Summary

A3 — Cable Schedule Summary
Total field cable runs198
Total field cable length (m)5940
Total trunk cable length (m)660
Total power feed length (m)180
GRAND TOTAL cable length (m)6780
By cable type (m)
4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)2940
4C × 1.5 mm² shielded FRLS (BMS signal — sensors)1380
4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)870
Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)690
Modbus shielded twisted-pair, 1pr × 22 AWG (e.g., Belden 9841)60

Field Cables

IDFromToEquipment ClassSystemLocationCable TypeConductors RequiredConductors SpecifiedLength (m)I/O Points CarriedNotes
C0001FCP-GFAHU-1.1 (BMS Contractor)AHU (Chilled-Water-Served)ACGround Floor4C × 1.5 mm² shielded FRLS (BMS signal — sensors)783055 I/O points carried, 8C cable per A-001 (avg 30 m)
C0002FCP-GFAHU-1.1 (Equipment Supplier)AHU (Chilled-Water-Served)ACGround Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0003FCP-GFAHU-1.1 (ME Contractor)AHU (Chilled-Water-Served)ACGround Floor4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0004FCP-GFAHU-1.2 (BMS Contractor)AHU (Chilled-Water-Served)ACGround Floor4C × 1.5 mm² shielded FRLS (BMS signal — sensors)783055 I/O points carried, 8C cable per A-001 (avg 30 m)
C0005FCP-GFAHU-1.2 (Equipment Supplier)AHU (Chilled-Water-Served)ACGround Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0006FCP-GFAHU-1.2 (ME Contractor)AHU (Chilled-Water-Served)ACGround Floor4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0007FCP-GFAHU-1.3 (BMS Contractor)AHU (Chilled-Water-Served)ACGround Floor4C × 1.5 mm² shielded FRLS (BMS signal — sensors)783055 I/O points carried, 8C cable per A-001 (avg 30 m)
C0008FCP-GFAHU-1.3 (Equipment Supplier)AHU (Chilled-Water-Served)ACGround Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0009FCP-GFAHU-1.3 (ME Contractor)AHU (Chilled-Water-Served)ACGround Floor4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0010FCP-2FAHU-2M.1 (BMS Contractor)AHU (Modulating CHW-served)AC2nd Floor (Casino)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)10123088 I/O points carried, 12C cable per A-001 (avg 30 m)
C0011FCP-2FAHU-2M.1 (Equipment Supplier)AHU (Modulating CHW-served)AC2nd Floor (Casino)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0012FCP-2FAHU-2M.1 (ME Contractor)AHU (Modulating CHW-served)AC2nd Floor (Casino)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0013FCP-2FAHU-2M.2 (BMS Contractor)AHU (Modulating CHW-served)AC2nd Floor (Casino)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)10123088 I/O points carried, 12C cable per A-001 (avg 30 m)
C0014FCP-2FAHU-2M.2 (Equipment Supplier)AHU (Modulating CHW-served)AC2nd Floor (Casino)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0015FCP-2FAHU-2M.2 (ME Contractor)AHU (Modulating CHW-served)AC2nd Floor (Casino)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0016FCP-2FAHU-B.1 (BMS Contractor)AHU (Chilled-Water-Served)AC2nd Floor4C × 1.5 mm² shielded FRLS (BMS signal — sensors)783055 I/O points carried, 8C cable per A-001 (avg 30 m)
C0017FCP-2FAHU-B.1 (Equipment Supplier)AHU (Chilled-Water-Served)AC2nd Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0018FCP-2FAHU-B.1 (ME Contractor)AHU (Chilled-Water-Served)AC2nd Floor4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0019FCP-2FAHU-B.2 (BMS Contractor)AHU (Chilled-Water-Served)AC2nd Floor4C × 1.5 mm² shielded FRLS (BMS signal — sensors)783055 I/O points carried, 8C cable per A-001 (avg 30 m)
C0020FCP-2FAHU-B.2 (Equipment Supplier)AHU (Chilled-Water-Served)AC2nd Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0021FCP-2FAHU-B.2 (ME Contractor)AHU (Chilled-Water-Served)AC2nd Floor4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0022FCP-2FAHU-B.3 (BMS Contractor)AHU (Chilled-Water-Served)AC2nd Floor4C × 1.5 mm² shielded FRLS (BMS signal — sensors)783055 I/O points carried, 8C cable per A-001 (avg 30 m)
C0023FCP-2FAHU-B.3 (Equipment Supplier)AHU (Chilled-Water-Served)AC2nd Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0024FCP-2FAHU-B.3 (ME Contractor)AHU (Chilled-Water-Served)AC2nd Floor4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0025FCP-2FAHU-EL (BMS Contractor)AHU (Chilled-Water-Served)AC2nd Floor4C × 1.5 mm² shielded FRLS (BMS signal — sensors)783055 I/O points carried, 8C cable per A-001 (avg 30 m)
C0026FCP-2FAHU-EL (Equipment Supplier)AHU (Chilled-Water-Served)AC2nd Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0027FCP-2FAHU-EL (ME Contractor)AHU (Chilled-Water-Served)AC2nd Floor4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0028FCP-2FAHU-FR2 (BMS Contractor)AHU (Chilled-Water-Served)AC2nd Floor4C × 1.5 mm² shielded FRLS (BMS signal — sensors)783055 I/O points carried, 8C cable per A-001 (avg 30 m)
C0029FCP-2FAHU-FR2 (Equipment Supplier)AHU (Chilled-Water-Served)AC2nd Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0030FCP-2FAHU-FR2 (ME Contractor)AHU (Chilled-Water-Served)AC2nd Floor4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0031FCP-2FAHU-FR3 (BMS Contractor)AHU (Chilled-Water-Served)AC2nd Floor4C × 1.5 mm² shielded FRLS (BMS signal — sensors)783055 I/O points carried, 8C cable per A-001 (avg 30 m)
C0032FCP-2FAHU-FR3 (Equipment Supplier)AHU (Chilled-Water-Served)AC2nd Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0033FCP-2FAHU-FR3 (ME Contractor)AHU (Chilled-Water-Served)AC2nd Floor4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0034FCP-2FAHU-PF (BMS Contractor)AHU (Chilled-Water-Served)AC2nd Floor4C × 1.5 mm² shielded FRLS (BMS signal — sensors)783055 I/O points carried, 8C cable per A-001 (avg 30 m)
C0035FCP-2FAHU-PF (Equipment Supplier)AHU (Chilled-Water-Served)AC2nd Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0036FCP-2FAHU-PF (ME Contractor)AHU (Chilled-Water-Served)AC2nd Floor4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0037FCP-BSMTATS-1 (EE Contractor)Multifunction Power Meter (Main)EEBasement (Genset)Modbus shielded twisted-pair, 1pr × 22 AWG (e.g., Belden 9841)443022 I/O points carried, 4C cable per A-001 (avg 30 m)
C0038FCP-BSMTBLR-1 (BMS Contractor)Steam BoilerVENTLower Ground4C × 1.5 mm² shielded FRLS (BMS signal — sensors)883066 I/O points carried, 8C cable per A-001 (avg 30 m)
C0039FCP-BSMTBLR-1 (Equipment Supplier)Steam BoilerVENTLower Ground4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)1212301010 I/O points carried, 12C cable per A-001 (avg 30 m)
C0040FCP-BSMTBLR-2 (BMS Contractor)Steam BoilerVENTLower Ground4C × 1.5 mm² shielded FRLS (BMS signal — sensors)883066 I/O points carried, 8C cable per A-001 (avg 30 m)
C0041FCP-BSMTBLR-2 (Equipment Supplier)Steam BoilerVENTLower Ground4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)1212301010 I/O points carried, 12C cable per A-001 (avg 30 m)
C0042MCP-PLANTCH-1 (BMS Contractor)Chiller (Package Water-Cooled)AC2nd Floor (Plant Room)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)9123077 I/O points carried, 12C cable per A-001 (avg 30 m)
C0043MCP-PLANTCH-1 (ME Contractor)Chiller (Package Water-Cooled)AC2nd Floor (Plant Room)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0044MCP-PLANTCH-2 (BMS Contractor)Chiller (Package Water-Cooled)AC2nd Floor (Plant Room)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)9123077 I/O points carried, 12C cable per A-001 (avg 30 m)
C0045MCP-PLANTCH-2 (ME Contractor)Chiller (Package Water-Cooled)AC2nd Floor (Plant Room)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0046MCP-PLANTCH-3 (BMS Contractor)Chiller (Package Water-Cooled)AC2nd Floor (Plant Room)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)9123077 I/O points carried, 12C cable per A-001 (avg 30 m)
C0047MCP-PLANTCH-3 (ME Contractor)Chiller (Package Water-Cooled)AC2nd Floor (Plant Room)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0048MCP-PLANTCHW-BYPASS (BMS Contractor)CHW Bypass HeaderAC2nd Floor (Plant Room)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0049MCP-PLANTCHW-HDR-R (BMS Contractor)CHW Return Main HeaderAC2nd Floor (Plant Room)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)443022 I/O points carried, 4C cable per A-001 (avg 30 m)
C0050MCP-PLANTCHW-HDR-S (BMS Contractor)CHW Supply Main HeaderAC2nd Floor (Plant Room)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)443022 I/O points carried, 4C cable per A-001 (avg 30 m)
C0051FCP-RDCOW-HDR (BMS Contractor)Condenser Water HeaderACRoofdeck4C × 1.5 mm² shielded FRLS (BMS signal — sensors)443022 I/O points carried, 4C cable per A-001 (avg 30 m)
C0052FCP-RDCT-1 (BMS Contractor)Cooling TowerACRoofdeck4C × 1.5 mm² shielded FRLS (BMS signal — sensors)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0053FCP-RDCT-1 (Equipment Supplier)Cooling TowerACRoofdeck4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)443022 I/O points carried, 4C cable per A-001 (avg 30 m)
C0054FCP-RDCT-1 (ME Contractor)Cooling TowerACRoofdeck4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)443022 I/O points carried, 4C cable per A-001 (avg 30 m)
C0055FCP-RDCT-2 (BMS Contractor)Cooling TowerACRoofdeck4C × 1.5 mm² shielded FRLS (BMS signal — sensors)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0056FCP-RDCT-2 (Equipment Supplier)Cooling TowerACRoofdeck4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)443022 I/O points carried, 4C cable per A-001 (avg 30 m)
C0057FCP-RDCT-2 (ME Contractor)Cooling TowerACRoofdeck4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)443022 I/O points carried, 4C cable per A-001 (avg 30 m)
C0058FCP-RDCT-3 (BMS Contractor)Cooling TowerACRoofdeck4C × 1.5 mm² shielded FRLS (BMS signal — sensors)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0059FCP-RDCT-3 (Equipment Supplier)Cooling TowerACRoofdeck4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)443022 I/O points carried, 4C cable per A-001 (avg 30 m)
C0060FCP-RDCT-3 (ME Contractor)Cooling TowerACRoofdeck4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)443022 I/O points carried, 4C cable per A-001 (avg 30 m)
C0061FCP-RDCT-COMMON (BMS Contractor)Cooling Tower (Common)ACRoofdeck4C × 1.5 mm² shielded FRLS (BMS signal — sensors)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0062FCP-2FDOAS-2M (BMS Contractor)DOAS UnitVENT2nd Floor (Casino)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)883066 I/O points carried, 8C cable per A-001 (avg 30 m)
C0063FCP-2FDOAS-2M (Equipment Supplier)DOAS UnitVENT2nd Floor (Casino)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)1212301010 I/O points carried, 12C cable per A-001 (avg 30 m)
C0064FCP-2FDOAS-2M (ME Contractor)DOAS UnitVENT2nd Floor (Casino)4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0065FCP-RDDOAS-RD.1 (BMS Contractor)DOAS UnitVENTRoofdeck4C × 1.5 mm² shielded FRLS (BMS signal — sensors)883066 I/O points carried, 8C cable per A-001 (avg 30 m)
C0066FCP-RDDOAS-RD.1 (Equipment Supplier)DOAS UnitVENTRoofdeck4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)1212301010 I/O points carried, 12C cable per A-001 (avg 30 m)
C0067FCP-RDDOAS-RD.1 (ME Contractor)DOAS UnitVENTRoofdeck4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0068FCP-RDDOAS-RD.2 (BMS Contractor)DOAS UnitVENTRoofdeck4C × 1.5 mm² shielded FRLS (BMS signal — sensors)883066 I/O points carried, 8C cable per A-001 (avg 30 m)
C0069FCP-RDDOAS-RD.2 (Equipment Supplier)DOAS UnitVENTRoofdeck4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)1212301010 I/O points carried, 12C cable per A-001 (avg 30 m)
C0070FCP-RDDOAS-RD.2 (ME Contractor)DOAS UnitVENTRoofdeck4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0071FCP-GFEF-1.2A (Equipment Supplier)Exhaust Fan (General)VENTGround Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0072FCP-GFEF-1MR.1 (Equipment Supplier)Exhaust Fan (General)VENTGround Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0073FCP-GFEF-1ST0.1 (Equipment Supplier)Exhaust Fan (General)VENTGround Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0074FCP-2FEF-2.1 (Equipment Supplier)Exhaust Fan (General)VENT2nd Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0075FCP-2FEF-2.2 (Equipment Supplier)Exhaust Fan (General)VENT2nd Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0076FCP-2FEF-2.3 (Equipment Supplier)Exhaust Fan (General)VENT2nd Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0077FCP-2FEF-2.4 (Equipment Supplier)Exhaust Fan (General)VENT2nd Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0078FCP-2FEF-2B.1 (Equipment Supplier)Exhaust Fan (General)VENT2nd Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0079FCP-2FEF-2B.2 (Equipment Supplier)Exhaust Fan (General)VENT2nd Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0080FCP-3FEF-3GE.1 (Equipment Supplier)Exhaust Fan (General)VENT3rd Floor (Amenity)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0081FCP-3FEF-3GE.2 (Equipment Supplier)Exhaust Fan (General)VENT3rd Floor (Amenity)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0082FCP-2FEF-CHR.1 (Equipment Supplier)Exhaust Fan (General)VENT2nd Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0083FCP-2FEF-CHR.2 (Equipment Supplier)Exhaust Fan (General)VENT2nd Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0084FCP-2FEF-GS.1 (Equipment Supplier)Exhaust Fan (General)VENT2nd Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0085FCP-2FEF-GS.2 (Equipment Supplier)Exhaust Fan (General)VENT2nd Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0086FCP-GFEF-LPG.1 (Equipment Supplier)Exhaust Fan (General)VENTGround Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0087FCP-GFEF-MRF.1 (Equipment Supplier)Exhaust Fan (General)VENTGround Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0088FCP-BSMTGEN-1 (EE Contractor)Multifunction Power Meter (Main)EEBasement (Genset)Modbus shielded twisted-pair, 1pr × 22 AWG (e.g., Belden 9841)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0089FCP-RDHP-HZ.1 (Equipment Supplier)Heat PumpHWLRoofdeck4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0090FCP-RDHP-HZ.2 (Equipment Supplier)Heat PumpHWLRoofdeck4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0091FCP-RDHP-HZ.3 (Equipment Supplier)Heat PumpHWLRoofdeck4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0092FCP-BSMTHP-LZ.1 (Equipment Supplier)Heat PumpHWLLower Ground4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0093FCP-BSMTHP-LZ.2 (Equipment Supplier)Heat PumpHWLLower Ground4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0094FCP-BSMTHP-LZ.3 (Equipment Supplier)Heat PumpHWLLower Ground4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0095FCP-RDHW-HDR-HZ (BMS Contractor)Hot Water Header SetHWLRoofdeck4C × 1.5 mm² shielded FRLS (BMS signal — sensors)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0096FCP-BSMTHW-HDR-LZ (BMS Contractor)Hot Water Header SetHWLLower Ground4C × 1.5 mm² shielded FRLS (BMS signal — sensors)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0097FCP-RDHWT-HZ.1 (BMS Contractor)Calorifier (Hot Water Storage Tank)HWLRoofdeck4C × 1.5 mm² shielded FRLS (BMS signal — sensors)343011 I/O points carried, 4C cable per A-001 (avg 30 m)
C0098FCP-RDHWT-HZ.2 (BMS Contractor)Calorifier (Hot Water Storage Tank)HWLRoofdeck4C × 1.5 mm² shielded FRLS (BMS signal — sensors)343011 I/O points carried, 4C cable per A-001 (avg 30 m)
C0099FCP-RDHWT-HZ.3 (BMS Contractor)Calorifier (Hot Water Storage Tank)HWLRoofdeck4C × 1.5 mm² shielded FRLS (BMS signal — sensors)343011 I/O points carried, 4C cable per A-001 (avg 30 m)
C0100FCP-BSMTHWT-LZ.1 (BMS Contractor)Calorifier (Hot Water Storage Tank)HWLLower Ground4C × 1.5 mm² shielded FRLS (BMS signal — sensors)343011 I/O points carried, 4C cable per A-001 (avg 30 m)
C0101FCP-BSMTHWT-LZ.2 (BMS Contractor)Calorifier (Hot Water Storage Tank)HWLLower Ground4C × 1.5 mm² shielded FRLS (BMS signal — sensors)343011 I/O points carried, 4C cable per A-001 (avg 30 m)
C0102FCP-BSMTHWT-LZ.3 (BMS Contractor)Calorifier (Hot Water Storage Tank)HWLLower Ground4C × 1.5 mm² shielded FRLS (BMS signal — sensors)343011 I/O points carried, 4C cable per A-001 (avg 30 m)
C0103FCP-2FION-2M.1 (BMS Contractor)Ozone Generator (UV-light or Corona)AC2nd Floor (Casino)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)343011 I/O points carried, 4C cable per A-001 (avg 30 m)
C0104FCP-2FION-2M.1 (Equipment Supplier)Ozone Generator (UV-light or Corona)AC2nd Floor (Casino)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)443022 I/O points carried, 4C cable per A-001 (avg 30 m)
C0105FCP-2FION-2M.2 (BMS Contractor)Ozone Generator (UV-light or Corona)AC2nd Floor (Casino)4C × 1.5 mm² shielded FRLS (BMS signal — sensors)343011 I/O points carried, 4C cable per A-001 (avg 30 m)
C0106FCP-2FION-2M.2 (Equipment Supplier)Ozone Generator (UV-light or Corona)AC2nd Floor (Casino)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)443022 I/O points carried, 4C cable per A-001 (avg 30 m)
C0107FCP-BSMTPAHU-0.1 (BMS Contractor)Precooled Air Handling UnitVENTBasement4C × 1.5 mm² shielded FRLS (BMS signal — sensors)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0108FCP-BSMTPAHU-0.1 (Equipment Supplier)Precooled Air Handling UnitVENTBasement4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)783055 I/O points carried, 8C cable per A-001 (avg 30 m)
C0109FCP-BSMTPAHU-0.1 (ME Contractor)Precooled Air Handling UnitVENTBasement4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)443022 I/O points carried, 4C cable per A-001 (avg 30 m)
C0110FCP-2FPAHU-B1 (BMS Contractor)Precooled Air Handling UnitVENT2nd Floor4C × 1.5 mm² shielded FRLS (BMS signal — sensors)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0111FCP-2FPAHU-B1 (Equipment Supplier)Precooled Air Handling UnitVENT2nd Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)783055 I/O points carried, 8C cable per A-001 (avg 30 m)
C0112FCP-2FPAHU-B1 (ME Contractor)Precooled Air Handling UnitVENT2nd Floor4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)443022 I/O points carried, 4C cable per A-001 (avg 30 m)
C0113FCP-2FPAHU-B2 (BMS Contractor)Precooled Air Handling UnitVENT2nd Floor4C × 1.5 mm² shielded FRLS (BMS signal — sensors)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0114FCP-2FPAHU-B2 (Equipment Supplier)Precooled Air Handling UnitVENT2nd Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)783055 I/O points carried, 8C cable per A-001 (avg 30 m)
C0115FCP-2FPAHU-B2 (ME Contractor)Precooled Air Handling UnitVENT2nd Floor4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)443022 I/O points carried, 4C cable per A-001 (avg 30 m)
C0116FCP-2FPAHU-B3 (BMS Contractor)Precooled Air Handling UnitVENT2nd Floor4C × 1.5 mm² shielded FRLS (BMS signal — sensors)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0117FCP-2FPAHU-B3 (Equipment Supplier)Precooled Air Handling UnitVENT2nd Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)783055 I/O points carried, 8C cable per A-001 (avg 30 m)
C0118FCP-2FPAHU-B3 (ME Contractor)Precooled Air Handling UnitVENT2nd Floor4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)443022 I/O points carried, 4C cable per A-001 (avg 30 m)
C0119FCP-2FPAHU-FR (BMS Contractor)Precooled Air Handling UnitVENT2nd Floor4C × 1.5 mm² shielded FRLS (BMS signal — sensors)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0120FCP-2FPAHU-FR (Equipment Supplier)Precooled Air Handling UnitVENT2nd Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)783055 I/O points carried, 8C cable per A-001 (avg 30 m)
C0121FCP-2FPAHU-FR (ME Contractor)Precooled Air Handling UnitVENT2nd Floor4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)443022 I/O points carried, 4C cable per A-001 (avg 30 m)
C0122FCP-2FPAHU-PF (BMS Contractor)Precooled Air Handling UnitVENT2nd Floor4C × 1.5 mm² shielded FRLS (BMS signal — sensors)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0123FCP-2FPAHU-PF (Equipment Supplier)Precooled Air Handling UnitVENT2nd Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)783055 I/O points carried, 8C cable per A-001 (avg 30 m)
C0124FCP-2FPAHU-PF (ME Contractor)Precooled Air Handling UnitVENT2nd Floor4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)443022 I/O points carried, 4C cable per A-001 (avg 30 m)
C0125FCP-RDPAHU-RD.1 (BMS Contractor)Precooled Air Handling UnitVENTRoofdeck4C × 1.5 mm² shielded FRLS (BMS signal — sensors)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0126FCP-RDPAHU-RD.1 (Equipment Supplier)Precooled Air Handling UnitVENTRoofdeck4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)783055 I/O points carried, 8C cable per A-001 (avg 30 m)
C0127FCP-RDPAHU-RD.1 (ME Contractor)Precooled Air Handling UnitVENTRoofdeck4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)443022 I/O points carried, 4C cable per A-001 (avg 30 m)
C0128FCP-RDPAHU-RD.2 (BMS Contractor)Precooled Air Handling UnitVENTRoofdeck4C × 1.5 mm² shielded FRLS (BMS signal — sensors)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0129FCP-RDPAHU-RD.2 (Equipment Supplier)Precooled Air Handling UnitVENTRoofdeck4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)783055 I/O points carried, 8C cable per A-001 (avg 30 m)
C0130FCP-RDPAHU-RD.2 (ME Contractor)Precooled Air Handling UnitVENTRoofdeck4C × 1.5 mm² FRLS (ME-supplied valves/dampers — status + control)443022 I/O points carried, 4C cable per A-001 (avg 30 m)
C0131MCP-PLANTPCHW-1 (Equipment Supplier)Primary CHW PumpAC2nd Floor (Plant Room)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0132MCP-PLANTPCHW-2 (Equipment Supplier)Primary CHW PumpAC2nd Floor (Plant Room)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0133MCP-PLANTPCHW-3 (Equipment Supplier)Primary CHW PumpAC2nd Floor (Plant Room)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0134MCP-PLANTPCHW-S (Equipment Supplier)Primary CHW Pump (Standby)AC2nd Floor (Plant Room)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)663044 I/O points carried, 6C cable per A-001 (avg 30 m)
C0135MCP-PLANTPCOW-1 (Equipment Supplier)Condenser Water PumpAC2nd Floor (Plant Room)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0136MCP-PLANTPCOW-2 (Equipment Supplier)Condenser Water PumpAC2nd Floor (Plant Room)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0137MCP-PLANTPCOW-3 (Equipment Supplier)Condenser Water PumpAC2nd Floor (Plant Room)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0138FCP-RDRP-HZ.1 (Equipment Supplier)Recirculating PumpHWLRoofdeck4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0139FCP-RDRP-HZ.2 (Equipment Supplier)Recirculating PumpHWLRoofdeck4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0140FCP-RDRP-HZ.3 (Equipment Supplier)Recirculating PumpHWLRoofdeck4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0141FCP-BSMTRP-LZ.1 (Equipment Supplier)Recirculating PumpHWLLower Ground4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0142FCP-BSMTRP-LZ.2 (Equipment Supplier)Recirculating PumpHWLLower Ground4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0143FCP-BSMTRP-LZ.3 (Equipment Supplier)Recirculating PumpHWLLower Ground4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0144FCP-GFTEF-1.1 (Equipment Supplier)Exhaust Fan (Toilet)VENTGround Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0145FCP-GFTEF-1.2 (Equipment Supplier)Exhaust Fan (Toilet)VENTGround Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0146FCP-GFTEF-1.3 (Equipment Supplier)Exhaust Fan (Toilet)VENTGround Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0147FCP-GFTEF-1.4 (Equipment Supplier)Exhaust Fan (Toilet)VENTGround Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0148FCP-2FTEF-2.1 (Equipment Supplier)Exhaust Fan (Toilet)VENT2nd Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0149FCP-2FTEF-2.3 (Equipment Supplier)Exhaust Fan (Toilet)VENT2nd Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0150FCP-2FTEF-2B.3 (Equipment Supplier)Exhaust Fan (Toilet)VENT2nd Floor4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0151FCP-3FTEF-3A.1 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor (Amenity)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0152FCP-3FTEF-3A.2 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor (Amenity)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0153FCP-3FTEF-3B.1 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor (Amenity)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0154FCP-3FTEF-3C.1 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor (Amenity)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0155FCP-3FTEF-3C.2 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor (Amenity)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0156FCP-3FTEF-3D.1 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor (Guestroom)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0157FCP-3FTEF-3D.10 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor (Guestroom)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0158FCP-3FTEF-3D.11 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor (Guestroom)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0159FCP-3FTEF-3D.12 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor (Guestroom)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0160FCP-3FTEF-3D.13 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor (Guestroom)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0161FCP-3FTEF-3D.14 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor (Guestroom)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0162FCP-3FTEF-3D.15 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor (Guestroom)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0163FCP-3FTEF-3D.16 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor (Guestroom)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0164FCP-3FTEF-3D.17 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor (Guestroom)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0165FCP-3FTEF-3D.18 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor (Guestroom)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0166FCP-3FTEF-3D.19 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor (Guestroom)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0167FCP-3FTEF-3D.2 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor (Guestroom)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0168FCP-3FTEF-3D.20 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor (Guestroom)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0169FCP-3FTEF-3D.3 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor (Guestroom)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0170FCP-3FTEF-3D.4 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor (Guestroom)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0171FCP-3FTEF-3D.5 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor (Guestroom)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0172FCP-3FTEF-3D.6 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor (Guestroom)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0173FCP-3FTEF-3D.7 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor (Guestroom)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0174FCP-3FTEF-3D.8 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor (Guestroom)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0175FCP-3FTEF-3D.9 (Equipment Supplier)Exhaust Fan (Toilet)VENT3rd Floor (Guestroom)4C × 1.5 mm² FRLS (equipment aux contacts — status/HOA/trip)563033 I/O points carried, 6C cable per A-001 (avg 30 m)
C0176FCP-BSMTPAHU-0.1 (Network)Precooled Air Handling UnitVENTBasementCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link301BACnet/IP or Modbus TCP — Cat6 to equipment controller
C0177FCP-2FPAHU-B1 (Network)Precooled Air Handling UnitVENT2nd FloorCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link301BACnet/IP or Modbus TCP — Cat6 to equipment controller
C0178FCP-2FPAHU-B2 (Network)Precooled Air Handling UnitVENT2nd FloorCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link301BACnet/IP or Modbus TCP — Cat6 to equipment controller
C0179FCP-2FPAHU-B3 (Network)Precooled Air Handling UnitVENT2nd FloorCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link301BACnet/IP or Modbus TCP — Cat6 to equipment controller
C0180FCP-2FPAHU-PF (Network)Precooled Air Handling UnitVENT2nd FloorCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link301BACnet/IP or Modbus TCP — Cat6 to equipment controller
C0181FCP-2FPAHU-FR (Network)Precooled Air Handling UnitVENT2nd FloorCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link301BACnet/IP or Modbus TCP — Cat6 to equipment controller
C0182FCP-2FDOAS-2M (Network)DOAS UnitVENT2nd Floor (Casino)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link301BACnet/IP or Modbus TCP — Cat6 to equipment controller
C0183FCP-RDDOAS-RD.1 (Network)DOAS UnitVENTRoofdeckCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link301BACnet/IP or Modbus TCP — Cat6 to equipment controller
C0184FCP-RDDOAS-RD.2 (Network)DOAS UnitVENTRoofdeckCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link301BACnet/IP or Modbus TCP — Cat6 to equipment controller
C0185FCP-RDPAHU-RD.1 (Network)Precooled Air Handling UnitVENTRoofdeckCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link301BACnet/IP or Modbus TCP — Cat6 to equipment controller
C0186FCP-RDPAHU-RD.2 (Network)Precooled Air Handling UnitVENTRoofdeckCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link301BACnet/IP or Modbus TCP — Cat6 to equipment controller
C0187MCP-PLANTCH-1 (Network)Chiller (Package Water-Cooled)AC2nd Floor (Plant Room)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link301BACnet/IP or Modbus TCP — Cat6 to equipment controller
C0188MCP-PLANTCH-2 (Network)Chiller (Package Water-Cooled)AC2nd Floor (Plant Room)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link301BACnet/IP or Modbus TCP — Cat6 to equipment controller
C0189MCP-PLANTCH-3 (Network)Chiller (Package Water-Cooled)AC2nd Floor (Plant Room)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link301BACnet/IP or Modbus TCP — Cat6 to equipment controller
C0190MCP-PLANTPM-MAIN (Network)Multifunction Power Meter (Main)EE2nd Floor (Plant Room)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link301BACnet/IP or Modbus TCP — Cat6 to equipment controller
C0191MCP-PLANTPM-GEN (Network)Multifunction Power Meter (Main)EE2nd Floor (Plant Room)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link301BACnet/IP or Modbus TCP — Cat6 to equipment controller
C0192MCP-PLANTPM-MCC-CHILLER (Network)Multifunction Power Meter (Feeder)EE2nd Floor (Plant Room)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link301BACnet/IP or Modbus TCP — Cat6 to equipment controller
C0193MCP-PLANTPM-MCC-CT (Network)Multifunction Power Meter (Feeder)EE2nd Floor (Plant Room)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link301BACnet/IP or Modbus TCP — Cat6 to equipment controller
C0194MCP-PLANTPM-MCC-BOILER (Network)Multifunction Power Meter (Feeder)EE2nd Floor (Plant Room)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link301BACnet/IP or Modbus TCP — Cat6 to equipment controller
C0195MCP-PLANTPM-MCC-FIRE-PUMP (Network)Multifunction Power Meter (Feeder)EE2nd Floor (Plant Room)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link301BACnet/IP or Modbus TCP — Cat6 to equipment controller
C0196MCP-PLANTPM-MCC-MDP-1 (Network)Multifunction Power Meter (Feeder)EE2nd Floor (Plant Room)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link301BACnet/IP or Modbus TCP — Cat6 to equipment controller
C0197MCP-PLANTPM-MCC-MDP-2 (Network)Multifunction Power Meter (Feeder)EE2nd Floor (Plant Room)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link301BACnet/IP or Modbus TCP — Cat6 to equipment controller
C0198MCP-PLANTPM-MCC-MDP-3 (Network)Multifunction Power Meter (Feeder)EE2nd Floor (Plant Room)Cat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP)4P (8 wires)Cat6 patch + permanent link301BACnet/IP or Modbus TCP — Cat6 to equipment controller

Trunks

IDFromToCable TypeLength (m)Notes
T0199BMS Server Room (head-end)All BMS panels at 2nd FloorCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80Network trunk for 2nd Floor — fiber to floor switch + Cat6 distribution to floor's BMS panels
T0200BMS Server Room (head-end)All BMS panels at 3rd FloorCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80Network trunk for 3rd Floor — fiber to floor switch + Cat6 distribution to floor's BMS panels
T0201BMS Server Room (head-end)All BMS panels at BasementCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80Network trunk for Basement — fiber to floor switch + Cat6 distribution to floor's BMS panels
T0202BMS Server Room (head-end)All BMS panels at GroundCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80Network trunk for Ground — fiber to floor switch + Cat6 distribution to floor's BMS panels
T0203BMS Server Room (head-end)All BMS panels at Lower GroundCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80Network trunk for Lower Ground — fiber to floor switch + Cat6 distribution to floor's BMS panels
T0204BMS Server Room (head-end)All BMS panels at RoofdeckCat6 4P × 23 AWG U/UTP, FRLS jacket (BACnet/IP) — riser fiber + Cat6 trunk80Network trunk for Roofdeck — fiber to floor switch + Cat6 distribution to floor's BMS panels
T0205BMS Server Room (head-end)All BMS panel controllers (MS/TP daisy-chain or branched)BACnet MS/TP shielded twisted-pair trunk, 1pr × 22 AWG low-cap180MS/TP backbone interconnecting 6 BMS panels — refine after Q-008 layout review

Panel Power Feeds

IDFromToCable TypeLength (m)Notes
P0206Local panelboard / EE-supplied feederFCP-2F — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7)
P0207Local panelboard / EE-supplied feederFCP-3F — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7)
P0208Local panelboard / EE-supplied feederFCP-BSMT — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7)
P0209Local panelboard / EE-supplied feederFCP-GF — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7)
P0210Local panelboard / EE-supplied feederFCP-RD — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7)
P0211Local panelboard / EE-supplied feederMCP-PLANT — BMS panel 240V power feed3C × 2.5 mm² FRLS (240V single-phase BMS panel power feed)30240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7)