Summary

A2 — Equipment Takeoff Summary
Total instances161
By equipment class
FCU (guestroom/zone, hardwired)90
Multifunction Power Meter (Feeder)10
BMS Network Drop8
AHU (Chilled-Water-Served)6
Calorifier (Hot Water Storage Tank)6
Recirculating Pump6
Exhaust Fan (General)4
Chiller (Package Water-Cooled)3
Primary CHW Pump3
Condenser Water Pump3
Cooling Tower3
DOAS Unit3
Heat Pump3
Multifunction Power Meter (Main)3
BTU Meter1
Primary CHW Pump (Standby)1
Cooling Tower (Common)1
CHW Bypass Header1
CHW Return Main Header1
CHW Supply Main Header1
Condenser Water Header1
Hot Water Header Set1
Precooled Air Handling Unit1
Steam Boiler1
By location
2F35
GF33
3F32
Plant Room27
Sub-Distribution Board10
panel8
Roofdeck7
Basement3
Plant Room (Basement)3
Main Switchgear3
By panel
PNL-GF47
PNL-2F35
PNL-3F33
PNL-CHPLANT-GND31
PNL-RD8
PNL-BSMT4
PNL-BOH-2F2
PNL-HE-GF1

Equipment Takeoff

IDEquipment ClassQuantityLocationSystemPanelPrimary C/OPhysical I/OHLI SubpointsNetwork DropsTotal I/OMake/Model AssumedNetwork TypeTypical SupplierNotes
AHU-AMEN-3FAHU (Chilled-Water-Served)13FVENT-AHUPNL-3FBMS Contractor120012Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-BALL-2FAHU (Chilled-Water-Served)12FVENT-AHUPNL-2FBMS Contractor120012Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-BOH-2FAHU (Chilled-Water-Served)12FVENT-AHUPNL-BOH-2FBMS Contractor120012Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-BOH-BSMTAHU (Chilled-Water-Served)1BasementVENT-AHUPNL-BSMTBMS Contractor120012Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-LOBBY-GFAHU (Chilled-Water-Served)1GFVENT-AHUPNL-GFBMS Contractor120012Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-REST-2FAHU (Chilled-Water-Served)12FVENT-AHUPNL-2FBMS Contractor120012Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
BTU-CHWS-MAINBTU Meter1Plant RoomHVAC-ChillersPNL-CHPLANT-GNDBMS Contractor0101Ultrasonic or insertion-type BTU meter with Modbus output (Onicon, Aichi, Kamstrup)Modbus RTU/TCPBMS contractorSystem-level energy submeter.
CAL-1Calorifier (Hot Water Storage Tank)1Plant RoomPL-CalorifiersPNL-CHPLANT-GNDBMS Contractor1001Pressurised hot-water storage tank with internal coil, sized per design hot water demandHardwiredPlumbing contractorBMS supplies tank temperature sensor (immersion or strapped probe).
CAL-2Calorifier (Hot Water Storage Tank)1Plant RoomPL-CalorifiersPNL-CHPLANT-GNDBMS Contractor1001Pressurised hot-water storage tank with internal coil, sized per design hot water demandHardwiredPlumbing contractorBMS supplies tank temperature sensor (immersion or strapped probe).
CAL-3Calorifier (Hot Water Storage Tank)1Plant RoomPL-CalorifiersPNL-CHPLANT-GNDBMS Contractor1001Pressurised hot-water storage tank with internal coil, sized per design hot water demandHardwiredPlumbing contractorBMS supplies tank temperature sensor (immersion or strapped probe).
CAL-4Calorifier (Hot Water Storage Tank)1Plant RoomPL-CalorifiersPNL-CHPLANT-GNDBMS Contractor1001Pressurised hot-water storage tank with internal coil, sized per design hot water demandHardwiredPlumbing contractorBMS supplies tank temperature sensor (immersion or strapped probe).
CAL-5Calorifier (Hot Water Storage Tank)1Plant RoomPL-CalorifiersPNL-CHPLANT-GNDBMS Contractor1001Pressurised hot-water storage tank with internal coil, sized per design hot water demandHardwiredPlumbing contractorBMS supplies tank temperature sensor (immersion or strapped probe).
CAL-6Calorifier (Hot Water Storage Tank)1Plant RoomPL-CalorifiersPNL-CHPLANT-GNDBMS Contractor1001Pressurised hot-water storage tank with internal coil, sized per design hot water demandHardwiredPlumbing contractorBMS supplies tank temperature sensor (immersion or strapped probe).
CH-1Chiller (Package Water-Cooled)1Plant Room (Basement)HVAC-ChillersPNL-CHPLANT-GNDEquipment Supplier0101Tier-1 BACnet IP chiller (Trane/York/Carrier/Daikin), water-cooled centrifugal or screw, sized per design cooling loadBACnet/IPMechanical contractor / Equipment supplierBMS reads via chiller's native BACnet gateway. BMS supplies external T-sensors on entering/leaving CHW & CW pipes.
CH-2Chiller (Package Water-Cooled)1Plant Room (Basement)HVAC-ChillersPNL-CHPLANT-GNDEquipment Supplier0101Tier-1 BACnet IP chiller (Trane/York/Carrier/Daikin), water-cooled centrifugal or screw, sized per design cooling loadBACnet/IPMechanical contractor / Equipment supplierBMS reads via chiller's native BACnet gateway. BMS supplies external T-sensors on entering/leaving CHW & CW pipes.
CH-3Chiller (Package Water-Cooled)1Plant Room (Basement)HVAC-ChillersPNL-CHPLANT-GNDEquipment Supplier0101Tier-1 BACnet IP chiller (Trane/York/Carrier/Daikin), water-cooled centrifugal or screw, sized per design cooling loadBACnet/IPMechanical contractor / Equipment supplierBMS reads via chiller's native BACnet gateway. BMS supplies external T-sensors on entering/leaving CHW & CW pipes.
CHWP-1.1Primary CHW Pump1Plant RoomHVAC-PumpsPNL-CHPLANT-GNDEquipment Supplier3205End-suction or split-case centrifugal with VFD, sized per design CHW flowHardwired (BMS reads VFD via BACnet HLI)Mechanical contractorVFD typically Equipment Supplier provided with BACnet card.
CHWP-1.2Primary CHW Pump1Plant RoomHVAC-PumpsPNL-CHPLANT-GNDEquipment Supplier3205End-suction or split-case centrifugal with VFD, sized per design CHW flowHardwired (BMS reads VFD via BACnet HLI)Mechanical contractorVFD typically Equipment Supplier provided with BACnet card.
CHWP-1.3Primary CHW Pump1Plant RoomHVAC-PumpsPNL-CHPLANT-GNDEquipment Supplier3205End-suction or split-case centrifugal with VFD, sized per design CHW flowHardwired (BMS reads VFD via BACnet HLI)Mechanical contractorVFD typically Equipment Supplier provided with BACnet card.
CHWP-1.STBYPrimary CHW Pump (Standby)1Plant RoomHVAC-PumpsPNL-CHPLANT-GNDEquipment Supplier2002Same as Primary CHW Pump (1 standby for N+1 redundancy)Hardwired (BMS reads VFD via BACnet HLI)Mechanical contractorStandby unit per A-CHW-001.
COWP-1Condenser Water Pump1Plant RoomHVAC-PumpsPNL-CHPLANT-GNDEquipment Supplier4004End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious)HardwiredMechanical contractorBMS reads aux contacts; commands start via DO.
COWP-2Condenser Water Pump1Plant RoomHVAC-PumpsPNL-CHPLANT-GNDEquipment Supplier4004End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious)HardwiredMechanical contractorBMS reads aux contacts; commands start via DO.
COWP-3Condenser Water Pump1Plant RoomHVAC-PumpsPNL-CHPLANT-GNDEquipment Supplier4004End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious)HardwiredMechanical contractorBMS reads aux contacts; commands start via DO.
CT-1Cooling Tower1RoofdeckHVAC-Cooling-TowersPNL-RDEquipment Supplier6006Induced-draft counterflow open cooling tower (Marley/BAC/EVAPCO), sized per condenser water flowHardwiredMechanical contractor / Equipment supplierBMS supplies basin level sensors and condenser water header T-sensors.
CT-2Cooling Tower1RoofdeckHVAC-Cooling-TowersPNL-RDEquipment Supplier6006Induced-draft counterflow open cooling tower (Marley/BAC/EVAPCO), sized per condenser water flowHardwiredMechanical contractor / Equipment supplierBMS supplies basin level sensors and condenser water header T-sensors.
CT-3Cooling Tower1RoofdeckHVAC-Cooling-TowersPNL-RDEquipment Supplier6006Induced-draft counterflow open cooling tower (Marley/BAC/EVAPCO), sized per condenser water flowHardwiredMechanical contractor / Equipment supplierBMS supplies basin level sensors and condenser water header T-sensors.
CT-COMMONCooling Tower (Common)1RoofdeckHVAC-Cooling-TowersPNL-RDBMS Contractor2002Common BMS sensors at cooling tower area (OA T/RH, condenser headers)HardwiredBMS contractorField instrumentation only — no equipment per se.
DOAS-2FDOAS Unit12FVENT-DOASPNL-2FEquipment Supplier210021Dedicated Outdoor Air System with energy recovery wheel, supply + exhaust fans, CHW coilBACnet/IPMechanical contractor / Equipment supplierNative BACnet controller typical. BMS supplies external sensors (OA T/RH/Flow, indoor T/RH, exhaust T) and modulating valve actuator.
DOAS-GFDOAS Unit1GFVENT-DOASPNL-GFEquipment Supplier210021Dedicated Outdoor Air System with energy recovery wheel, supply + exhaust fans, CHW coilBACnet/IPMechanical contractor / Equipment supplierNative BACnet controller typical. BMS supplies external sensors (OA T/RH/Flow, indoor T/RH, exhaust T) and modulating valve actuator.
DOAS-RDDOAS Unit1RoofdeckVENT-DOASPNL-RDEquipment Supplier210021Dedicated Outdoor Air System with energy recovery wheel, supply + exhaust fans, CHW coilBACnet/IPMechanical contractor / Equipment supplierNative BACnet controller typical. BMS supplies external sensors (OA T/RH/Flow, indoor T/RH, exhaust T) and modulating valve actuator.
EAS-2FExhaust Fan (General)12FVENT-EASPNL-2FEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EAS-3FExhaust Fan (General)13FVENT-EASPNL-3FEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EAS-BSMTExhaust Fan (General)1BasementVENT-EASPNL-BSMTEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EAS-GFExhaust Fan (General)1GFVENT-EASPNL-GFEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
FCU-2F.01FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.02FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.03FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.04FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.05FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.06FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.07FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.08FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.09FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.10FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.11FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.12FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.13FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.14FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.15FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.16FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.17FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.18FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.19FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.20FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.21FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.22FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.23FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.24FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.25FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.26FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.27FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.28FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.29FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-2F.30FCU (guestroom/zone, hardwired)12FVENT-FCUPNL-2FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.01FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.02FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.03FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.04FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.05FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.06FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.07FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.08FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.09FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.10FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.11FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.12FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.13FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.14FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.15FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.16FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.17FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.18FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.19FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.20FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.21FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.22FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.23FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.24FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.25FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.26FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.27FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.28FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.29FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-3F.30FCU (guestroom/zone, hardwired)13FVENT-FCUPNL-3FEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.01FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.02FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.03FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.04FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.05FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.06FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.07FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.08FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.09FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.10FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.11FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.12FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.13FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.14FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.15FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.16FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.17FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.18FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.19FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.20FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.21FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.22FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.23FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.24FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.25FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.26FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.27FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.28FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.29FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
FCU-GF.30FCU (guestroom/zone, hardwired)1GFVENT-FCUPNL-GFEquipment Supplier3003(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
HDR-CHW-BPCHW Bypass Header1Plant RoomHVAC-ChillersPNL-CHPLANT-GNDBMS Contractor3003BMS dP/dT sensors + motorized bypass valve (BMS-supplied)HardwiredBMS contractorBMS controls bypass valve to maintain CHW differential.
HDR-CHWRCHW Return Main Header1Plant RoomHVAC-ChillersPNL-CHPLANT-GNDBMS Contractor3003BMS T+P sensors on CHW return manifoldHardwiredBMS contractorField instrumentation only.
HDR-CHWSCHW Supply Main Header1Plant RoomHVAC-ChillersPNL-CHPLANT-GNDBMS Contractor3003BMS T+P sensors on CHW supply manifoldHardwiredBMS contractorField instrumentation only.
HDR-COWCondenser Water Header1RoofdeckHVAC-ChillersPNL-RDBMS Contractor3003BMS T sensors on condenser water headers at roofdeckHardwiredBMS contractorField instrumentation only.
HDR-HWHot Water Header Set1Plant RoomPL-HotWaterPNL-CHPLANT-GNDBMS Contractor6006Hot water supply/return manifolds with BMS T sensors and make-up cold water T sensorHardwiredBMS contractorField instrumentation on existing piping.
HP-1Heat Pump1Plant RoomPL-HeatPumpsPNL-CHPLANT-GNDEquipment Supplier3003Air-source or water-source heat pump for hot water heatingHardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractor / Equipment supplierBMS reads pump status/HOA/trip via aux contacts.
HP-2Heat Pump1Plant RoomPL-HeatPumpsPNL-CHPLANT-GNDEquipment Supplier3003Air-source or water-source heat pump for hot water heatingHardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractor / Equipment supplierBMS reads pump status/HOA/trip via aux contacts.
HP-3Heat Pump1Plant RoomPL-HeatPumpsPNL-CHPLANT-GNDEquipment Supplier3003Air-source or water-source heat pump for hot water heatingHardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractor / Equipment supplierBMS reads pump status/HOA/trip via aux contacts.
MTR-FDR-01Multifunction Power Meter (Feeder)1Sub-Distribution BoardPower-EEPNL-GFBMS Contractor0101Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
MTR-FDR-02Multifunction Power Meter (Feeder)1Sub-Distribution BoardPower-EEPNL-GFBMS Contractor0101Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
MTR-FDR-03Multifunction Power Meter (Feeder)1Sub-Distribution BoardPower-EEPNL-GFBMS Contractor0101Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
MTR-FDR-04Multifunction Power Meter (Feeder)1Sub-Distribution BoardPower-EEPNL-GFBMS Contractor0101Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
MTR-FDR-05Multifunction Power Meter (Feeder)1Sub-Distribution BoardPower-EEPNL-GFBMS Contractor0101Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
MTR-FDR-06Multifunction Power Meter (Feeder)1Sub-Distribution BoardPower-EEPNL-GFBMS Contractor0101Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
MTR-FDR-07Multifunction Power Meter (Feeder)1Sub-Distribution BoardPower-EEPNL-GFBMS Contractor0101Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
MTR-FDR-08Multifunction Power Meter (Feeder)1Sub-Distribution BoardPower-EEPNL-GFBMS Contractor0101Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
MTR-FDR-09Multifunction Power Meter (Feeder)1Sub-Distribution BoardPower-EEPNL-GFBMS Contractor0101Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
MTR-FDR-10Multifunction Power Meter (Feeder)1Sub-Distribution BoardPower-EEPNL-GFBMS Contractor0101Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
MTR-MAIN-1Multifunction Power Meter (Main)1Main SwitchgearPower-EEPNL-GFBMS Contractor0101Multifunction power meter with Modbus output (Schneider PM-series, ABB M2M, Siemens SENTRON), main switchgear classModbus RTU/TCPBMS contractorMounted in main switchgear or on dedicated BMS-side panel.
MTR-MAIN-2Multifunction Power Meter (Main)1Main SwitchgearPower-EEPNL-GFBMS Contractor0101Multifunction power meter with Modbus output (Schneider PM-series, ABB M2M, Siemens SENTRON), main switchgear classModbus RTU/TCPBMS contractorMounted in main switchgear or on dedicated BMS-side panel.
MTR-MAIN-3Multifunction Power Meter (Main)1Main SwitchgearPower-EEPNL-GFBMS Contractor0101Multifunction power meter with Modbus output (Schneider PM-series, ABB M2M, Siemens SENTRON), main switchgear classModbus RTU/TCPBMS contractorMounted in main switchgear or on dedicated BMS-side panel.
NET-PNL-2FBMS Network Drop1panelNetworkPNL-2FBMS Contractor0011(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
NET-PNL-3FBMS Network Drop1panelNetworkPNL-3FBMS Contractor0011(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
NET-PNL-BOH-2FBMS Network Drop1panelNetworkPNL-BOH-2FBMS Contractor0011(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
NET-PNL-BSMTBMS Network Drop1panelNetworkPNL-BSMTBMS Contractor0011(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
NET-PNL-CHPLANT-GNDBMS Network Drop1panelNetworkPNL-CHPLANT-GNDBMS Contractor0011(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
NET-PNL-GFBMS Network Drop1panelNetworkPNL-GFBMS Contractor0011(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
NET-PNL-HE-GFBMS Network Drop1panelNetworkPNL-HE-GFBMS Contractor0011(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
NET-PNL-RDBMS Network Drop1panelNetworkPNL-RDBMS Contractor0011(class default not defined — add to equipment-class-defaults.yaml)TBDTBD
PAHU-RDPrecooled Air Handling Unit1RoofdeckVENT-PAHUPNL-RDEquipment Supplier100010Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust pathHardwired (VFD via BACnet HLI)Mechanical contractor / Equipment supplierPrecool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors.
RP-1Recirculating Pump1Plant RoomPL-RecircPumpsPNL-CHPLANT-GNDEquipment Supplier2002Hot water recirculating pump, fixed-speed (typical for hotwater systems)Hardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractorBMS reads aux contacts only.
RP-2Recirculating Pump1Plant RoomPL-RecircPumpsPNL-CHPLANT-GNDEquipment Supplier2002Hot water recirculating pump, fixed-speed (typical for hotwater systems)Hardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractorBMS reads aux contacts only.
RP-3Recirculating Pump1Plant RoomPL-RecircPumpsPNL-CHPLANT-GNDEquipment Supplier2002Hot water recirculating pump, fixed-speed (typical for hotwater systems)Hardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractorBMS reads aux contacts only.
RP-4Recirculating Pump1Plant RoomPL-RecircPumpsPNL-CHPLANT-GNDEquipment Supplier2002Hot water recirculating pump, fixed-speed (typical for hotwater systems)Hardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractorBMS reads aux contacts only.
RP-5Recirculating Pump1Plant RoomPL-RecircPumpsPNL-CHPLANT-GNDEquipment Supplier2002Hot water recirculating pump, fixed-speed (typical for hotwater systems)Hardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractorBMS reads aux contacts only.
RP-6Recirculating Pump1Plant RoomPL-RecircPumpsPNL-CHPLANT-GNDEquipment Supplier2002Hot water recirculating pump, fixed-speed (typical for hotwater systems)Hardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractorBMS reads aux contacts only.
SB-1Steam Boiler1BasementPL-BoilerPNL-BSMTBMS Contractor8008Fire-tube steam boiler with multi-stage burner, fuel-oil fired (typical for hotel laundry)HardwiredMechanical contractor / Equipment supplierBMS supplies steam pressure, feedwater T, fluegas T+O2 sensors. Boiler equipment provides aux contacts for status/HOA/trip points.