| Panel | Location | System Scope | Equipment Count | Physical I/O | HLI Subpoints | Network Drops | Total I/O | DDC Controllers | Network Gateway | Total Controllers | Power (W) | Enclosure |
| PNL-AIR-2F | 2F Common Public | Air Conditioning, Exhaust, Power Monitoring, Ventilation | 7 | 70 | 4 | 1 | 75 | 2 | 1 | 2 | 55 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| PNL-AIR-3F | 3F Amenity | Air Conditioning, Exhaust | 3 | 20 | 0 | 0 | 20 | 1 | 0 | 1 | 25 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| PNL-AIR-BSMT | Basement BOH | Exhaust, Ventilation | 3 | 18 | 0 | 0 | 18 | 1 | 0 | 1 | 25 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| PNL-AIR-GF | Ground Floor Lobby / Ground Floor Restaurant | Air Conditioning, Exhaust, Power Monitoring | 5 | 34 | 4 | 1 | 39 | 1 | 1 | 2 | 55 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| PNL-AIR-ROOF | Roofdeck DOAS | Exhaust, Hot Water, Ventilation | 7 | 70 | 0 | 0 | 70 | 2 | 0 | 2 | 50 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| PNL-BLR-LG | Lower Ground Boiler Room | Boiler, Power Monitoring | 3 | 32 | 4 | 1 | 37 | 1 | 1 | 2 | 55 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| PNL-CASINO-GF | Ground Floor Casino / Ground Floor Casino Lobby | Air Conditioning, Casino Air Conditioning, Power Monitoring | 5 | 45 | 4 | 1 | 50 | 2 | 1 | 2 | 55 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| PNL-CH-PLANT-2F | 2F Chiller Plant Room | Chilled Water Plant, Condenser Water Loop, Power Monitoring | 13 | 59 | 44 | 4 | 107 | 2 | 1 | 2 | 70 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| PNL-CT-ROOF | Roofdeck Cooling Tower | Condenser Water Loop, Power Monitoring | 5 | 22 | 4 | 1 | 27 | 1 | 1 | 2 | 55 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| PNL-PL-LG | Lower Ground Boiler Room / Lower Ground Calorifier Room | Hot Water, Power Monitoring | 7 | 13 | 8 | 2 | 23 | 1 | 1 | 2 | 60 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |
| PNL-PM-LG | Lower Ground Main Switchgear | Power Monitoring | 1 | 0 | 7 | 1 | 8 | 1 | 1 | 2 | 55 | Wall-mount IP54 metal cabinet, sized per controller count + 30% spare |