Summary

A3 — Cable Schedule, Audit View
ProjectKingsford Hotel Bacolod — BMS Rehabilitation (A/B run)
Canonical sourceA3-cable-schedule.yaml
How to record correctionsEdit the canonical YAML directly — add a verification: block to the affected row(s)
Totals
Total cables211
Total length (m)6,780
Field cables198
Trunk cables7
Panel power feeds6
Verification status
StatusCount% of total
verified00%
needs_correction00%
uncertain00%
unverified211100%
⚠ Known weak points
Cable lengths are estimates based on assumption A-001 (30 m average panel-to-device run, 80 m trunk per floor). Field-verified lengths typically vary by ±20% per cable. THIS IS THE SYSTEM'S WEAKEST AUTO-GENERATED QUANTITY — please verify before issuing the BOQ to the customer.
How corrections flow
1. Open A3-cable-schedule.yaml in any text editor.
2. Find the affected row by ID (column A in the Detail sheet).
3. Add a verification: block — see the 'Verification schema' sheet for the template.
4. Re-run: python3 _playbook/tools/generate-deliverables.py <project>
5. Corrections flow through B4 manhours, BOQ material costs, and final deliverables automatically.

By Panel

PanelCable countTotal length (m)
FCP-2F682040
FCP-RD371110
MCP-PLANT28840
FCP-3F27810
FCP-BSMT20600
FCP-GF18540
TOTAL (field cables)1985940

By Floor

FloorCable countTotal length (m)
2nd Floor962880
Roofdeck371110
3rd Floor27810
Ground18540
Lower Ground14420
Basement6180
TOTAL1985940

By Cable Type

Cable typeCountTotal length (m)
4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)982940
4C × 1.5 mm² shielded FRLS (BMS signal — sensors)461380
4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)29870
Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)23690
Modbus shielded twisted-pair, 1pr × 22 AWG (e.g., Belden 9841)260

Detail (cables)

IDFromToCable typeLength (m)StatusCorrected (m)Verified byDateDrawing refNotes
C0001FCP-GFAHU-1.1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0002FCP-GFAHU-1.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0003FCP-GFAHU-1.1 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0004FCP-GFAHU-1.2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0005FCP-GFAHU-1.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0006FCP-GFAHU-1.2 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0007FCP-GFAHU-1.3 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0008FCP-GFAHU-1.3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0009FCP-GFAHU-1.3 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0010FCP-2FAHU-2M.1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0011FCP-2FAHU-2M.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0012FCP-2FAHU-2M.1 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0013FCP-2FAHU-2M.2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0014FCP-2FAHU-2M.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0015FCP-2FAHU-2M.2 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0016FCP-2FAHU-B.1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0017FCP-2FAHU-B.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0018FCP-2FAHU-B.1 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0019FCP-2FAHU-B.2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0020FCP-2FAHU-B.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0021FCP-2FAHU-B.2 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0022FCP-2FAHU-B.3 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0023FCP-2FAHU-B.3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0024FCP-2FAHU-B.3 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0025FCP-2FAHU-EL (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0026FCP-2FAHU-EL (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0027FCP-2FAHU-EL (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0028FCP-2FAHU-FR2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0029FCP-2FAHU-FR2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0030FCP-2FAHU-FR2 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0031FCP-2FAHU-FR3 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0032FCP-2FAHU-FR3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0033FCP-2FAHU-FR3 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0034FCP-2FAHU-PF (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0035FCP-2FAHU-PF (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0036FCP-2FAHU-PF (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0037FCP-BSMTATS-1 (EE Contractor)Modbus shielded twisted-pair, 1pr × 22 AWG (e.g., Belden 9841)30unverified
C0038FCP-BSMTBLR-1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0039FCP-BSMTBLR-1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0040FCP-BSMTBLR-2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0041FCP-BSMTBLR-2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0042MCP-PLANTCH-1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0043MCP-PLANTCH-1 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0044MCP-PLANTCH-2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0045MCP-PLANTCH-2 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0046MCP-PLANTCH-3 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0047MCP-PLANTCH-3 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0048MCP-PLANTCHW-BYPASS (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0049MCP-PLANTCHW-HDR-R (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0050MCP-PLANTCHW-HDR-S (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0051FCP-RDCOW-HDR (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0052FCP-RDCT-1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0053FCP-RDCT-1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0054FCP-RDCT-1 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0055FCP-RDCT-2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0056FCP-RDCT-2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0057FCP-RDCT-2 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0058FCP-RDCT-3 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0059FCP-RDCT-3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0060FCP-RDCT-3 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0061FCP-RDCT-COMMON (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0062FCP-2FDOAS-2M (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0063FCP-2FDOAS-2M (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0064FCP-2FDOAS-2M (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0065FCP-RDDOAS-RD.1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0066FCP-RDDOAS-RD.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0067FCP-RDDOAS-RD.1 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0068FCP-RDDOAS-RD.2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0069FCP-RDDOAS-RD.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0070FCP-RDDOAS-RD.2 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0071FCP-GFEF-1.2A (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0072FCP-GFEF-1MR.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0073FCP-GFEF-1ST0.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0074FCP-2FEF-2.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0075FCP-2FEF-2.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0076FCP-2FEF-2.3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0077FCP-2FEF-2.4 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0078FCP-2FEF-2B.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0079FCP-2FEF-2B.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0080FCP-3FEF-3GE.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0081FCP-3FEF-3GE.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0082FCP-2FEF-CHR.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0083FCP-2FEF-CHR.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0084FCP-2FEF-GS.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0085FCP-2FEF-GS.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0086FCP-GFEF-LPG.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0087FCP-GFEF-MRF.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0088FCP-BSMTGEN-1 (EE Contractor)Modbus shielded twisted-pair, 1pr × 22 AWG (e.g., Belden 9841)30unverified
C0089FCP-RDHP-HZ.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0090FCP-RDHP-HZ.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0091FCP-RDHP-HZ.3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0092FCP-BSMTHP-LZ.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0093FCP-BSMTHP-LZ.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0094FCP-BSMTHP-LZ.3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0095FCP-RDHW-HDR-HZ (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0096FCP-BSMTHW-HDR-LZ (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0097FCP-RDHWT-HZ.1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0098FCP-RDHWT-HZ.2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0099FCP-RDHWT-HZ.3 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0100FCP-BSMTHWT-LZ.1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0101FCP-BSMTHWT-LZ.2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0102FCP-BSMTHWT-LZ.3 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0103FCP-2FION-2M.1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0104FCP-2FION-2M.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0105FCP-2FION-2M.2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0106FCP-2FION-2M.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0107FCP-BSMTPAHU-0.1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0108FCP-BSMTPAHU-0.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0109FCP-BSMTPAHU-0.1 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0110FCP-2FPAHU-B1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0111FCP-2FPAHU-B1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0112FCP-2FPAHU-B1 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0113FCP-2FPAHU-B2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0114FCP-2FPAHU-B2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0115FCP-2FPAHU-B2 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0116FCP-2FPAHU-B3 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0117FCP-2FPAHU-B3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0118FCP-2FPAHU-B3 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0119FCP-2FPAHU-FR (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0120FCP-2FPAHU-FR (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0121FCP-2FPAHU-FR (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0122FCP-2FPAHU-PF (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0123FCP-2FPAHU-PF (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0124FCP-2FPAHU-PF (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0125FCP-RDPAHU-RD.1 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0126FCP-RDPAHU-RD.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0127FCP-RDPAHU-RD.1 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0128FCP-RDPAHU-RD.2 (BMS Contractor)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)30unverified
C0129FCP-RDPAHU-RD.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0130FCP-RDPAHU-RD.2 (ME Contractor)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)30unverified
C0131MCP-PLANTPCHW-1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0132MCP-PLANTPCHW-2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0133MCP-PLANTPCHW-3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0134MCP-PLANTPCHW-S (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0135MCP-PLANTPCOW-1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0136MCP-PLANTPCOW-2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0137MCP-PLANTPCOW-3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0138FCP-RDRP-HZ.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0139FCP-RDRP-HZ.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0140FCP-RDRP-HZ.3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0141FCP-BSMTRP-LZ.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0142FCP-BSMTRP-LZ.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0143FCP-BSMTRP-LZ.3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0144FCP-GFTEF-1.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0145FCP-GFTEF-1.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0146FCP-GFTEF-1.3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0147FCP-GFTEF-1.4 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0148FCP-2FTEF-2.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0149FCP-2FTEF-2.3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0150FCP-2FTEF-2B.3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0151FCP-3FTEF-3A.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0152FCP-3FTEF-3A.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0153FCP-3FTEF-3B.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0154FCP-3FTEF-3C.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0155FCP-3FTEF-3C.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0156FCP-3FTEF-3D.1 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0157FCP-3FTEF-3D.10 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0158FCP-3FTEF-3D.11 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0159FCP-3FTEF-3D.12 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0160FCP-3FTEF-3D.13 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0161FCP-3FTEF-3D.14 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0162FCP-3FTEF-3D.15 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0163FCP-3FTEF-3D.16 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0164FCP-3FTEF-3D.17 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0165FCP-3FTEF-3D.18 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0166FCP-3FTEF-3D.19 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0167FCP-3FTEF-3D.2 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0168FCP-3FTEF-3D.20 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0169FCP-3FTEF-3D.3 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0170FCP-3FTEF-3D.4 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0171FCP-3FTEF-3D.5 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0172FCP-3FTEF-3D.6 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0173FCP-3FTEF-3D.7 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0174FCP-3FTEF-3D.8 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0175FCP-3FTEF-3D.9 (Equipment Supplier)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)30unverified
C0176FCP-BSMTPAHU-0.1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0177FCP-2FPAHU-B1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0178FCP-2FPAHU-B2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0179FCP-2FPAHU-B3 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0180FCP-2FPAHU-PF (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0181FCP-2FPAHU-FR (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0182FCP-2FDOAS-2M (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0183FCP-RDDOAS-RD.1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0184FCP-RDDOAS-RD.2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0185FCP-RDPAHU-RD.1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0186FCP-RDPAHU-RD.2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0187MCP-PLANTCH-1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0188MCP-PLANTCH-2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0189MCP-PLANTCH-3 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0190MCP-PLANTPM-MAIN (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0191MCP-PLANTPM-GEN (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0192MCP-PLANTPM-MCC-CHILLER (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0193MCP-PLANTPM-MCC-CT (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0194MCP-PLANTPM-MCC-BOILER (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0195MCP-PLANTPM-MCC-FIRE-PUMP (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0196MCP-PLANTPM-MCC-MDP-1 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0197MCP-PLANTPM-MCC-MDP-2 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
C0198MCP-PLANTPM-MCC-MDP-3 (Network)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)30unverified
T0199BMS Server Room (head-end)All BMS panels at 2nd FloorCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80unverified
T0200BMS Server Room (head-end)All BMS panels at 3rd FloorCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80unverified
T0201BMS Server Room (head-end)All BMS panels at BasementCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80unverified
T0202BMS Server Room (head-end)All BMS panels at GroundCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80unverified
T0203BMS Server Room (head-end)All BMS panels at Lower GroundCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80unverified
T0204BMS Server Room (head-end)All BMS panels at RoofdeckCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80unverified
T0205BMS Server Room (head-end)All BMS panel controllers (MS/TP daisy-chain or branched)BACnet MS/TP shielded twisted-pair trunk, 1pr × 22 AWG low-cap180unverified
P0206Local panelboard / EE-supplied feederFCP-2F — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30unverified
P0207Local panelboard / EE-supplied feederFCP-3F — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30unverified
P0208Local panelboard / EE-supplied feederFCP-BSMT — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30unverified
P0209Local panelboard / EE-supplied feederFCP-GF — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30unverified
P0210Local panelboard / EE-supplied feederFCP-RD — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30unverified
P0211Local panelboard / EE-supplied feederMCP-PLANT — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30unverified

Verification schema

How to record verification / corrections in A3-cable-schedule.yaml
Find the affected row in the YAML by ID (Detail sheet column A) and add a verification: block:
- id: C0001
from: PNL-CH-PLANT-GND
to: CH-1 (BMS Contractor)
cable_type: 4C × 1.5 mm² shielded FRLS
length_m: 30
verification: # ADDED by team
status: needs_correction # unverified | verified | needs_correction | uncertain
corrected_length_m: 42 # team's measured / confirmed value
verified_by: J. Cruz
verified_date: 2026-05-10
drawing_ref: "EE-09 grid B-2"
notes: ""
After saving, re-run: python3 _playbook/tools/generate-deliverables.py <project>
Corrections propagate to B4 manhours, BOQ, and final deliverables automatically.
Recommended verification methods (priority order):
1. Site walkthrough with measurement (most accurate; for cable lengths, after structural completion).
2. Properly-scaled architectural drawings.
3. Mechanical contractor's tray layout combined with BMS panel locations.
4. A-001 default with ±20% contingency in BOQ — last resort.