Summary

A3 — Cable Schedule, Audit View
ProjectKingsford Hotel Bacolod — BMS (AB-Run-2)
Canonical sourceA3-cable-schedule.yaml
How to record correctionsEdit the canonical YAML directly — add a verification: block to the affected row(s)
Totals
Total cables113
Total length (m)2,832
Field cables96
Trunk cables6
Panel power feeds11
Verification status
StatusCount% of total
verified00%
needs_correction00%
uncertain00%
unverified113100%
⚠ Known weak points
Cable lengths are estimates based on assumption A-001 (30 m average panel-to-device run, 80 m trunk per floor). Field-verified lengths typically vary by ±20% per cable. THIS IS THE SYSTEM'S WEAKEST AUTO-GENERATED QUANTITY — please verify before issuing the BOQ to the customer.
How corrections flow
1. Open A3-cable-schedule.yaml in any text editor.
2. Find the affected row by ID (column A in the Detail sheet).
3. Add a verification: block — see the 'Verification schema' sheet for the template.
4. Re-run: python3 _playbook/tools/generate-deliverables.py <project>
5. Corrections flow through B4 manhours, BOQ material costs, and final deliverables automatically.

By Panel

PanelCable countTotal length (m)
PNL-AIR-2F15450
PNL-CASINO-GF11330
PNL-AIR-GF9270
PNL-CH-PLANT-2F17204
PNL-AIR-ROOF13156
PNL-AIR-3F5150
PNL-CT-ROOF8102
PNL-PL-LG778
PNL-AIR-BSMT560
PNL-BLR-LG558
PNL-PM-LG112
TOTAL (field cables)961870

By Floor

FloorCable countTotal length (m)
2nd Floor32654
Ground20600
Roofdeck21258
3F Amenity5150
Lower Ground13148
Basement560
TOTAL961870

By Cable Type

Cable typeCountTotal length (m)
4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)39781
4C × 1.5 mm² shielded FRLS (BMS signal — sensors)28507
4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)17384
Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12198

Detail (cables)

IDFromToCable typeLength (m)StatusCorrected (m)Verified byDateDrawing refNotes
C0001PNL-AIR-2FAHU-2F-A (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0002PNL-AIR-2FAHU-2F-A (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0003PNL-AIR-2FAHU-2F-A (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0004PNL-AIR-2FAHU-2F-B (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0005PNL-AIR-2FAHU-2F-B (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0006PNL-AIR-2FAHU-2F-B (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0007PNL-AIR-3FAHU-3F-AM (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0008PNL-AIR-3FAHU-3F-AM (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0009PNL-AIR-3FAHU-3F-AM (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0010PNL-CASINO-GFAHU-CASINO-1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0011PNL-CASINO-GFAHU-CASINO-1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0012PNL-CASINO-GFAHU-CASINO-1 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0013PNL-CASINO-GFAHU-CASINO-2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0014PNL-CASINO-GFAHU-CASINO-2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0015PNL-CASINO-GFAHU-CASINO-2 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0016PNL-CASINO-GFAHU-GF-CASINO (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0017PNL-CASINO-GFAHU-GF-CASINO (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0018PNL-CASINO-GFAHU-GF-CASINO (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0019PNL-AIR-GFAHU-GF-LOB (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0020PNL-AIR-GFAHU-GF-LOB (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0021PNL-AIR-GFAHU-GF-LOB (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0022PNL-AIR-GFAHU-GF-REST (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0023PNL-AIR-GFAHU-GF-REST (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0024PNL-AIR-GFAHU-GF-REST (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0025PNL-BLR-LGBLR-1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)10unverified
C0026PNL-BLR-LGBLR-1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)12unverified
C0027PNL-BLR-LGBLR-2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)12unverified
C0028PNL-BLR-LGBLR-2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)12unverified
C0029PNL-PL-LGCALOR-LG (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)8unverified
C0030PNL-AIR-ROOFCALOR-ROOF (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)12unverified
C0031PNL-CH-PLANT-2FCH-1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)15unverified
C0032PNL-CH-PLANT-2FCH-1 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)12unverified
C0033PNL-CH-PLANT-2FCH-2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)18unverified
C0034PNL-CH-PLANT-2FCH-2 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)12unverified
C0035PNL-CH-PLANT-2FCHW-BYP (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)10unverified
C0036PNL-CH-PLANT-2FCHW-RET-HDR (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)8unverified
C0037PNL-CH-PLANT-2FCHW-SUP-HDR (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)8unverified
C0038PNL-CH-PLANT-2FCHWP-1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)10unverified
C0039PNL-CH-PLANT-2FCHWP-2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)11unverified
C0040PNL-CH-PLANT-2FCHWP-3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)12unverified
C0041PNL-CT-ROOFCT-1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)12unverified
C0042PNL-CT-ROOFCT-1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)14unverified
C0043PNL-CT-ROOFCT-2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)12unverified
C0044PNL-CT-ROOFCT-2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)16unverified
C0045PNL-CT-ROOFCT-COMMON (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)12unverified
C0046PNL-CT-ROOFCT-COMMON (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)12unverified
C0047PNL-CT-ROOFCW-HDR (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)12unverified
C0048PNL-CH-PLANT-2FCWP-1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)13unverified
C0049PNL-CH-PLANT-2FCWP-2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)13unverified
C0050PNL-CH-PLANT-2FCWP-3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)14unverified
C0051PNL-AIR-2FDOAS-2F (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0052PNL-AIR-2FDOAS-2F (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0053PNL-AIR-2FDOAS-2F (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0054PNL-AIR-ROOFDOAS-RD1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)12unverified
C0055PNL-AIR-ROOFDOAS-RD1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)12unverified
C0056PNL-AIR-ROOFDOAS-RD1 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)12unverified
C0057PNL-AIR-ROOFDOAS-RD2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)12unverified
C0058PNL-AIR-ROOFDOAS-RD2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)12unverified
C0059PNL-AIR-ROOFDOAS-RD2 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)12unverified
C0060PNL-AIR-2FEAS-GEN-2F (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0061PNL-AIR-3FEAS-GEN-3F (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0062PNL-AIR-BSMTEAS-GEN-BSMT (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)12unverified
C0063PNL-AIR-GFEAS-GEN-GF (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0064PNL-AIR-ROOFEAS-GEN-ROOF (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)12unverified
C0065PNL-AIR-2FEAS-TOILET-2F (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0066PNL-AIR-3FEAS-TOILET-3F (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0067PNL-AIR-BSMTEAS-TOILET-BSMT (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)12unverified
C0068PNL-AIR-GFEAS-TOILET-GF (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0069PNL-PL-LGHP-LG-1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)12unverified
C0070PNL-AIR-ROOFHP-ROOF-1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)12unverified
C0071PNL-PL-LGHW-HEADERS-LG (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)10unverified
C0072PNL-PL-LGHW-PUMP-LG-1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)12unverified
C0073PNL-PL-LGHW-PUMP-LG-2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)12unverified
C0074PNL-AIR-ROOFHW-PUMP-ROOF-1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)12unverified
C0075PNL-CASINO-GFOZ-CASINO-1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0076PNL-AIR-2FPAHU-2F (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0077PNL-AIR-2FPAHU-2F (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0078PNL-AIR-2FPAHU-2F (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0079PNL-AIR-BSMTPAHU-BSMT (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)12unverified
C0080PNL-AIR-BSMTPAHU-BSMT (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)12unverified
C0081PNL-AIR-BSMTPAHU-BSMT (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)12unverified
C0082PNL-AIR-ROOFPAHU-ROOF (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)12unverified
C0083PNL-AIR-ROOFPAHU-ROOF (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)12unverified
C0084PNL-AIR-ROOFPAHU-ROOF (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)12unverified
C0085PNL-CH-PLANT-2FCH-1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0086PNL-CH-PLANT-2FCH-2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0087PNL-CH-PLANT-2FBTU-CHW-MAIN (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0088PNL-PM-LGPM-MAIN-LG (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0089PNL-CH-PLANT-2FPM-CHILLER (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0090PNL-CT-ROOFPM-COOLING (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0091PNL-AIR-2FPM-AIR-2F (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0092PNL-AIR-GFPM-AIR-GF (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0093PNL-CASINO-GFPM-CASINO (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0094PNL-BLR-LGPM-BOILER (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0095PNL-PL-LGPM-PLUMB (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
C0096PNL-PL-LGPM-FIREPMP (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)12unverified
T0097BMS Server Room (head-end)All BMS panels at 2nd FloorCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80unverified
T0098BMS Server Room (head-end)All BMS panels at BasementCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80unverified
T0099BMS Server Room (head-end)All BMS panels at GroundCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80unverified
T0100BMS Server Room (head-end)All BMS panels at Lower GroundCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80unverified
T0101BMS Server Room (head-end)All BMS panels at RoofdeckCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80unverified
T0102BMS Server Room (head-end)All BMS panel controllers (MS/TP daisy-chain or branched)BACnet MS/TP shielded twisted-pair trunk, 1pr × 22 AWG low-cap330unverified
P0103Local panelboard / EE-supplied feederPNL-AIR-2F — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18unverified
P0104Local panelboard / EE-supplied feederPNL-AIR-3F — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18unverified
P0105Local panelboard / EE-supplied feederPNL-AIR-BSMT — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18unverified
P0106Local panelboard / EE-supplied feederPNL-AIR-GF — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18unverified
P0107Local panelboard / EE-supplied feederPNL-AIR-ROOF — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)35unverified
P0108Local panelboard / EE-supplied feederPNL-BLR-LG — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18unverified
P0109Local panelboard / EE-supplied feederPNL-CASINO-GF — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18unverified
P0110Local panelboard / EE-supplied feederPNL-CH-PLANT-2F — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18unverified
P0111Local panelboard / EE-supplied feederPNL-CT-ROOF — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)35unverified
P0112Local panelboard / EE-supplied feederPNL-PL-LG — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18unverified
P0113Local panelboard / EE-supplied feederPNL-PM-LG — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18unverified

Verification schema

How to record verification / corrections in A3-cable-schedule.yaml
Find the affected row in the YAML by ID (Detail sheet column A) and add a verification: block:
- id: C0001
from: PNL-CH-PLANT-GND
to: CH-1 (BMS Contractor)
cable_type: 4C × 1.5 mm² shielded FRLS
length_m: 30
verification: # ADDED by team
status: needs_correction # unverified | verified | needs_correction | uncertain
corrected_length_m: 42 # team's measured / confirmed value
verified_by: J. Cruz
verified_date: 2026-05-10
drawing_ref: "EE-09 grid B-2"
notes: ""
After saving, re-run: python3 _playbook/tools/generate-deliverables.py <project>
Corrections propagate to B4 manhours, BOQ, and final deliverables automatically.
Recommended verification methods (priority order):
1. Site walkthrough with measurement (most accurate; for cable lengths, after structural completion).
2. Properly-scaled architectural drawings.
3. Mechanical contractor's tray layout combined with BMS panel locations.
4. A-001 default with ±20% contingency in BOQ — last resort.