PNL-CHPLANT-GNDRP-2 (Equipment Supplier)Recirculating PumpPL-RecircPumpsPlant Room4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)241222 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0245PNL-CHPLANT-GNDRP-3 (Equipment Supplier)Recirculating PumpPL-RecircPumpsPlant Room4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)241222 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0246PNL-CHPLANT-GNDRP-4 (Equipment Supplier)Recirculating PumpPL-RecircPumpsPlant Room4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)241222 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0247PNL-CHPLANT-GNDRP-5 (Equipment Supplier)Recirculating PumpPL-RecircPumpsPlant Room4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)241222 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0248PNL-CHPLANT-GNDRP-6 (Equipment Supplier)Recirculating PumpPL-RecircPumpsPlant Room4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)241222 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0249PNL-BSMTSB-1 (BMS Contractor)Steam BoilerPL-BoilerBasement4C × 1.5 mm² shielded FRLS (BMS signal — sensors)663255 I/O points carried, 6C cable; length 32 m (typical_range:boh_corridor_field)
C0250PNL-BSMTSB-1 (Equipment Supplier)Steam BoilerPL-BoilerBasement4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)343233 I/O points carried, 4C cable; length 32 m (typical_range:boh_corridor_field)
C0251PNL-RDNET-PNL-RD (Network)BMS Network DropNetworkpanelCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link181BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 18 m (typical_range:roofdeck_same_area)
C0252PNL-3FNET-PNL-3F (Network)BMS Network DropNetworkpanelCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link351BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 35 m (typical_range:same_floor_corridor_field)
C0253PNL-2FNET-PNL-2F (Network)BMS Network DropNetworkpanelCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link351BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 35 m (typical_range:same_floor_corridor_field)
C0254PNL-GFNET-PNL-GF (Network)BMS Network DropNetworkpanelCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link351BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 35 m (typical_range:same_floor_corridor_field)
C0255PNL-BSMTNET-PNL-BSMT (Network)BMS Network DropNetworkpanelCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link351BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 35 m (typical_range:same_floor_corridor_field)
C0256PNL-CHPLANT-GNDNET-PNL-CHPLANT-GND (Network)BMS Network DropNetworkpanelCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link121BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)
C0257PNL-BOH-2FNET-PNL-BOH-2F (Network)BMS Network DropNetworkpanelCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link321BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 32 m (typical_range:boh_corridor_field)
C0258PNL-HE-GFNET-PNL-HE-GF (Network)BMS Network DropNetworkpanelCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link351BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 35 m (typical_range:same_floor_corridor_field)

Trunks

IDFromToCable TypeLength (m)Notes
T0259BMS Server Room (head-end)All BMS panels at 2nd FloorCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80Network trunk for 2nd Floor — fiber to floor switch + Cat6 distribution to floor's BMS panels
T0260BMS Server Room (head-end)All BMS panels at BasementCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80Network trunk for Basement — fiber to floor switch + Cat6 distribution to floor's BMS panels
T0261BMS Server Room (head-end)All BMS panels at RoofdeckCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80Network trunk for Roofdeck — fiber to floor switch + Cat6 distribution to floor's BMS panels
T0262BMS Server Room (head-end)BMS panel controllers (per topology id mstp_main_backbone)BACnet MS/TP shielded twisted-pair trunk, 1pr × 22 AWG low-cap245Backbone routed from PNL-CHPLANT-GND through PNL-BSMT → PNL-HE-GF → PNL-GF → PNL-BOH-2F → PNL-2F → PNL-3F → PNL-RD. 7 inter-panel hops; mix of intra-floor and inter-floor segments. Total length applied below.

Panel Power Feeds

IDFromToCable TypeLength (m)Notes
P0263Local panelboard / EE-supplied feederPNL-2F — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)12240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 12 m (typical_range:plant_room_same_room)
P0264Local panelboard / EE-supplied feederPNL-3F — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)12240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 12 m (typical_range:plant_room_same_room)
P0265Local panelboard / EE-supplied feederPNL-BOH-2F — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)12240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 12 m (typical_range:plant_room_same_room)
P0266Local panelboard / EE-supplied feederPNL-BSMT — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)12240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 12 m (typical_range:plant_room_same_room)
P0267Local panelboard / EE-supplied feederPNL-CHPLANT-GND — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)12240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 12 m (typical_range:plant_room_same_room)
P0268Local panelboard / EE-supplied feederPNL-GF — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)12240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 12 m (typical_range:plant_room_same_room)
P0269Local panelboard / EE-supplied feederPNL-HE-GF — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)12240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 12 m (typical_range:plant_room_same_room)
P0270Local panelboard / EE-supplied feederPNL-RD — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)12240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 12 m (typical_range:plant_room_same_room)