Summary

A4 — Panel Schedule Summary
Total panels11
Total physical I/O383
Total HLI subpoints79
Total network drops12
Total I/O points474
Estimated total controllers20
Estimated total power (W)560

Panel Schedule

PanelLocationSystem ScopeEquipment CountPhysical I/OHLI SubpointsNetwork DropsTotal I/ODDC ControllersNetwork GatewayTotal ControllersPower (W)Enclosure
PNL-AIR-2F2F Common PublicAir Conditioning, Exhaust, Power Monitoring, Ventilation770417521255Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
PNL-AIR-3F3F AmenityAir Conditioning, Exhaust320002010125Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
PNL-AIR-BSMTBasement BOHExhaust, Ventilation318001810125Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
PNL-AIR-GFGround Floor Lobby / Ground Floor RestaurantAir Conditioning, Exhaust, Power Monitoring534413911255Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
PNL-AIR-ROOFRoofdeck DOASExhaust, Hot Water, Ventilation770007020250Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
PNL-BLR-LGLower Ground Boiler RoomBoiler, Power Monitoring332413711255Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
PNL-CASINO-GFGround Floor Casino / Ground Floor Casino LobbyAir Conditioning, Casino Air Conditioning, Power Monitoring545415021255Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
PNL-CH-PLANT-2F2F Chiller Plant RoomChilled Water Plant, Condenser Water Loop, Power Monitoring135944410721270Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
PNL-CT-ROOFRoofdeck Cooling TowerCondenser Water Loop, Power Monitoring522412711255Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
PNL-PL-LGLower Ground Boiler Room / Lower Ground Calorifier RoomHot Water, Power Monitoring713822311260Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
PNL-PM-LGLower Ground Main SwitchgearPower Monitoring1071811255Wall-mount IP54 metal cabinet, sized per controller count + 30% spare

Equipment per Panel

PanelEquipment Instance
PNL-AIR-2FAHU-2F-A
PNL-AIR-2FAHU-2F-B
PNL-AIR-2FDOAS-2F
PNL-AIR-2FEAS-GEN-2F
PNL-AIR-2FEAS-TOILET-2F
PNL-AIR-2FPAHU-2F
PNL-AIR-2FPM-AIR-2F
PNL-AIR-3FAHU-3F-AM
PNL-AIR-3FEAS-GEN-3F
PNL-AIR-3FEAS-TOILET-3F
PNL-AIR-BSMTEAS-GEN-BSMT
PNL-AIR-BSMTEAS-TOILET-BSMT
PNL-AIR-BSMTPAHU-BSMT
PNL-AIR-GFAHU-GF-LOB
PNL-AIR-GFAHU-GF-REST
PNL-AIR-GFEAS-GEN-GF
PNL-AIR-GFEAS-TOILET-GF
PNL-AIR-GFPM-AIR-GF
PNL-AIR-ROOFCALOR-ROOF
PNL-AIR-ROOFDOAS-RD1
PNL-AIR-ROOFDOAS-RD2
PNL-AIR-ROOFEAS-GEN-ROOF
PNL-AIR-ROOFHP-ROOF-1
PNL-AIR-ROOFHW-PUMP-ROOF-1
PNL-AIR-ROOFPAHU-ROOF
PNL-BLR-LGBLR-1
PNL-BLR-LGBLR-2
PNL-BLR-LGPM-BOILER
PNL-CASINO-GFAHU-CASINO-1
PNL-CASINO-GFAHU-CASINO-2
PNL-CASINO-GFAHU-GF-CASINO
PNL-CASINO-GFOZ-CASINO-1
PNL-CASINO-GFPM-CASINO
PNL-CH-PLANT-2FBTU-CHW-MAIN
PNL-CH-PLANT-2FCH-1
PNL-CH-PLANT-2FCH-2
PNL-CH-PLANT-2FCHW-BYP
PNL-CH-PLANT-2FCHW-RET-HDR
PNL-CH-PLANT-2FCHW-SUP-HDR
PNL-CH-PLANT-2FCHWP-1
PNL-CH-PLANT-2FCHWP-2
PNL-CH-PLANT-2FCHWP-3
PNL-CH-PLANT-2FCWP-1
PNL-CH-PLANT-2FCWP-2
PNL-CH-PLANT-2FCWP-3
PNL-CH-PLANT-2FPM-CHILLER
PNL-CT-ROOFCT-1
PNL-CT-ROOFCT-2
PNL-CT-ROOFCT-COMMON
PNL-CT-ROOFCW-HDR
PNL-CT-ROOFPM-COOLING
PNL-PL-LGCALOR-LG
PNL-PL-LGHP-LG-1
PNL-PL-LGHW-HEADERS-LG
PNL-PL-LGHW-PUMP-LG-1
PNL-PL-LGHW-PUMP-LG-2
PNL-PL-LGPM-FIREPMP
PNL-PL-LGPM-PLUMB
PNL-PM-LGPM-MAIN-LG