Summary

A2 — Equipment Takeoff Summary
Total instances125
By equipment class
Exhaust Fan (Toilet)32
Exhaust Fan (General)17
AHU (Chilled-Water-Served)10
Precooled Air Handling Unit8
Multifunction Power Meter (Feeder)7
Heat Pump6
Calorifier (Hot Water Storage Tank)6
Recirculating Pump6
Multifunction Power Meter (Main)4
Chiller (Package Water-Cooled)3
Cooling Tower3
DOAS Unit3
Primary CHW Pump3
Condenser Water Pump3
AHU (Modulating CHW-served)2
Steam Boiler2
Hot Water Header Set2
Ozone Generator (UV-light or Corona)2
CHW Bypass Header1
CHW Return Main Header1
CHW Supply Main Header1
Condenser Water Header1
Cooling Tower (Common)1
Primary CHW Pump (Standby)1
By location
2nd Floor25
2nd Floor (Plant Room)22
3rd Floor (Guestroom)20
Roofdeck19
Ground Floor12
Lower Ground12
3rd Floor (Amenity)7
2nd Floor (Casino)5
Basement (Genset)2
Basement1
By panel
FCP-2F30
FCP-3F27
MCP-PLANT22
FCP-RD19
FCP-BSMT15
FCP-GF12

Equipment Takeoff

IDEquipment ClassQuantityLocationSystemPanelPrimary C/OPhysical I/OHLI SubpointsNetwork DropsTotal I/OMake/Model AssumedNetwork TypeTypical SupplierNotes
AHU-1.1AHU (Chilled-Water-Served)1Ground FloorACFCP-GFEquipment Supplier122014Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-1.2AHU (Chilled-Water-Served)1Ground FloorACFCP-GFEquipment Supplier122014Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-1.3AHU (Chilled-Water-Served)1Ground FloorACFCP-GFEquipment Supplier122014Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-2M.1AHU (Modulating CHW-served)12nd Floor (Casino)ACFCP-2FBMS Contractor152017Modulating CHW-served AHU with VFD, modulating valve and dampers (position feedback)Hardwired (VFD via BACnet HLI)Mechanical contractorCasino-spec AHU — modulating actuators with position feedback; CO/CO2 monitoring at return duct.
AHU-2M.2AHU (Modulating CHW-served)12nd Floor (Casino)ACFCP-2FBMS Contractor152017Modulating CHW-served AHU with VFD, modulating valve and dampers (position feedback)Hardwired (VFD via BACnet HLI)Mechanical contractorCasino-spec AHU — modulating actuators with position feedback; CO/CO2 monitoring at return duct.
AHU-B.1AHU (Chilled-Water-Served)12nd FloorACFCP-2FEquipment Supplier122014Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-B.2AHU (Chilled-Water-Served)12nd FloorACFCP-2FEquipment Supplier122014Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-B.3AHU (Chilled-Water-Served)12nd FloorACFCP-2FEquipment Supplier122014Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-ELAHU (Chilled-Water-Served)12nd FloorACFCP-2FEquipment Supplier122014Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-FR2AHU (Chilled-Water-Served)12nd FloorACFCP-2FEquipment Supplier122014Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-FR3AHU (Chilled-Water-Served)12nd FloorACFCP-2FEquipment Supplier122014Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
AHU-PFAHU (Chilled-Water-Served)12nd FloorACFCP-2FEquipment Supplier122014Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampersHardwired (VFD via BACnet HLI)Mechanical contractorBMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
ATS-1Multifunction Power Meter (Main)1Basement (Genset)EEFCP-BSMTEE Contractor2002Multifunction power meter with Modbus output (Schneider PM-series, ABB M2M, Siemens SENTRON), main switchgear classModbus RTU/TCPBMS contractorMounted in main switchgear or on dedicated BMS-side panel.
BLR-1Steam Boiler1Lower GroundVENTFCP-BSMTEquipment Supplier160016Fire-tube steam boiler with multi-stage burner, fuel-oil fired (typical for hotel laundry)HardwiredMechanical contractor / Equipment supplierBMS supplies steam pressure, feedwater T, fluegas T+O2 sensors. Boiler equipment provides aux contacts for status/HOA/trip points.
BLR-2Steam Boiler1Lower GroundVENTFCP-BSMTEquipment Supplier160016Fire-tube steam boiler with multi-stage burner, fuel-oil fired (typical for hotel laundry)HardwiredMechanical contractor / Equipment supplierBMS supplies steam pressure, feedwater T, fluegas T+O2 sensors. Boiler equipment provides aux contacts for status/HOA/trip points.
CH-1Chiller (Package Water-Cooled)12nd Floor (Plant Room)ACMCP-PLANTEquipment Supplier1118130Tier-1 BACnet IP chiller (Trane/York/Carrier/Daikin), water-cooled centrifugal or screw, sized per design cooling loadBACnet/IPMechanical contractor / Equipment supplierBMS reads via chiller's native BACnet gateway. BMS supplies external T-sensors on entering/leaving CHW & CW pipes.
CH-2Chiller (Package Water-Cooled)12nd Floor (Plant Room)ACMCP-PLANTEquipment Supplier1118130Tier-1 BACnet IP chiller (Trane/York/Carrier/Daikin), water-cooled centrifugal or screw, sized per design cooling loadBACnet/IPMechanical contractor / Equipment supplierBMS reads via chiller's native BACnet gateway. BMS supplies external T-sensors on entering/leaving CHW & CW pipes.
CH-3Chiller (Package Water-Cooled)12nd Floor (Plant Room)ACMCP-PLANTEquipment Supplier1118130Tier-1 BACnet IP chiller (Trane/York/Carrier/Daikin), water-cooled centrifugal or screw, sized per design cooling loadBACnet/IPMechanical contractor / Equipment supplierBMS reads via chiller's native BACnet gateway. BMS supplies external T-sensors on entering/leaving CHW & CW pipes.
CHW-BYPASSCHW Bypass Header12nd Floor (Plant Room)ACMCP-PLANTBMS Contractor4004BMS dP/dT sensors + motorized bypass valve (BMS-supplied)HardwiredBMS contractorBMS controls bypass valve to maintain CHW differential.
CHW-HDR-RCHW Return Main Header12nd Floor (Plant Room)ACMCP-PLANTBMS Contractor2002BMS T+P sensors on CHW return manifoldHardwiredBMS contractorField instrumentation only.
CHW-HDR-SCHW Supply Main Header12nd Floor (Plant Room)ACMCP-PLANTBMS Contractor2002BMS T+P sensors on CHW supply manifoldHardwiredBMS contractorField instrumentation only.
COW-HDRCondenser Water Header1RoofdeckACFCP-RDBMS Contractor2002BMS T sensors on condenser water headers at roofdeckHardwiredBMS contractorField instrumentation only.
CT-1Cooling Tower1RoofdeckACFCP-RDBMS Contractor7007Induced-draft counterflow open cooling tower (Marley/BAC/EVAPCO), sized per condenser water flowHardwiredMechanical contractor / Equipment supplierBMS supplies basin level sensors and condenser water header T-sensors.
CT-2Cooling Tower1RoofdeckACFCP-RDBMS Contractor7007Induced-draft counterflow open cooling tower (Marley/BAC/EVAPCO), sized per condenser water flowHardwiredMechanical contractor / Equipment supplierBMS supplies basin level sensors and condenser water header T-sensors.
CT-3Cooling Tower1RoofdeckACFCP-RDBMS Contractor7007Induced-draft counterflow open cooling tower (Marley/BAC/EVAPCO), sized per condenser water flowHardwiredMechanical contractor / Equipment supplierBMS supplies basin level sensors and condenser water header T-sensors.
CT-COMMONCooling Tower (Common)1RoofdeckACFCP-RDBMS Contractor4004Common BMS sensors at cooling tower area (OA T/RH, condenser headers)HardwiredBMS contractorField instrumentation only — no equipment per se.
DOAS-2MDOAS Unit12nd Floor (Casino)VENTFCP-2FEquipment Supplier204125Dedicated Outdoor Air System with energy recovery wheel, supply + exhaust fans, CHW coilBACnet/IPMechanical contractor / Equipment supplierNative BACnet controller typical. BMS supplies external sensors (OA T/RH/Flow, indoor T/RH, exhaust T) and modulating valve actuator.
DOAS-RD.1DOAS Unit1RoofdeckVENTFCP-RDEquipment Supplier204125Dedicated Outdoor Air System with energy recovery wheel, supply + exhaust fans, CHW coilBACnet/IPMechanical contractor / Equipment supplierNative BACnet controller typical. BMS supplies external sensors (OA T/RH/Flow, indoor T/RH, exhaust T) and modulating valve actuator.
DOAS-RD.2DOAS Unit1RoofdeckVENTFCP-RDEquipment Supplier204125Dedicated Outdoor Air System with energy recovery wheel, supply + exhaust fans, CHW coilBACnet/IPMechanical contractor / Equipment supplierNative BACnet controller typical. BMS supplies external sensors (OA T/RH/Flow, indoor T/RH, exhaust T) and modulating valve actuator.
EF-1.2AExhaust Fan (General)1Ground FloorVENTFCP-GFEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-1MR.1Exhaust Fan (General)1Ground FloorVENTFCP-GFEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-1ST0.1Exhaust Fan (General)1Ground FloorVENTFCP-GFEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-2.1Exhaust Fan (General)12nd FloorVENTFCP-2FEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-2.2Exhaust Fan (General)12nd FloorVENTFCP-2FEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-2.3Exhaust Fan (General)12nd FloorVENTFCP-2FEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-2.4Exhaust Fan (General)12nd FloorVENTFCP-2FEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-2B.1Exhaust Fan (General)12nd FloorVENTFCP-2FEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-2B.2Exhaust Fan (General)12nd FloorVENTFCP-2FEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-3GE.1Exhaust Fan (General)13rd Floor (Amenity)VENTFCP-3FEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-3GE.2Exhaust Fan (General)13rd Floor (Amenity)VENTFCP-3FEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-CHR.1Exhaust Fan (General)12nd FloorVENTFCP-2FEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-CHR.2Exhaust Fan (General)12nd FloorVENTFCP-2FEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-GS.1Exhaust Fan (General)12nd FloorVENTFCP-2FEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-GS.2Exhaust Fan (General)12nd FloorVENTFCP-2FEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-LPG.1Exhaust Fan (General)1Ground FloorVENTFCP-GFEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
EF-MRF.1Exhaust Fan (General)1Ground FloorVENTFCP-GFEquipment Supplier3003Constant-speed in-line, ceiling, or roof-mounted general exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
GEN-1Multifunction Power Meter (Main)1Basement (Genset)EEFCP-BSMTEE Contractor3003Multifunction power meter with Modbus output (Schneider PM-series, ABB M2M, Siemens SENTRON), main switchgear classModbus RTU/TCPBMS contractorMounted in main switchgear or on dedicated BMS-side panel.
HP-HZ.1Heat Pump1RoofdeckHWLFCP-RDEquipment Supplier3003Air-source or water-source heat pump for hot water heatingHardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractor / Equipment supplierBMS reads pump status/HOA/trip via aux contacts.
HP-HZ.2Heat Pump1RoofdeckHWLFCP-RDEquipment Supplier3003Air-source or water-source heat pump for hot water heatingHardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractor / Equipment supplierBMS reads pump status/HOA/trip via aux contacts.
HP-HZ.3Heat Pump1RoofdeckHWLFCP-RDEquipment Supplier3003Air-source or water-source heat pump for hot water heatingHardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractor / Equipment supplierBMS reads pump status/HOA/trip via aux contacts.
HP-LZ.1Heat Pump1Lower GroundHWLFCP-BSMTEquipment Supplier3003Air-source or water-source heat pump for hot water heatingHardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractor / Equipment supplierBMS reads pump status/HOA/trip via aux contacts.
HP-LZ.2Heat Pump1Lower GroundHWLFCP-BSMTEquipment Supplier3003Air-source or water-source heat pump for hot water heatingHardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractor / Equipment supplierBMS reads pump status/HOA/trip via aux contacts.
HP-LZ.3Heat Pump1Lower GroundHWLFCP-BSMTEquipment Supplier3003Air-source or water-source heat pump for hot water heatingHardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractor / Equipment supplierBMS reads pump status/HOA/trip via aux contacts.
HW-HDR-HZHot Water Header Set1RoofdeckHWLFCP-RDBMS Contractor3003Hot water supply/return manifolds with BMS T sensors and make-up cold water T sensorHardwiredBMS contractorField instrumentation on existing piping.
HW-HDR-LZHot Water Header Set1Lower GroundHWLFCP-BSMTBMS Contractor3003Hot water supply/return manifolds with BMS T sensors and make-up cold water T sensorHardwiredBMS contractorField instrumentation on existing piping.
HWT-HZ.1Calorifier (Hot Water Storage Tank)1RoofdeckHWLFCP-RDBMS Contractor1001Pressurised hot-water storage tank with internal coil, sized per design hot water demandHardwiredPlumbing contractorBMS supplies tank temperature sensor (immersion or strapped probe).
HWT-HZ.2Calorifier (Hot Water Storage Tank)1RoofdeckHWLFCP-RDBMS Contractor1001Pressurised hot-water storage tank with internal coil, sized per design hot water demandHardwiredPlumbing contractorBMS supplies tank temperature sensor (immersion or strapped probe).
HWT-HZ.3Calorifier (Hot Water Storage Tank)1RoofdeckHWLFCP-RDBMS Contractor1001Pressurised hot-water storage tank with internal coil, sized per design hot water demandHardwiredPlumbing contractorBMS supplies tank temperature sensor (immersion or strapped probe).
HWT-LZ.1Calorifier (Hot Water Storage Tank)1Lower GroundHWLFCP-BSMTBMS Contractor1001Pressurised hot-water storage tank with internal coil, sized per design hot water demandHardwiredPlumbing contractorBMS supplies tank temperature sensor (immersion or strapped probe).
HWT-LZ.2Calorifier (Hot Water Storage Tank)1Lower GroundHWLFCP-BSMTBMS Contractor1001Pressurised hot-water storage tank with internal coil, sized per design hot water demandHardwiredPlumbing contractorBMS supplies tank temperature sensor (immersion or strapped probe).
HWT-LZ.3Calorifier (Hot Water Storage Tank)1Lower GroundHWLFCP-BSMTBMS Contractor1001Pressurised hot-water storage tank with internal coil, sized per design hot water demandHardwiredPlumbing contractorBMS supplies tank temperature sensor (immersion or strapped probe).
ION-2M.1Ozone Generator (UV-light or Corona)12nd Floor (Casino)ACFCP-2FEquipment Supplier3003UV-light or corona-discharge ozone generator (paired with Casino AHU)HardwiredEquipment supplierCasino-specific air-treatment device. BMS monitors status/trip and reads VOC sensor (BMS-supplied).
ION-2M.2Ozone Generator (UV-light or Corona)12nd Floor (Casino)ACFCP-2FEquipment Supplier3003UV-light or corona-discharge ozone generator (paired with Casino AHU)HardwiredEquipment supplierCasino-specific air-treatment device. BMS monitors status/trip and reads VOC sensor (BMS-supplied).
PAHU-0.1Precooled Air Handling Unit1BasementVENTFCP-BSMTEquipment Supplier112114Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust pathHardwired (VFD via BACnet HLI)Mechanical contractor / Equipment supplierPrecool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors.
PAHU-B1Precooled Air Handling Unit12nd FloorVENTFCP-2FEquipment Supplier112114Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust pathHardwired (VFD via BACnet HLI)Mechanical contractor / Equipment supplierPrecool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors.
PAHU-B2Precooled Air Handling Unit12nd FloorVENTFCP-2FEquipment Supplier112114Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust pathHardwired (VFD via BACnet HLI)Mechanical contractor / Equipment supplierPrecool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors.
PAHU-B3Precooled Air Handling Unit12nd FloorVENTFCP-2FEquipment Supplier112114Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust pathHardwired (VFD via BACnet HLI)Mechanical contractor / Equipment supplierPrecool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors.
PAHU-FRPrecooled Air Handling Unit12nd FloorVENTFCP-2FEquipment Supplier112114Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust pathHardwired (VFD via BACnet HLI)Mechanical contractor / Equipment supplierPrecool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors.
PAHU-PFPrecooled Air Handling Unit12nd FloorVENTFCP-2FEquipment Supplier112114Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust pathHardwired (VFD via BACnet HLI)Mechanical contractor / Equipment supplierPrecool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors.
PAHU-RD.1Precooled Air Handling Unit1RoofdeckVENTFCP-RDEquipment Supplier112114Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust pathHardwired (VFD via BACnet HLI)Mechanical contractor / Equipment supplierPrecool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors.
PAHU-RD.2Precooled Air Handling Unit1RoofdeckVENTFCP-RDEquipment Supplier112114Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust pathHardwired (VFD via BACnet HLI)Mechanical contractor / Equipment supplierPrecool function: cools outdoor air before it's distributed to other systems. BMS supplies OA/supply T sensors.
PCHW-1Primary CHW Pump12nd Floor (Plant Room)ACMCP-PLANTEquipment Supplier4105End-suction or split-case centrifugal with VFD, sized per design CHW flowHardwired (BMS reads VFD via BACnet HLI)Mechanical contractorVFD typically Equipment Supplier provided with BACnet card.
PCHW-2Primary CHW Pump12nd Floor (Plant Room)ACMCP-PLANTEquipment Supplier4105End-suction or split-case centrifugal with VFD, sized per design CHW flowHardwired (BMS reads VFD via BACnet HLI)Mechanical contractorVFD typically Equipment Supplier provided with BACnet card.
PCHW-3Primary CHW Pump12nd Floor (Plant Room)ACMCP-PLANTEquipment Supplier4105End-suction or split-case centrifugal with VFD, sized per design CHW flowHardwired (BMS reads VFD via BACnet HLI)Mechanical contractorVFD typically Equipment Supplier provided with BACnet card.
PCHW-SPrimary CHW Pump (Standby)12nd Floor (Plant Room)ACMCP-PLANTEquipment Supplier4105Same as Primary CHW Pump (1 standby for N+1 redundancy)Hardwired (BMS reads VFD via BACnet HLI)Mechanical contractorStandby unit per A-CHW-001.
PCOW-1Condenser Water Pump12nd Floor (Plant Room)ACMCP-PLANTEquipment Supplier3003End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious)HardwiredMechanical contractorBMS reads aux contacts; commands start via DO.
PCOW-2Condenser Water Pump12nd Floor (Plant Room)ACMCP-PLANTEquipment Supplier3003End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious)HardwiredMechanical contractorBMS reads aux contacts; commands start via DO.
PCOW-3Condenser Water Pump12nd Floor (Plant Room)ACMCP-PLANTEquipment Supplier3003End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious)HardwiredMechanical contractorBMS reads aux contacts; commands start via DO.
PM-GENMultifunction Power Meter (Main)12nd Floor (Plant Room)EEMCP-PLANTBMS Contractor0011Multifunction power meter with Modbus output (Schneider PM-series, ABB M2M, Siemens SENTRON), main switchgear classModbus RTU/TCPBMS contractorMounted in main switchgear or on dedicated BMS-side panel.
PM-MAINMultifunction Power Meter (Main)12nd Floor (Plant Room)EEMCP-PLANTBMS Contractor0011Multifunction power meter with Modbus output (Schneider PM-series, ABB M2M, Siemens SENTRON), main switchgear classModbus RTU/TCPBMS contractorMounted in main switchgear or on dedicated BMS-side panel.
PM-MCC-BOILERMultifunction Power Meter (Feeder)12nd Floor (Plant Room)EEMCP-PLANTBMS Contractor0011Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
PM-MCC-CHILLERMultifunction Power Meter (Feeder)12nd Floor (Plant Room)EEMCP-PLANTBMS Contractor0011Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
PM-MCC-CTMultifunction Power Meter (Feeder)12nd Floor (Plant Room)EEMCP-PLANTBMS Contractor0011Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
PM-MCC-FIRE-PUMPMultifunction Power Meter (Feeder)12nd Floor (Plant Room)EEMCP-PLANTBMS Contractor0011Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
PM-MCC-MDP-1Multifunction Power Meter (Feeder)12nd Floor (Plant Room)EEMCP-PLANTBMS Contractor0011Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
PM-MCC-MDP-2Multifunction Power Meter (Feeder)12nd Floor (Plant Room)EEMCP-PLANTBMS Contractor0011Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
PM-MCC-MDP-3Multifunction Power Meter (Feeder)12nd Floor (Plant Room)EEMCP-PLANTBMS Contractor0011Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)Modbus RTUBMS contractorDaisy-chained on Modbus bus(es) back to BMS gateway.
RP-HZ.1Recirculating Pump1RoofdeckHWLFCP-RDEquipment Supplier3003Hot water recirculating pump, fixed-speed (typical for hotwater systems)Hardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractorBMS reads aux contacts only.
RP-HZ.2Recirculating Pump1RoofdeckHWLFCP-RDEquipment Supplier3003Hot water recirculating pump, fixed-speed (typical for hotwater systems)Hardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractorBMS reads aux contacts only.
RP-HZ.3Recirculating Pump1RoofdeckHWLFCP-RDEquipment Supplier3003Hot water recirculating pump, fixed-speed (typical for hotwater systems)Hardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractorBMS reads aux contacts only.
RP-LZ.1Recirculating Pump1Lower GroundHWLFCP-BSMTEquipment Supplier3003Hot water recirculating pump, fixed-speed (typical for hotwater systems)Hardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractorBMS reads aux contacts only.
RP-LZ.2Recirculating Pump1Lower GroundHWLFCP-BSMTEquipment Supplier3003Hot water recirculating pump, fixed-speed (typical for hotwater systems)Hardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractorBMS reads aux contacts only.
RP-LZ.3Recirculating Pump1Lower GroundHWLFCP-BSMTEquipment Supplier3003Hot water recirculating pump, fixed-speed (typical for hotwater systems)Hardwired (LZ) or HLI (HZ — per A-PL-001)Plumbing contractorBMS reads aux contacts only.
TEF-1.1Exhaust Fan (Toilet)1Ground FloorVENTFCP-GFEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-1.2Exhaust Fan (Toilet)1Ground FloorVENTFCP-GFEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-1.3Exhaust Fan (Toilet)1Ground FloorVENTFCP-GFEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-1.4Exhaust Fan (Toilet)1Ground FloorVENTFCP-GFEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-2.1Exhaust Fan (Toilet)12nd FloorVENTFCP-2FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-2.3Exhaust Fan (Toilet)12nd FloorVENTFCP-2FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-2B.3Exhaust Fan (Toilet)12nd FloorVENTFCP-2FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3A.1Exhaust Fan (Toilet)13rd Floor (Amenity)VENTFCP-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3A.2Exhaust Fan (Toilet)13rd Floor (Amenity)VENTFCP-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3B.1Exhaust Fan (Toilet)13rd Floor (Amenity)VENTFCP-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3C.1Exhaust Fan (Toilet)13rd Floor (Amenity)VENTFCP-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3C.2Exhaust Fan (Toilet)13rd Floor (Amenity)VENTFCP-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.1Exhaust Fan (Toilet)13rd Floor (Guestroom)VENTFCP-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.10Exhaust Fan (Toilet)13rd Floor (Guestroom)VENTFCP-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.11Exhaust Fan (Toilet)13rd Floor (Guestroom)VENTFCP-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.12Exhaust Fan (Toilet)13rd Floor (Guestroom)VENTFCP-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.13Exhaust Fan (Toilet)13rd Floor (Guestroom)VENTFCP-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.14Exhaust Fan (Toilet)13rd Floor (Guestroom)VENTFCP-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.15Exhaust Fan (Toilet)13rd Floor (Guestroom)VENTFCP-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.16Exhaust Fan (Toilet)13rd Floor (Guestroom)VENTFCP-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.17Exhaust Fan (Toilet)13rd Floor (Guestroom)VENTFCP-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.18Exhaust Fan (Toilet)13rd Floor (Guestroom)VENTFCP-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.19Exhaust Fan (Toilet)13rd Floor (Guestroom)VENTFCP-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.2Exhaust Fan (Toilet)13rd Floor (Guestroom)VENTFCP-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.20Exhaust Fan (Toilet)13rd Floor (Guestroom)VENTFCP-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.3Exhaust Fan (Toilet)13rd Floor (Guestroom)VENTFCP-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.4Exhaust Fan (Toilet)13rd Floor (Guestroom)VENTFCP-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.5Exhaust Fan (Toilet)13rd Floor (Guestroom)VENTFCP-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.6Exhaust Fan (Toilet)13rd Floor (Guestroom)VENTFCP-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.7Exhaust Fan (Toilet)13rd Floor (Guestroom)VENTFCP-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.8Exhaust Fan (Toilet)13rd Floor (Guestroom)VENTFCP-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.
TEF-3D.9Exhaust Fan (Toilet)13rd Floor (Guestroom)VENTFCP-3FEquipment Supplier3003Constant-speed in-line or roof-mounted toilet exhaust fanHardwiredMechanical contractorBMS reads aux contacts only — no control points.