Summary

A2 — Equipment Takeoff Summary
Total instances59
By equipment class
Multifunction Power Meter (Feeder)8
AHU (Chilled-Water-Served)5
Exhaust Fan (General)5
Exhaust Fan (Toilet)4
AHU (Modulating CHW-served)3
Condenser Water Pump3
DOAS Unit3
Recirculating Pump3
Precooled Air Handling Unit3
Steam Boiler2
Calorifier (Hot Water Storage Tank)2
Chiller (Package Water-Cooled)2
Primary CHW Pump2
Cooling Tower2
Heat Pump2
BTU Meter1
CHW Bypass Header1
CHW Return Main Header1
CHW Supply Main Header1
Primary CHW Pump (Standby)1
Cooling Tower (Common)1
Condenser Water Header1
Hot Water Header Set1
Ozone Generator (UV-light or Corona)1
Multifunction Power Meter (Main)1
By location
2F Chiller Plant Room13
2F Common Public7
Roofdeck DOAS7
Lower Ground Calorifier Room6
Roofdeck Cooling Tower5
Ground Floor Casino4
Ground Floor Lobby4
Lower Ground Boiler Room4
3F Amenity3
Basement BOH3
Ground Floor Casino Lobby1
Ground Floor Restaurant1
Lower Ground Main Switchgear1
By panel
PNL-CH-PLANT-2F13
PNL-AIR-2F7
PNL-PL-LG7
PNL-AIR-ROOF7
PNL-CASINO-GF5
PNL-AIR-GF5
PNL-CT-ROOF5
PNL-AIR-3F3
PNL-BLR-LG3
PNL-AIR-BSMT3
PNL-PM-LG1

Equipment Takeoff

IDEquipment ClassQuantityLocationSystemPanelPrimary C/OPhysical I/OHLI SubpointsNetwork DropsTotal I/OMake/Model AssumedNetwork TypeTypical SupplierNotes
AHU-2F-AAHU (Chilled-Water-Served)12F Common PublicAir ConditioningPNL-AIR-2FEquipment Supplier140014Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-2F-BAHU (Chilled-Water-Served)12F Common PublicAir ConditioningPNL-AIR-2FEquipment Supplier140014Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-3F-AMAHU (Chilled-Water-Served)13F AmenityAir ConditioningPNL-AIR-3FEquipment Supplier140014Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-CASINO-1AHU (Modulating CHW-served)1Ground Floor CasinoCasino Air ConditioningPNL-CASINO-GFEquipment Supplier140014Modulating CHW-served AHU with VFD, modulating valve and dampers (position feedback)Hardwired (VFD via BACnet HLI)Mechanical contractorCasino-spec AHU — modulating actuators with position feedback; CO/CO2 monitoring at return duct.
AHU-CASINO-2AHU (Modulating CHW-served)1Ground Floor CasinoCasino Air ConditioningPNL-CASINO-GFEquipment Supplier140014Modulating CHW-served AHU with VFD, modulating valve and dampers (position feedback)Hardwired (VFD via BACnet HLI)Mechanical contractorCasino-spec AHU — modulating actuators with position feedback; CO/CO2 monitoring at return duct.
AHU-GF-CASINOAHU (Modulating CHW-served)1Ground Floor Casino LobbyAir ConditioningPNL-CASINO-GFEquipment Supplier140014Modulating CHW-served AHU with VFD, modulating valve and dampers (position feedback)Hardwired (VFD via BACnet HLI)Mechanical contractorCasino-spec AHU — modulating actuators with position feedback; CO/CO2 monitoring at return duct.
AHU-GF-LOBAHU (Chilled-Water-Served)1Ground Floor LobbyAir ConditioningPNL-AIR-GFEquipment Supplier140014Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-GF-RESTAHU (Chilled-Water-Served)1Ground Floor RestaurantAir ConditioningPNL-AIR-GFEquipment Supplier140014Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
BLR-1Steam Boiler1Lower Ground Boiler RoomBoilerPNL-BLR-LGEquipment Supplier160016Fire-tube steam boiler with multi-stage burner, fuel-oil fired (typical for hotel laundry)HardwiredMechanical contractor / Equipment supplierBMS supplies steam pressure, feedwater T, fluegas T+O2 sensors. Boiler equipment provides aux contacts for status/HOA/trip points.
BLR-2Steam Boiler1Lower Ground Boiler RoomBoilerPNL-BLR-LGEquipment Supplier160016Fire-tube steam boiler with multi-stage burner, fuel-oil fired (typical for hotel laundry)HardwiredMechanical contractor / Equipment supplierBMS supplies steam pressure, feedwater T, fluegas T+O2 sensors. Boiler equipment provides aux contacts for status/HOA/trip points.
BTU-CHW-MAINBTU Meter12F Chiller Plant RoomChilled Water PlantPNL-CH-PLANT-2FBMS Contractor0415Ultrasonic or insertion-type BTU meter with Modbus output (Onicon, Aichi, Kamstrup)Modbus RTU/TCPBMS contractorSystem-level energy submeter.
CALOR-LGCalorifier (Hot Water Storage Tank)1Lower Ground Calorifier RoomHot WaterPNL-PL-LGBMS Contractor1001Pressurised hot-water storage tank with internal coil, sized per design hot water demandHardwiredPlumbing contractorBMS supplies tank temperature sensor (immersion or strapped probe).
CALOR-ROOFCalorifier (Hot Water Storage Tank)1Roofdeck DOASHot WaterPNL-AIR-ROOFBMS Contractor1001Pressurised hot-water storage tank with internal coil, sized per design hot water demandHardwiredPlumbing contractorBMS supplies tank temperature sensor (immersion or strapped probe).
CH-1Chiller (Package Water-Cooled)12F Chiller Plant RoomChilled Water PlantPNL-CH-PLANT-2FEquipment Supplier918128Tier-1 BACnet IP chiller (Trane/York/Carrier/Daikin), water-cooled centrifugal or screw, sized per design cooling loadBACnet/IPMechanical contractor / Equipment supplierBMS reads via chiller's native BACnet gateway. BMS supplies external T-sensors on entering/leaving CHW & CW pipes.
CH-2Chiller (Package Water-Cooled)12F Chiller Plant RoomChilled Water PlantPNL-CH-PLANT-2FEquipment Supplier918128Tier-1 BACnet IP chiller (Trane/York/Carrier/Daikin), water-cooled centrifugal or screw, sized per design cooling loadBACnet/IPMechanical contractor / Equipment supplierBMS reads via chiller's native BACnet gateway. BMS supplies external T-sensors on entering/leaving CHW & CW pipes.
CHW-BYPCHW Bypass Header12F Chiller Plant RoomChilled Water PlantPNL-CH-PLANT-2FBMS Contractor4004BMS dP/dT sensors + motorized bypass valve (BMS-supplied)HardwiredBMS contractorBMS controls bypass valve to maintain CHW differential.
CHW-RET-HDRCHW Return Main Header12F Chiller Plant RoomChilled Water PlantPNL-CH-PLANT-2FBMS Contractor2002BMS T+P sensors on CHW return manifoldHardwiredBMS contractorField instrumentation only.
CHW-SUP-HDRCHW Supply Main Header12F Chiller Plant RoomChilled Water PlantPNL-CH-PLANT-2FBMS Contractor2002BMS T+P sensors on CHW supply manifoldHardwiredBMS contractorField instrumentation only.
CHWP-1Primary CHW Pump12F Chiller Plant RoomChilled Water PlantPNL-CH-PLANT-2FEquipment Supplier7007End-suction or split-case centrifugal with VFD, sized per design CHW flowHardwired (BMS reads VFD via BACnet HLI)Mechanical contractorVFD typically Equipment Supplier provided with BACnet card.
CHWP-2Primary CHW Pump12F Chiller Plant RoomChilled Water PlantPNL-CH-PLANT-2FEquipment Supplier7007End-suction or split-case centrifugal with VFD, sized per design CHW flowHardwired (BMS reads VFD via BACnet HLI)Mechanical contractorVFD typically Equipment Supplier provided with BACnet card.
CHWP-3Primary CHW Pump (Standby)12F Chiller Plant RoomChilled Water PlantPNL-CH-PLANT-2FEquipment Supplier7007Same as Primary CHW Pump (1 standby for N+1 redundancy)Hardwired (BMS reads VFD via BACnet HLI)Mechanical contractorStandby unit per A-CHW-001.
CT-1Cooling Tower1Roofdeck Cooling TowerCondenser Water LoopPNL-CT-ROOFBMS Contractor7007Induced-draft counterflow open cooling tower (Marley/BAC/EVAPCO), sized per condenser water flowHardwiredMechanical contractor / Equipment supplierBMS supplies basin level sensors and condenser water header T-sensors.
CT-2Cooling Tower1Roofdeck Cooling TowerCondenser Water LoopPNL-CT-ROOFBMS Contractor7007Induced-draft counterflow open cooling tower (Marley/BAC/EVAPCO), sized per condenser water flowHardwiredMechanical contractor / Equipment supplierBMS supplies basin level sensors and condenser water header T-sensors.
CT-COMMONCooling Tower (Common)1Roofdeck Cooling TowerCondenser Water LoopPNL-CT-ROOFBMS Contractor6006Common BMS sensors at cooling tower area (OA T/RH, condenser headers)HardwiredBMS contractorField instrumentation only — no equipment per se.
CW-HDRCondenser Water Header1Roofdeck Cooling TowerCondenser Water LoopPNL-CT-ROOFBMS Contractor2002BMS T sensors on condenser water headers at roofdeckHardwiredBMS contractorField instrumentation only.
CWP-1Condenser Water Pump12F Chiller Plant RoomCondenser Water LoopPNL-CH-PLANT-2FEquipment Supplier4004End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious)HardwiredMechanical contractorBMS reads aux contacts; commands start via DO.
CWP-2Condenser Water Pump12F Chiller Plant RoomCondenser Water LoopPNL-CH-PLANT-2FEquipment Supplier4004End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious)HardwiredMechanical contractorBMS reads aux contacts; commands start via DO.
CWP-3Condenser Water Pump12F Chiller Plant RoomCondenser Water LoopPNL-CH-PLANT-2FEquipment Supplier4004End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious)HardwiredMechanical contractorBMS reads aux contacts; commands start via DO.
DOAS-2FDOAS Unit12F Common PublicVentilationPNL-AIR-2FEquipment Supplier240024Dedicated Outdoor Air System with energy recovery wheel, supply + exhaust fans, CHW coilBACnet/IPMechanical contractor / Equipment supplierNative BACnet controller typical. BMS supplies external sensors (OA T/RH/Flow, indoor T/RH, exhaust T) and modulating valve actuator.
DOAS-RD1DOAS Unit1Roofdeck DOASVentilationPNL-AIR-ROOFEquipment Supplier240024Dedicated Outdoor Air System with energy recovery wheel, supply + exhaust fans, CHW coilBACnet/IPMechanical contractor / Equipment supplierNative BACnet controller typical. BMS supplies external sensors (OA T/RH/Flow, indoor T/RH, exhaust T) and modulating valve actuator.
DOAS-RD2DOAS Unit1Roofdeck DOASVentilationPNL-AIR-ROOFEquipment Supplier240024Dedicated Outdoor Air System with energy recovery wheel, supply + exhaust fans, CHW coilBACnet/IPMechanical contractor / Equipment supplierNative BACnet controller typical. BMS supplies external sensors (OA T/RH/Flow, indoor T/RH, exhaust T) and modulating valve actuator.
EAS-GEN-2FExhaust Fan (General)12F Common PublicExhaustPNL-AIR-2FEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EAS-GEN-3FExhaust Fan (General)13F AmenityExhaustPNL-AIR-3FEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EAS-GEN-BSMTExhaust Fan (General)1Basement BOHExhaustPNL-AIR-BSMTEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EAS-GEN-GFExhaust Fan (General)1Ground Floor LobbyExhaustPNL-AIR-GFEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EAS-GEN-ROOFExhaust Fan (General)1Roofdeck DOASExhaustPNL-AIR-ROOFEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EAS-TOILET-2FExhaust Fan (Toilet)12F Common PublicExhaustPNL-AIR-2FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EAS-TOILET-3FExhaust Fan (Toilet)13F AmenityExhaustPNL-AIR-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EAS-TOILET-BSMTExhaust Fan (Toilet)1Basement BOHExhaustPNL-AIR-BSMTEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EAS-TOILET-GFExhaust Fan (Toilet)1Ground Floor LobbyExhaustPNL-AIR-GFEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
HP-LG-1Heat Pump1Lower Ground Calorifier RoomHot WaterPNL-PL-LGEquipment Supplier3003Air-source or water-source heat pump for hot water heatingHardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractor / Equipment supplierBMS reads pump status/HOA/trip via aux contacts.
HP-ROOF-1Heat Pump1Roofdeck DOASHot WaterPNL-AIR-ROOFEquipment Supplier3003Air-source or water-source heat pump for hot water heatingHardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractor / Equipment supplierBMS reads pump status/HOA/trip via aux contacts.
HW-HEADERS-LGHot Water Header Set1Lower Ground Calorifier RoomHot WaterPNL-PL-LGBMS Contractor3003Hot water supply/return manifolds with BMS T sensors and make-up cold water T sensorHardwiredBMS contractorField instrumentation on existing piping.
HW-PUMP-LG-1Recirculating Pump1Lower Ground Calorifier RoomHot WaterPNL-PL-LGEquipment Supplier3003Hot water recirculating pump, fixed-speed (typical for hotwater systems)Hardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractorBMS reads aux contacts only.
HW-PUMP-LG-2Recirculating Pump1Lower Ground Calorifier RoomHot WaterPNL-PL-LGEquipment Supplier3003Hot water recirculating pump, fixed-speed (typical for hotwater systems)Hardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractorBMS reads aux contacts only.
HW-PUMP-ROOF-1Recirculating Pump1Roofdeck DOASHot WaterPNL-AIR-ROOFEquipment Supplier3003Hot water recirculating pump, fixed-speed (typical for hotwater systems)Hardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractorBMS reads aux contacts only.
OZ-CASINO-1Ozone Generator (UV-light or Corona)1Ground Floor CasinoCasino Air ConditioningPNL-CASINO-GFEquipment Supplier3003UV-light or corona-discharge ozone generator (paired with Casino AHU)HardwiredEquipment supplierCasino-specific air-treatment device. BMS monitors status/trip and reads VOC sensor (BMS-supplied).
PAHU-2FPrecooled Air Handling Unit12F Common PublicVentilationPNL-AIR-2FEquipment Supplier120012Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust pathHardwired (VFD via BACnet HLI)Mechanical contractor / Equipment supplierPrecool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors.
PAHU-BSMTPrecooled Air Handling Unit1Basement BOHVentilationPNL-AIR-BSMTEquipment Supplier120012Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust pathHardwired (VFD via BACnet HLI)Mechanical contractor / Equipment supplierPrecool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors.
PAHU-ROOFPrecooled Air Handling Unit1Roofdeck DOASVentilationPNL-AIR-ROOFEquipment Supplier120012Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust pathHardwired (VFD via BACnet HLI)Mechanical contractor / Equipment supplierPrecool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors.
PM-AIR-2FMultifunction Power Meter (Feeder)12F Common PublicPower MonitoringPNL-AIR-2FBMS Contractor0415Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
PM-AIR-GFMultifunction Power Meter (Feeder)1Ground Floor LobbyPower MonitoringPNL-AIR-GFBMS Contractor0415Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
PM-BOILERMultifunction Power Meter (Feeder)1Lower Ground Boiler RoomPower MonitoringPNL-BLR-LGBMS Contractor0415Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
PM-CASINOMultifunction Power Meter (Feeder)1Ground Floor CasinoPower MonitoringPNL-CASINO-GFBMS Contractor0415Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
PM-CHILLERMultifunction Power Meter (Feeder)12F Chiller Plant RoomPower MonitoringPNL-CH-PLANT-2FBMS Contractor0415Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
PM-COOLINGMultifunction Power Meter (Feeder)1Roofdeck Cooling TowerPower MonitoringPNL-CT-ROOFBMS Contractor0415Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
PM-FIREPMPMultifunction Power Meter (Feeder)1Lower Ground Boiler RoomPower MonitoringPNL-PL-LGBMS Contractor0415Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
PM-MAIN-LGMultifunction Power Meter (Main)1Lower Ground Main SwitchgearPower MonitoringPNL-PM-LGBMS Contractor0718Multifunction power meter with Modbus output (Schneider PM-series, ABB M2M, Siemens SENTRON), main switchgear classModbus RTU/TCPBMS contractorMounted in main switchgear or on dedicated BMS-side panel.
PM-PLUMBMultifunction Power Meter (Feeder)1Lower Ground Calorifier RoomPower MonitoringPNL-PL-LGBMS Contractor0415Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.