Summary

A3 — Cable Schedule Summary
Total field cable runs96
Total field cable length (m)1870
Total trunk cable length (m)730
Total power feed length (m)232
GRAND TOTAL cable length (m)2832
By cable type (m)
4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)781
4C × 1.5 mm² shielded FRLS (BMS signal — sensors)507
4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)384
Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)198

Field Cables

IDFromToEquipment ClassSystemLocationCable TypeConductors RequiredConductors SpecifiedLength (m)I/O Points CarriedNotes
C0001PNL-AIR-2FAHU-2F-A (BMS Contractor)AHU (Chilled-Water-Served)Air Conditioning2F Common Public4C × 1.5 mm² shielded FRLS (BMS signal — sensors)663044 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
C0002PNL-AIR-2FAHU-2F-A (Equipment Supplier)AHU (Chilled-Water-Served)Air Conditioning2F Common Public4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)883066 I/O points carried, 8C cable; length 30 m (typical_range:boh_same_floor_field)
C0003PNL-AIR-2FAHU-2F-A (ME Contractor)AHU (Chilled-Water-Served)Air Conditioning2F Common Public4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)663044 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
C0004PNL-AIR-2FAHU-2F-B (BMS Contractor)AHU (Chilled-Water-Served)Air Conditioning2F Common Public4C × 1.5 mm² shielded FRLS (BMS signal — sensors)663044 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
C0005PNL-AIR-2FAHU-2F-B (Equipment Supplier)AHU (Chilled-Water-Served)Air Conditioning2F Common Public4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)883066 I/O points carried, 8C cable; length 30 m (typical_range:boh_same_floor_field)
C0006PNL-AIR-2FAHU-2F-B (ME Contractor)AHU (Chilled-Water-Served)Air Conditioning2F Common Public4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)663044 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
C0007PNL-AIR-3FAHU-3F-AM (BMS Contractor)AHU (Chilled-Water-Served)Air Conditioning3F Amenity4C × 1.5 mm² shielded FRLS (BMS signal — sensors)663044 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
C0008PNL-AIR-3FAHU-3F-AM (Equipment Supplier)AHU (Chilled-Water-Served)Air Conditioning3F Amenity4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)883066 I/O points carried, 8C cable; length 30 m (typical_range:boh_same_floor_field)
C0009PNL-AIR-3FAHU-3F-AM (ME Contractor)AHU (Chilled-Water-Served)Air Conditioning3F Amenity4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)663044 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
C0010PNL-CASINO-GFAHU-CASINO-1 (BMS Contractor)AHU (Modulating CHW-served)Casino Air ConditioningGround Floor Casino4C × 1.5 mm² shielded FRLS (BMS signal — sensors)663044 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
C0011PNL-CASINO-GFAHU-CASINO-1 (Equipment Supplier)AHU (Modulating CHW-served)Casino Air ConditioningGround Floor Casino4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)883066 I/O points carried, 8C cable; length 30 m (typical_range:boh_same_floor_field)
C0012PNL-CASINO-GFAHU-CASINO-1 (ME Contractor)AHU (Modulating CHW-served)Casino Air ConditioningGround Floor Casino4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)663044 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
C0013PNL-CASINO-GFAHU-CASINO-2 (BMS Contractor)AHU (Modulating CHW-served)Casino Air ConditioningGround Floor Casino4C × 1.5 mm² shielded FRLS (BMS signal — sensors)663044 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
C0014PNL-CASINO-GFAHU-CASINO-2 (Equipment Supplier)AHU (Modulating CHW-served)Casino Air ConditioningGround Floor Casino4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)883066 I/O points carried, 8C cable; length 30 m (typical_range:boh_same_floor_field)
C0015PNL-CASINO-GFAHU-CASINO-2 (ME Contractor)AHU (Modulating CHW-served)Casino Air ConditioningGround Floor Casino4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)663044 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
C0016PNL-CASINO-GFAHU-GF-CASINO (BMS Contractor)AHU (Modulating CHW-served)Air ConditioningGround Floor Casino Lobby4C × 1.5 mm² shielded FRLS (BMS signal — sensors)663044 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
C0017PNL-CASINO-GFAHU-GF-CASINO (Equipment Supplier)AHU (Modulating CHW-served)Air ConditioningGround Floor Casino Lobby4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)883066 I/O points carried, 8C cable; length 30 m (typical_range:boh_same_floor_field)
C0018PNL-CASINO-GFAHU-GF-CASINO (ME Contractor)AHU (Modulating CHW-served)Air ConditioningGround Floor Casino Lobby4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)663044 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
C0019PNL-AIR-GFAHU-GF-LOB (BMS Contractor)AHU (Chilled-Water-Served)Air ConditioningGround Floor Lobby4C × 1.5 mm² shielded FRLS (BMS signal — sensors)663044 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
C0020PNL-AIR-GFAHU-GF-LOB (Equipment Supplier)AHU (Chilled-Water-Served)Air ConditioningGround Floor Lobby4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)883066 I/O points carried, 8C cable; length 30 m (typical_range:boh_same_floor_field)
C0021PNL-AIR-GFAHU-GF-LOB (ME Contractor)AHU (Chilled-Water-Served)Air ConditioningGround Floor Lobby4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)663044 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
C0022PNL-AIR-GFAHU-GF-REST (BMS Contractor)AHU (Chilled-Water-Served)Air ConditioningGround Floor Restaurant4C × 1.5 mm² shielded FRLS (BMS signal — sensors)663044 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
C0023PNL-AIR-GFAHU-GF-REST (Equipment Supplier)AHU (Chilled-Water-Served)Air ConditioningGround Floor Restaurant4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)883066 I/O points carried, 8C cable; length 30 m (typical_range:boh_same_floor_field)
C0024PNL-AIR-GFAHU-GF-REST (ME Contractor)AHU (Chilled-Water-Served)Air ConditioningGround Floor Restaurant4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)663044 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
C0025PNL-BLR-LGBLR-1 (BMS Contractor)Steam BoilerBoilerLower Ground Boiler Room4C × 1.5 mm² shielded FRLS (BMS signal — sensors)881066 I/O points carried, 8C cable; length 10 m (measured)
C0026PNL-BLR-LGBLR-1 (Equipment Supplier)Steam BoilerBoilerLower Ground Boiler Room4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)1212121010 I/O points carried, 12C cable; length 12 m (typical_range:plant_room_same_room)
C0027PNL-BLR-LGBLR-2 (BMS Contractor)Steam BoilerBoilerLower Ground Boiler Room4C × 1.5 mm² shielded FRLS (BMS signal — sensors)881266 I/O points carried, 8C cable; length 12 m (measured)
C0028PNL-BLR-LGBLR-2 (Equipment Supplier)Steam BoilerBoilerLower Ground Boiler Room4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)1212121010 I/O points carried, 12C cable; length 12 m (typical_range:plant_room_same_room)
C0029PNL-PL-LGCALOR-LG (BMS Contractor)Calorifier (Hot Water Storage Tank)Hot WaterLower Ground Calorifier Room4C × 1.5 mm² shielded FRLS (BMS signal — sensors)34811 I/O points carried, 4C cable; length 8 m (measured)
C0030PNL-AIR-ROOFCALOR-ROOF (BMS Contractor)Calorifier (Hot Water Storage Tank)Hot WaterRoofdeck DOAS4C × 1.5 mm² shielded FRLS (BMS signal — sensors)341211 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0031PNL-CH-PLANT-2FCH-1 (BMS Contractor)Chiller (Package Water-Cooled)Chilled Water Plant2F Chiller Plant Room4C × 1.5 mm² shielded FRLS (BMS signal — sensors)9121577 I/O points carried, 12C cable; length 15 m (measured)
C0032PNL-CH-PLANT-2FCH-1 (ME Contractor)Chiller (Package Water-Cooled)Chilled Water Plant2F Chiller Plant Room4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)441222 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0033PNL-CH-PLANT-2FCH-2 (BMS Contractor)Chiller (Package Water-Cooled)Chilled Water Plant2F Chiller Plant Room4C × 1.5 mm² shielded FRLS (BMS signal — sensors)9121877 I/O points carried, 12C cable; length 18 m (measured)
C0034PNL-CH-PLANT-2FCH-2 (ME Contractor)Chiller (Package Water-Cooled)Chilled Water Plant2F Chiller Plant Room4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)441222 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0035PNL-CH-PLANT-2FCHW-BYP (BMS Contractor)CHW Bypass HeaderChilled Water Plant2F Chiller Plant Room4C × 1.5 mm² shielded FRLS (BMS signal — sensors)661044 I/O points carried, 6C cable; length 10 m (measured)
C0036PNL-CH-PLANT-2FCHW-RET-HDR (BMS Contractor)CHW Return Main HeaderChilled Water Plant2F Chiller Plant Room4C × 1.5 mm² shielded FRLS (BMS signal — sensors)44822 I/O points carried, 4C cable; length 8 m (measured)
C0037PNL-CH-PLANT-2FCHW-SUP-HDR (BMS Contractor)CHW Supply Main HeaderChilled Water Plant2F Chiller Plant Room4C × 1.5 mm² shielded FRLS (BMS signal — sensors)44822 I/O points carried, 4C cable; length 8 m (measured)
C0038PNL-CH-PLANT-2FCHWP-1 (Equipment Supplier)Primary CHW PumpChilled Water Plant2F Chiller Plant Room4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)9121077 I/O points carried, 12C cable; length 10 m (measured)
C0039PNL-CH-PLANT-2FCHWP-2 (Equipment Supplier)Primary CHW PumpChilled Water Plant2F Chiller Plant Room4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)9121177 I/O points carried, 12C cable; length 11 m (measured)
C0040PNL-CH-PLANT-2FCHWP-3 (Equipment Supplier)Primary CHW Pump (Standby)Chilled Water Plant2F Chiller Plant Room4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)9121277 I/O points carried, 12C cable; length 12 m (measured)
C0041PNL-CT-ROOFCT-1 (BMS Contractor)Cooling TowerCondenser Water LoopRoofdeck Cooling Tower4C × 1.5 mm² shielded FRLS (BMS signal — sensors)661244 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
C0042PNL-CT-ROOFCT-1 (Equipment Supplier)Cooling TowerCondenser Water LoopRoofdeck Cooling Tower4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)561433 I/O points carried, 6C cable; length 14 m (measured)
C0043PNL-CT-ROOFCT-2 (BMS Contractor)Cooling TowerCondenser Water LoopRoofdeck Cooling Tower4C × 1.5 mm² shielded FRLS (BMS signal — sensors)661244 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
C0044PNL-CT-ROOFCT-2 (Equipment Supplier)Cooling TowerCondenser Water LoopRoofdeck Cooling Tower4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)561633 I/O points carried, 6C cable; length 16 m (measured)
C0045PNL-CT-ROOFCT-COMMON (BMS Contractor)Cooling Tower (Common)Condenser Water LoopRoofdeck Cooling Tower4C × 1.5 mm² shielded FRLS (BMS signal — sensors)661244 I/O points carried, 6C cable; length 12 m (measured)
C0046PNL-CT-ROOFCT-COMMON (ME Contractor)Cooling Tower (Common)Condenser Water LoopRoofdeck Cooling Tower4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)441222 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0047PNL-CT-ROOFCW-HDR (BMS Contractor)Condenser Water HeaderCondenser Water LoopRoofdeck Cooling Tower4C × 1.5 mm² shielded FRLS (BMS signal — sensors)441222 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0048PNL-CH-PLANT-2FCWP-1 (Equipment Supplier)Condenser Water PumpCondenser Water Loop2F Chiller Plant Room4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)661344 I/O points carried, 6C cable; length 13 m (measured)
C0049PNL-CH-PLANT-2FCWP-2 (Equipment Supplier)Condenser Water PumpCondenser Water Loop2F Chiller Plant Room4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)661344 I/O points carried, 6C cable; length 13 m (measured)
C0050PNL-CH-PLANT-2FCWP-3 (Equipment Supplier)Condenser Water PumpCondenser Water Loop2F Chiller Plant Room4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)661444 I/O points carried, 6C cable; length 14 m (measured)
C0051PNL-AIR-2FDOAS-2F (BMS Contractor)DOAS UnitVentilation2F Common Public4C × 1.5 mm² shielded FRLS (BMS signal — sensors)883066 I/O points carried, 8C cable; length 30 m (typical_range:boh_same_floor_field)
C0052PNL-AIR-2FDOAS-2F (Equipment Supplier)DOAS UnitVentilation2F Common Public4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)1616301414 I/O points carried, 16C cable; length 30 m (typical_range:boh_same_floor_field)
C0053PNL-AIR-2FDOAS-2F (ME Contractor)DOAS UnitVentilation2F Common Public4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)663044 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
C0054PNL-AIR-ROOFDOAS-RD1 (BMS Contractor)DOAS UnitVentilationRoofdeck DOAS4C × 1.5 mm² shielded FRLS (BMS signal — sensors)881266 I/O points carried, 8C cable; length 12 m (typical_range:plant_room_same_room)
C0055PNL-AIR-ROOFDOAS-RD1 (Equipment Supplier)DOAS UnitVentilationRoofdeck DOAS4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)1616121414 I/O points carried, 16C cable; length 12 m (typical_range:plant_room_same_room)
C0056PNL-AIR-ROOFDOAS-RD1 (ME Contractor)DOAS UnitVentilationRoofdeck DOAS4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)661244 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
C0057PNL-AIR-ROOFDOAS-RD2 (BMS Contractor)DOAS UnitVentilationRoofdeck DOAS4C × 1.5 mm² shielded FRLS (BMS signal — sensors)881266 I/O points carried, 8C cable; length 12 m (typical_range:plant_room_same_room)
C0058PNL-AIR-ROOFDOAS-RD2 (Equipment Supplier)DOAS UnitVentilationRoofdeck DOAS4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)1616121414 I/O points carried, 16C cable; length 12 m (typical_range:plant_room_same_room)
C0059PNL-AIR-ROOFDOAS-RD2 (ME Contractor)DOAS UnitVentilationRoofdeck DOAS4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)661244 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
C0060PNL-AIR-2FEAS-GEN-2F (Equipment Supplier)Exhaust Fan (General)Exhaust2F Common Public4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
C0061PNL-AIR-3FEAS-GEN-3F (Equipment Supplier)Exhaust Fan (General)Exhaust3F Amenity4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
C0062PNL-AIR-BSMTEAS-GEN-BSMT (Equipment Supplier)Exhaust Fan (General)ExhaustBasement BOH4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)561233 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
C0063PNL-AIR-GFEAS-GEN-GF (Equipment Supplier)Exhaust Fan (General)ExhaustGround Floor Lobby4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
C0064PNL-AIR-ROOFEAS-GEN-ROOF (Equipment Supplier)Exhaust Fan (General)ExhaustRoofdeck DOAS4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)561233 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
C0065PNL-AIR-2FEAS-TOILET-2F (Equipment Supplier)Exhaust Fan (Toilet)Exhaust2F Common Public4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
C0066PNL-AIR-3FEAS-TOILET-3F (Equipment Supplier)Exhaust Fan (Toilet)Exhaust3F Amenity4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
C0067PNL-AIR-BSMTEAS-TOILET-BSMT (Equipment Supplier)Exhaust Fan (Toilet)ExhaustBasement BOH4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)561233 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
C0068PNL-AIR-GFEAS-TOILET-GF (Equipment Supplier)Exhaust Fan (Toilet)ExhaustGround Floor Lobby4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
C0069PNL-PL-LGHP-LG-1 (Equipment Supplier)Heat PumpHot WaterLower Ground Calorifier Room4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)561233 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
C0070PNL-AIR-ROOFHP-ROOF-1 (Equipment Supplier)Heat PumpHot WaterRoofdeck DOAS4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)561233 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
C0071PNL-PL-LGHW-HEADERS-LG (BMS Contractor)Hot Water Header SetHot WaterLower Ground Calorifier Room4C × 1.5 mm² shielded FRLS (BMS signal — sensors)561033 I/O points carried, 6C cable; length 10 m (measured)
C0072PNL-PL-LGHW-PUMP-LG-1 (Equipment Supplier)Recirculating PumpHot WaterLower Ground Calorifier Room4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)561233 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
C0073PNL-PL-LGHW-PUMP-LG-2 (Equipment Supplier)Recirculating PumpHot WaterLower Ground Calorifier Room4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)561233 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
C0074PNL-AIR-ROOFHW-PUMP-ROOF-1 (Equipment Supplier)Recirculating PumpHot WaterRoofdeck DOAS4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)561233 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
C0075PNL-CASINO-GFOZ-CASINO-1 (Equipment Supplier)Ozone Generator (UV-light or Corona)Casino Air ConditioningGround Floor Casino4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
C0076PNL-AIR-2FPAHU-2F (BMS Contractor)Precooled Air Handling UnitVentilation2F Common Public4C × 1.5 mm² shielded FRLS (BMS signal — sensors)563033 I/O points carried, 6C cable; length 30 m (typical_range:boh_same_floor_field)
C0077PNL-AIR-2FPAHU-2F (Equipment Supplier)Precooled Air Handling UnitVentilation2F Common Public4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)9123077 I/O points carried, 12C cable; length 30 m (typical_range:boh_same_floor_field)
C0078PNL-AIR-2FPAHU-2F (ME Contractor)Precooled Air Handling UnitVentilation2F Common Public4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)443022 I/O points carried, 4C cable; length 30 m (typical_range:boh_same_floor_field)
C0079PNL-AIR-BSMTPAHU-BSMT (BMS Contractor)Precooled Air Handling UnitVentilationBasement BOH4C × 1.5 mm² shielded FRLS (BMS signal — sensors)561233 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
C0080PNL-AIR-BSMTPAHU-BSMT (Equipment Supplier)Precooled Air Handling UnitVentilationBasement BOH4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)9121277 I/O points carried, 12C cable; length 12 m (typical_range:plant_room_same_room)
C0081PNL-AIR-BSMTPAHU-BSMT (ME Contractor)Precooled Air Handling UnitVentilationBasement BOH4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)441222 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0082PNL-AIR-ROOFPAHU-ROOF (BMS Contractor)Precooled Air Handling UnitVentilationRoofdeck DOAS4C × 1.5 mm² shielded FRLS (BMS signal — sensors)561233 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
C0083PNL-AIR-ROOFPAHU-ROOF (Equipment Supplier)Precooled Air Handling UnitVentilationRoofdeck DOAS4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)9121277 I/O points carried, 12C cable; length 12 m (typical_range:plant_room_same_room)
C0084PNL-AIR-ROOFPAHU-ROOF (ME Contractor)Precooled Air Handling UnitVentilationRoofdeck DOAS4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)441222 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
C0085PNL-CH-PLANT-2FCH-1 (Network)Chiller (Package Water-Cooled)Chilled Water Plant2F Chiller Plant RoomCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link121BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)
C0086PNL-CH-PLANT-2FCH-2 (Network)Chiller (Package Water-Cooled)Chilled Water Plant2F Chiller Plant RoomCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link121BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)
C0087PNL-CH-PLANT-2FBTU-CHW-MAIN (Network)BTU MeterChilled Water Plant2F Chiller Plant RoomCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link121BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)
C0088PNL-PM-LGPM-MAIN-LG (Network)Multifunction Power Meter (Main)Power MonitoringLower Ground Main SwitchgearCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link121BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)
C0089PNL-CH-PLANT-2FPM-CHILLER (Network)Multifunction Power Meter (Feeder)Power Monitoring2F Chiller Plant RoomCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link121BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)
C0090PNL-CT-ROOFPM-COOLING (Network)Multifunction Power Meter (Feeder)Power MonitoringRoofdeck Cooling TowerCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link121BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)
C0091PNL-AIR-2FPM-AIR-2F (Network)Multifunction Power Meter (Feeder)Power Monitoring2F Common PublicCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link301BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 30 m (typical_range:boh_same_floor_field)
C0092PNL-AIR-GFPM-AIR-GF (Network)Multifunction Power Meter (Feeder)Power MonitoringGround Floor LobbyCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link301BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 30 m (typical_range:boh_same_floor_field)
C0093PNL-CASINO-GFPM-CASINO (Network)Multifunction Power Meter (Feeder)Power MonitoringGround Floor CasinoCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link301BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 30 m (typical_range:boh_same_floor_field)
C0094PNL-BLR-LGPM-BOILER (Network)Multifunction Power Meter (Feeder)Power MonitoringLower Ground Boiler RoomCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link121BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)
C0095PNL-PL-LGPM-PLUMB (Network)Multifunction Power Meter (Feeder)Power MonitoringLower Ground Calorifier RoomCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link121BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)
C0096PNL-PL-LGPM-FIREPMP (Network)Multifunction Power Meter (Feeder)Power MonitoringLower Ground Boiler RoomCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link121BACnet/IP or Modbus TCP — Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)

Trunks

IDFromToCable TypeLength (m)Notes
T0097BMS Server Room (head-end)All BMS panels at 2nd FloorCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80Network trunk for 2nd Floor — fiber to floor switch + Cat6 distribution to floor's BMS panels
T0098BMS Server Room (head-end)All BMS panels at BasementCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80Network trunk for Basement — fiber to floor switch + Cat6 distribution to floor's BMS panels
T0099BMS Server Room (head-end)All BMS panels at GroundCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80Network trunk for Ground — fiber to floor switch + Cat6 distribution to floor's BMS panels
T0100BMS Server Room (head-end)All BMS panels at Lower GroundCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80Network trunk for Lower Ground — fiber to floor switch + Cat6 distribution to floor's BMS panels
T0101BMS Server Room (head-end)All BMS panels at RoofdeckCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80Network trunk for Roofdeck — fiber to floor switch + Cat6 distribution to floor's BMS panels
T0102BMS Server Room (head-end)All BMS panel controllers (MS/TP daisy-chain or branched)BACnet MS/TP shielded twisted-pair trunk, 1pr × 22 AWG low-cap330MS/TP backbone interconnecting 11 BMS panels — refine after Q-008 layout review

Panel Power Feeds

IDFromToCable TypeLength (m)Notes
P0103Local panelboard / EE-supplied feederPNL-AIR-2F — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:panel_power_feed_local)
P0104Local panelboard / EE-supplied feederPNL-AIR-3F — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:panel_power_feed_local)
P0105Local panelboard / EE-supplied feederPNL-AIR-BSMT — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:panel_power_feed_local)
P0106Local panelboard / EE-supplied feederPNL-AIR-GF — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:panel_power_feed_local)
P0107Local panelboard / EE-supplied feederPNL-AIR-ROOF — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)35240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 35 m (typical_range:panel_power_feed_remote)
P0108Local panelboard / EE-supplied feederPNL-BLR-LG — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:panel_power_feed_local)
P0109Local panelboard / EE-supplied feederPNL-CASINO-GF — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:panel_power_feed_local)
P0110Local panelboard / EE-supplied feederPNL-CH-PLANT-2F — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:panel_power_feed_local)
P0111Local panelboard / EE-supplied feederPNL-CT-ROOF — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)35240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 35 m (typical_range:panel_power_feed_remote)
P0112Local panelboard / EE-supplied feederPNL-PL-LG — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:panel_power_feed_local)
P0113Local panelboard / EE-supplied feederPNL-PM-LG — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)18240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:panel_power_feed_local)