Summary

A1 — Consolidated I/O List Summary
ProjectKingsford Hotel Bacolod — BMS Rehabilitation (A/B run)
Total I/O rows762
By type
DI381
AI184
HLI110
AO64
Network23
By C/O
Equipment Supplier469
BMS Contractor206
ME Contractor82
EE Contractor5
By system
VENT366
AC334
HWL48
EE14
By panel
FCP-2F272
MCP-PLANT136
FCP-RD129
FCP-3F81
FCP-BSMT75
FCP-GF69

All IO Points

IDSystemEquipment ClassEquipment InstanceLocationPoint DescriptionTypeField DeviceC/ODoO RefPanelSourceNotes
P0001ACAHU (Chilled-Water-Served)AHU-1.1Ground FloorIndoor Return Air Damper StatusDIDamper ControllerME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0002ACAHU (Chilled-Water-Served)AHU-1.1Ground FloorIndoor Return Air Damper ControlAODamper ControllerME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0003ACAHU (Chilled-Water-Served)AHU-1.1Ground FloorIndoor Return Air CO2AICO2 SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0004ACAHU (Chilled-Water-Served)AHU-1.1Ground FloorIndoor Return Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0005ACAHU (Chilled-Water-Served)AHU-1.1Ground FloorCHWS Valve ControlAOElectric Valve ActuatorME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0006ACAHU (Chilled-Water-Served)AHU-1.1Ground FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0007ACAHU (Chilled-Water-Served)AHU-1.1Ground FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0008ACAHU (Chilled-Water-Served)AHU-1.1Ground FloorFan VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0009ACAHU (Chilled-Water-Served)AHU-1.1Ground FloorFan ControlHLIVFDEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0010ACAHU (Chilled-Water-Served)AHU-1.1Ground FloorIndoor Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0011ACAHU (Chilled-Water-Served)AHU-1.1Ground FloorIndoor Mixed Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0012ACAHU (Chilled-Water-Served)AHU-1.1Ground FloorOutdoor Damper StatusDIDamper ControllerEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0013ACAHU (Chilled-Water-Served)AHU-1.1Ground FloorOutdoor Damper ControlAODamper ControllerEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0014ACAHU (Chilled-Water-Served)AHU-1.1Ground FloorOutside Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0015ACAHU (Chilled-Water-Served)AHU-1.2Ground FloorIndoor Return Air Damper StatusDIDamper ControllerME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0016ACAHU (Chilled-Water-Served)AHU-1.2Ground FloorIndoor Return Air Damper ControlAODamper ControllerME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0017ACAHU (Chilled-Water-Served)AHU-1.2Ground FloorIndoor Return Air CO2AICO2 SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0018ACAHU (Chilled-Water-Served)AHU-1.2Ground FloorIndoor Return Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0019ACAHU (Chilled-Water-Served)AHU-1.2Ground FloorCHWS Valve ControlAOElectric Valve ActuatorME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0020ACAHU (Chilled-Water-Served)AHU-1.2Ground FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0021ACAHU (Chilled-Water-Served)AHU-1.2Ground FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0022ACAHU (Chilled-Water-Served)AHU-1.2Ground FloorFan VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0023ACAHU (Chilled-Water-Served)AHU-1.2Ground FloorFan ControlHLIVFDEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0024ACAHU (Chilled-Water-Served)AHU-1.2Ground FloorIndoor Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0025ACAHU (Chilled-Water-Served)AHU-1.2Ground FloorIndoor Mixed Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0026ACAHU (Chilled-Water-Served)AHU-1.2Ground FloorOutdoor Damper StatusDIDamper ControllerEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0027ACAHU (Chilled-Water-Served)AHU-1.2Ground FloorOutdoor Damper ControlAODamper ControllerEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0028ACAHU (Chilled-Water-Served)AHU-1.2Ground FloorOutside Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0029ACAHU (Chilled-Water-Served)AHU-1.3Ground FloorIndoor Return Air Damper StatusDIDamper ControllerME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0030ACAHU (Chilled-Water-Served)AHU-1.3Ground FloorIndoor Return Air Damper ControlAODamper ControllerME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0031ACAHU (Chilled-Water-Served)AHU-1.3Ground FloorIndoor Return Air CO2AICO2 SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0032ACAHU (Chilled-Water-Served)AHU-1.3Ground FloorIndoor Return Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0033ACAHU (Chilled-Water-Served)AHU-1.3Ground FloorCHWS Valve ControlAOElectric Valve ActuatorME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0034ACAHU (Chilled-Water-Served)AHU-1.3Ground FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0035ACAHU (Chilled-Water-Served)AHU-1.3Ground FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0036ACAHU (Chilled-Water-Served)AHU-1.3Ground FloorFan VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0037ACAHU (Chilled-Water-Served)AHU-1.3Ground FloorFan ControlHLIVFDEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0038ACAHU (Chilled-Water-Served)AHU-1.3Ground FloorIndoor Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0039ACAHU (Chilled-Water-Served)AHU-1.3Ground FloorIndoor Mixed Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0040ACAHU (Chilled-Water-Served)AHU-1.3Ground FloorOutdoor Damper StatusDIDamper ControllerEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0041ACAHU (Chilled-Water-Served)AHU-1.3Ground FloorOutdoor Damper ControlAODamper ControllerEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0042ACAHU (Chilled-Water-Served)AHU-1.3Ground FloorOutside Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0043ACAHU (Chilled-Water-Served)AHU-B.12nd FloorIndoor Return Air Damper StatusDIDamper ControllerME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0044ACAHU (Chilled-Water-Served)AHU-B.12nd FloorIndoor Return Air Damper ControlAODamper ControllerME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0045ACAHU (Chilled-Water-Served)AHU-B.12nd FloorIndoor Return Air CO2AICO2 SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0046ACAHU (Chilled-Water-Served)AHU-B.12nd FloorIndoor Return Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0047ACAHU (Chilled-Water-Served)AHU-B.12nd FloorCHWS Valve ControlAOElectric Valve ActuatorME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0048ACAHU (Chilled-Water-Served)AHU-B.12nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0049ACAHU (Chilled-Water-Served)AHU-B.12nd FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0050ACAHU (Chilled-Water-Served)AHU-B.12nd FloorFan VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0051ACAHU (Chilled-Water-Served)AHU-B.12nd FloorFan ControlHLIVFDEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0052ACAHU (Chilled-Water-Served)AHU-B.12nd FloorIndoor Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0053ACAHU (Chilled-Water-Served)AHU-B.12nd FloorIndoor Mixed Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0054ACAHU (Chilled-Water-Served)AHU-B.12nd FloorOutdoor Damper StatusDIDamper ControllerEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0055ACAHU (Chilled-Water-Served)AHU-B.12nd FloorOutdoor Damper ControlAODamper ControllerEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0056ACAHU (Chilled-Water-Served)AHU-B.12nd FloorOutside Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0057ACAHU (Chilled-Water-Served)AHU-B.22nd FloorIndoor Return Air Damper StatusDIDamper ControllerME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0058ACAHU (Chilled-Water-Served)AHU-B.22nd FloorIndoor Return Air Damper ControlAODamper ControllerME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0059ACAHU (Chilled-Water-Served)AHU-B.22nd FloorIndoor Return Air CO2AICO2 SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0060ACAHU (Chilled-Water-Served)AHU-B.22nd FloorIndoor Return Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0061ACAHU (Chilled-Water-Served)AHU-B.22nd FloorCHWS Valve ControlAOElectric Valve ActuatorME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0062ACAHU (Chilled-Water-Served)AHU-B.22nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0063ACAHU (Chilled-Water-Served)AHU-B.22nd FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0064ACAHU (Chilled-Water-Served)AHU-B.22nd FloorFan VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0065ACAHU (Chilled-Water-Served)AHU-B.22nd FloorFan ControlHLIVFDEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0066ACAHU (Chilled-Water-Served)AHU-B.22nd FloorIndoor Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0067ACAHU (Chilled-Water-Served)AHU-B.22nd FloorIndoor Mixed Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0068ACAHU (Chilled-Water-Served)AHU-B.22nd FloorOutdoor Damper StatusDIDamper ControllerEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0069ACAHU (Chilled-Water-Served)AHU-B.22nd FloorOutdoor Damper ControlAODamper ControllerEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0070ACAHU (Chilled-Water-Served)AHU-B.22nd FloorOutside Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0071ACAHU (Chilled-Water-Served)AHU-B.32nd FloorIndoor Return Air Damper StatusDIDamper ControllerME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0072ACAHU (Chilled-Water-Served)AHU-B.32nd FloorIndoor Return Air Damper ControlAODamper ControllerME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0073ACAHU (Chilled-Water-Served)AHU-B.32nd FloorIndoor Return Air CO2AICO2 SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0074ACAHU (Chilled-Water-Served)AHU-B.32nd FloorIndoor Return Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0075ACAHU (Chilled-Water-Served)AHU-B.32nd FloorCHWS Valve ControlAOElectric Valve ActuatorME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0076ACAHU (Chilled-Water-Served)AHU-B.32nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0077ACAHU (Chilled-Water-Served)AHU-B.32nd FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0078ACAHU (Chilled-Water-Served)AHU-B.32nd FloorFan VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0079ACAHU (Chilled-Water-Served)AHU-B.32nd FloorFan ControlHLIVFDEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0080ACAHU (Chilled-Water-Served)AHU-B.32nd FloorIndoor Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0081ACAHU (Chilled-Water-Served)AHU-B.32nd FloorIndoor Mixed Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0082ACAHU (Chilled-Water-Served)AHU-B.32nd FloorOutdoor Damper StatusDIDamper ControllerEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0083ACAHU (Chilled-Water-Served)AHU-B.32nd FloorOutdoor Damper ControlAODamper ControllerEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0084ACAHU (Chilled-Water-Served)AHU-B.32nd FloorOutside Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0085ACAHU (Chilled-Water-Served)AHU-PF2nd FloorIndoor Return Air Damper StatusDIDamper ControllerME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0086ACAHU (Chilled-Water-Served)AHU-PF2nd FloorIndoor Return Air Damper ControlAODamper ControllerME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0087ACAHU (Chilled-Water-Served)AHU-PF2nd FloorIndoor Return Air CO2AICO2 SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0088ACAHU (Chilled-Water-Served)AHU-PF2nd FloorIndoor Return Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0089ACAHU (Chilled-Water-Served)AHU-PF2nd FloorCHWS Valve ControlAOElectric Valve ActuatorME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0090ACAHU (Chilled-Water-Served)AHU-PF2nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0091ACAHU (Chilled-Water-Served)AHU-PF2nd FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0092ACAHU (Chilled-Water-Served)AHU-PF2nd FloorFan VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0093ACAHU (Chilled-Water-Served)AHU-PF2nd FloorFan ControlHLIVFDEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0094ACAHU (Chilled-Water-Served)AHU-PF2nd FloorIndoor Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0095ACAHU (Chilled-Water-Served)AHU-PF2nd FloorIndoor Mixed Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0096ACAHU (Chilled-Water-Served)AHU-PF2nd FloorOutdoor Damper StatusDIDamper ControllerEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0097ACAHU (Chilled-Water-Served)AHU-PF2nd FloorOutdoor Damper ControlAODamper ControllerEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0098ACAHU (Chilled-Water-Served)AHU-PF2nd FloorOutside Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0099ACAHU (Chilled-Water-Served)AHU-EL2nd FloorIndoor Return Air Damper StatusDIDamper ControllerME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0100ACAHU (Chilled-Water-Served)AHU-EL2nd FloorIndoor Return Air Damper ControlAODamper ControllerME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0101ACAHU (Chilled-Water-Served)AHU-EL2nd FloorIndoor Return Air CO2AICO2 SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0102ACAHU (Chilled-Water-Served)AHU-EL2nd FloorIndoor Return Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0103ACAHU (Chilled-Water-Served)AHU-EL2nd FloorCHWS Valve ControlAOElectric Valve ActuatorME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0104ACAHU (Chilled-Water-Served)AHU-EL2nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0105ACAHU (Chilled-Water-Served)AHU-EL2nd FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0106ACAHU (Chilled-Water-Served)AHU-EL2nd FloorFan VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0107ACAHU (Chilled-Water-Served)AHU-EL2nd FloorFan ControlHLIVFDEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0108ACAHU (Chilled-Water-Served)AHU-EL2nd FloorIndoor Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0109ACAHU (Chilled-Water-Served)AHU-EL2nd FloorIndoor Mixed Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0110ACAHU (Chilled-Water-Served)AHU-EL2nd FloorOutdoor Damper StatusDIDamper ControllerEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0111ACAHU (Chilled-Water-Served)AHU-EL2nd FloorOutdoor Damper ControlAODamper ControllerEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0112ACAHU (Chilled-Water-Served)AHU-EL2nd FloorOutside Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0113ACAHU (Chilled-Water-Served)AHU-FR22nd FloorIndoor Return Air Damper StatusDIDamper ControllerME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0114ACAHU (Chilled-Water-Served)AHU-FR22nd FloorIndoor Return Air Damper ControlAODamper ControllerME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0115ACAHU (Chilled-Water-Served)AHU-FR22nd FloorIndoor Return Air CO2AICO2 SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0116ACAHU (Chilled-Water-Served)AHU-FR22nd FloorIndoor Return Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0117ACAHU (Chilled-Water-Served)AHU-FR22nd FloorCHWS Valve ControlAOElectric Valve ActuatorME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0118ACAHU (Chilled-Water-Served)AHU-FR22nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0119ACAHU (Chilled-Water-Served)AHU-FR22nd FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0120ACAHU (Chilled-Water-Served)AHU-FR22nd FloorFan VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0121ACAHU (Chilled-Water-Served)AHU-FR22nd FloorFan ControlHLIVFDEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0122ACAHU (Chilled-Water-Served)AHU-FR22nd FloorIndoor Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0123ACAHU (Chilled-Water-Served)AHU-FR22nd FloorIndoor Mixed Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0124ACAHU (Chilled-Water-Served)AHU-FR22nd FloorOutdoor Damper StatusDIDamper ControllerEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0125ACAHU (Chilled-Water-Served)AHU-FR22nd FloorOutdoor Damper ControlAODamper ControllerEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0126ACAHU (Chilled-Water-Served)AHU-FR22nd FloorOutside Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0127ACAHU (Chilled-Water-Served)AHU-FR32nd FloorIndoor Return Air Damper StatusDIDamper ControllerME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0128ACAHU (Chilled-Water-Served)AHU-FR32nd FloorIndoor Return Air Damper ControlAODamper ControllerME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0129ACAHU (Chilled-Water-Served)AHU-FR32nd FloorIndoor Return Air CO2AICO2 SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0130ACAHU (Chilled-Water-Served)AHU-FR32nd FloorIndoor Return Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0131ACAHU (Chilled-Water-Served)AHU-FR32nd FloorCHWS Valve ControlAOElectric Valve ActuatorME ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0132ACAHU (Chilled-Water-Served)AHU-FR32nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0133ACAHU (Chilled-Water-Served)AHU-FR32nd FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0134ACAHU (Chilled-Water-Served)AHU-FR32nd FloorFan VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0135ACAHU (Chilled-Water-Served)AHU-FR32nd FloorFan ControlHLIVFDEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0136ACAHU (Chilled-Water-Served)AHU-FR32nd FloorIndoor Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0137ACAHU (Chilled-Water-Served)AHU-FR32nd FloorIndoor Mixed Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0138ACAHU (Chilled-Water-Served)AHU-FR32nd FloorOutdoor Damper StatusDIDamper ControllerEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0139ACAHU (Chilled-Water-Served)AHU-FR32nd FloorOutdoor Damper ControlAODamper ControllerEquipment SupplierDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0140ACAHU (Chilled-Water-Served)AHU-FR32nd FloorOutside Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Chilled-Water-Served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0141VENTPrecooled Air Handling UnitPAHU-0.1BasementOutside Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0142VENTPrecooled Air Handling UnitPAHU-0.1BasementOutside Supply Air FlowAIFlow SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0143VENTPrecooled Air Handling UnitPAHU-0.1BasementOutdoor Supply Air HumidityAIHumidity SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0144VENTPrecooled Air Handling UnitPAHU-0.1BasementOutdoor Damper StatusDIDamper ControllerEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0145VENTPrecooled Air Handling UnitPAHU-0.1BasementOutdoor Damper ControlAODamper ControllerEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0146VENTPrecooled Air Handling UnitPAHU-0.1BasementCHWS Valve StatusDIElectric Valve ActuatorME ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0147VENTPrecooled Air Handling UnitPAHU-0.1BasementCHWS Valve ControlAOElectric Valve ActuatorME ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0148VENTPrecooled Air Handling UnitPAHU-0.1BasementFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0149VENTPrecooled Air Handling UnitPAHU-0.1BasementFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0150VENTPrecooled Air Handling UnitPAHU-0.1BasementFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0151VENTPrecooled Air Handling UnitPAHU-0.1BasementFan VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0152VENTPrecooled Air Handling UnitPAHU-0.1BasementFan ControlHLIVFDEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0153VENTPrecooled Air Handling UnitPAHU-0.1BasementIndoor Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0154VENTPrecooled Air Handling UnitPAHU-0.1BasementBACnet/IP dropNetworkRJ45 to edge switchBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0155VENTPrecooled Air Handling UnitPAHU-B12nd FloorOutside Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0156VENTPrecooled Air Handling UnitPAHU-B12nd FloorOutside Supply Air FlowAIFlow SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0157VENTPrecooled Air Handling UnitPAHU-B12nd FloorOutdoor Supply Air HumidityAIHumidity SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0158VENTPrecooled Air Handling UnitPAHU-B12nd FloorOutdoor Damper StatusDIDamper ControllerEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0159VENTPrecooled Air Handling UnitPAHU-B12nd FloorOutdoor Damper ControlAODamper ControllerEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0160VENTPrecooled Air Handling UnitPAHU-B12nd FloorCHWS Valve StatusDIElectric Valve ActuatorME ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0161VENTPrecooled Air Handling UnitPAHU-B12nd FloorCHWS Valve ControlAOElectric Valve ActuatorME ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0162VENTPrecooled Air Handling UnitPAHU-B12nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0163VENTPrecooled Air Handling UnitPAHU-B12nd FloorFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0164VENTPrecooled Air Handling UnitPAHU-B12nd FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0165VENTPrecooled Air Handling UnitPAHU-B12nd FloorFan VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0166VENTPrecooled Air Handling UnitPAHU-B12nd FloorFan ControlHLIVFDEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0167VENTPrecooled Air Handling UnitPAHU-B12nd FloorIndoor Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0168VENTPrecooled Air Handling UnitPAHU-B12nd FloorBACnet/IP dropNetworkRJ45 to edge switchBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0169VENTPrecooled Air Handling UnitPAHU-B22nd FloorOutside Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0170VENTPrecooled Air Handling UnitPAHU-B22nd FloorOutside Supply Air FlowAIFlow SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0171VENTPrecooled Air Handling UnitPAHU-B22nd FloorOutdoor Supply Air HumidityAIHumidity SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0172VENTPrecooled Air Handling UnitPAHU-B22nd FloorOutdoor Damper StatusDIDamper ControllerEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0173VENTPrecooled Air Handling UnitPAHU-B22nd FloorOutdoor Damper ControlAODamper ControllerEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0174VENTPrecooled Air Handling UnitPAHU-B22nd FloorCHWS Valve StatusDIElectric Valve ActuatorME ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0175VENTPrecooled Air Handling UnitPAHU-B22nd FloorCHWS Valve ControlAOElectric Valve ActuatorME ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0176VENTPrecooled Air Handling UnitPAHU-B22nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0177VENTPrecooled Air Handling UnitPAHU-B22nd FloorFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0178VENTPrecooled Air Handling UnitPAHU-B22nd FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0179VENTPrecooled Air Handling UnitPAHU-B22nd FloorFan VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0180VENTPrecooled Air Handling UnitPAHU-B22nd FloorFan ControlHLIVFDEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0181VENTPrecooled Air Handling UnitPAHU-B22nd FloorIndoor Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0182VENTPrecooled Air Handling UnitPAHU-B22nd FloorBACnet/IP dropNetworkRJ45 to edge switchBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0183VENTPrecooled Air Handling UnitPAHU-B32nd FloorOutside Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0184VENTPrecooled Air Handling UnitPAHU-B32nd FloorOutside Supply Air FlowAIFlow SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0185VENTPrecooled Air Handling UnitPAHU-B32nd FloorOutdoor Supply Air HumidityAIHumidity SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0186VENTPrecooled Air Handling UnitPAHU-B32nd FloorOutdoor Damper StatusDIDamper ControllerEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0187VENTPrecooled Air Handling UnitPAHU-B32nd FloorOutdoor Damper ControlAODamper ControllerEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0188VENTPrecooled Air Handling UnitPAHU-B32nd FloorCHWS Valve StatusDIElectric Valve ActuatorME ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0189VENTPrecooled Air Handling UnitPAHU-B32nd FloorCHWS Valve ControlAOElectric Valve ActuatorME ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0190VENTPrecooled Air Handling UnitPAHU-B32nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0191VENTPrecooled Air Handling UnitPAHU-B32nd FloorFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0192VENTPrecooled Air Handling UnitPAHU-B32nd FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0193VENTPrecooled Air Handling UnitPAHU-B32nd FloorFan VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0194VENTPrecooled Air Handling UnitPAHU-B32nd FloorFan ControlHLIVFDEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0195VENTPrecooled Air Handling UnitPAHU-B32nd FloorIndoor Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0196VENTPrecooled Air Handling UnitPAHU-B32nd FloorBACnet/IP dropNetworkRJ45 to edge switchBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0197VENTPrecooled Air Handling UnitPAHU-PF2nd FloorOutside Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0198VENTPrecooled Air Handling UnitPAHU-PF2nd FloorOutside Supply Air FlowAIFlow SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0199VENTPrecooled Air Handling UnitPAHU-PF2nd FloorOutdoor Supply Air HumidityAIHumidity SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0200VENTPrecooled Air Handling UnitPAHU-PF2nd FloorOutdoor Damper StatusDIDamper ControllerEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0201VENTPrecooled Air Handling UnitPAHU-PF2nd FloorOutdoor Damper ControlAODamper ControllerEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0202VENTPrecooled Air Handling UnitPAHU-PF2nd FloorCHWS Valve StatusDIElectric Valve ActuatorME ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0203VENTPrecooled Air Handling UnitPAHU-PF2nd FloorCHWS Valve ControlAOElectric Valve ActuatorME ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0204VENTPrecooled Air Handling UnitPAHU-PF2nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0205VENTPrecooled Air Handling UnitPAHU-PF2nd FloorFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0206VENTPrecooled Air Handling UnitPAHU-PF2nd FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0207VENTPrecooled Air Handling UnitPAHU-PF2nd FloorFan VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0208VENTPrecooled Air Handling UnitPAHU-PF2nd FloorFan ControlHLIVFDEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0209VENTPrecooled Air Handling UnitPAHU-PF2nd FloorIndoor Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0210VENTPrecooled Air Handling UnitPAHU-PF2nd FloorBACnet/IP dropNetworkRJ45 to edge switchBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0211VENTPrecooled Air Handling UnitPAHU-FR2nd FloorOutside Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0212VENTPrecooled Air Handling UnitPAHU-FR2nd FloorOutside Supply Air FlowAIFlow SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0213VENTPrecooled Air Handling UnitPAHU-FR2nd FloorOutdoor Supply Air HumidityAIHumidity SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0214VENTPrecooled Air Handling UnitPAHU-FR2nd FloorOutdoor Damper StatusDIDamper ControllerEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0215VENTPrecooled Air Handling UnitPAHU-FR2nd FloorOutdoor Damper ControlAODamper ControllerEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0216VENTPrecooled Air Handling UnitPAHU-FR2nd FloorCHWS Valve StatusDIElectric Valve ActuatorME ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0217VENTPrecooled Air Handling UnitPAHU-FR2nd FloorCHWS Valve ControlAOElectric Valve ActuatorME ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0218VENTPrecooled Air Handling UnitPAHU-FR2nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0219VENTPrecooled Air Handling UnitPAHU-FR2nd FloorFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0220VENTPrecooled Air Handling UnitPAHU-FR2nd FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0221VENTPrecooled Air Handling UnitPAHU-FR2nd FloorFan VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0222VENTPrecooled Air Handling UnitPAHU-FR2nd FloorFan ControlHLIVFDEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0223VENTPrecooled Air Handling UnitPAHU-FR2nd FloorIndoor Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0224VENTPrecooled Air Handling UnitPAHU-FR2nd FloorBACnet/IP dropNetworkRJ45 to edge switchBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0225ACAHU (Modulating CHW-served)AHU-2M.12nd Floor (Casino)Indoor Return Air Damper StatusDIDamper ControllerME ContractorDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0226ACAHU (Modulating CHW-served)AHU-2M.12nd Floor (Casino)Indoor Return Air Damper ControlAODamper ControllerME ContractorDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0227ACAHU (Modulating CHW-served)AHU-2M.12nd Floor (Casino)Indoor Return Air CO2AICO2 SensorBMS ContractorDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0228ACAHU (Modulating CHW-served)AHU-2M.12nd Floor (Casino)Indoor Return Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0229ACAHU (Modulating CHW-served)AHU-2M.12nd Floor (Casino)CHWS Valve ControlAOElectric Valve ActuatorME ContractorDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0230ACAHU (Modulating CHW-served)AHU-2M.12nd Floor (Casino)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0231ACAHU (Modulating CHW-served)AHU-2M.12nd Floor (Casino)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0232ACAHU (Modulating CHW-served)AHU-2M.12nd Floor (Casino)Fan VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0233ACAHU (Modulating CHW-served)AHU-2M.12nd Floor (Casino)Fan ControlHLIVFDEquipment SupplierDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0234ACAHU (Modulating CHW-served)AHU-2M.12nd Floor (Casino)Indoor Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0235ACAHU (Modulating CHW-served)AHU-2M.12nd Floor (Casino)Indoor Mixed Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0236ACAHU (Modulating CHW-served)AHU-2M.12nd Floor (Casino)Outdoor Damper StatusDIDamper ControllerEquipment SupplierDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0237ACAHU (Modulating CHW-served)AHU-2M.12nd Floor (Casino)Outdoor Damper ControlAODamper ControllerEquipment SupplierDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0238ACAHU (Modulating CHW-served)AHU-2M.12nd Floor (Casino)Outside Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0239ACAHU (Modulating CHW-served)AHU-2M.12nd Floor (Casino)Outdoor Air Humidity (Casino)AIHumidity SensorBMS ContractorDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0240ACAHU (Modulating CHW-served)AHU-2M.12nd Floor (Casino)Indoor Mixed Air HumidityAIHumidity SensorBMS ContractorDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0241ACAHU (Modulating CHW-served)AHU-2M.12nd Floor (Casino)Return Air CO sensor (Casino)AICO SensorBMS ContractorDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0242ACAHU (Modulating CHW-served)AHU-2M.22nd Floor (Casino)Indoor Return Air Damper StatusDIDamper ControllerME ContractorDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0243ACAHU (Modulating CHW-served)AHU-2M.22nd Floor (Casino)Indoor Return Air Damper ControlAODamper ControllerME ContractorDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0244ACAHU (Modulating CHW-served)AHU-2M.22nd Floor (Casino)Indoor Return Air CO2AICO2 SensorBMS ContractorDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0245ACAHU (Modulating CHW-served)AHU-2M.22nd Floor (Casino)Indoor Return Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0246ACAHU (Modulating CHW-served)AHU-2M.22nd Floor (Casino)CHWS Valve ControlAOElectric Valve ActuatorME ContractorDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0247ACAHU (Modulating CHW-served)AHU-2M.22nd Floor (Casino)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0248ACAHU (Modulating CHW-served)AHU-2M.22nd Floor (Casino)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0249ACAHU (Modulating CHW-served)AHU-2M.22nd Floor (Casino)Fan VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0250ACAHU (Modulating CHW-served)AHU-2M.22nd Floor (Casino)Fan ControlHLIVFDEquipment SupplierDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0251ACAHU (Modulating CHW-served)AHU-2M.22nd Floor (Casino)Indoor Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0252ACAHU (Modulating CHW-served)AHU-2M.22nd Floor (Casino)Indoor Mixed Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0253ACAHU (Modulating CHW-served)AHU-2M.22nd Floor (Casino)Outdoor Damper StatusDIDamper ControllerEquipment SupplierDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0254ACAHU (Modulating CHW-served)AHU-2M.22nd Floor (Casino)Outdoor Damper ControlAODamper ControllerEquipment SupplierDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0255ACAHU (Modulating CHW-served)AHU-2M.22nd Floor (Casino)Outside Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0256ACAHU (Modulating CHW-served)AHU-2M.22nd Floor (Casino)Outdoor Air Humidity (Casino)AIHumidity SensorBMS ContractorDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0257ACAHU (Modulating CHW-served)AHU-2M.22nd Floor (Casino)Indoor Mixed Air HumidityAIHumidity SensorBMS ContractorDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0258ACAHU (Modulating CHW-served)AHU-2M.22nd Floor (Casino)Return Air CO sensor (Casino)AICO SensorBMS ContractorDRC-004-2024 AC/AHU (Modulating CHW-served)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0259VENTDOAS UnitDOAS-2M2nd Floor (Casino)Outside Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/DOAS UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0260VENTDOAS UnitDOAS-2M2nd Floor (Casino)Outside Supply Air FlowAIFlow SensorBMS ContractorDRC-004-2024 VENT/DOAS UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0261VENTDOAS UnitDOAS-2M2nd Floor (Casino)Outdoor Supply Air HumidityAIHumidity SensorBMS ContractorDRC-004-2024 VENT/DOAS UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0262VENTDOAS UnitDOAS-2M2nd Floor (Casino)Outdoor Supply Air Motorized Damper StatusDIDamper ControllerME ContractorDRC-004-2024 VENT/DOAS UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0263VENTDOAS UnitDOAS-2M2nd Floor (Casino)Outdoor Supply Air Motorized Damper ControlAODamper ControllerME ContractorDRC-004-2024 VENT/DOAS UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0264VENTDOAS UnitDOAS-2M2nd Floor (Casino)Recovery Wheel Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0265VENTDOAS UnitDOAS-2M2nd Floor (Casino)Recovery Wheel Motor TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0266VENTDOAS UnitDOAS-2M2nd Floor (Casino)Supply Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0267VENTDOAS UnitDOAS-2M2nd Floor (Casino)Supply Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0268VENTDOAS UnitDOAS-2M2nd Floor (Casino)Supply Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0269VENTDOAS UnitDOAS-2M2nd Floor (Casino)Supply Fan VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0270VENTDOAS UnitDOAS-2M2nd Floor (Casino)Supply Fan ControlHLIVFDEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0271VENTDOAS UnitDOAS-2M2nd Floor (Casino)Indoor Mixed Air TemperatureAITemperature SensorEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0272VENTDOAS UnitDOAS-2M2nd Floor (Casino)Indoor Mixed Air HumidityAIHumidity SensorEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0273VENTDOAS UnitDOAS-2M2nd Floor (Casino)CHWS Cooling Coil Valve StatusDIElectric Valve ActuatorME ContractorDRC-004-2024 VENT/DOAS UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0274VENTDOAS UnitDOAS-2M2nd Floor (Casino)CHWS Valve ControlAOElectric Valve ActuatorME ContractorDRC-004-2024 VENT/DOAS UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0275VENTDOAS UnitDOAS-2M2nd Floor (Casino)Indoor Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/DOAS UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0276VENTDOAS UnitDOAS-2M2nd Floor (Casino)Indoor Exhaust Air HumidityAIHumidity SensorBMS ContractorDRC-004-2024 VENT/DOAS UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0277VENTDOAS UnitDOAS-2M2nd Floor (Casino)Indoor Exhaust Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/DOAS UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0278VENTDOAS UnitDOAS-2M2nd Floor (Casino)Exhaust Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0279VENTDOAS UnitDOAS-2M2nd Floor (Casino)Exhaust Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0280VENTDOAS UnitDOAS-2M2nd Floor (Casino)Exhaust Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0281VENTDOAS UnitDOAS-2M2nd Floor (Casino)Exhaust Fan VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0282VENTDOAS UnitDOAS-2M2nd Floor (Casino)Exhaust Fan ControlHLIVFDEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0283VENTDOAS UnitDOAS-2M2nd Floor (Casino)BACnet/IP dropNetworkRJ45 to edge switchBMS ContractorDRC-004-2024 VENT/DOAS UnitFCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0284VENTDOAS UnitDOAS-RD.1RoofdeckOutside Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0285VENTDOAS UnitDOAS-RD.1RoofdeckOutside Supply Air FlowAIFlow SensorBMS ContractorDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0286VENTDOAS UnitDOAS-RD.1RoofdeckOutdoor Supply Air HumidityAIHumidity SensorBMS ContractorDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0287VENTDOAS UnitDOAS-RD.1RoofdeckOutdoor Supply Air Motorized Damper StatusDIDamper ControllerME ContractorDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0288VENTDOAS UnitDOAS-RD.1RoofdeckOutdoor Supply Air Motorized Damper ControlAODamper ControllerME ContractorDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0289VENTDOAS UnitDOAS-RD.1RoofdeckRecovery Wheel Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0290VENTDOAS UnitDOAS-RD.1RoofdeckRecovery Wheel Motor TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0291VENTDOAS UnitDOAS-RD.1RoofdeckSupply Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0292VENTDOAS UnitDOAS-RD.1RoofdeckSupply Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0293VENTDOAS UnitDOAS-RD.1RoofdeckSupply Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0294VENTDOAS UnitDOAS-RD.1RoofdeckSupply Fan VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0295VENTDOAS UnitDOAS-RD.1RoofdeckSupply Fan ControlHLIVFDEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0296VENTDOAS UnitDOAS-RD.1RoofdeckIndoor Mixed Air TemperatureAITemperature SensorEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0297VENTDOAS UnitDOAS-RD.1RoofdeckIndoor Mixed Air HumidityAIHumidity SensorEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0298VENTDOAS UnitDOAS-RD.1RoofdeckCHWS Cooling Coil Valve StatusDIElectric Valve ActuatorME ContractorDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0299VENTDOAS UnitDOAS-RD.1RoofdeckCHWS Valve ControlAOElectric Valve ActuatorME ContractorDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0300VENTDOAS UnitDOAS-RD.1RoofdeckIndoor Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0301VENTDOAS UnitDOAS-RD.1RoofdeckIndoor Exhaust Air HumidityAIHumidity SensorBMS ContractorDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0302VENTDOAS UnitDOAS-RD.1RoofdeckIndoor Exhaust Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0303VENTDOAS UnitDOAS-RD.1RoofdeckExhaust Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0304VENTDOAS UnitDOAS-RD.1RoofdeckExhaust Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0305VENTDOAS UnitDOAS-RD.1RoofdeckExhaust Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0306VENTDOAS UnitDOAS-RD.1RoofdeckExhaust Fan VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0307VENTDOAS UnitDOAS-RD.1RoofdeckExhaust Fan ControlHLIVFDEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0308VENTDOAS UnitDOAS-RD.1RoofdeckBACnet/IP dropNetworkRJ45 to edge switchBMS ContractorDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0309VENTDOAS UnitDOAS-RD.2RoofdeckOutside Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0310VENTDOAS UnitDOAS-RD.2RoofdeckOutside Supply Air FlowAIFlow SensorBMS ContractorDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0311VENTDOAS UnitDOAS-RD.2RoofdeckOutdoor Supply Air HumidityAIHumidity SensorBMS ContractorDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0312VENTDOAS UnitDOAS-RD.2RoofdeckOutdoor Supply Air Motorized Damper StatusDIDamper ControllerME ContractorDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0313VENTDOAS UnitDOAS-RD.2RoofdeckOutdoor Supply Air Motorized Damper ControlAODamper ControllerME ContractorDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0314VENTDOAS UnitDOAS-RD.2RoofdeckRecovery Wheel Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0315VENTDOAS UnitDOAS-RD.2RoofdeckRecovery Wheel Motor TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0316VENTDOAS UnitDOAS-RD.2RoofdeckSupply Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0317VENTDOAS UnitDOAS-RD.2RoofdeckSupply Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0318VENTDOAS UnitDOAS-RD.2RoofdeckSupply Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0319VENTDOAS UnitDOAS-RD.2RoofdeckSupply Fan VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0320VENTDOAS UnitDOAS-RD.2RoofdeckSupply Fan ControlHLIVFDEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0321VENTDOAS UnitDOAS-RD.2RoofdeckIndoor Mixed Air TemperatureAITemperature SensorEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0322VENTDOAS UnitDOAS-RD.2RoofdeckIndoor Mixed Air HumidityAIHumidity SensorEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0323VENTDOAS UnitDOAS-RD.2RoofdeckCHWS Cooling Coil Valve StatusDIElectric Valve ActuatorME ContractorDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0324VENTDOAS UnitDOAS-RD.2RoofdeckCHWS Valve ControlAOElectric Valve ActuatorME ContractorDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0325VENTDOAS UnitDOAS-RD.2RoofdeckIndoor Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0326VENTDOAS UnitDOAS-RD.2RoofdeckIndoor Exhaust Air HumidityAIHumidity SensorBMS ContractorDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0327VENTDOAS UnitDOAS-RD.2RoofdeckIndoor Exhaust Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0328VENTDOAS UnitDOAS-RD.2RoofdeckExhaust Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0329VENTDOAS UnitDOAS-RD.2RoofdeckExhaust Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0330VENTDOAS UnitDOAS-RD.2RoofdeckExhaust Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0331VENTDOAS UnitDOAS-RD.2RoofdeckExhaust Fan VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0332VENTDOAS UnitDOAS-RD.2RoofdeckExhaust Fan ControlHLIVFDEquipment SupplierDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0333VENTDOAS UnitDOAS-RD.2RoofdeckBACnet/IP dropNetworkRJ45 to edge switchBMS ContractorDRC-004-2024 VENT/DOAS UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0334VENTPrecooled Air Handling UnitPAHU-RD.1RoofdeckOutside Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0335VENTPrecooled Air Handling UnitPAHU-RD.1RoofdeckOutside Supply Air FlowAIFlow SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0336VENTPrecooled Air Handling UnitPAHU-RD.1RoofdeckOutdoor Supply Air HumidityAIHumidity SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0337VENTPrecooled Air Handling UnitPAHU-RD.1RoofdeckOutdoor Damper StatusDIDamper ControllerEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0338VENTPrecooled Air Handling UnitPAHU-RD.1RoofdeckOutdoor Damper ControlAODamper ControllerEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0339VENTPrecooled Air Handling UnitPAHU-RD.1RoofdeckCHWS Valve StatusDIElectric Valve ActuatorME ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0340VENTPrecooled Air Handling UnitPAHU-RD.1RoofdeckCHWS Valve ControlAOElectric Valve ActuatorME ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0341VENTPrecooled Air Handling UnitPAHU-RD.1RoofdeckFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0342VENTPrecooled Air Handling UnitPAHU-RD.1RoofdeckFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0343VENTPrecooled Air Handling UnitPAHU-RD.1RoofdeckFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0344VENTPrecooled Air Handling UnitPAHU-RD.1RoofdeckFan VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0345VENTPrecooled Air Handling UnitPAHU-RD.1RoofdeckFan ControlHLIVFDEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0346VENTPrecooled Air Handling UnitPAHU-RD.1RoofdeckIndoor Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0347VENTPrecooled Air Handling UnitPAHU-RD.1RoofdeckBACnet/IP dropNetworkRJ45 to edge switchBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0348VENTPrecooled Air Handling UnitPAHU-RD.2RoofdeckOutside Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0349VENTPrecooled Air Handling UnitPAHU-RD.2RoofdeckOutside Supply Air FlowAIFlow SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0350VENTPrecooled Air Handling UnitPAHU-RD.2RoofdeckOutdoor Supply Air HumidityAIHumidity SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0351VENTPrecooled Air Handling UnitPAHU-RD.2RoofdeckOutdoor Damper StatusDIDamper ControllerEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0352VENTPrecooled Air Handling UnitPAHU-RD.2RoofdeckOutdoor Damper ControlAODamper ControllerEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0353VENTPrecooled Air Handling UnitPAHU-RD.2RoofdeckCHWS Valve StatusDIElectric Valve ActuatorME ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0354VENTPrecooled Air Handling UnitPAHU-RD.2RoofdeckCHWS Valve ControlAOElectric Valve ActuatorME ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0355VENTPrecooled Air Handling UnitPAHU-RD.2RoofdeckFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0356VENTPrecooled Air Handling UnitPAHU-RD.2RoofdeckFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0357VENTPrecooled Air Handling UnitPAHU-RD.2RoofdeckFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0358VENTPrecooled Air Handling UnitPAHU-RD.2RoofdeckFan VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0359VENTPrecooled Air Handling UnitPAHU-RD.2RoofdeckFan ControlHLIVFDEquipment SupplierDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0360VENTPrecooled Air Handling UnitPAHU-RD.2RoofdeckIndoor Supply Air TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0361VENTPrecooled Air Handling UnitPAHU-RD.2RoofdeckBACnet/IP dropNetworkRJ45 to edge switchBMS ContractorDRC-004-2024 VENT/Precooled Air Handling UnitFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0362ACOzone Generator (UV-light or Corona)ION-2M.12nd Floor (Casino)Equipment StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Ozone Generator (UV-light or Corona)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0363ACOzone Generator (UV-light or Corona)ION-2M.12nd Floor (Casino)Equipment TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Ozone Generator (UV-light or Corona)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0364ACOzone Generator (UV-light or Corona)ION-2M.12nd Floor (Casino)VOC MonitoringAIVOC SensorBMS ContractorDRC-004-2024 AC/Ozone Generator (UV-light or Corona)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0365ACOzone Generator (UV-light or Corona)ION-2M.22nd Floor (Casino)Equipment StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Ozone Generator (UV-light or Corona)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0366ACOzone Generator (UV-light or Corona)ION-2M.22nd Floor (Casino)Equipment TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Ozone Generator (UV-light or Corona)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0367ACOzone Generator (UV-light or Corona)ION-2M.22nd Floor (Casino)VOC MonitoringAIVOC SensorBMS ContractorDRC-004-2024 AC/Ozone Generator (UV-light or Corona)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0368VENTExhaust Fan (Toilet)TEF-1.1Ground FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0369VENTExhaust Fan (Toilet)TEF-1.1Ground FloorFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0370VENTExhaust Fan (Toilet)TEF-1.1Ground FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0371VENTExhaust Fan (Toilet)TEF-1.2Ground FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0372VENTExhaust Fan (Toilet)TEF-1.2Ground FloorFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0373VENTExhaust Fan (Toilet)TEF-1.2Ground FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0374VENTExhaust Fan (Toilet)TEF-1.3Ground FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0375VENTExhaust Fan (Toilet)TEF-1.3Ground FloorFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0376VENTExhaust Fan (Toilet)TEF-1.3Ground FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0377VENTExhaust Fan (Toilet)TEF-1.4Ground FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0378VENTExhaust Fan (Toilet)TEF-1.4Ground FloorFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0379VENTExhaust Fan (Toilet)TEF-1.4Ground FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0380VENTExhaust Fan (General)EF-1.2AGround FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0381VENTExhaust Fan (General)EF-1.2AGround FloorFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0382VENTExhaust Fan (General)EF-1.2AGround FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0383VENTExhaust Fan (General)EF-LPG.1Ground FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0384VENTExhaust Fan (General)EF-LPG.1Ground FloorFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0385VENTExhaust Fan (General)EF-LPG.1Ground FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0386VENTExhaust Fan (General)EF-1MR.1Ground FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0387VENTExhaust Fan (General)EF-1MR.1Ground FloorFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0388VENTExhaust Fan (General)EF-1MR.1Ground FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0389VENTExhaust Fan (General)EF-1ST0.1Ground FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0390VENTExhaust Fan (General)EF-1ST0.1Ground FloorFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0391VENTExhaust Fan (General)EF-1ST0.1Ground FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0392VENTExhaust Fan (General)EF-MRF.1Ground FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0393VENTExhaust Fan (General)EF-MRF.1Ground FloorFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0394VENTExhaust Fan (General)EF-MRF.1Ground FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-GFSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0395VENTExhaust Fan (Toilet)TEF-2.12nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0396VENTExhaust Fan (Toilet)TEF-2.12nd FloorFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0397VENTExhaust Fan (Toilet)TEF-2.12nd FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0398VENTExhaust Fan (Toilet)TEF-2.32nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0399VENTExhaust Fan (Toilet)TEF-2.32nd FloorFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0400VENTExhaust Fan (Toilet)TEF-2.32nd FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0401VENTExhaust Fan (Toilet)TEF-2B.32nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0402VENTExhaust Fan (Toilet)TEF-2B.32nd FloorFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0403VENTExhaust Fan (Toilet)TEF-2B.32nd FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0404VENTExhaust Fan (General)EF-2B.12nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0405VENTExhaust Fan (General)EF-2B.12nd FloorFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0406VENTExhaust Fan (General)EF-2B.12nd FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0407VENTExhaust Fan (General)EF-2B.22nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0408VENTExhaust Fan (General)EF-2B.22nd FloorFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0409VENTExhaust Fan (General)EF-2B.22nd FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0410VENTExhaust Fan (General)EF-GS.12nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0411VENTExhaust Fan (General)EF-GS.12nd FloorFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0412VENTExhaust Fan (General)EF-GS.12nd FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0413VENTExhaust Fan (General)EF-GS.22nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0414VENTExhaust Fan (General)EF-GS.22nd FloorFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0415VENTExhaust Fan (General)EF-GS.22nd FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0416VENTExhaust Fan (General)EF-2.12nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0417VENTExhaust Fan (General)EF-2.12nd FloorFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0418VENTExhaust Fan (General)EF-2.12nd FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0419VENTExhaust Fan (General)EF-2.22nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0420VENTExhaust Fan (General)EF-2.22nd FloorFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0421VENTExhaust Fan (General)EF-2.22nd FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0422VENTExhaust Fan (General)EF-2.32nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0423VENTExhaust Fan (General)EF-2.32nd FloorFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0424VENTExhaust Fan (General)EF-2.32nd FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0425VENTExhaust Fan (General)EF-2.42nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0426VENTExhaust Fan (General)EF-2.42nd FloorFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0427VENTExhaust Fan (General)EF-2.42nd FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0428VENTExhaust Fan (General)EF-CHR.12nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0429VENTExhaust Fan (General)EF-CHR.12nd FloorFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0430VENTExhaust Fan (General)EF-CHR.12nd FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0431VENTExhaust Fan (General)EF-CHR.22nd FloorFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0432VENTExhaust Fan (General)EF-CHR.22nd FloorFan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0433VENTExhaust Fan (General)EF-CHR.22nd FloorFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-2FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0434VENTExhaust Fan (Toilet)TEF-3A.13rd Floor (Amenity)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0435VENTExhaust Fan (Toilet)TEF-3A.13rd Floor (Amenity)Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0436VENTExhaust Fan (Toilet)TEF-3A.13rd Floor (Amenity)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0437VENTExhaust Fan (Toilet)TEF-3A.23rd Floor (Amenity)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0438VENTExhaust Fan (Toilet)TEF-3A.23rd Floor (Amenity)Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0439VENTExhaust Fan (Toilet)TEF-3A.23rd Floor (Amenity)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0440VENTExhaust Fan (Toilet)TEF-3B.13rd Floor (Amenity)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0441VENTExhaust Fan (Toilet)TEF-3B.13rd Floor (Amenity)Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0442VENTExhaust Fan (Toilet)TEF-3B.13rd Floor (Amenity)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0443VENTExhaust Fan (Toilet)TEF-3C.13rd Floor (Amenity)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0444VENTExhaust Fan (Toilet)TEF-3C.13rd Floor (Amenity)Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0445VENTExhaust Fan (Toilet)TEF-3C.13rd Floor (Amenity)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0446VENTExhaust Fan (Toilet)TEF-3C.23rd Floor (Amenity)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0447VENTExhaust Fan (Toilet)TEF-3C.23rd Floor (Amenity)Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0448VENTExhaust Fan (Toilet)TEF-3C.23rd Floor (Amenity)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0449VENTExhaust Fan (Toilet)TEF-3D.13rd Floor (Guestroom)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0450VENTExhaust Fan (Toilet)TEF-3D.13rd Floor (Guestroom)Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0451VENTExhaust Fan (Toilet)TEF-3D.13rd Floor (Guestroom)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0452VENTExhaust Fan (Toilet)TEF-3D.23rd Floor (Guestroom)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0453VENTExhaust Fan (Toilet)TEF-3D.23rd Floor (Guestroom)Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0454VENTExhaust Fan (Toilet)TEF-3D.23rd Floor (Guestroom)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0455VENTExhaust Fan (Toilet)TEF-3D.33rd Floor (Guestroom)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0456VENTExhaust Fan (Toilet)TEF-3D.33rd Floor (Guestroom)Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0457VENTExhaust Fan (Toilet)TEF-3D.33rd Floor (Guestroom)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0458VENTExhaust Fan (Toilet)TEF-3D.43rd Floor (Guestroom)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0459VENTExhaust Fan (Toilet)TEF-3D.43rd Floor (Guestroom)Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0460VENTExhaust Fan (Toilet)TEF-3D.43rd Floor (Guestroom)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0461VENTExhaust Fan (Toilet)TEF-3D.53rd Floor (Guestroom)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0462VENTExhaust Fan (Toilet)TEF-3D.53rd Floor (Guestroom)Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0463VENTExhaust Fan (Toilet)TEF-3D.53rd Floor (Guestroom)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0464VENTExhaust Fan (Toilet)TEF-3D.63rd Floor (Guestroom)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0465VENTExhaust Fan (Toilet)TEF-3D.63rd Floor (Guestroom)Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0466VENTExhaust Fan (Toilet)TEF-3D.63rd Floor (Guestroom)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0467VENTExhaust Fan (Toilet)TEF-3D.73rd Floor (Guestroom)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0468VENTExhaust Fan (Toilet)TEF-3D.73rd Floor (Guestroom)Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0469VENTExhaust Fan (Toilet)TEF-3D.73rd Floor (Guestroom)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0470VENTExhaust Fan (Toilet)TEF-3D.83rd Floor (Guestroom)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0471VENTExhaust Fan (Toilet)TEF-3D.83rd Floor (Guestroom)Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0472VENTExhaust Fan (Toilet)TEF-3D.83rd Floor (Guestroom)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0473VENTExhaust Fan (Toilet)TEF-3D.93rd Floor (Guestroom)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0474VENTExhaust Fan (Toilet)TEF-3D.93rd Floor (Guestroom)Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0475VENTExhaust Fan (Toilet)TEF-3D.93rd Floor (Guestroom)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0476VENTExhaust Fan (Toilet)TEF-3D.103rd Floor (Guestroom)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0477VENTExhaust Fan (Toilet)TEF-3D.103rd Floor (Guestroom)Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0478VENTExhaust Fan (Toilet)TEF-3D.103rd Floor (Guestroom)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0479VENTExhaust Fan (Toilet)TEF-3D.113rd Floor (Guestroom)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0480VENTExhaust Fan (Toilet)TEF-3D.113rd Floor (Guestroom)Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0481VENTExhaust Fan (Toilet)TEF-3D.113rd Floor (Guestroom)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0482VENTExhaust Fan (Toilet)TEF-3D.123rd Floor (Guestroom)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0483VENTExhaust Fan (Toilet)TEF-3D.123rd Floor (Guestroom)Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0484VENTExhaust Fan (Toilet)TEF-3D.123rd Floor (Guestroom)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0485VENTExhaust Fan (Toilet)TEF-3D.133rd Floor (Guestroom)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0486VENTExhaust Fan (Toilet)TEF-3D.133rd Floor (Guestroom)Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0487VENTExhaust Fan (Toilet)TEF-3D.133rd Floor (Guestroom)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0488VENTExhaust Fan (Toilet)TEF-3D.143rd Floor (Guestroom)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0489VENTExhaust Fan (Toilet)TEF-3D.143rd Floor (Guestroom)Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0490VENTExhaust Fan (Toilet)TEF-3D.143rd Floor (Guestroom)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0491VENTExhaust Fan (Toilet)TEF-3D.153rd Floor (Guestroom)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0492VENTExhaust Fan (Toilet)TEF-3D.153rd Floor (Guestroom)Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0493VENTExhaust Fan (Toilet)TEF-3D.153rd Floor (Guestroom)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0494VENTExhaust Fan (Toilet)TEF-3D.163rd Floor (Guestroom)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0495VENTExhaust Fan (Toilet)TEF-3D.163rd Floor (Guestroom)Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0496VENTExhaust Fan (Toilet)TEF-3D.163rd Floor (Guestroom)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0497VENTExhaust Fan (Toilet)TEF-3D.173rd Floor (Guestroom)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0498VENTExhaust Fan (Toilet)TEF-3D.173rd Floor (Guestroom)Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0499VENTExhaust Fan (Toilet)TEF-3D.173rd Floor (Guestroom)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0500VENTExhaust Fan (Toilet)TEF-3D.183rd Floor (Guestroom)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0501VENTExhaust Fan (Toilet)TEF-3D.183rd Floor (Guestroom)Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0502VENTExhaust Fan (Toilet)TEF-3D.183rd Floor (Guestroom)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0503VENTExhaust Fan (Toilet)TEF-3D.193rd Floor (Guestroom)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0504VENTExhaust Fan (Toilet)TEF-3D.193rd Floor (Guestroom)Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0505VENTExhaust Fan (Toilet)TEF-3D.193rd Floor (Guestroom)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0506VENTExhaust Fan (Toilet)TEF-3D.203rd Floor (Guestroom)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0507VENTExhaust Fan (Toilet)TEF-3D.203rd Floor (Guestroom)Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0508VENTExhaust Fan (Toilet)TEF-3D.203rd Floor (Guestroom)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (Toilet)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0509VENTExhaust Fan (General)EF-3GE.13rd Floor (Amenity)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0510VENTExhaust Fan (General)EF-3GE.13rd Floor (Amenity)Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0511VENTExhaust Fan (General)EF-3GE.13rd Floor (Amenity)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0512VENTExhaust Fan (General)EF-3GE.23rd Floor (Amenity)Fan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0513VENTExhaust Fan (General)EF-3GE.23rd Floor (Amenity)Fan HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0514VENTExhaust Fan (General)EF-3GE.23rd Floor (Amenity)Fan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Exhaust Fan (General)FCP-3FSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0515ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)Entering Chilled Water TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0516ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)Leaving Chilled Water TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0517ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)CHW Isolation Valve Status (Return)DIElectric Valve ActuatorME ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0518ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)CHW Isolation Valve Status (Supply)DIElectric Valve ActuatorME ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0519ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)Evaporator Approach dTHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0520ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)Evaporator Approach dPHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0521ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)Evaporator Refrigerant PressureHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0522ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)Evaporator Refrigerant TemperatureHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0523ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)Oil Sump PressureHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0524ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)Oil Sump TemperatureHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0525ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)Oil Pump StatusHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0526ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)Oil Pump TripHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0527ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)Compressor StatusHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0528ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)Compressor HOA StatusHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0529ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)Compressor TripHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0530ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)Motor Load CurrentHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0531ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)Motor kW / BTU MeterHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0532ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)Winding TemperatureHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0533ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)Condenser Refrigerant PressureHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0534ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)Condenser Refrigerant TemperatureHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0535ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)Condenser Approach dTHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0536ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)Condenser Approach dPHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0537ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)COW Isolation Valve Status (Return)DIElectric Valve ActuatorME ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0538ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)COW Isolation Valve Status (Supply)DIElectric Valve ActuatorME ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0539ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)Entering Condenser Water TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0540ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)Leaving Condenser Water TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0541ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)CHW Return FlowAIFlow SensorBMS ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0542ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)CHW Supply FlowAIFlow SensorBMS ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0543ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)COW Supply FlowAIFlow SensorBMS ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0544ACChiller (Package Water-Cooled)CH-12nd Floor (Plant Room)BACnet/IP gatewayNetworkChiller native BACnetEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0545ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)Entering Chilled Water TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0546ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)Leaving Chilled Water TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0547ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)CHW Isolation Valve Status (Return)DIElectric Valve ActuatorME ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0548ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)CHW Isolation Valve Status (Supply)DIElectric Valve ActuatorME ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0549ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)Evaporator Approach dTHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0550ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)Evaporator Approach dPHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0551ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)Evaporator Refrigerant PressureHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0552ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)Evaporator Refrigerant TemperatureHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0553ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)Oil Sump PressureHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0554ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)Oil Sump TemperatureHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0555ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)Oil Pump StatusHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0556ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)Oil Pump TripHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0557ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)Compressor StatusHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0558ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)Compressor HOA StatusHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0559ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)Compressor TripHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0560ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)Motor Load CurrentHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0561ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)Motor kW / BTU MeterHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0562ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)Winding TemperatureHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0563ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)Condenser Refrigerant PressureHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0564ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)Condenser Refrigerant TemperatureHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0565ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)Condenser Approach dTHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0566ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)Condenser Approach dPHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0567ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)COW Isolation Valve Status (Return)DIElectric Valve ActuatorME ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0568ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)COW Isolation Valve Status (Supply)DIElectric Valve ActuatorME ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0569ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)Entering Condenser Water TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0570ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)Leaving Condenser Water TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0571ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)CHW Return FlowAIFlow SensorBMS ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0572ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)CHW Supply FlowAIFlow SensorBMS ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0573ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)COW Supply FlowAIFlow SensorBMS ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0574ACChiller (Package Water-Cooled)CH-22nd Floor (Plant Room)BACnet/IP gatewayNetworkChiller native BACnetEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0575ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)Entering Chilled Water TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0576ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)Leaving Chilled Water TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0577ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)CHW Isolation Valve Status (Return)DIElectric Valve ActuatorME ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0578ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)CHW Isolation Valve Status (Supply)DIElectric Valve ActuatorME ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0579ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)Evaporator Approach dTHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0580ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)Evaporator Approach dPHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0581ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)Evaporator Refrigerant PressureHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0582ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)Evaporator Refrigerant TemperatureHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0583ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)Oil Sump PressureHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0584ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)Oil Sump TemperatureHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0585ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)Oil Pump StatusHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0586ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)Oil Pump TripHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0587ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)Compressor StatusHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0588ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)Compressor HOA StatusHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0589ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)Compressor TripHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0590ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)Motor Load CurrentHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0591ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)Motor kW / BTU MeterHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0592ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)Winding TemperatureHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0593ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)Condenser Refrigerant PressureHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0594ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)Condenser Refrigerant TemperatureHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0595ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)Condenser Approach dTHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0596ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)Condenser Approach dPHLIChiller NativeEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0597ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)COW Isolation Valve Status (Return)DIElectric Valve ActuatorME ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0598ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)COW Isolation Valve Status (Supply)DIElectric Valve ActuatorME ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0599ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)Entering Condenser Water TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0600ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)Leaving Condenser Water TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0601ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)CHW Return FlowAIFlow SensorBMS ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0602ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)CHW Supply FlowAIFlow SensorBMS ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0603ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)COW Supply FlowAIFlow SensorBMS ContractorDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0604ACChiller (Package Water-Cooled)CH-32nd Floor (Plant Room)BACnet/IP gatewayNetworkChiller native BACnetEquipment SupplierDRC-004-2024 AC/Chiller (Package Water-Cooled)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0605ACPrimary CHW PumpPCHW-12nd Floor (Plant Room)CHW Supply PressureAIPressure SensorEquipment SupplierDRC-004-2024 AC/Primary CHW PumpMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0606ACPrimary CHW PumpPCHW-12nd Floor (Plant Room)On/Off StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Primary CHW PumpMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0607ACPrimary CHW PumpPCHW-12nd Floor (Plant Room)HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Primary CHW PumpMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0608ACPrimary CHW PumpPCHW-12nd Floor (Plant Room)VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 AC/Primary CHW PumpMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0609ACPrimary CHW PumpPCHW-12nd Floor (Plant Room)Trip AlarmDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Primary CHW PumpMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0610ACPrimary CHW PumpPCHW-22nd Floor (Plant Room)CHW Supply PressureAIPressure SensorEquipment SupplierDRC-004-2024 AC/Primary CHW PumpMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0611ACPrimary CHW PumpPCHW-22nd Floor (Plant Room)On/Off StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Primary CHW PumpMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0612ACPrimary CHW PumpPCHW-22nd Floor (Plant Room)HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Primary CHW PumpMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0613ACPrimary CHW PumpPCHW-22nd Floor (Plant Room)VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 AC/Primary CHW PumpMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0614ACPrimary CHW PumpPCHW-22nd Floor (Plant Room)Trip AlarmDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Primary CHW PumpMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0615ACPrimary CHW PumpPCHW-32nd Floor (Plant Room)CHW Supply PressureAIPressure SensorEquipment SupplierDRC-004-2024 AC/Primary CHW PumpMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0616ACPrimary CHW PumpPCHW-32nd Floor (Plant Room)On/Off StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Primary CHW PumpMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0617ACPrimary CHW PumpPCHW-32nd Floor (Plant Room)HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Primary CHW PumpMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0618ACPrimary CHW PumpPCHW-32nd Floor (Plant Room)VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 AC/Primary CHW PumpMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0619ACPrimary CHW PumpPCHW-32nd Floor (Plant Room)Trip AlarmDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Primary CHW PumpMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0620ACPrimary CHW Pump (Standby)PCHW-S2nd Floor (Plant Room)CHW Supply PressureAIPressure SensorEquipment SupplierDRC-004-2024 AC/Primary CHW Pump (Standby)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0621ACPrimary CHW Pump (Standby)PCHW-S2nd Floor (Plant Room)On/Off StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Primary CHW Pump (Standby)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0622ACPrimary CHW Pump (Standby)PCHW-S2nd Floor (Plant Room)HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Primary CHW Pump (Standby)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0623ACPrimary CHW Pump (Standby)PCHW-S2nd Floor (Plant Room)VFD SpeedHLIVFDEquipment SupplierDRC-004-2024 AC/Primary CHW Pump (Standby)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0624ACPrimary CHW Pump (Standby)PCHW-S2nd Floor (Plant Room)Trip AlarmDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Primary CHW Pump (Standby)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0625ACCondenser Water PumpPCOW-12nd Floor (Plant Room)On/Off StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Condenser Water PumpMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0626ACCondenser Water PumpPCOW-12nd Floor (Plant Room)HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Condenser Water PumpMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0627ACCondenser Water PumpPCOW-12nd Floor (Plant Room)Trip AlarmDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Condenser Water PumpMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0628ACCondenser Water PumpPCOW-22nd Floor (Plant Room)On/Off StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Condenser Water PumpMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0629ACCondenser Water PumpPCOW-22nd Floor (Plant Room)HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Condenser Water PumpMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0630ACCondenser Water PumpPCOW-22nd Floor (Plant Room)Trip AlarmDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Condenser Water PumpMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0631ACCondenser Water PumpPCOW-32nd Floor (Plant Room)On/Off StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Condenser Water PumpMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0632ACCondenser Water PumpPCOW-32nd Floor (Plant Room)HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Condenser Water PumpMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0633ACCondenser Water PumpPCOW-32nd Floor (Plant Room)Trip AlarmDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Condenser Water PumpMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0634ACCooling TowerCT-1RoofdeckFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Cooling TowerFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0635ACCooling TowerCT-1RoofdeckFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Cooling TowerFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0636ACCooling TowerCT-1RoofdeckBasin Low LevelDILevel SensorBMS ContractorDRC-004-2024 AC/Cooling TowerFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0637ACCooling TowerCT-1RoofdeckBasin High LevelDILevel SensorBMS ContractorDRC-004-2024 AC/Cooling TowerFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0638ACCooling TowerCT-1RoofdeckCOW Isolation Valve Status (Return)DIElectric Valve ActuatorME ContractorDRC-004-2024 AC/Cooling TowerFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0639ACCooling TowerCT-1RoofdeckBlowdown Corrosion/Scale (pH)AIpH/Cond SensorME ContractorDRC-004-2024 AC/Cooling TowerFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0640ACCooling TowerCT-1RoofdeckBlowdown Valve ControlAOElectric Valve ActuatorBMS ContractorDRC-004-2024 AC/Cooling TowerFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0641ACCooling TowerCT-2RoofdeckFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Cooling TowerFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0642ACCooling TowerCT-2RoofdeckFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Cooling TowerFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0643ACCooling TowerCT-2RoofdeckBasin Low LevelDILevel SensorBMS ContractorDRC-004-2024 AC/Cooling TowerFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0644ACCooling TowerCT-2RoofdeckBasin High LevelDILevel SensorBMS ContractorDRC-004-2024 AC/Cooling TowerFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0645ACCooling TowerCT-2RoofdeckCOW Isolation Valve Status (Return)DIElectric Valve ActuatorME ContractorDRC-004-2024 AC/Cooling TowerFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0646ACCooling TowerCT-2RoofdeckBlowdown Corrosion/Scale (pH)AIpH/Cond SensorME ContractorDRC-004-2024 AC/Cooling TowerFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0647ACCooling TowerCT-2RoofdeckBlowdown Valve ControlAOElectric Valve ActuatorBMS ContractorDRC-004-2024 AC/Cooling TowerFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0648ACCooling TowerCT-3RoofdeckFan Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Cooling TowerFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0649ACCooling TowerCT-3RoofdeckFan TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 AC/Cooling TowerFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0650ACCooling TowerCT-3RoofdeckBasin Low LevelDILevel SensorBMS ContractorDRC-004-2024 AC/Cooling TowerFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0651ACCooling TowerCT-3RoofdeckBasin High LevelDILevel SensorBMS ContractorDRC-004-2024 AC/Cooling TowerFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0652ACCooling TowerCT-3RoofdeckCOW Isolation Valve Status (Return)DIElectric Valve ActuatorME ContractorDRC-004-2024 AC/Cooling TowerFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0653ACCooling TowerCT-3RoofdeckBlowdown Corrosion/Scale (pH)AIpH/Cond SensorME ContractorDRC-004-2024 AC/Cooling TowerFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0654ACCooling TowerCT-3RoofdeckBlowdown Valve ControlAOElectric Valve ActuatorBMS ContractorDRC-004-2024 AC/Cooling TowerFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0655ACCooling Tower (Common)CT-COMMONRoofdeckOutside Air Temperature (CT area)AITemperature SensorBMS ContractorDRC-004-2024 AC/Cooling Tower (Common)FCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0656ACCooling Tower (Common)CT-COMMONRoofdeckOutside Air Humidity (CT area)AIHumidity SensorBMS ContractorDRC-004-2024 AC/Cooling Tower (Common)FCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0657ACCooling Tower (Common)CT-COMMONRoofdeckCondenser Return Header TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/Cooling Tower (Common)FCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0658ACCooling Tower (Common)CT-COMMONRoofdeckCondenser Supply Header TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/Cooling Tower (Common)FCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0659ACCHW Supply Main HeaderCHW-HDR-S2nd Floor (Plant Room)CHW Supply Header TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/CHW Supply Main HeaderMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0660ACCHW Supply Main HeaderCHW-HDR-S2nd Floor (Plant Room)CHW Supply Header PressureAIPressure SensorBMS ContractorDRC-004-2024 AC/CHW Supply Main HeaderMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0661ACCHW Return Main HeaderCHW-HDR-R2nd Floor (Plant Room)CHW Return Header TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/CHW Return Main HeaderMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0662ACCHW Return Main HeaderCHW-HDR-R2nd Floor (Plant Room)CHW Return Header PressureAIPressure SensorBMS ContractorDRC-004-2024 AC/CHW Return Main HeaderMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0663ACCHW Bypass HeaderCHW-BYPASS2nd Floor (Plant Room)Differential PressureAIDiff. Pressure SensorBMS ContractorDRC-004-2024 AC/CHW Bypass HeaderMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0664ACCHW Bypass HeaderCHW-BYPASS2nd Floor (Plant Room)Differential TemperatureAIDiff. Temp SensorBMS ContractorDRC-004-2024 AC/CHW Bypass HeaderMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0665ACCHW Bypass HeaderCHW-BYPASS2nd Floor (Plant Room)CHW Bypass Valve StatusDIElectric Valve ActuatorBMS ContractorDRC-004-2024 AC/CHW Bypass HeaderMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0666ACCHW Bypass HeaderCHW-BYPASS2nd Floor (Plant Room)CHW Bypass Valve ControlAOElectric Valve ActuatorBMS ContractorDRC-004-2024 AC/CHW Bypass HeaderMCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0667ACCondenser Water HeaderCOW-HDRRoofdeckCondenser Supply Header TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/Condenser Water HeaderFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0668ACCondenser Water HeaderCOW-HDRRoofdeckCondenser Return Header TemperatureAITemperature SensorBMS ContractorDRC-004-2024 AC/Condenser Water HeaderFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0669VENTSteam BoilerBLR-1Lower GroundSupply Steam PressureAIPressure SensorBMS ContractorDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0670VENTSteam BoilerBLR-1Lower GroundLow Water LevelDILevel SensorEquipment SupplierDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0671VENTSteam BoilerBLR-1Lower GroundHigh Water LevelDILevel SensorEquipment SupplierDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0672VENTSteam BoilerBLR-1Lower GroundBurner PowerDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0673VENTSteam BoilerBLR-1Lower GroundSmall Fire ControlDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0674VENTSteam BoilerBLR-1Lower GroundBig Fire ControlDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0675VENTSteam BoilerBLR-1Lower GroundFeedwater Pump StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0676VENTSteam BoilerBLR-1Lower GroundBurner StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0677VENTSteam BoilerBLR-1Lower GroundBurner Fire RunningDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0678VENTSteam BoilerBLR-1Lower GroundBlower Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0679VENTSteam BoilerBLR-1Lower GroundFuel Oil Pump StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0680VENTSteam BoilerBLR-1Lower GroundBlowdown Valve StatusDIElectric Valve ActuatorBMS ContractorDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0681VENTSteam BoilerBLR-1Lower GroundBlowdown Valve ControlAOElectric Valve ActuatorBMS ContractorDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0682VENTSteam BoilerBLR-1Lower GroundFeedwater Supply TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0683VENTSteam BoilerBLR-1Lower GroundFluegas TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0684VENTSteam BoilerBLR-1Lower GroundFluegas Oxygen LevelAIOxygen SensorBMS ContractorDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0685VENTSteam BoilerBLR-2Lower GroundSupply Steam PressureAIPressure SensorBMS ContractorDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0686VENTSteam BoilerBLR-2Lower GroundLow Water LevelDILevel SensorEquipment SupplierDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0687VENTSteam BoilerBLR-2Lower GroundHigh Water LevelDILevel SensorEquipment SupplierDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0688VENTSteam BoilerBLR-2Lower GroundBurner PowerDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0689VENTSteam BoilerBLR-2Lower GroundSmall Fire ControlDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0690VENTSteam BoilerBLR-2Lower GroundBig Fire ControlDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0691VENTSteam BoilerBLR-2Lower GroundFeedwater Pump StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0692VENTSteam BoilerBLR-2Lower GroundBurner StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0693VENTSteam BoilerBLR-2Lower GroundBurner Fire RunningDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0694VENTSteam BoilerBLR-2Lower GroundBlower Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0695VENTSteam BoilerBLR-2Lower GroundFuel Oil Pump StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0696VENTSteam BoilerBLR-2Lower GroundBlowdown Valve StatusDIElectric Valve ActuatorBMS ContractorDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0697VENTSteam BoilerBLR-2Lower GroundBlowdown Valve ControlAOElectric Valve ActuatorBMS ContractorDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0698VENTSteam BoilerBLR-2Lower GroundFeedwater Supply TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0699VENTSteam BoilerBLR-2Lower GroundFluegas TemperatureAITemperature SensorBMS ContractorDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0700VENTSteam BoilerBLR-2Lower GroundFluegas Oxygen LevelAIOxygen SensorBMS ContractorDRC-004-2024 VENT/Steam BoilerFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0701HWLCalorifier (Hot Water Storage Tank)HWT-LZ.1Lower GroundTank TemperatureAITemperature SensorBMS ContractorDRC-004-2024 HWL/Calorifier (Hot Water Storage Tank)FCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0702HWLCalorifier (Hot Water Storage Tank)HWT-LZ.2Lower GroundTank TemperatureAITemperature SensorBMS ContractorDRC-004-2024 HWL/Calorifier (Hot Water Storage Tank)FCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0703HWLCalorifier (Hot Water Storage Tank)HWT-LZ.3Lower GroundTank TemperatureAITemperature SensorBMS ContractorDRC-004-2024 HWL/Calorifier (Hot Water Storage Tank)FCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0704HWLCalorifier (Hot Water Storage Tank)HWT-HZ.1RoofdeckTank TemperatureAITemperature SensorBMS ContractorDRC-004-2024 HWL/Calorifier (Hot Water Storage Tank)FCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0705HWLCalorifier (Hot Water Storage Tank)HWT-HZ.2RoofdeckTank TemperatureAITemperature SensorBMS ContractorDRC-004-2024 HWL/Calorifier (Hot Water Storage Tank)FCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0706HWLCalorifier (Hot Water Storage Tank)HWT-HZ.3RoofdeckTank TemperatureAITemperature SensorBMS ContractorDRC-004-2024 HWL/Calorifier (Hot Water Storage Tank)FCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0707HWLHot Water Header SetHW-HDR-LZLower GroundHot Water Supply Header TemperatureAITemperature SensorBMS ContractorDRC-004-2024 HWL/Hot Water Header SetFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0708HWLHot Water Header SetHW-HDR-LZLower GroundHot Water Return Header TemperatureAITemperature SensorBMS ContractorDRC-004-2024 HWL/Hot Water Header SetFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0709HWLHot Water Header SetHW-HDR-LZLower GroundMake-Up Cold Water Header TemperatureAITemperature SensorBMS ContractorDRC-004-2024 HWL/Hot Water Header SetFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0710HWLHot Water Header SetHW-HDR-HZRoofdeckHot Water Supply Header TemperatureAITemperature SensorBMS ContractorDRC-004-2024 HWL/Hot Water Header SetFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0711HWLHot Water Header SetHW-HDR-HZRoofdeckHot Water Return Header TemperatureAITemperature SensorBMS ContractorDRC-004-2024 HWL/Hot Water Header SetFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0712HWLHot Water Header SetHW-HDR-HZRoofdeckMake-Up Cold Water Header TemperatureAITemperature SensorBMS ContractorDRC-004-2024 HWL/Hot Water Header SetFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0713HWLHeat PumpHP-LZ.1Lower GroundPump Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Heat PumpFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0714HWLHeat PumpHP-LZ.1Lower GroundPump HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Heat PumpFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0715HWLHeat PumpHP-LZ.1Lower GroundPump TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Heat PumpFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0716HWLHeat PumpHP-LZ.2Lower GroundPump Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Heat PumpFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0717HWLHeat PumpHP-LZ.2Lower GroundPump HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Heat PumpFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0718HWLHeat PumpHP-LZ.2Lower GroundPump TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Heat PumpFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0719HWLHeat PumpHP-LZ.3Lower GroundPump Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Heat PumpFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0720HWLHeat PumpHP-LZ.3Lower GroundPump HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Heat PumpFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0721HWLHeat PumpHP-LZ.3Lower GroundPump TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Heat PumpFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0722HWLHeat PumpHP-HZ.1RoofdeckPump Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Heat PumpFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0723HWLHeat PumpHP-HZ.1RoofdeckPump HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Heat PumpFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0724HWLHeat PumpHP-HZ.1RoofdeckPump TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Heat PumpFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0725HWLHeat PumpHP-HZ.2RoofdeckPump Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Heat PumpFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0726HWLHeat PumpHP-HZ.2RoofdeckPump HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Heat PumpFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0727HWLHeat PumpHP-HZ.2RoofdeckPump TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Heat PumpFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0728HWLHeat PumpHP-HZ.3RoofdeckPump Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Heat PumpFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0729HWLHeat PumpHP-HZ.3RoofdeckPump HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Heat PumpFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0730HWLHeat PumpHP-HZ.3RoofdeckPump TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Heat PumpFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0731HWLRecirculating PumpRP-LZ.1Lower GroundPump Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Recirculating PumpFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0732HWLRecirculating PumpRP-LZ.1Lower GroundPump HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Recirculating PumpFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0733HWLRecirculating PumpRP-LZ.1Lower GroundPump TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Recirculating PumpFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0734HWLRecirculating PumpRP-LZ.2Lower GroundPump Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Recirculating PumpFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0735HWLRecirculating PumpRP-LZ.2Lower GroundPump HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Recirculating PumpFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0736HWLRecirculating PumpRP-LZ.2Lower GroundPump TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Recirculating PumpFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0737HWLRecirculating PumpRP-LZ.3Lower GroundPump Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Recirculating PumpFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0738HWLRecirculating PumpRP-LZ.3Lower GroundPump HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Recirculating PumpFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0739HWLRecirculating PumpRP-LZ.3Lower GroundPump TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Recirculating PumpFCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0740HWLRecirculating PumpRP-HZ.1RoofdeckPump Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Recirculating PumpFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0741HWLRecirculating PumpRP-HZ.1RoofdeckPump HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Recirculating PumpFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0742HWLRecirculating PumpRP-HZ.1RoofdeckPump TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Recirculating PumpFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0743HWLRecirculating PumpRP-HZ.2RoofdeckPump Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Recirculating PumpFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0744HWLRecirculating PumpRP-HZ.2RoofdeckPump HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Recirculating PumpFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0745HWLRecirculating PumpRP-HZ.2RoofdeckPump TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Recirculating PumpFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0746HWLRecirculating PumpRP-HZ.3RoofdeckPump Motor StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Recirculating PumpFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0747HWLRecirculating PumpRP-HZ.3RoofdeckPump HOA StatusDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Recirculating PumpFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0748HWLRecirculating PumpRP-HZ.3RoofdeckPump TripDIAuxiliary ContactEquipment SupplierDRC-004-2024 HWL/Recirculating PumpFCP-RDSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0749EEMultifunction Power Meter (Main)PM-MAIN2nd Floor (Plant Room)Multifunction Power Meter (Modbus)NetworkModbus RTU meterBMS ContractorDRC-004-2024 EE/Multifunction Power Meter (Main)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0750EEMultifunction Power Meter (Main)PM-GEN2nd Floor (Plant Room)Multifunction Power Meter (Modbus)NetworkModbus RTU meterBMS ContractorDRC-004-2024 EE/Multifunction Power Meter (Main)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0751EEMultifunction Power Meter (Feeder)PM-MCC-CHILLER2nd Floor (Plant Room)Multifunction Power Meter (Modbus)NetworkModbus RTU meterBMS ContractorDRC-004-2024 EE/Multifunction Power Meter (Feeder)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0752EEMultifunction Power Meter (Feeder)PM-MCC-CT2nd Floor (Plant Room)Multifunction Power Meter (Modbus)NetworkModbus RTU meterBMS ContractorDRC-004-2024 EE/Multifunction Power Meter (Feeder)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0753EEMultifunction Power Meter (Feeder)PM-MCC-BOILER2nd Floor (Plant Room)Multifunction Power Meter (Modbus)NetworkModbus RTU meterBMS ContractorDRC-004-2024 EE/Multifunction Power Meter (Feeder)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0754EEMultifunction Power Meter (Feeder)PM-MCC-FIRE-PUMP2nd Floor (Plant Room)Multifunction Power Meter (Modbus)NetworkModbus RTU meterBMS ContractorDRC-004-2024 EE/Multifunction Power Meter (Feeder)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0755EEMultifunction Power Meter (Feeder)PM-MCC-MDP-12nd Floor (Plant Room)Multifunction Power Meter (Modbus)NetworkModbus RTU meterBMS ContractorDRC-004-2024 EE/Multifunction Power Meter (Feeder)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0756EEMultifunction Power Meter (Feeder)PM-MCC-MDP-22nd Floor (Plant Room)Multifunction Power Meter (Modbus)NetworkModbus RTU meterBMS ContractorDRC-004-2024 EE/Multifunction Power Meter (Feeder)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0757EEMultifunction Power Meter (Feeder)PM-MCC-MDP-32nd Floor (Plant Room)Multifunction Power Meter (Modbus)NetworkModbus RTU meterBMS ContractorDRC-004-2024 EE/Multifunction Power Meter (Feeder)MCP-PLANTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0758EEMultifunction Power Meter (Main)GEN-1Basement (Genset)Generator Run StatusDIAuxiliary ContactEE ContractorDRC-004-2024 EE/Multifunction Power Meter (Main)FCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0759EEMultifunction Power Meter (Main)GEN-1Basement (Genset)Generator Common TripDIAuxiliary ContactEE ContractorDRC-004-2024 EE/Multifunction Power Meter (Main)FCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0760EEMultifunction Power Meter (Main)GEN-1Basement (Genset)Generator Common AlarmDIAuxiliary ContactEE ContractorDRC-004-2024 EE/Multifunction Power Meter (Main)FCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0761EEMultifunction Power Meter (Main)ATS-1Basement (Genset)ATS Position (Mains/Gen)DIAuxiliary ContactEE ContractorDRC-004-2024 EE/Multifunction Power Meter (Main)FCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)
P0762EEMultifunction Power Meter (Main)ATS-1Basement (Genset)ATS TripDIAuxiliary ContactEE ContractorDRC-004-2024 EE/Multifunction Power Meter (Main)FCP-BSMTSynthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities)