| ID | System | Equipment Class | Equipment Instance | Location | Point Description | Type | Field Device | C/O | DoO Ref | Panel | Source | Notes |
| P0001 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | Entering Chilled Water Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0002 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | Leaving Chilled Water Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0003 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | Entering Condenser Water Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0004 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | Leaving Condenser Water Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0005 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | Chilled Water Return Flow | AI | Flow Sensor | BMS Contractor | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0006 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | Chilled Water Supply Flow | AI | Flow Sensor | BMS Contractor | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0007 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | Condenser Water Supply Flow | AI | Flow Sensor | BMS Contractor | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0008 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | CHW Isolation Motorized Valve Status | DI | Electric Valve Actuator | ME Contractor | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0009 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | COW Isolation Motorized Valve Status | DI | Electric Valve Actuator | ME Contractor | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0010 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | Chiller Native — comprehensive package data (HLI) | Network | Chiller Native BACnet IP | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0011 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | Chiller Compressor Pump On/Off Status | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0012 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | Chiller Compressor HOA Status | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0013 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | Chiller Compressor Trip Alarm | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0014 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | Motor Load Current | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0015 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | Motor Consumption (kW/BTU) | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0016 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | Winding Temperature | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0017 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | Oil Pump Status | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0018 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | Oil Pump Trip | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0019 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | Oil Sump Pressure | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0020 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | Oil Sump Temperature | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0021 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | Evaporator Refrigerant Pressure | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0022 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | Evaporator Refrigerant Temperature | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0023 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | Evaporator Approach Δ Temperature | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0024 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | Evaporator Approach Δ Pressure | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0025 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | Condenser Refrigerant Pressure | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0026 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | Condenser Refrigerant Temperature | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0027 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | Condenser Approach Δ Temperature | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0028 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-1 | 2F Chiller Plant Room | Condenser Approach Δ Pressure | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 (Chillers @ 2nd Level) + MC-ME | |
| P0029 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | Entering Chilled Water Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0030 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | Leaving Chilled Water Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0031 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | Entering Condenser Water Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0032 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | Leaving Condenser Water Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0033 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | Chilled Water Return Flow | AI | Flow Sensor | BMS Contractor | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0034 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | Chilled Water Supply Flow | AI | Flow Sensor | BMS Contractor | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0035 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | Condenser Water Supply Flow | AI | Flow Sensor | BMS Contractor | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0036 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | CHW Isolation Motorized Valve Status | DI | Electric Valve Actuator | ME Contractor | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0037 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | COW Isolation Motorized Valve Status | DI | Electric Valve Actuator | ME Contractor | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0038 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | Chiller Native — comprehensive package data (HLI) | Network | Chiller Native BACnet IP | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0039 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | Chiller Compressor Pump On/Off Status | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0040 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | Chiller Compressor HOA Status | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0041 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | Chiller Compressor Trip Alarm | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0042 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | Motor Load Current | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0043 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | Motor Consumption (kW/BTU) | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0044 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | Winding Temperature | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0045 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | Oil Pump Status | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0046 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | Oil Pump Trip | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0047 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | Oil Sump Pressure | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0048 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | Oil Sump Temperature | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0049 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | Evaporator Refrigerant Pressure | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0050 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | Evaporator Refrigerant Temperature | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0051 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | Evaporator Approach Δ Temperature | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0052 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | Evaporator Approach Δ Pressure | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0053 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | Condenser Refrigerant Pressure | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0054 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | Condenser Refrigerant Temperature | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0055 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | Condenser Approach Δ Temperature | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0056 | Chilled Water Plant | Chiller (Package Water-Cooled) | CH-2 | 2F Chiller Plant Room | Condenser Approach Δ Pressure | HLI | Chiller Native | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0057 | Chilled Water Plant | Primary CHW Pump | CHWP-1 | 2F Chiller Plant Room | CHW Supply Pressure | AI | Pressure Sensor | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME (Primary CHW Circulating Pumps @ 2nd Level) | |
| P0058 | Chilled Water Plant | Primary CHW Pump | CHWP-1 | 2F Chiller Plant Room | On/Off Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME (Primary CHW Circulating Pumps @ 2nd Level) | |
| P0059 | Chilled Water Plant | Primary CHW Pump | CHWP-1 | 2F Chiller Plant Room | HOA Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME (Primary CHW Circulating Pumps @ 2nd Level) | |
| P0060 | Chilled Water Plant | Primary CHW Pump | CHWP-1 | 2F Chiller Plant Room | VFD Speed Feedback | AI | VFD | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME (Primary CHW Circulating Pumps @ 2nd Level) | |
| P0061 | Chilled Water Plant | Primary CHW Pump | CHWP-1 | 2F Chiller Plant Room | VFD Speed Command | AO | VFD | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME (Primary CHW Circulating Pumps @ 2nd Level) | |
| P0062 | Chilled Water Plant | Primary CHW Pump | CHWP-1 | 2F Chiller Plant Room | Trip Alarm | DI | Auxiliary Contact | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME (Primary CHW Circulating Pumps @ 2nd Level) | |
| P0063 | Chilled Water Plant | Primary CHW Pump | CHWP-1 | 2F Chiller Plant Room | Start/Stop Command | DO | Auxiliary Contact | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME (Primary CHW Circulating Pumps @ 2nd Level) | |
| P0064 | Chilled Water Plant | Primary CHW Pump | CHWP-2 | 2F Chiller Plant Room | CHW Supply Pressure | AI | Pressure Sensor | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0065 | Chilled Water Plant | Primary CHW Pump | CHWP-2 | 2F Chiller Plant Room | On/Off Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0066 | Chilled Water Plant | Primary CHW Pump | CHWP-2 | 2F Chiller Plant Room | HOA Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0067 | Chilled Water Plant | Primary CHW Pump | CHWP-2 | 2F Chiller Plant Room | VFD Speed Feedback | AI | VFD | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0068 | Chilled Water Plant | Primary CHW Pump | CHWP-2 | 2F Chiller Plant Room | VFD Speed Command | AO | VFD | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0069 | Chilled Water Plant | Primary CHW Pump | CHWP-2 | 2F Chiller Plant Room | Trip Alarm | DI | Auxiliary Contact | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0070 | Chilled Water Plant | Primary CHW Pump | CHWP-2 | 2F Chiller Plant Room | Start/Stop Command | DO | Auxiliary Contact | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0071 | Chilled Water Plant | Primary CHW Pump (Standby) | CHWP-3 | 2F Chiller Plant Room | CHW Supply Pressure | AI | Pressure Sensor | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0072 | Chilled Water Plant | Primary CHW Pump (Standby) | CHWP-3 | 2F Chiller Plant Room | On/Off Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0073 | Chilled Water Plant | Primary CHW Pump (Standby) | CHWP-3 | 2F Chiller Plant Room | HOA Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0074 | Chilled Water Plant | Primary CHW Pump (Standby) | CHWP-3 | 2F Chiller Plant Room | VFD Speed Feedback | AI | VFD | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0075 | Chilled Water Plant | Primary CHW Pump (Standby) | CHWP-3 | 2F Chiller Plant Room | VFD Speed Command | AO | VFD | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0076 | Chilled Water Plant | Primary CHW Pump (Standby) | CHWP-3 | 2F Chiller Plant Room | Trip Alarm | DI | Auxiliary Contact | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0077 | Chilled Water Plant | Primary CHW Pump (Standby) | CHWP-3 | 2F Chiller Plant Room | Start/Stop Command | DO | Auxiliary Contact | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0078 | Condenser Water Loop | Condenser Water Pump | CWP-1 | 2F Chiller Plant Room | On/Off Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0079 | Condenser Water Loop | Condenser Water Pump | CWP-1 | 2F Chiller Plant Room | HOA Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0080 | Condenser Water Loop | Condenser Water Pump | CWP-1 | 2F Chiller Plant Room | Trip Alarm | DI | Auxiliary Contact | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0081 | Condenser Water Loop | Condenser Water Pump | CWP-1 | 2F Chiller Plant Room | Start/Stop Command | DO | Auxiliary Contact | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0082 | Condenser Water Loop | Condenser Water Pump | CWP-2 | 2F Chiller Plant Room | On/Off Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0083 | Condenser Water Loop | Condenser Water Pump | CWP-2 | 2F Chiller Plant Room | HOA Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0084 | Condenser Water Loop | Condenser Water Pump | CWP-2 | 2F Chiller Plant Room | Trip Alarm | DI | Auxiliary Contact | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0085 | Condenser Water Loop | Condenser Water Pump | CWP-2 | 2F Chiller Plant Room | Start/Stop Command | DO | Auxiliary Contact | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0086 | Condenser Water Loop | Condenser Water Pump | CWP-3 | 2F Chiller Plant Room | On/Off Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0087 | Condenser Water Loop | Condenser Water Pump | CWP-3 | 2F Chiller Plant Room | HOA Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0088 | Condenser Water Loop | Condenser Water Pump | CWP-3 | 2F Chiller Plant Room | Trip Alarm | DI | Auxiliary Contact | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0089 | Condenser Water Loop | Condenser Water Pump | CWP-3 | 2F Chiller Plant Room | Start/Stop Command | DO | Auxiliary Contact | Equipment Supplier | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0090 | Chilled Water Plant | CHW Supply Main Header | CHW-SUP-HDR | 2F Chiller Plant Room | Header Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0091 | Chilled Water Plant | CHW Supply Main Header | CHW-SUP-HDR | 2F Chiller Plant Room | Header Pressure | AI | Pressure Sensor | BMS Contractor | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0092 | Chilled Water Plant | CHW Return Main Header | CHW-RET-HDR | 2F Chiller Plant Room | Header Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0093 | Chilled Water Plant | CHW Return Main Header | CHW-RET-HDR | 2F Chiller Plant Room | Header Pressure | AI | Pressure Sensor | BMS Contractor | | PNL-CH-PLANT-2F | BMS-01 + MC-ME | |
| P0094 | Chilled Water Plant | CHW Bypass Header | CHW-BYP | 2F Chiller Plant Room | Differential Pressure | AI | Diff. Pressure Sensor | BMS Contractor | | PNL-CH-PLANT-2F | BMS-01 + MC-ME (CHW Main Header Supply & Return) | |
| P0095 | Chilled Water Plant | CHW Bypass Header | CHW-BYP | 2F Chiller Plant Room | Differential Temperature | AI | Diff. Temp Sensor | BMS Contractor | | PNL-CH-PLANT-2F | BMS-01 + MC-ME (CHW Main Header Supply & Return) | |
| P0096 | Chilled Water Plant | CHW Bypass Header | CHW-BYP | 2F Chiller Plant Room | CHW Bypass Isolation Valve Status | DI | Electric Valve Actuator | BMS Contractor | | PNL-CH-PLANT-2F | BMS-01 + MC-ME (CHW Main Header Supply & Return) | |
| P0097 | Chilled Water Plant | CHW Bypass Header | CHW-BYP | 2F Chiller Plant Room | CHW Bypass Isolation Valve Command | DO | Electric Valve Actuator | BMS Contractor | | PNL-CH-PLANT-2F | BMS-01 + MC-ME (CHW Main Header Supply & Return) | |
| P0098 | Condenser Water Loop | Condenser Water Header | CW-HDR | Roofdeck Cooling Tower | Condenser Water Supply Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-CT-ROOF | BMS-01 + MC-ME | |
| P0099 | Condenser Water Loop | Condenser Water Header | CW-HDR | Roofdeck Cooling Tower | Condenser Water Return Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-CT-ROOF | BMS-01 + MC-ME | |
| P0100 | Chilled Water Plant | BTU Meter | BTU-CHW-MAIN | 2F Chiller Plant Room | BTU Meter HLI | Network | Modbus BTU Meter | BMS Contractor | | PNL-CH-PLANT-2F | BMS-01 | |
| P0101 | Chilled Water Plant | BTU Meter | BTU-CHW-MAIN | 2F Chiller Plant Room | Energy (kWh/BTU) | HLI | Modbus BTU Meter | BMS Contractor | | PNL-CH-PLANT-2F | BMS-01 | |
| P0102 | Chilled Water Plant | BTU Meter | BTU-CHW-MAIN | 2F Chiller Plant Room | Flow | HLI | Modbus BTU Meter | BMS Contractor | | PNL-CH-PLANT-2F | BMS-01 | |
| P0103 | Chilled Water Plant | BTU Meter | BTU-CHW-MAIN | 2F Chiller Plant Room | Supply T | HLI | Modbus BTU Meter | BMS Contractor | | PNL-CH-PLANT-2F | BMS-01 | |
| P0104 | Chilled Water Plant | BTU Meter | BTU-CHW-MAIN | 2F Chiller Plant Room | Return T | HLI | Modbus BTU Meter | BMS Contractor | | PNL-CH-PLANT-2F | BMS-01 | |
| P0105 | Condenser Water Loop | Cooling Tower | CT-1 | Roofdeck Cooling Tower | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-CT-ROOF | BMS-01 + MC-ME (Cooling Towers @ Roofdeck) | |
| P0106 | Condenser Water Loop | Cooling Tower | CT-1 | Roofdeck Cooling Tower | Fan Trip Alarm | DI | Auxiliary Contact | Equipment Supplier | | PNL-CT-ROOF | BMS-01 + MC-ME (Cooling Towers @ Roofdeck) | |
| P0107 | Condenser Water Loop | Cooling Tower | CT-1 | Roofdeck Cooling Tower | Fan Start/Stop Command | DO | Auxiliary Contact | Equipment Supplier | | PNL-CT-ROOF | BMS-01 + MC-ME (Cooling Towers @ Roofdeck) | |
| P0108 | Condenser Water Loop | Cooling Tower | CT-1 | Roofdeck Cooling Tower | Basin Level Low Alarm | DI | Level Sensor / Electrode | BMS Contractor | | PNL-CT-ROOF | BMS-01 + MC-ME (Cooling Towers @ Roofdeck) | |
| P0109 | Condenser Water Loop | Cooling Tower | CT-1 | Roofdeck Cooling Tower | Basin Level High Alarm | DI | Level Sensor / Electrode | BMS Contractor | | PNL-CT-ROOF | BMS-01 + MC-ME (Cooling Towers @ Roofdeck) | |
| P0110 | Condenser Water Loop | Cooling Tower | CT-1 | Roofdeck Cooling Tower | Motorized Blowdown Valve Status | DI | Electric Valve Actuator | BMS Contractor | | PNL-CT-ROOF | BMS-01 + MC-ME (Cooling Towers @ Roofdeck) | |
| P0111 | Condenser Water Loop | Cooling Tower | CT-1 | Roofdeck Cooling Tower | Motorized Blowdown Valve Command | DO | Electric Valve Actuator | BMS Contractor | | PNL-CT-ROOF | BMS-01 + MC-ME (Cooling Towers @ Roofdeck) | |
| P0112 | Condenser Water Loop | Cooling Tower | CT-2 | Roofdeck Cooling Tower | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-CT-ROOF | BMS-01 + MC-ME | |
| P0113 | Condenser Water Loop | Cooling Tower | CT-2 | Roofdeck Cooling Tower | Fan Trip Alarm | DI | Auxiliary Contact | Equipment Supplier | | PNL-CT-ROOF | BMS-01 + MC-ME | |
| P0114 | Condenser Water Loop | Cooling Tower | CT-2 | Roofdeck Cooling Tower | Fan Start/Stop Command | DO | Auxiliary Contact | Equipment Supplier | | PNL-CT-ROOF | BMS-01 + MC-ME | |
| P0115 | Condenser Water Loop | Cooling Tower | CT-2 | Roofdeck Cooling Tower | Basin Level Low Alarm | DI | Level Sensor / Electrode | BMS Contractor | | PNL-CT-ROOF | BMS-01 + MC-ME | |
| P0116 | Condenser Water Loop | Cooling Tower | CT-2 | Roofdeck Cooling Tower | Basin Level High Alarm | DI | Level Sensor / Electrode | BMS Contractor | | PNL-CT-ROOF | BMS-01 + MC-ME | |
| P0117 | Condenser Water Loop | Cooling Tower | CT-2 | Roofdeck Cooling Tower | Motorized Blowdown Valve Status | DI | Electric Valve Actuator | BMS Contractor | | PNL-CT-ROOF | BMS-01 + MC-ME | |
| P0118 | Condenser Water Loop | Cooling Tower | CT-2 | Roofdeck Cooling Tower | Motorized Blowdown Valve Command | DO | Electric Valve Actuator | BMS Contractor | | PNL-CT-ROOF | BMS-01 + MC-ME | |
| P0119 | Condenser Water Loop | Cooling Tower (Common) | CT-COMMON | Roofdeck Cooling Tower | Outside Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-CT-ROOF | BMS-01 + MC-ME (basin level + OA T/RH + COW headers) | |
| P0120 | Condenser Water Loop | Cooling Tower (Common) | CT-COMMON | Roofdeck Cooling Tower | Outside Air Humidity | AI | Humidity Sensor | BMS Contractor | | PNL-CT-ROOF | BMS-01 + MC-ME (basin level + OA T/RH + COW headers) | |
| P0121 | Condenser Water Loop | Cooling Tower (Common) | CT-COMMON | Roofdeck Cooling Tower | CW Return Header Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-CT-ROOF | BMS-01 + MC-ME (basin level + OA T/RH + COW headers) | |
| P0122 | Condenser Water Loop | Cooling Tower (Common) | CT-COMMON | Roofdeck Cooling Tower | CW Supply Header Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-CT-ROOF | BMS-01 + MC-ME (basin level + OA T/RH + COW headers) | |
| P0123 | Condenser Water Loop | Cooling Tower (Common) | CT-COMMON | Roofdeck Cooling Tower | Blowdown pH/Conductivity | AI | pH Sensor / Conductivity Sensor | ME Contractor | | PNL-CT-ROOF | BMS-01 + MC-ME (basin level + OA T/RH + COW headers) | |
| P0124 | Condenser Water Loop | Cooling Tower (Common) | CT-COMMON | Roofdeck Cooling Tower | COW Isolation Motorized Valve Status | DI | Electric Valve Actuator | ME Contractor | | PNL-CT-ROOF | BMS-01 + MC-ME (basin level + OA T/RH + COW headers) | |
| P0125 | Ventilation | DOAS Unit | DOAS-RD1 | Roofdeck DOAS | Outdoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1) | |
| P0126 | Ventilation | DOAS Unit | DOAS-RD1 | Roofdeck DOAS | Outdoor Supply Air Flow | AI | Flow Sensor | BMS Contractor | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1) | |
| P0127 | Ventilation | DOAS Unit | DOAS-RD1 | Roofdeck DOAS | Outdoor Supply Air Humidity | AI | Humidity Sensor | BMS Contractor | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1) | |
| P0128 | Ventilation | DOAS Unit | DOAS-RD1 | Roofdeck DOAS | Indoor Mixed Air Temperature | AI | Temperature Sensor | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1) | |
| P0129 | Ventilation | DOAS Unit | DOAS-RD1 | Roofdeck DOAS | Indoor Mixed Air Humidity | AI | Humidity Sensor | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1) | |
| P0130 | Ventilation | DOAS Unit | DOAS-RD1 | Roofdeck DOAS | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1) | |
| P0131 | Ventilation | DOAS Unit | DOAS-RD1 | Roofdeck DOAS | Indoor Exhaust Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1) | |
| P0132 | Ventilation | DOAS Unit | DOAS-RD1 | Roofdeck DOAS | Indoor Exhaust Air Humidity | AI | Humidity Sensor | BMS Contractor | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1) | |
| P0133 | Ventilation | DOAS Unit | DOAS-RD1 | Roofdeck DOAS | OA Damper Status | DI | Damper Controller | ME Contractor | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1) | |
| P0134 | Ventilation | DOAS Unit | DOAS-RD1 | Roofdeck DOAS | OA Damper Command | AO | Damper Controller | ME Contractor | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1) | |
| P0135 | Ventilation | DOAS Unit | DOAS-RD1 | Roofdeck DOAS | Recovery Wheel Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1) | |
| P0136 | Ventilation | DOAS Unit | DOAS-RD1 | Roofdeck DOAS | Recovery Wheel Motor Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1) | |
| P0137 | Ventilation | DOAS Unit | DOAS-RD1 | Roofdeck DOAS | Supply Fan Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1) | |
| P0138 | Ventilation | DOAS Unit | DOAS-RD1 | Roofdeck DOAS | Supply Fan HOA | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1) | |
| P0139 | Ventilation | DOAS Unit | DOAS-RD1 | Roofdeck DOAS | Supply Fan Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1) | |
| P0140 | Ventilation | DOAS Unit | DOAS-RD1 | Roofdeck DOAS | Supply Fan VFD Speed | AI | VFD | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1) | |
| P0141 | Ventilation | DOAS Unit | DOAS-RD1 | Roofdeck DOAS | Supply Fan VFD Command | AO | VFD | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1) | |
| P0142 | Ventilation | DOAS Unit | DOAS-RD1 | Roofdeck DOAS | Exhaust Fan Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1) | |
| P0143 | Ventilation | DOAS Unit | DOAS-RD1 | Roofdeck DOAS | Exhaust Fan HOA | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1) | |
| P0144 | Ventilation | DOAS Unit | DOAS-RD1 | Roofdeck DOAS | Exhaust Fan Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1) | |
| P0145 | Ventilation | DOAS Unit | DOAS-RD1 | Roofdeck DOAS | Exhaust Fan VFD Speed | AI | VFD | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1) | |
| P0146 | Ventilation | DOAS Unit | DOAS-RD1 | Roofdeck DOAS | Exhaust Fan VFD Command | AO | VFD | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1) | |
| P0147 | Ventilation | DOAS Unit | DOAS-RD1 | Roofdeck DOAS | CHWS Coil Valve Status | DI | Electric Valve Actuator | ME Contractor | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1) | |
| P0148 | Ventilation | DOAS Unit | DOAS-RD1 | Roofdeck DOAS | CHWS Coil Valve Command | AO | Electric Valve Actuator | ME Contractor | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck Serving Guestrooms RD1) | |
| P0149 | Ventilation | DOAS Unit | DOAS-RD2 | Roofdeck DOAS | Outdoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck RD2) | |
| P0150 | Ventilation | DOAS Unit | DOAS-RD2 | Roofdeck DOAS | Outdoor Supply Air Flow | AI | Flow Sensor | BMS Contractor | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck RD2) | |
| P0151 | Ventilation | DOAS Unit | DOAS-RD2 | Roofdeck DOAS | Outdoor Supply Air Humidity | AI | Humidity Sensor | BMS Contractor | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck RD2) | |
| P0152 | Ventilation | DOAS Unit | DOAS-RD2 | Roofdeck DOAS | Indoor Mixed Air Temperature | AI | Temperature Sensor | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck RD2) | |
| P0153 | Ventilation | DOAS Unit | DOAS-RD2 | Roofdeck DOAS | Indoor Mixed Air Humidity | AI | Humidity Sensor | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck RD2) | |
| P0154 | Ventilation | DOAS Unit | DOAS-RD2 | Roofdeck DOAS | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck RD2) | |
| P0155 | Ventilation | DOAS Unit | DOAS-RD2 | Roofdeck DOAS | Indoor Exhaust Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck RD2) | |
| P0156 | Ventilation | DOAS Unit | DOAS-RD2 | Roofdeck DOAS | Indoor Exhaust Air Humidity | AI | Humidity Sensor | BMS Contractor | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck RD2) | |
| P0157 | Ventilation | DOAS Unit | DOAS-RD2 | Roofdeck DOAS | OA Damper Status | DI | Damper Controller | ME Contractor | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck RD2) | |
| P0158 | Ventilation | DOAS Unit | DOAS-RD2 | Roofdeck DOAS | OA Damper Command | AO | Damper Controller | ME Contractor | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck RD2) | |
| P0159 | Ventilation | DOAS Unit | DOAS-RD2 | Roofdeck DOAS | Recovery Wheel Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck RD2) | |
| P0160 | Ventilation | DOAS Unit | DOAS-RD2 | Roofdeck DOAS | Recovery Wheel Motor Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck RD2) | |
| P0161 | Ventilation | DOAS Unit | DOAS-RD2 | Roofdeck DOAS | Supply Fan Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck RD2) | |
| P0162 | Ventilation | DOAS Unit | DOAS-RD2 | Roofdeck DOAS | Supply Fan HOA | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck RD2) | |
| P0163 | Ventilation | DOAS Unit | DOAS-RD2 | Roofdeck DOAS | Supply Fan Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck RD2) | |
| P0164 | Ventilation | DOAS Unit | DOAS-RD2 | Roofdeck DOAS | Supply Fan VFD Speed | AI | VFD | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck RD2) | |
| P0165 | Ventilation | DOAS Unit | DOAS-RD2 | Roofdeck DOAS | Supply Fan VFD Command | AO | VFD | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck RD2) | |
| P0166 | Ventilation | DOAS Unit | DOAS-RD2 | Roofdeck DOAS | Exhaust Fan Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck RD2) | |
| P0167 | Ventilation | DOAS Unit | DOAS-RD2 | Roofdeck DOAS | Exhaust Fan HOA | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck RD2) | |
| P0168 | Ventilation | DOAS Unit | DOAS-RD2 | Roofdeck DOAS | Exhaust Fan Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck RD2) | |
| P0169 | Ventilation | DOAS Unit | DOAS-RD2 | Roofdeck DOAS | Exhaust Fan VFD Speed | AI | VFD | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck RD2) | |
| P0170 | Ventilation | DOAS Unit | DOAS-RD2 | Roofdeck DOAS | Exhaust Fan VFD Command | AO | VFD | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck RD2) | |
| P0171 | Ventilation | DOAS Unit | DOAS-RD2 | Roofdeck DOAS | CHWS Coil Valve Status | DI | Electric Valve Actuator | ME Contractor | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck RD2) | |
| P0172 | Ventilation | DOAS Unit | DOAS-RD2 | Roofdeck DOAS | CHWS Coil Valve Command | AO | Electric Valve Actuator | ME Contractor | | PNL-AIR-ROOF | MC-ME (DOAS @ Roofdeck RD2) | |
| P0173 | Ventilation | DOAS Unit | DOAS-2F | 2F Common Public | Outdoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-2F | MC-ME (DOAS @ 2nd Level common/public) | |
| P0174 | Ventilation | DOAS Unit | DOAS-2F | 2F Common Public | Outdoor Supply Air Flow | AI | Flow Sensor | BMS Contractor | | PNL-AIR-2F | MC-ME (DOAS @ 2nd Level common/public) | |
| P0175 | Ventilation | DOAS Unit | DOAS-2F | 2F Common Public | Outdoor Supply Air Humidity | AI | Humidity Sensor | BMS Contractor | | PNL-AIR-2F | MC-ME (DOAS @ 2nd Level common/public) | |
| P0176 | Ventilation | DOAS Unit | DOAS-2F | 2F Common Public | Indoor Mixed Air Temperature | AI | Temperature Sensor | Equipment Supplier | | PNL-AIR-2F | MC-ME (DOAS @ 2nd Level common/public) | |
| P0177 | Ventilation | DOAS Unit | DOAS-2F | 2F Common Public | Indoor Mixed Air Humidity | AI | Humidity Sensor | Equipment Supplier | | PNL-AIR-2F | MC-ME (DOAS @ 2nd Level common/public) | |
| P0178 | Ventilation | DOAS Unit | DOAS-2F | 2F Common Public | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-2F | MC-ME (DOAS @ 2nd Level common/public) | |
| P0179 | Ventilation | DOAS Unit | DOAS-2F | 2F Common Public | Indoor Exhaust Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-2F | MC-ME (DOAS @ 2nd Level common/public) | |
| P0180 | Ventilation | DOAS Unit | DOAS-2F | 2F Common Public | Indoor Exhaust Air Humidity | AI | Humidity Sensor | BMS Contractor | | PNL-AIR-2F | MC-ME (DOAS @ 2nd Level common/public) | |
| P0181 | Ventilation | DOAS Unit | DOAS-2F | 2F Common Public | OA Damper Status | DI | Damper Controller | ME Contractor | | PNL-AIR-2F | MC-ME (DOAS @ 2nd Level common/public) | |
| P0182 | Ventilation | DOAS Unit | DOAS-2F | 2F Common Public | OA Damper Command | AO | Damper Controller | ME Contractor | | PNL-AIR-2F | MC-ME (DOAS @ 2nd Level common/public) | |
| P0183 | Ventilation | DOAS Unit | DOAS-2F | 2F Common Public | Recovery Wheel Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-2F | MC-ME (DOAS @ 2nd Level common/public) | |
| P0184 | Ventilation | DOAS Unit | DOAS-2F | 2F Common Public | Recovery Wheel Motor Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-2F | MC-ME (DOAS @ 2nd Level common/public) | |
| P0185 | Ventilation | DOAS Unit | DOAS-2F | 2F Common Public | Supply Fan Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-2F | MC-ME (DOAS @ 2nd Level common/public) | |
| P0186 | Ventilation | DOAS Unit | DOAS-2F | 2F Common Public | Supply Fan HOA | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-2F | MC-ME (DOAS @ 2nd Level common/public) | |
| P0187 | Ventilation | DOAS Unit | DOAS-2F | 2F Common Public | Supply Fan Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-2F | MC-ME (DOAS @ 2nd Level common/public) | |
| P0188 | Ventilation | DOAS Unit | DOAS-2F | 2F Common Public | Supply Fan VFD Speed | AI | VFD | Equipment Supplier | | PNL-AIR-2F | MC-ME (DOAS @ 2nd Level common/public) | |
| P0189 | Ventilation | DOAS Unit | DOAS-2F | 2F Common Public | Supply Fan VFD Command | AO | VFD | Equipment Supplier | | PNL-AIR-2F | MC-ME (DOAS @ 2nd Level common/public) | |
| P0190 | Ventilation | DOAS Unit | DOAS-2F | 2F Common Public | Exhaust Fan Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-2F | MC-ME (DOAS @ 2nd Level common/public) | |
| P0191 | Ventilation | DOAS Unit | DOAS-2F | 2F Common Public | Exhaust Fan HOA | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-2F | MC-ME (DOAS @ 2nd Level common/public) | |
| P0192 | Ventilation | DOAS Unit | DOAS-2F | 2F Common Public | Exhaust Fan Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-2F | MC-ME (DOAS @ 2nd Level common/public) | |
| P0193 | Ventilation | DOAS Unit | DOAS-2F | 2F Common Public | Exhaust Fan VFD Speed | AI | VFD | Equipment Supplier | | PNL-AIR-2F | MC-ME (DOAS @ 2nd Level common/public) | |
| P0194 | Ventilation | DOAS Unit | DOAS-2F | 2F Common Public | Exhaust Fan VFD Command | AO | VFD | Equipment Supplier | | PNL-AIR-2F | MC-ME (DOAS @ 2nd Level common/public) | |
| P0195 | Ventilation | DOAS Unit | DOAS-2F | 2F Common Public | CHWS Coil Valve Status | DI | Electric Valve Actuator | ME Contractor | | PNL-AIR-2F | MC-ME (DOAS @ 2nd Level common/public) | |
| P0196 | Ventilation | DOAS Unit | DOAS-2F | 2F Common Public | CHWS Coil Valve Command | AO | Electric Valve Actuator | ME Contractor | | PNL-AIR-2F | MC-ME (DOAS @ 2nd Level common/public) | |
| P0197 | Ventilation | Precooled Air Handling Unit | PAHU-ROOF | Roofdeck DOAS | Outdoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-ROOF | MC-ME (PAHU @ Roofdeck) | |
| P0198 | Ventilation | Precooled Air Handling Unit | PAHU-ROOF | Roofdeck DOAS | Outdoor Supply Air Flow | AI | Flow Sensor | BMS Contractor | | PNL-AIR-ROOF | MC-ME (PAHU @ Roofdeck) | |
| P0199 | Ventilation | Precooled Air Handling Unit | PAHU-ROOF | Roofdeck DOAS | OA Damper Status | DI | Damper Controller | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (PAHU @ Roofdeck) | |
| P0200 | Ventilation | Precooled Air Handling Unit | PAHU-ROOF | Roofdeck DOAS | OA Damper Command | AO | Damper Controller | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (PAHU @ Roofdeck) | |
| P0201 | Ventilation | Precooled Air Handling Unit | PAHU-ROOF | Roofdeck DOAS | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-ROOF | MC-ME (PAHU @ Roofdeck) | |
| P0202 | Ventilation | Precooled Air Handling Unit | PAHU-ROOF | Roofdeck DOAS | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (PAHU @ Roofdeck) | |
| P0203 | Ventilation | Precooled Air Handling Unit | PAHU-ROOF | Roofdeck DOAS | Fan Motor HOA | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (PAHU @ Roofdeck) | |
| P0204 | Ventilation | Precooled Air Handling Unit | PAHU-ROOF | Roofdeck DOAS | Fan Motor Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (PAHU @ Roofdeck) | |
| P0205 | Ventilation | Precooled Air Handling Unit | PAHU-ROOF | Roofdeck DOAS | Fan VFD Speed | AI | VFD | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (PAHU @ Roofdeck) | |
| P0206 | Ventilation | Precooled Air Handling Unit | PAHU-ROOF | Roofdeck DOAS | Fan VFD Command | AO | VFD | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (PAHU @ Roofdeck) | |
| P0207 | Ventilation | Precooled Air Handling Unit | PAHU-ROOF | Roofdeck DOAS | CHWS Coil Valve Status | DI | Electric Valve Actuator | ME Contractor | | PNL-AIR-ROOF | MC-ME (PAHU @ Roofdeck) | |
| P0208 | Ventilation | Precooled Air Handling Unit | PAHU-ROOF | Roofdeck DOAS | CHWS Coil Valve Command | AO | Electric Valve Actuator | ME Contractor | | PNL-AIR-ROOF | MC-ME (PAHU @ Roofdeck) | |
| P0209 | Ventilation | Precooled Air Handling Unit | PAHU-2F | 2F Common Public | Outdoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-2F | MC-ME (PAHU @ 2nd Level) | |
| P0210 | Ventilation | Precooled Air Handling Unit | PAHU-2F | 2F Common Public | Outdoor Supply Air Flow | AI | Flow Sensor | BMS Contractor | | PNL-AIR-2F | MC-ME (PAHU @ 2nd Level) | |
| P0211 | Ventilation | Precooled Air Handling Unit | PAHU-2F | 2F Common Public | OA Damper Status | DI | Damper Controller | Equipment Supplier | | PNL-AIR-2F | MC-ME (PAHU @ 2nd Level) | |
| P0212 | Ventilation | Precooled Air Handling Unit | PAHU-2F | 2F Common Public | OA Damper Command | AO | Damper Controller | Equipment Supplier | | PNL-AIR-2F | MC-ME (PAHU @ 2nd Level) | |
| P0213 | Ventilation | Precooled Air Handling Unit | PAHU-2F | 2F Common Public | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-2F | MC-ME (PAHU @ 2nd Level) | |
| P0214 | Ventilation | Precooled Air Handling Unit | PAHU-2F | 2F Common Public | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-2F | MC-ME (PAHU @ 2nd Level) | |
| P0215 | Ventilation | Precooled Air Handling Unit | PAHU-2F | 2F Common Public | Fan Motor HOA | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-2F | MC-ME (PAHU @ 2nd Level) | |
| P0216 | Ventilation | Precooled Air Handling Unit | PAHU-2F | 2F Common Public | Fan Motor Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-2F | MC-ME (PAHU @ 2nd Level) | |
| P0217 | Ventilation | Precooled Air Handling Unit | PAHU-2F | 2F Common Public | Fan VFD Speed | AI | VFD | Equipment Supplier | | PNL-AIR-2F | MC-ME (PAHU @ 2nd Level) | |
| P0218 | Ventilation | Precooled Air Handling Unit | PAHU-2F | 2F Common Public | Fan VFD Command | AO | VFD | Equipment Supplier | | PNL-AIR-2F | MC-ME (PAHU @ 2nd Level) | |
| P0219 | Ventilation | Precooled Air Handling Unit | PAHU-2F | 2F Common Public | CHWS Coil Valve Status | DI | Electric Valve Actuator | ME Contractor | | PNL-AIR-2F | MC-ME (PAHU @ 2nd Level) | |
| P0220 | Ventilation | Precooled Air Handling Unit | PAHU-2F | 2F Common Public | CHWS Coil Valve Command | AO | Electric Valve Actuator | ME Contractor | | PNL-AIR-2F | MC-ME (PAHU @ 2nd Level) | |
| P0221 | Ventilation | Precooled Air Handling Unit | PAHU-BSMT | Basement BOH | Outdoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-BSMT | MC-ME (PAHU @ Basement) | |
| P0222 | Ventilation | Precooled Air Handling Unit | PAHU-BSMT | Basement BOH | Outdoor Supply Air Flow | AI | Flow Sensor | BMS Contractor | | PNL-AIR-BSMT | MC-ME (PAHU @ Basement) | |
| P0223 | Ventilation | Precooled Air Handling Unit | PAHU-BSMT | Basement BOH | OA Damper Status | DI | Damper Controller | Equipment Supplier | | PNL-AIR-BSMT | MC-ME (PAHU @ Basement) | |
| P0224 | Ventilation | Precooled Air Handling Unit | PAHU-BSMT | Basement BOH | OA Damper Command | AO | Damper Controller | Equipment Supplier | | PNL-AIR-BSMT | MC-ME (PAHU @ Basement) | |
| P0225 | Ventilation | Precooled Air Handling Unit | PAHU-BSMT | Basement BOH | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-BSMT | MC-ME (PAHU @ Basement) | |
| P0226 | Ventilation | Precooled Air Handling Unit | PAHU-BSMT | Basement BOH | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-BSMT | MC-ME (PAHU @ Basement) | |
| P0227 | Ventilation | Precooled Air Handling Unit | PAHU-BSMT | Basement BOH | Fan Motor HOA | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-BSMT | MC-ME (PAHU @ Basement) | |
| P0228 | Ventilation | Precooled Air Handling Unit | PAHU-BSMT | Basement BOH | Fan Motor Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-BSMT | MC-ME (PAHU @ Basement) | |
| P0229 | Ventilation | Precooled Air Handling Unit | PAHU-BSMT | Basement BOH | Fan VFD Speed | AI | VFD | Equipment Supplier | | PNL-AIR-BSMT | MC-ME (PAHU @ Basement) | |
| P0230 | Ventilation | Precooled Air Handling Unit | PAHU-BSMT | Basement BOH | Fan VFD Command | AO | VFD | Equipment Supplier | | PNL-AIR-BSMT | MC-ME (PAHU @ Basement) | |
| P0231 | Ventilation | Precooled Air Handling Unit | PAHU-BSMT | Basement BOH | CHWS Coil Valve Status | DI | Electric Valve Actuator | ME Contractor | | PNL-AIR-BSMT | MC-ME (PAHU @ Basement) | |
| P0232 | Ventilation | Precooled Air Handling Unit | PAHU-BSMT | Basement BOH | CHWS Coil Valve Command | AO | Electric Valve Actuator | ME Contractor | | PNL-AIR-BSMT | MC-ME (PAHU @ Basement) | |
| P0233 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-A | 2F Common Public | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-2F | MC-ME (AHU @ 2nd Level) + BMS-02 | |
| P0234 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-A | 2F Common Public | Indoor Mixed Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-2F | MC-ME (AHU @ 2nd Level) + BMS-02 | |
| P0235 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-A | 2F Common Public | Indoor Return Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-2F | MC-ME (AHU @ 2nd Level) + BMS-02 | |
| P0236 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-A | 2F Common Public | Indoor Return Air CO2 | AI | CO2 Sensor | BMS Contractor | | PNL-AIR-2F | MC-ME (AHU @ 2nd Level) + BMS-02 | |
| P0237 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-A | 2F Common Public | OA Damper Status | DI | Damper Controller | Equipment Supplier | | PNL-AIR-2F | MC-ME (AHU @ 2nd Level) + BMS-02 | |
| P0238 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-A | 2F Common Public | OA Damper Command | AO | Damper Controller | Equipment Supplier | | PNL-AIR-2F | MC-ME (AHU @ 2nd Level) + BMS-02 | |
| P0239 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-A | 2F Common Public | Return Air Damper Status | DI | Damper Controller | ME Contractor | | PNL-AIR-2F | MC-ME (AHU @ 2nd Level) + BMS-02 | |
| P0240 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-A | 2F Common Public | Return Air Damper Command | AO | Damper Controller | ME Contractor | | PNL-AIR-2F | MC-ME (AHU @ 2nd Level) + BMS-02 | |
| P0241 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-A | 2F Common Public | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-2F | MC-ME (AHU @ 2nd Level) + BMS-02 | |
| P0242 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-A | 2F Common Public | Fan Motor Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-2F | MC-ME (AHU @ 2nd Level) + BMS-02 | |
| P0243 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-A | 2F Common Public | Fan VFD Speed | AI | VFD | Equipment Supplier | | PNL-AIR-2F | MC-ME (AHU @ 2nd Level) + BMS-02 | |
| P0244 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-A | 2F Common Public | Fan VFD Command | AO | VFD | Equipment Supplier | | PNL-AIR-2F | MC-ME (AHU @ 2nd Level) + BMS-02 | |
| P0245 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-A | 2F Common Public | CHWS Valve Status | DI | Electric Valve Actuator | ME Contractor | | PNL-AIR-2F | MC-ME (AHU @ 2nd Level) + BMS-02 | |
| P0246 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-A | 2F Common Public | CHWS Valve Command | AO | Electric Valve Actuator | ME Contractor | | PNL-AIR-2F | MC-ME (AHU @ 2nd Level) + BMS-02 | |
| P0247 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-B | 2F Common Public | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-2F | MC-ME + BMS-02 | |
| P0248 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-B | 2F Common Public | Indoor Mixed Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-2F | MC-ME + BMS-02 | |
| P0249 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-B | 2F Common Public | Indoor Return Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-2F | MC-ME + BMS-02 | |
| P0250 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-B | 2F Common Public | Indoor Return Air CO2 | AI | CO2 Sensor | BMS Contractor | | PNL-AIR-2F | MC-ME + BMS-02 | |
| P0251 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-B | 2F Common Public | OA Damper Status | DI | Damper Controller | Equipment Supplier | | PNL-AIR-2F | MC-ME + BMS-02 | |
| P0252 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-B | 2F Common Public | OA Damper Command | AO | Damper Controller | Equipment Supplier | | PNL-AIR-2F | MC-ME + BMS-02 | |
| P0253 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-B | 2F Common Public | Return Air Damper Status | DI | Damper Controller | ME Contractor | | PNL-AIR-2F | MC-ME + BMS-02 | |
| P0254 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-B | 2F Common Public | Return Air Damper Command | AO | Damper Controller | ME Contractor | | PNL-AIR-2F | MC-ME + BMS-02 | |
| P0255 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-B | 2F Common Public | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-2F | MC-ME + BMS-02 | |
| P0256 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-B | 2F Common Public | Fan Motor Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-2F | MC-ME + BMS-02 | |
| P0257 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-B | 2F Common Public | Fan VFD Speed | AI | VFD | Equipment Supplier | | PNL-AIR-2F | MC-ME + BMS-02 | |
| P0258 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-B | 2F Common Public | Fan VFD Command | AO | VFD | Equipment Supplier | | PNL-AIR-2F | MC-ME + BMS-02 | |
| P0259 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-B | 2F Common Public | CHWS Valve Status | DI | Electric Valve Actuator | ME Contractor | | PNL-AIR-2F | MC-ME + BMS-02 | |
| P0260 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-2F-B | 2F Common Public | CHWS Valve Command | AO | Electric Valve Actuator | ME Contractor | | PNL-AIR-2F | MC-ME + BMS-02 | |
| P0261 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-LOB | Ground Floor Lobby | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0262 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-LOB | Ground Floor Lobby | Indoor Mixed Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0263 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-LOB | Ground Floor Lobby | Indoor Return Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0264 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-LOB | Ground Floor Lobby | Indoor Return Air CO2 | AI | CO2 Sensor | BMS Contractor | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0265 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-LOB | Ground Floor Lobby | OA Damper Status | DI | Damper Controller | Equipment Supplier | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0266 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-LOB | Ground Floor Lobby | OA Damper Command | AO | Damper Controller | Equipment Supplier | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0267 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-LOB | Ground Floor Lobby | Return Air Damper Status | DI | Damper Controller | ME Contractor | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0268 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-LOB | Ground Floor Lobby | Return Air Damper Command | AO | Damper Controller | ME Contractor | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0269 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-LOB | Ground Floor Lobby | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0270 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-LOB | Ground Floor Lobby | Fan Motor Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0271 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-LOB | Ground Floor Lobby | Fan VFD Speed | AI | VFD | Equipment Supplier | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0272 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-LOB | Ground Floor Lobby | Fan VFD Command | AO | VFD | Equipment Supplier | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0273 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-LOB | Ground Floor Lobby | CHWS Valve Status | DI | Electric Valve Actuator | ME Contractor | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0274 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-LOB | Ground Floor Lobby | CHWS Valve Command | AO | Electric Valve Actuator | ME Contractor | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0275 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-REST | Ground Floor Restaurant | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0276 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-REST | Ground Floor Restaurant | Indoor Mixed Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0277 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-REST | Ground Floor Restaurant | Indoor Return Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0278 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-REST | Ground Floor Restaurant | Indoor Return Air CO2 | AI | CO2 Sensor | BMS Contractor | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0279 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-REST | Ground Floor Restaurant | OA Damper Status | DI | Damper Controller | Equipment Supplier | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0280 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-REST | Ground Floor Restaurant | OA Damper Command | AO | Damper Controller | Equipment Supplier | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0281 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-REST | Ground Floor Restaurant | Return Air Damper Status | DI | Damper Controller | ME Contractor | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0282 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-REST | Ground Floor Restaurant | Return Air Damper Command | AO | Damper Controller | ME Contractor | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0283 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-REST | Ground Floor Restaurant | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0284 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-REST | Ground Floor Restaurant | Fan Motor Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0285 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-REST | Ground Floor Restaurant | Fan VFD Speed | AI | VFD | Equipment Supplier | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0286 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-REST | Ground Floor Restaurant | Fan VFD Command | AO | VFD | Equipment Supplier | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0287 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-REST | Ground Floor Restaurant | CHWS Valve Status | DI | Electric Valve Actuator | ME Contractor | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0288 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-GF-REST | Ground Floor Restaurant | CHWS Valve Command | AO | Electric Valve Actuator | ME Contractor | | PNL-AIR-GF | MC-ME (AHU @ GF) | |
| P0289 | Air Conditioning | AHU (Modulating CHW-served) | AHU-GF-CASINO | Ground Floor Casino Lobby | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-CASINO-GF | BMS-02 (Casino BMS) + MC-ME | |
| P0290 | Air Conditioning | AHU (Modulating CHW-served) | AHU-GF-CASINO | Ground Floor Casino Lobby | Indoor Return Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-CASINO-GF | BMS-02 (Casino BMS) + MC-ME | |
| P0291 | Air Conditioning | AHU (Modulating CHW-served) | AHU-GF-CASINO | Ground Floor Casino Lobby | Indoor Return Air CO/CO2 | AI | CO/CO2 Sensor | BMS Contractor | | PNL-CASINO-GF | BMS-02 (Casino BMS) + MC-ME | |
| P0292 | Air Conditioning | AHU (Modulating CHW-served) | AHU-GF-CASINO | Ground Floor Casino Lobby | OA Damper Position Feedback | AI | Damper Controller | Equipment Supplier | | PNL-CASINO-GF | BMS-02 (Casino BMS) + MC-ME | |
| P0293 | Air Conditioning | AHU (Modulating CHW-served) | AHU-GF-CASINO | Ground Floor Casino Lobby | OA Damper Modulating Command | AO | Damper Controller | Equipment Supplier | | PNL-CASINO-GF | BMS-02 (Casino BMS) + MC-ME | |
| P0294 | Air Conditioning | AHU (Modulating CHW-served) | AHU-GF-CASINO | Ground Floor Casino Lobby | Return Damper Position Feedback | AI | Damper Controller | ME Contractor | | PNL-CASINO-GF | BMS-02 (Casino BMS) + MC-ME | |
| P0295 | Air Conditioning | AHU (Modulating CHW-served) | AHU-GF-CASINO | Ground Floor Casino Lobby | Return Damper Modulating Command | AO | Damper Controller | ME Contractor | | PNL-CASINO-GF | BMS-02 (Casino BMS) + MC-ME | |
| P0296 | Air Conditioning | AHU (Modulating CHW-served) | AHU-GF-CASINO | Ground Floor Casino Lobby | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-CASINO-GF | BMS-02 (Casino BMS) + MC-ME | |
| P0297 | Air Conditioning | AHU (Modulating CHW-served) | AHU-GF-CASINO | Ground Floor Casino Lobby | Fan Motor Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-CASINO-GF | BMS-02 (Casino BMS) + MC-ME | |
| P0298 | Air Conditioning | AHU (Modulating CHW-served) | AHU-GF-CASINO | Ground Floor Casino Lobby | Fan VFD Speed | AI | VFD | Equipment Supplier | | PNL-CASINO-GF | BMS-02 (Casino BMS) + MC-ME | |
| P0299 | Air Conditioning | AHU (Modulating CHW-served) | AHU-GF-CASINO | Ground Floor Casino Lobby | Fan VFD Command | AO | VFD | Equipment Supplier | | PNL-CASINO-GF | BMS-02 (Casino BMS) + MC-ME | |
| P0300 | Air Conditioning | AHU (Modulating CHW-served) | AHU-GF-CASINO | Ground Floor Casino Lobby | CHWS Modulating Valve Position Feedback | AI | Electric Valve Actuator | ME Contractor | | PNL-CASINO-GF | BMS-02 (Casino BMS) + MC-ME | |
| P0301 | Air Conditioning | AHU (Modulating CHW-served) | AHU-GF-CASINO | Ground Floor Casino Lobby | CHWS Modulating Valve Command | AO | Electric Valve Actuator | ME Contractor | | PNL-CASINO-GF | BMS-02 (Casino BMS) + MC-ME | |
| P0302 | Air Conditioning | AHU (Modulating CHW-served) | AHU-GF-CASINO | Ground Floor Casino Lobby | Ozone VOC Reading | AI | VOC Sensor | BMS Contractor | | PNL-CASINO-GF | BMS-02 (Casino BMS) + MC-ME | |
| P0303 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-1 | Ground Floor Casino | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-CASINO-GF | BMS-02 (Casino BMS Equipment I/O Tabulation) | |
| P0304 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-1 | Ground Floor Casino | Indoor Return Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-CASINO-GF | BMS-02 (Casino BMS Equipment I/O Tabulation) | |
| P0305 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-1 | Ground Floor Casino | Indoor Return Air CO/CO2 | AI | CO/CO2 Sensor | BMS Contractor | | PNL-CASINO-GF | BMS-02 (Casino BMS Equipment I/O Tabulation) | |
| P0306 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-1 | Ground Floor Casino | OA Damper Position Feedback | AI | Damper Controller | Equipment Supplier | | PNL-CASINO-GF | BMS-02 (Casino BMS Equipment I/O Tabulation) | |
| P0307 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-1 | Ground Floor Casino | OA Damper Modulating Command | AO | Damper Controller | Equipment Supplier | | PNL-CASINO-GF | BMS-02 (Casino BMS Equipment I/O Tabulation) | |
| P0308 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-1 | Ground Floor Casino | Return Damper Position Feedback | AI | Damper Controller | ME Contractor | | PNL-CASINO-GF | BMS-02 (Casino BMS Equipment I/O Tabulation) | |
| P0309 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-1 | Ground Floor Casino | Return Damper Modulating Command | AO | Damper Controller | ME Contractor | | PNL-CASINO-GF | BMS-02 (Casino BMS Equipment I/O Tabulation) | |
| P0310 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-1 | Ground Floor Casino | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-CASINO-GF | BMS-02 (Casino BMS Equipment I/O Tabulation) | |
| P0311 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-1 | Ground Floor Casino | Fan Motor Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-CASINO-GF | BMS-02 (Casino BMS Equipment I/O Tabulation) | |
| P0312 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-1 | Ground Floor Casino | Fan VFD Speed | AI | VFD | Equipment Supplier | | PNL-CASINO-GF | BMS-02 (Casino BMS Equipment I/O Tabulation) | |
| P0313 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-1 | Ground Floor Casino | Fan VFD Command | AO | VFD | Equipment Supplier | | PNL-CASINO-GF | BMS-02 (Casino BMS Equipment I/O Tabulation) | |
| P0314 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-1 | Ground Floor Casino | CHWS Modulating Valve Position Feedback | AI | Electric Valve Actuator | ME Contractor | | PNL-CASINO-GF | BMS-02 (Casino BMS Equipment I/O Tabulation) | |
| P0315 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-1 | Ground Floor Casino | CHWS Modulating Valve Command | AO | Electric Valve Actuator | ME Contractor | | PNL-CASINO-GF | BMS-02 (Casino BMS Equipment I/O Tabulation) | |
| P0316 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-1 | Ground Floor Casino | Ozone VOC Reading | AI | VOC Sensor | BMS Contractor | | PNL-CASINO-GF | BMS-02 (Casino BMS Equipment I/O Tabulation) | |
| P0317 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-2 | Ground Floor Casino | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-CASINO-GF | BMS-02 | |
| P0318 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-2 | Ground Floor Casino | Indoor Return Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-CASINO-GF | BMS-02 | |
| P0319 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-2 | Ground Floor Casino | Indoor Return Air CO/CO2 | AI | CO/CO2 Sensor | BMS Contractor | | PNL-CASINO-GF | BMS-02 | |
| P0320 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-2 | Ground Floor Casino | OA Damper Position Feedback | AI | Damper Controller | Equipment Supplier | | PNL-CASINO-GF | BMS-02 | |
| P0321 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-2 | Ground Floor Casino | OA Damper Modulating Command | AO | Damper Controller | Equipment Supplier | | PNL-CASINO-GF | BMS-02 | |
| P0322 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-2 | Ground Floor Casino | Return Damper Position Feedback | AI | Damper Controller | ME Contractor | | PNL-CASINO-GF | BMS-02 | |
| P0323 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-2 | Ground Floor Casino | Return Damper Modulating Command | AO | Damper Controller | ME Contractor | | PNL-CASINO-GF | BMS-02 | |
| P0324 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-2 | Ground Floor Casino | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-CASINO-GF | BMS-02 | |
| P0325 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-2 | Ground Floor Casino | Fan Motor Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-CASINO-GF | BMS-02 | |
| P0326 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-2 | Ground Floor Casino | Fan VFD Speed | AI | VFD | Equipment Supplier | | PNL-CASINO-GF | BMS-02 | |
| P0327 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-2 | Ground Floor Casino | Fan VFD Command | AO | VFD | Equipment Supplier | | PNL-CASINO-GF | BMS-02 | |
| P0328 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-2 | Ground Floor Casino | CHWS Modulating Valve Position Feedback | AI | Electric Valve Actuator | ME Contractor | | PNL-CASINO-GF | BMS-02 | |
| P0329 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-2 | Ground Floor Casino | CHWS Modulating Valve Command | AO | Electric Valve Actuator | ME Contractor | | PNL-CASINO-GF | BMS-02 | |
| P0330 | Casino Air Conditioning | AHU (Modulating CHW-served) | AHU-CASINO-2 | Ground Floor Casino | Ozone VOC Reading | AI | VOC Sensor | BMS Contractor | | PNL-CASINO-GF | BMS-02 | |
| P0331 | Casino Air Conditioning | Ozone Generator (UV-light or Corona) | OZ-CASINO-1 | Ground Floor Casino | Ozone Generator Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-CASINO-GF | BMS-02 | |
| P0332 | Casino Air Conditioning | Ozone Generator (UV-light or Corona) | OZ-CASINO-1 | Ground Floor Casino | Ozone Generator Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-CASINO-GF | BMS-02 | |
| P0333 | Casino Air Conditioning | Ozone Generator (UV-light or Corona) | OZ-CASINO-1 | Ground Floor Casino | Ozone Generator Start/Stop | DO | Auxiliary Contact | Equipment Supplier | | PNL-CASINO-GF | BMS-02 | |
| P0334 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-3F-AM | 3F Amenity | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-3F | MC-ME (3F amenity) | |
| P0335 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-3F-AM | 3F Amenity | Indoor Mixed Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-3F | MC-ME (3F amenity) | |
| P0336 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-3F-AM | 3F Amenity | Indoor Return Air Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-3F | MC-ME (3F amenity) | |
| P0337 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-3F-AM | 3F Amenity | Indoor Return Air CO2 | AI | CO2 Sensor | BMS Contractor | | PNL-AIR-3F | MC-ME (3F amenity) | |
| P0338 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-3F-AM | 3F Amenity | OA Damper Status | DI | Damper Controller | Equipment Supplier | | PNL-AIR-3F | MC-ME (3F amenity) | |
| P0339 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-3F-AM | 3F Amenity | OA Damper Command | AO | Damper Controller | Equipment Supplier | | PNL-AIR-3F | MC-ME (3F amenity) | |
| P0340 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-3F-AM | 3F Amenity | Return Air Damper Status | DI | Damper Controller | ME Contractor | | PNL-AIR-3F | MC-ME (3F amenity) | |
| P0341 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-3F-AM | 3F Amenity | Return Air Damper Command | AO | Damper Controller | ME Contractor | | PNL-AIR-3F | MC-ME (3F amenity) | |
| P0342 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-3F-AM | 3F Amenity | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-3F | MC-ME (3F amenity) | |
| P0343 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-3F-AM | 3F Amenity | Fan Motor Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-3F | MC-ME (3F amenity) | |
| P0344 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-3F-AM | 3F Amenity | Fan VFD Speed | AI | VFD | Equipment Supplier | | PNL-AIR-3F | MC-ME (3F amenity) | |
| P0345 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-3F-AM | 3F Amenity | Fan VFD Command | AO | VFD | Equipment Supplier | | PNL-AIR-3F | MC-ME (3F amenity) | |
| P0346 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-3F-AM | 3F Amenity | CHWS Valve Status | DI | Electric Valve Actuator | ME Contractor | | PNL-AIR-3F | MC-ME (3F amenity) | |
| P0347 | Air Conditioning | AHU (Chilled-Water-Served) | AHU-3F-AM | 3F Amenity | CHWS Valve Command | AO | Electric Valve Actuator | ME Contractor | | PNL-AIR-3F | MC-ME (3F amenity) | |
| P0348 | Exhaust | Exhaust Fan (Toilet) | EAS-TOILET-BSMT | Basement BOH | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-BSMT | BMS-01 (Basement toilet exhaust) | |
| P0349 | Exhaust | Exhaust Fan (Toilet) | EAS-TOILET-BSMT | Basement BOH | Fan Motor HOA | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-BSMT | BMS-01 (Basement toilet exhaust) | |
| P0350 | Exhaust | Exhaust Fan (Toilet) | EAS-TOILET-BSMT | Basement BOH | Fan Motor Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-BSMT | BMS-01 (Basement toilet exhaust) | |
| P0351 | Exhaust | Exhaust Fan (General) | EAS-GEN-BSMT | Basement BOH | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-BSMT | BMS-01 | |
| P0352 | Exhaust | Exhaust Fan (General) | EAS-GEN-BSMT | Basement BOH | Fan Motor HOA | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-BSMT | BMS-01 | |
| P0353 | Exhaust | Exhaust Fan (General) | EAS-GEN-BSMT | Basement BOH | Fan Motor Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-BSMT | BMS-01 | |
| P0354 | Exhaust | Exhaust Fan (Toilet) | EAS-TOILET-GF | Ground Floor Lobby | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-GF | MC-ME (GF main lobby toilet exhaust) | |
| P0355 | Exhaust | Exhaust Fan (Toilet) | EAS-TOILET-GF | Ground Floor Lobby | Fan Motor HOA | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-GF | MC-ME (GF main lobby toilet exhaust) | |
| P0356 | Exhaust | Exhaust Fan (Toilet) | EAS-TOILET-GF | Ground Floor Lobby | Fan Motor Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-GF | MC-ME (GF main lobby toilet exhaust) | |
| P0357 | Exhaust | Exhaust Fan (General) | EAS-GEN-GF | Ground Floor Lobby | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-GF | MC-ME | |
| P0358 | Exhaust | Exhaust Fan (General) | EAS-GEN-GF | Ground Floor Lobby | Fan Motor HOA | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-GF | MC-ME | |
| P0359 | Exhaust | Exhaust Fan (General) | EAS-GEN-GF | Ground Floor Lobby | Fan Motor Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-GF | MC-ME | |
| P0360 | Exhaust | Exhaust Fan (Toilet) | EAS-TOILET-2F | 2F Common Public | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-2F | MC-ME (2nd Floor toilet exhaust) | |
| P0361 | Exhaust | Exhaust Fan (Toilet) | EAS-TOILET-2F | 2F Common Public | Fan Motor HOA | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-2F | MC-ME (2nd Floor toilet exhaust) | |
| P0362 | Exhaust | Exhaust Fan (Toilet) | EAS-TOILET-2F | 2F Common Public | Fan Motor Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-2F | MC-ME (2nd Floor toilet exhaust) | |
| P0363 | Exhaust | Exhaust Fan (General) | EAS-GEN-2F | 2F Common Public | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-2F | MC-ME | |
| P0364 | Exhaust | Exhaust Fan (General) | EAS-GEN-2F | 2F Common Public | Fan Motor HOA | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-2F | MC-ME | |
| P0365 | Exhaust | Exhaust Fan (General) | EAS-GEN-2F | 2F Common Public | Fan Motor Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-2F | MC-ME | |
| P0366 | Exhaust | Exhaust Fan (Toilet) | EAS-TOILET-3F | 3F Amenity | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-3F | MC-ME (3F amenity toilet exhaust) | |
| P0367 | Exhaust | Exhaust Fan (Toilet) | EAS-TOILET-3F | 3F Amenity | Fan Motor HOA | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-3F | MC-ME (3F amenity toilet exhaust) | |
| P0368 | Exhaust | Exhaust Fan (Toilet) | EAS-TOILET-3F | 3F Amenity | Fan Motor Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-3F | MC-ME (3F amenity toilet exhaust) | |
| P0369 | Exhaust | Exhaust Fan (General) | EAS-GEN-3F | 3F Amenity | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-3F | MC-ME | |
| P0370 | Exhaust | Exhaust Fan (General) | EAS-GEN-3F | 3F Amenity | Fan Motor HOA | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-3F | MC-ME | |
| P0371 | Exhaust | Exhaust Fan (General) | EAS-GEN-3F | 3F Amenity | Fan Motor Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-3F | MC-ME | |
| P0372 | Exhaust | Exhaust Fan (General) | EAS-GEN-ROOF | Roofdeck DOAS | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (Roofdeck general exhaust) | |
| P0373 | Exhaust | Exhaust Fan (General) | EAS-GEN-ROOF | Roofdeck DOAS | Fan Motor HOA | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (Roofdeck general exhaust) | |
| P0374 | Exhaust | Exhaust Fan (General) | EAS-GEN-ROOF | Roofdeck DOAS | Fan Motor Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-ME (Roofdeck general exhaust) | |
| P0375 | Hot Water | Calorifier (Hot Water Storage Tank) | CALOR-LG | Lower Ground Calorifier Room | Tank Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-PL-LG | MC-PL (Calorifiers @ Lower Ground) | |
| P0376 | Hot Water | Calorifier (Hot Water Storage Tank) | CALOR-ROOF | Roofdeck DOAS | Tank Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-AIR-ROOF | MC-PL (Calorifiers @ Roofdeck) | |
| P0377 | Hot Water | Hot Water Header Set | HW-HEADERS-LG | Lower Ground Calorifier Room | HW Supply Header Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-PL-LG | MC-PL (Supply & Return Headers @ Lower Ground) | |
| P0378 | Hot Water | Hot Water Header Set | HW-HEADERS-LG | Lower Ground Calorifier Room | Make-up Cold Water Header Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-PL-LG | MC-PL (Supply & Return Headers @ Lower Ground) | |
| P0379 | Hot Water | Hot Water Header Set | HW-HEADERS-LG | Lower Ground Calorifier Room | HW Return Header Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-PL-LG | MC-PL (Supply & Return Headers @ Lower Ground) | |
| P0380 | Hot Water | Heat Pump | HP-LG-1 | Lower Ground Calorifier Room | Pump Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-PL-LG | MC-PL (Heat Pump @ Lower Ground) | |
| P0381 | Hot Water | Heat Pump | HP-LG-1 | Lower Ground Calorifier Room | Pump Motor HOA | DI | Auxiliary Contact | Equipment Supplier | | PNL-PL-LG | MC-PL (Heat Pump @ Lower Ground) | |
| P0382 | Hot Water | Heat Pump | HP-LG-1 | Lower Ground Calorifier Room | Pump Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-PL-LG | MC-PL (Heat Pump @ Lower Ground) | |
| P0383 | Hot Water | Heat Pump | HP-ROOF-1 | Roofdeck DOAS | Pump Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-PL (Heat Pump @ Roofdeck) | |
| P0384 | Hot Water | Heat Pump | HP-ROOF-1 | Roofdeck DOAS | Pump Motor HOA | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-PL (Heat Pump @ Roofdeck) | |
| P0385 | Hot Water | Heat Pump | HP-ROOF-1 | Roofdeck DOAS | Pump Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-PL (Heat Pump @ Roofdeck) | |
| P0386 | Hot Water | Recirculating Pump | HW-PUMP-LG-1 | Lower Ground Calorifier Room | Pump Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-PL-LG | MC-PL (Circulating Pumps @ Lower Ground) | |
| P0387 | Hot Water | Recirculating Pump | HW-PUMP-LG-1 | Lower Ground Calorifier Room | Pump Motor HOA | DI | Auxiliary Contact | Equipment Supplier | | PNL-PL-LG | MC-PL (Circulating Pumps @ Lower Ground) | |
| P0388 | Hot Water | Recirculating Pump | HW-PUMP-LG-1 | Lower Ground Calorifier Room | Pump Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-PL-LG | MC-PL (Circulating Pumps @ Lower Ground) | |
| P0389 | Hot Water | Recirculating Pump | HW-PUMP-LG-2 | Lower Ground Calorifier Room | Pump Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-PL-LG | MC-PL | |
| P0390 | Hot Water | Recirculating Pump | HW-PUMP-LG-2 | Lower Ground Calorifier Room | Pump Motor HOA | DI | Auxiliary Contact | Equipment Supplier | | PNL-PL-LG | MC-PL | |
| P0391 | Hot Water | Recirculating Pump | HW-PUMP-LG-2 | Lower Ground Calorifier Room | Pump Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-PL-LG | MC-PL | |
| P0392 | Hot Water | Recirculating Pump | HW-PUMP-ROOF-1 | Roofdeck DOAS | Pump Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-PL (Roofdeck circulating pumps) | |
| P0393 | Hot Water | Recirculating Pump | HW-PUMP-ROOF-1 | Roofdeck DOAS | Pump Motor HOA | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-PL (Roofdeck circulating pumps) | |
| P0394 | Hot Water | Recirculating Pump | HW-PUMP-ROOF-1 | Roofdeck DOAS | Pump Trip | DI | Auxiliary Contact | Equipment Supplier | | PNL-AIR-ROOF | MC-PL (Roofdeck circulating pumps) | |
| P0395 | Boiler | Steam Boiler | BLR-1 | Lower Ground Boiler Room | Supply Steam Pressure | AI | Pressure Sensor | BMS Contractor | | PNL-BLR-LG | BMS-01 (Boilers @ Lower Ground) + MC-ME | |
| P0396 | Boiler | Steam Boiler | BLR-1 | Lower Ground Boiler Room | Feedwater Supply Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-BLR-LG | BMS-01 (Boilers @ Lower Ground) + MC-ME | |
| P0397 | Boiler | Steam Boiler | BLR-1 | Lower Ground Boiler Room | Fluegas Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-BLR-LG | BMS-01 (Boilers @ Lower Ground) + MC-ME | |
| P0398 | Boiler | Steam Boiler | BLR-1 | Lower Ground Boiler Room | Fluegas Oxygen Level | AI | Oxygen Sensor | BMS Contractor | | PNL-BLR-LG | BMS-01 (Boilers @ Lower Ground) + MC-ME | |
| P0399 | Boiler | Steam Boiler | BLR-1 | Lower Ground Boiler Room | Boiler Water Low Level | DI | Level Sensor | Equipment Supplier | | PNL-BLR-LG | BMS-01 (Boilers @ Lower Ground) + MC-ME | |
| P0400 | Boiler | Steam Boiler | BLR-1 | Lower Ground Boiler Room | Boiler Water High Level | DI | Level Sensor | Equipment Supplier | | PNL-BLR-LG | BMS-01 (Boilers @ Lower Ground) + MC-ME | |
| P0401 | Boiler | Steam Boiler | BLR-1 | Lower Ground Boiler Room | Burner Power | DI | Auxiliary Contact | Equipment Supplier | | PNL-BLR-LG | BMS-01 (Boilers @ Lower Ground) + MC-ME | |
| P0402 | Boiler | Steam Boiler | BLR-1 | Lower Ground Boiler Room | Small Fire Control Signal | DI | Auxiliary Contact | Equipment Supplier | | PNL-BLR-LG | BMS-01 (Boilers @ Lower Ground) + MC-ME | |
| P0403 | Boiler | Steam Boiler | BLR-1 | Lower Ground Boiler Room | Big Fire Control Signal | DI | Auxiliary Contact | Equipment Supplier | | PNL-BLR-LG | BMS-01 (Boilers @ Lower Ground) + MC-ME | |
| P0404 | Boiler | Steam Boiler | BLR-1 | Lower Ground Boiler Room | Waterfeed Pump Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-BLR-LG | BMS-01 (Boilers @ Lower Ground) + MC-ME | |
| P0405 | Boiler | Steam Boiler | BLR-1 | Lower Ground Boiler Room | Burner Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-BLR-LG | BMS-01 (Boilers @ Lower Ground) + MC-ME | |
| P0406 | Boiler | Steam Boiler | BLR-1 | Lower Ground Boiler Room | Burner Fire Running Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-BLR-LG | BMS-01 (Boilers @ Lower Ground) + MC-ME | |
| P0407 | Boiler | Steam Boiler | BLR-1 | Lower Ground Boiler Room | Blower Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-BLR-LG | BMS-01 (Boilers @ Lower Ground) + MC-ME | |
| P0408 | Boiler | Steam Boiler | BLR-1 | Lower Ground Boiler Room | Fuel Oil Pump Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-BLR-LG | BMS-01 (Boilers @ Lower Ground) + MC-ME | |
| P0409 | Boiler | Steam Boiler | BLR-1 | Lower Ground Boiler Room | Motorized Blowdown Valve Status | DI | Electric Valve Actuator | BMS Contractor | | PNL-BLR-LG | BMS-01 (Boilers @ Lower Ground) + MC-ME | |
| P0410 | Boiler | Steam Boiler | BLR-1 | Lower Ground Boiler Room | Motorized Blowdown Valve Command | DO | Electric Valve Actuator | BMS Contractor | | PNL-BLR-LG | BMS-01 (Boilers @ Lower Ground) + MC-ME | |
| P0411 | Boiler | Steam Boiler | BLR-2 | Lower Ground Boiler Room | Supply Steam Pressure | AI | Pressure Sensor | BMS Contractor | | PNL-BLR-LG | BMS-01 + MC-ME | |
| P0412 | Boiler | Steam Boiler | BLR-2 | Lower Ground Boiler Room | Feedwater Supply Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-BLR-LG | BMS-01 + MC-ME | |
| P0413 | Boiler | Steam Boiler | BLR-2 | Lower Ground Boiler Room | Fluegas Temperature | AI | Temperature Sensor | BMS Contractor | | PNL-BLR-LG | BMS-01 + MC-ME | |
| P0414 | Boiler | Steam Boiler | BLR-2 | Lower Ground Boiler Room | Fluegas Oxygen Level | AI | Oxygen Sensor | BMS Contractor | | PNL-BLR-LG | BMS-01 + MC-ME | |
| P0415 | Boiler | Steam Boiler | BLR-2 | Lower Ground Boiler Room | Boiler Water Low Level | DI | Level Sensor | Equipment Supplier | | PNL-BLR-LG | BMS-01 + MC-ME | |
| P0416 | Boiler | Steam Boiler | BLR-2 | Lower Ground Boiler Room | Boiler Water High Level | DI | Level Sensor | Equipment Supplier | | PNL-BLR-LG | BMS-01 + MC-ME | |
| P0417 | Boiler | Steam Boiler | BLR-2 | Lower Ground Boiler Room | Burner Power | DI | Auxiliary Contact | Equipment Supplier | | PNL-BLR-LG | BMS-01 + MC-ME | |
| P0418 | Boiler | Steam Boiler | BLR-2 | Lower Ground Boiler Room | Small Fire Control Signal | DI | Auxiliary Contact | Equipment Supplier | | PNL-BLR-LG | BMS-01 + MC-ME | |
| P0419 | Boiler | Steam Boiler | BLR-2 | Lower Ground Boiler Room | Big Fire Control Signal | DI | Auxiliary Contact | Equipment Supplier | | PNL-BLR-LG | BMS-01 + MC-ME | |
| P0420 | Boiler | Steam Boiler | BLR-2 | Lower Ground Boiler Room | Waterfeed Pump Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-BLR-LG | BMS-01 + MC-ME | |
| P0421 | Boiler | Steam Boiler | BLR-2 | Lower Ground Boiler Room | Burner Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-BLR-LG | BMS-01 + MC-ME | |
| P0422 | Boiler | Steam Boiler | BLR-2 | Lower Ground Boiler Room | Burner Fire Running Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-BLR-LG | BMS-01 + MC-ME | |
| P0423 | Boiler | Steam Boiler | BLR-2 | Lower Ground Boiler Room | Blower Motor Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-BLR-LG | BMS-01 + MC-ME | |
| P0424 | Boiler | Steam Boiler | BLR-2 | Lower Ground Boiler Room | Fuel Oil Pump Status | DI | Auxiliary Contact | Equipment Supplier | | PNL-BLR-LG | BMS-01 + MC-ME | |
| P0425 | Boiler | Steam Boiler | BLR-2 | Lower Ground Boiler Room | Motorized Blowdown Valve Status | DI | Electric Valve Actuator | BMS Contractor | | PNL-BLR-LG | BMS-01 + MC-ME | |
| P0426 | Boiler | Steam Boiler | BLR-2 | Lower Ground Boiler Room | Motorized Blowdown Valve Command | DO | Electric Valve Actuator | BMS Contractor | | PNL-BLR-LG | BMS-01 + MC-ME | |
| P0427 | Power Monitoring | Multifunction Power Meter (Main) | PM-MAIN-LG | Lower Ground Main Switchgear | Power Meter Modbus Network | Network | Modbus Power Meter | BMS Contractor | | PNL-PM-LG | EE-21 (main service entry) + BMS-01 spec | |
| P0428 | Power Monitoring | Multifunction Power Meter (Main) | PM-MAIN-LG | Lower Ground Main Switchgear | Voltage L-L (3-phase) | HLI | Modbus Power Meter | BMS Contractor | | PNL-PM-LG | EE-21 (main service entry) + BMS-01 spec | |
| P0429 | Power Monitoring | Multifunction Power Meter (Main) | PM-MAIN-LG | Lower Ground Main Switchgear | Current per phase | HLI | Modbus Power Meter | BMS Contractor | | PNL-PM-LG | EE-21 (main service entry) + BMS-01 spec | |
| P0430 | Power Monitoring | Multifunction Power Meter (Main) | PM-MAIN-LG | Lower Ground Main Switchgear | Real Power kW | HLI | Modbus Power Meter | BMS Contractor | | PNL-PM-LG | EE-21 (main service entry) + BMS-01 spec | |
| P0431 | Power Monitoring | Multifunction Power Meter (Main) | PM-MAIN-LG | Lower Ground Main Switchgear | Reactive Power kVAR | HLI | Modbus Power Meter | BMS Contractor | | PNL-PM-LG | EE-21 (main service entry) + BMS-01 spec | |
| P0432 | Power Monitoring | Multifunction Power Meter (Main) | PM-MAIN-LG | Lower Ground Main Switchgear | Power Factor | HLI | Modbus Power Meter | BMS Contractor | | PNL-PM-LG | EE-21 (main service entry) + BMS-01 spec | |
| P0433 | Power Monitoring | Multifunction Power Meter (Main) | PM-MAIN-LG | Lower Ground Main Switchgear | Energy kWh | HLI | Modbus Power Meter | BMS Contractor | | PNL-PM-LG | EE-21 (main service entry) + BMS-01 spec | |
| P0434 | Power Monitoring | Multifunction Power Meter (Main) | PM-MAIN-LG | Lower Ground Main Switchgear | Frequency Hz | HLI | Modbus Power Meter | BMS Contractor | | PNL-PM-LG | EE-21 (main service entry) + BMS-01 spec | |
| P0435 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-CHILLER | 2F Chiller Plant Room | Power Meter Modbus Network | Network | Modbus Power Meter | BMS Contractor | | PNL-CH-PLANT-2F | EE-21 + BMS-01 (chiller feeders) | |
| P0436 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-CHILLER | 2F Chiller Plant Room | Voltage L-L (3-phase) | HLI | Modbus Power Meter | BMS Contractor | | PNL-CH-PLANT-2F | EE-21 + BMS-01 (chiller feeders) | |
| P0437 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-CHILLER | 2F Chiller Plant Room | Current per phase | HLI | Modbus Power Meter | BMS Contractor | | PNL-CH-PLANT-2F | EE-21 + BMS-01 (chiller feeders) | |
| P0438 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-CHILLER | 2F Chiller Plant Room | Real Power kW | HLI | Modbus Power Meter | BMS Contractor | | PNL-CH-PLANT-2F | EE-21 + BMS-01 (chiller feeders) | |
| P0439 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-CHILLER | 2F Chiller Plant Room | Energy kWh | HLI | Modbus Power Meter | BMS Contractor | | PNL-CH-PLANT-2F | EE-21 + BMS-01 (chiller feeders) | |
| P0440 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-COOLING | Roofdeck Cooling Tower | Power Meter Modbus Network | Network | Modbus Power Meter | BMS Contractor | | PNL-CT-ROOF | EE-22 + BMS-01 | |
| P0441 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-COOLING | Roofdeck Cooling Tower | Voltage L-L (3-phase) | HLI | Modbus Power Meter | BMS Contractor | | PNL-CT-ROOF | EE-22 + BMS-01 | |
| P0442 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-COOLING | Roofdeck Cooling Tower | Current per phase | HLI | Modbus Power Meter | BMS Contractor | | PNL-CT-ROOF | EE-22 + BMS-01 | |
| P0443 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-COOLING | Roofdeck Cooling Tower | Real Power kW | HLI | Modbus Power Meter | BMS Contractor | | PNL-CT-ROOF | EE-22 + BMS-01 | |
| P0444 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-COOLING | Roofdeck Cooling Tower | Energy kWh | HLI | Modbus Power Meter | BMS Contractor | | PNL-CT-ROOF | EE-22 + BMS-01 | |
| P0445 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-AIR-2F | 2F Common Public | Power Meter Modbus Network | Network | Modbus Power Meter | BMS Contractor | | PNL-AIR-2F | EE-22 | |
| P0446 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-AIR-2F | 2F Common Public | Voltage L-L (3-phase) | HLI | Modbus Power Meter | BMS Contractor | | PNL-AIR-2F | EE-22 | |
| P0447 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-AIR-2F | 2F Common Public | Current per phase | HLI | Modbus Power Meter | BMS Contractor | | PNL-AIR-2F | EE-22 | |
| P0448 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-AIR-2F | 2F Common Public | Real Power kW | HLI | Modbus Power Meter | BMS Contractor | | PNL-AIR-2F | EE-22 | |
| P0449 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-AIR-2F | 2F Common Public | Energy kWh | HLI | Modbus Power Meter | BMS Contractor | | PNL-AIR-2F | EE-22 | |
| P0450 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-AIR-GF | Ground Floor Lobby | Power Meter Modbus Network | Network | Modbus Power Meter | BMS Contractor | | PNL-AIR-GF | EE-22 | |
| P0451 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-AIR-GF | Ground Floor Lobby | Voltage L-L (3-phase) | HLI | Modbus Power Meter | BMS Contractor | | PNL-AIR-GF | EE-22 | |
| P0452 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-AIR-GF | Ground Floor Lobby | Current per phase | HLI | Modbus Power Meter | BMS Contractor | | PNL-AIR-GF | EE-22 | |
| P0453 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-AIR-GF | Ground Floor Lobby | Real Power kW | HLI | Modbus Power Meter | BMS Contractor | | PNL-AIR-GF | EE-22 | |
| P0454 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-AIR-GF | Ground Floor Lobby | Energy kWh | HLI | Modbus Power Meter | BMS Contractor | | PNL-AIR-GF | EE-22 | |
| P0455 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-CASINO | Ground Floor Casino | Power Meter Modbus Network | Network | Modbus Power Meter | BMS Contractor | | PNL-CASINO-GF | EE-22 (Casino feeder) | |
| P0456 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-CASINO | Ground Floor Casino | Voltage L-L (3-phase) | HLI | Modbus Power Meter | BMS Contractor | | PNL-CASINO-GF | EE-22 (Casino feeder) | |
| P0457 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-CASINO | Ground Floor Casino | Current per phase | HLI | Modbus Power Meter | BMS Contractor | | PNL-CASINO-GF | EE-22 (Casino feeder) | |
| P0458 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-CASINO | Ground Floor Casino | Real Power kW | HLI | Modbus Power Meter | BMS Contractor | | PNL-CASINO-GF | EE-22 (Casino feeder) | |
| P0459 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-CASINO | Ground Floor Casino | Energy kWh | HLI | Modbus Power Meter | BMS Contractor | | PNL-CASINO-GF | EE-22 (Casino feeder) | |
| P0460 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-BOILER | Lower Ground Boiler Room | Power Meter Modbus Network | Network | Modbus Power Meter | BMS Contractor | | PNL-BLR-LG | EE-23 (boiler feeder) | |
| P0461 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-BOILER | Lower Ground Boiler Room | Voltage L-L (3-phase) | HLI | Modbus Power Meter | BMS Contractor | | PNL-BLR-LG | EE-23 (boiler feeder) | |
| P0462 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-BOILER | Lower Ground Boiler Room | Current per phase | HLI | Modbus Power Meter | BMS Contractor | | PNL-BLR-LG | EE-23 (boiler feeder) | |
| P0463 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-BOILER | Lower Ground Boiler Room | Real Power kW | HLI | Modbus Power Meter | BMS Contractor | | PNL-BLR-LG | EE-23 (boiler feeder) | |
| P0464 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-BOILER | Lower Ground Boiler Room | Energy kWh | HLI | Modbus Power Meter | BMS Contractor | | PNL-BLR-LG | EE-23 (boiler feeder) | |
| P0465 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-PLUMB | Lower Ground Calorifier Room | Power Meter Modbus Network | Network | Modbus Power Meter | BMS Contractor | | PNL-PL-LG | EE-23 (plumbing pumproom feeder) | |
| P0466 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-PLUMB | Lower Ground Calorifier Room | Voltage L-L (3-phase) | HLI | Modbus Power Meter | BMS Contractor | | PNL-PL-LG | EE-23 (plumbing pumproom feeder) | |
| P0467 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-PLUMB | Lower Ground Calorifier Room | Current per phase | HLI | Modbus Power Meter | BMS Contractor | | PNL-PL-LG | EE-23 (plumbing pumproom feeder) | |
| P0468 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-PLUMB | Lower Ground Calorifier Room | Real Power kW | HLI | Modbus Power Meter | BMS Contractor | | PNL-PL-LG | EE-23 (plumbing pumproom feeder) | |
| P0469 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-PLUMB | Lower Ground Calorifier Room | Energy kWh | HLI | Modbus Power Meter | BMS Contractor | | PNL-PL-LG | EE-23 (plumbing pumproom feeder) | |
| P0470 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-FIREPMP | Lower Ground Boiler Room | Power Meter Modbus Network | Network | Modbus Power Meter | BMS Contractor | | PNL-PL-LG | EE-23 (fire pump feeder per CB#8 — single-feeder scheme) | |
| P0471 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-FIREPMP | Lower Ground Boiler Room | Voltage L-L (3-phase) | HLI | Modbus Power Meter | BMS Contractor | | PNL-PL-LG | EE-23 (fire pump feeder per CB#8 — single-feeder scheme) | |
| P0472 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-FIREPMP | Lower Ground Boiler Room | Current per phase | HLI | Modbus Power Meter | BMS Contractor | | PNL-PL-LG | EE-23 (fire pump feeder per CB#8 — single-feeder scheme) | |
| P0473 | Power Monitoring | Multifunction Power Meter (Feeder) | PM-FIREPMP | Lower Ground Boiler Room | Real Power kW | HLI | Modbus Power Meter | BMS Contractor | | PNL-PL-LG | EE-23 (fire pump feeder per CB#8 — single-feeder scheme) | |