| ID | System | Equipment Class | Equipment Instance | Location | Point Description | Type | Field Device | C/O | DoO Ref | Panel | Source | Notes |
| P0001 | AC | AHU (Chilled-Water-Served) | AHU-1.1 | Ground Floor | Indoor Return Air Damper Status | DI | Damper Controller | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0002 | AC | AHU (Chilled-Water-Served) | AHU-1.1 | Ground Floor | Indoor Return Air Damper Control | AO | Damper Controller | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0003 | AC | AHU (Chilled-Water-Served) | AHU-1.1 | Ground Floor | Indoor Return Air CO2 | AI | CO2 Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0004 | AC | AHU (Chilled-Water-Served) | AHU-1.1 | Ground Floor | Indoor Return Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0005 | AC | AHU (Chilled-Water-Served) | AHU-1.1 | Ground Floor | CHWS Valve Control | AO | Electric Valve Actuator | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0006 | AC | AHU (Chilled-Water-Served) | AHU-1.1 | Ground Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0007 | AC | AHU (Chilled-Water-Served) | AHU-1.1 | Ground Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0008 | AC | AHU (Chilled-Water-Served) | AHU-1.1 | Ground Floor | Fan VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0009 | AC | AHU (Chilled-Water-Served) | AHU-1.1 | Ground Floor | Fan Control | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0010 | AC | AHU (Chilled-Water-Served) | AHU-1.1 | Ground Floor | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0011 | AC | AHU (Chilled-Water-Served) | AHU-1.1 | Ground Floor | Indoor Mixed Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0012 | AC | AHU (Chilled-Water-Served) | AHU-1.1 | Ground Floor | Outdoor Damper Status | DI | Damper Controller | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0013 | AC | AHU (Chilled-Water-Served) | AHU-1.1 | Ground Floor | Outdoor Damper Control | AO | Damper Controller | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0014 | AC | AHU (Chilled-Water-Served) | AHU-1.1 | Ground Floor | Outside Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0015 | AC | AHU (Chilled-Water-Served) | AHU-1.2 | Ground Floor | Indoor Return Air Damper Status | DI | Damper Controller | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0016 | AC | AHU (Chilled-Water-Served) | AHU-1.2 | Ground Floor | Indoor Return Air Damper Control | AO | Damper Controller | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0017 | AC | AHU (Chilled-Water-Served) | AHU-1.2 | Ground Floor | Indoor Return Air CO2 | AI | CO2 Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0018 | AC | AHU (Chilled-Water-Served) | AHU-1.2 | Ground Floor | Indoor Return Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0019 | AC | AHU (Chilled-Water-Served) | AHU-1.2 | Ground Floor | CHWS Valve Control | AO | Electric Valve Actuator | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0020 | AC | AHU (Chilled-Water-Served) | AHU-1.2 | Ground Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0021 | AC | AHU (Chilled-Water-Served) | AHU-1.2 | Ground Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0022 | AC | AHU (Chilled-Water-Served) | AHU-1.2 | Ground Floor | Fan VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0023 | AC | AHU (Chilled-Water-Served) | AHU-1.2 | Ground Floor | Fan Control | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0024 | AC | AHU (Chilled-Water-Served) | AHU-1.2 | Ground Floor | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0025 | AC | AHU (Chilled-Water-Served) | AHU-1.2 | Ground Floor | Indoor Mixed Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0026 | AC | AHU (Chilled-Water-Served) | AHU-1.2 | Ground Floor | Outdoor Damper Status | DI | Damper Controller | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0027 | AC | AHU (Chilled-Water-Served) | AHU-1.2 | Ground Floor | Outdoor Damper Control | AO | Damper Controller | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0028 | AC | AHU (Chilled-Water-Served) | AHU-1.2 | Ground Floor | Outside Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0029 | AC | AHU (Chilled-Water-Served) | AHU-1.3 | Ground Floor | Indoor Return Air Damper Status | DI | Damper Controller | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0030 | AC | AHU (Chilled-Water-Served) | AHU-1.3 | Ground Floor | Indoor Return Air Damper Control | AO | Damper Controller | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0031 | AC | AHU (Chilled-Water-Served) | AHU-1.3 | Ground Floor | Indoor Return Air CO2 | AI | CO2 Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0032 | AC | AHU (Chilled-Water-Served) | AHU-1.3 | Ground Floor | Indoor Return Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0033 | AC | AHU (Chilled-Water-Served) | AHU-1.3 | Ground Floor | CHWS Valve Control | AO | Electric Valve Actuator | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0034 | AC | AHU (Chilled-Water-Served) | AHU-1.3 | Ground Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0035 | AC | AHU (Chilled-Water-Served) | AHU-1.3 | Ground Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0036 | AC | AHU (Chilled-Water-Served) | AHU-1.3 | Ground Floor | Fan VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0037 | AC | AHU (Chilled-Water-Served) | AHU-1.3 | Ground Floor | Fan Control | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0038 | AC | AHU (Chilled-Water-Served) | AHU-1.3 | Ground Floor | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0039 | AC | AHU (Chilled-Water-Served) | AHU-1.3 | Ground Floor | Indoor Mixed Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0040 | AC | AHU (Chilled-Water-Served) | AHU-1.3 | Ground Floor | Outdoor Damper Status | DI | Damper Controller | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0041 | AC | AHU (Chilled-Water-Served) | AHU-1.3 | Ground Floor | Outdoor Damper Control | AO | Damper Controller | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0042 | AC | AHU (Chilled-Water-Served) | AHU-1.3 | Ground Floor | Outside Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0043 | AC | AHU (Chilled-Water-Served) | AHU-B.1 | 2nd Floor | Indoor Return Air Damper Status | DI | Damper Controller | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0044 | AC | AHU (Chilled-Water-Served) | AHU-B.1 | 2nd Floor | Indoor Return Air Damper Control | AO | Damper Controller | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0045 | AC | AHU (Chilled-Water-Served) | AHU-B.1 | 2nd Floor | Indoor Return Air CO2 | AI | CO2 Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0046 | AC | AHU (Chilled-Water-Served) | AHU-B.1 | 2nd Floor | Indoor Return Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0047 | AC | AHU (Chilled-Water-Served) | AHU-B.1 | 2nd Floor | CHWS Valve Control | AO | Electric Valve Actuator | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0048 | AC | AHU (Chilled-Water-Served) | AHU-B.1 | 2nd Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0049 | AC | AHU (Chilled-Water-Served) | AHU-B.1 | 2nd Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0050 | AC | AHU (Chilled-Water-Served) | AHU-B.1 | 2nd Floor | Fan VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0051 | AC | AHU (Chilled-Water-Served) | AHU-B.1 | 2nd Floor | Fan Control | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0052 | AC | AHU (Chilled-Water-Served) | AHU-B.1 | 2nd Floor | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0053 | AC | AHU (Chilled-Water-Served) | AHU-B.1 | 2nd Floor | Indoor Mixed Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0054 | AC | AHU (Chilled-Water-Served) | AHU-B.1 | 2nd Floor | Outdoor Damper Status | DI | Damper Controller | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0055 | AC | AHU (Chilled-Water-Served) | AHU-B.1 | 2nd Floor | Outdoor Damper Control | AO | Damper Controller | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0056 | AC | AHU (Chilled-Water-Served) | AHU-B.1 | 2nd Floor | Outside Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0057 | AC | AHU (Chilled-Water-Served) | AHU-B.2 | 2nd Floor | Indoor Return Air Damper Status | DI | Damper Controller | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0058 | AC | AHU (Chilled-Water-Served) | AHU-B.2 | 2nd Floor | Indoor Return Air Damper Control | AO | Damper Controller | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0059 | AC | AHU (Chilled-Water-Served) | AHU-B.2 | 2nd Floor | Indoor Return Air CO2 | AI | CO2 Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0060 | AC | AHU (Chilled-Water-Served) | AHU-B.2 | 2nd Floor | Indoor Return Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0061 | AC | AHU (Chilled-Water-Served) | AHU-B.2 | 2nd Floor | CHWS Valve Control | AO | Electric Valve Actuator | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0062 | AC | AHU (Chilled-Water-Served) | AHU-B.2 | 2nd Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0063 | AC | AHU (Chilled-Water-Served) | AHU-B.2 | 2nd Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0064 | AC | AHU (Chilled-Water-Served) | AHU-B.2 | 2nd Floor | Fan VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0065 | AC | AHU (Chilled-Water-Served) | AHU-B.2 | 2nd Floor | Fan Control | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0066 | AC | AHU (Chilled-Water-Served) | AHU-B.2 | 2nd Floor | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0067 | AC | AHU (Chilled-Water-Served) | AHU-B.2 | 2nd Floor | Indoor Mixed Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0068 | AC | AHU (Chilled-Water-Served) | AHU-B.2 | 2nd Floor | Outdoor Damper Status | DI | Damper Controller | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0069 | AC | AHU (Chilled-Water-Served) | AHU-B.2 | 2nd Floor | Outdoor Damper Control | AO | Damper Controller | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0070 | AC | AHU (Chilled-Water-Served) | AHU-B.2 | 2nd Floor | Outside Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0071 | AC | AHU (Chilled-Water-Served) | AHU-B.3 | 2nd Floor | Indoor Return Air Damper Status | DI | Damper Controller | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0072 | AC | AHU (Chilled-Water-Served) | AHU-B.3 | 2nd Floor | Indoor Return Air Damper Control | AO | Damper Controller | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0073 | AC | AHU (Chilled-Water-Served) | AHU-B.3 | 2nd Floor | Indoor Return Air CO2 | AI | CO2 Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0074 | AC | AHU (Chilled-Water-Served) | AHU-B.3 | 2nd Floor | Indoor Return Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0075 | AC | AHU (Chilled-Water-Served) | AHU-B.3 | 2nd Floor | CHWS Valve Control | AO | Electric Valve Actuator | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0076 | AC | AHU (Chilled-Water-Served) | AHU-B.3 | 2nd Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0077 | AC | AHU (Chilled-Water-Served) | AHU-B.3 | 2nd Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0078 | AC | AHU (Chilled-Water-Served) | AHU-B.3 | 2nd Floor | Fan VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0079 | AC | AHU (Chilled-Water-Served) | AHU-B.3 | 2nd Floor | Fan Control | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0080 | AC | AHU (Chilled-Water-Served) | AHU-B.3 | 2nd Floor | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0081 | AC | AHU (Chilled-Water-Served) | AHU-B.3 | 2nd Floor | Indoor Mixed Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0082 | AC | AHU (Chilled-Water-Served) | AHU-B.3 | 2nd Floor | Outdoor Damper Status | DI | Damper Controller | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0083 | AC | AHU (Chilled-Water-Served) | AHU-B.3 | 2nd Floor | Outdoor Damper Control | AO | Damper Controller | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0084 | AC | AHU (Chilled-Water-Served) | AHU-B.3 | 2nd Floor | Outside Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0085 | AC | AHU (Chilled-Water-Served) | AHU-PF | 2nd Floor | Indoor Return Air Damper Status | DI | Damper Controller | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0086 | AC | AHU (Chilled-Water-Served) | AHU-PF | 2nd Floor | Indoor Return Air Damper Control | AO | Damper Controller | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0087 | AC | AHU (Chilled-Water-Served) | AHU-PF | 2nd Floor | Indoor Return Air CO2 | AI | CO2 Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0088 | AC | AHU (Chilled-Water-Served) | AHU-PF | 2nd Floor | Indoor Return Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0089 | AC | AHU (Chilled-Water-Served) | AHU-PF | 2nd Floor | CHWS Valve Control | AO | Electric Valve Actuator | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0090 | AC | AHU (Chilled-Water-Served) | AHU-PF | 2nd Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0091 | AC | AHU (Chilled-Water-Served) | AHU-PF | 2nd Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0092 | AC | AHU (Chilled-Water-Served) | AHU-PF | 2nd Floor | Fan VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0093 | AC | AHU (Chilled-Water-Served) | AHU-PF | 2nd Floor | Fan Control | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0094 | AC | AHU (Chilled-Water-Served) | AHU-PF | 2nd Floor | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0095 | AC | AHU (Chilled-Water-Served) | AHU-PF | 2nd Floor | Indoor Mixed Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0096 | AC | AHU (Chilled-Water-Served) | AHU-PF | 2nd Floor | Outdoor Damper Status | DI | Damper Controller | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0097 | AC | AHU (Chilled-Water-Served) | AHU-PF | 2nd Floor | Outdoor Damper Control | AO | Damper Controller | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0098 | AC | AHU (Chilled-Water-Served) | AHU-PF | 2nd Floor | Outside Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0099 | AC | AHU (Chilled-Water-Served) | AHU-EL | 2nd Floor | Indoor Return Air Damper Status | DI | Damper Controller | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0100 | AC | AHU (Chilled-Water-Served) | AHU-EL | 2nd Floor | Indoor Return Air Damper Control | AO | Damper Controller | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0101 | AC | AHU (Chilled-Water-Served) | AHU-EL | 2nd Floor | Indoor Return Air CO2 | AI | CO2 Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0102 | AC | AHU (Chilled-Water-Served) | AHU-EL | 2nd Floor | Indoor Return Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0103 | AC | AHU (Chilled-Water-Served) | AHU-EL | 2nd Floor | CHWS Valve Control | AO | Electric Valve Actuator | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0104 | AC | AHU (Chilled-Water-Served) | AHU-EL | 2nd Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0105 | AC | AHU (Chilled-Water-Served) | AHU-EL | 2nd Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0106 | AC | AHU (Chilled-Water-Served) | AHU-EL | 2nd Floor | Fan VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0107 | AC | AHU (Chilled-Water-Served) | AHU-EL | 2nd Floor | Fan Control | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0108 | AC | AHU (Chilled-Water-Served) | AHU-EL | 2nd Floor | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0109 | AC | AHU (Chilled-Water-Served) | AHU-EL | 2nd Floor | Indoor Mixed Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0110 | AC | AHU (Chilled-Water-Served) | AHU-EL | 2nd Floor | Outdoor Damper Status | DI | Damper Controller | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0111 | AC | AHU (Chilled-Water-Served) | AHU-EL | 2nd Floor | Outdoor Damper Control | AO | Damper Controller | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0112 | AC | AHU (Chilled-Water-Served) | AHU-EL | 2nd Floor | Outside Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0113 | AC | AHU (Chilled-Water-Served) | AHU-FR2 | 2nd Floor | Indoor Return Air Damper Status | DI | Damper Controller | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0114 | AC | AHU (Chilled-Water-Served) | AHU-FR2 | 2nd Floor | Indoor Return Air Damper Control | AO | Damper Controller | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0115 | AC | AHU (Chilled-Water-Served) | AHU-FR2 | 2nd Floor | Indoor Return Air CO2 | AI | CO2 Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0116 | AC | AHU (Chilled-Water-Served) | AHU-FR2 | 2nd Floor | Indoor Return Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0117 | AC | AHU (Chilled-Water-Served) | AHU-FR2 | 2nd Floor | CHWS Valve Control | AO | Electric Valve Actuator | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0118 | AC | AHU (Chilled-Water-Served) | AHU-FR2 | 2nd Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0119 | AC | AHU (Chilled-Water-Served) | AHU-FR2 | 2nd Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0120 | AC | AHU (Chilled-Water-Served) | AHU-FR2 | 2nd Floor | Fan VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0121 | AC | AHU (Chilled-Water-Served) | AHU-FR2 | 2nd Floor | Fan Control | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0122 | AC | AHU (Chilled-Water-Served) | AHU-FR2 | 2nd Floor | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0123 | AC | AHU (Chilled-Water-Served) | AHU-FR2 | 2nd Floor | Indoor Mixed Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0124 | AC | AHU (Chilled-Water-Served) | AHU-FR2 | 2nd Floor | Outdoor Damper Status | DI | Damper Controller | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0125 | AC | AHU (Chilled-Water-Served) | AHU-FR2 | 2nd Floor | Outdoor Damper Control | AO | Damper Controller | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0126 | AC | AHU (Chilled-Water-Served) | AHU-FR2 | 2nd Floor | Outside Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0127 | AC | AHU (Chilled-Water-Served) | AHU-FR3 | 2nd Floor | Indoor Return Air Damper Status | DI | Damper Controller | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0128 | AC | AHU (Chilled-Water-Served) | AHU-FR3 | 2nd Floor | Indoor Return Air Damper Control | AO | Damper Controller | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0129 | AC | AHU (Chilled-Water-Served) | AHU-FR3 | 2nd Floor | Indoor Return Air CO2 | AI | CO2 Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0130 | AC | AHU (Chilled-Water-Served) | AHU-FR3 | 2nd Floor | Indoor Return Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0131 | AC | AHU (Chilled-Water-Served) | AHU-FR3 | 2nd Floor | CHWS Valve Control | AO | Electric Valve Actuator | ME Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0132 | AC | AHU (Chilled-Water-Served) | AHU-FR3 | 2nd Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0133 | AC | AHU (Chilled-Water-Served) | AHU-FR3 | 2nd Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0134 | AC | AHU (Chilled-Water-Served) | AHU-FR3 | 2nd Floor | Fan VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0135 | AC | AHU (Chilled-Water-Served) | AHU-FR3 | 2nd Floor | Fan Control | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0136 | AC | AHU (Chilled-Water-Served) | AHU-FR3 | 2nd Floor | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0137 | AC | AHU (Chilled-Water-Served) | AHU-FR3 | 2nd Floor | Indoor Mixed Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0138 | AC | AHU (Chilled-Water-Served) | AHU-FR3 | 2nd Floor | Outdoor Damper Status | DI | Damper Controller | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0139 | AC | AHU (Chilled-Water-Served) | AHU-FR3 | 2nd Floor | Outdoor Damper Control | AO | Damper Controller | Equipment Supplier | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0140 | AC | AHU (Chilled-Water-Served) | AHU-FR3 | 2nd Floor | Outside Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Chilled-Water-Served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0141 | VENT | Precooled Air Handling Unit | PAHU-0.1 | Basement | Outside Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0142 | VENT | Precooled Air Handling Unit | PAHU-0.1 | Basement | Outside Supply Air Flow | AI | Flow Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0143 | VENT | Precooled Air Handling Unit | PAHU-0.1 | Basement | Outdoor Supply Air Humidity | AI | Humidity Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0144 | VENT | Precooled Air Handling Unit | PAHU-0.1 | Basement | Outdoor Damper Status | DI | Damper Controller | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0145 | VENT | Precooled Air Handling Unit | PAHU-0.1 | Basement | Outdoor Damper Control | AO | Damper Controller | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0146 | VENT | Precooled Air Handling Unit | PAHU-0.1 | Basement | CHWS Valve Status | DI | Electric Valve Actuator | ME Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0147 | VENT | Precooled Air Handling Unit | PAHU-0.1 | Basement | CHWS Valve Control | AO | Electric Valve Actuator | ME Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0148 | VENT | Precooled Air Handling Unit | PAHU-0.1 | Basement | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0149 | VENT | Precooled Air Handling Unit | PAHU-0.1 | Basement | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0150 | VENT | Precooled Air Handling Unit | PAHU-0.1 | Basement | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0151 | VENT | Precooled Air Handling Unit | PAHU-0.1 | Basement | Fan VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0152 | VENT | Precooled Air Handling Unit | PAHU-0.1 | Basement | Fan Control | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0153 | VENT | Precooled Air Handling Unit | PAHU-0.1 | Basement | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0154 | VENT | Precooled Air Handling Unit | PAHU-0.1 | Basement | BACnet/IP drop | Network | RJ45 to edge switch | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0155 | VENT | Precooled Air Handling Unit | PAHU-B1 | 2nd Floor | Outside Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0156 | VENT | Precooled Air Handling Unit | PAHU-B1 | 2nd Floor | Outside Supply Air Flow | AI | Flow Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0157 | VENT | Precooled Air Handling Unit | PAHU-B1 | 2nd Floor | Outdoor Supply Air Humidity | AI | Humidity Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0158 | VENT | Precooled Air Handling Unit | PAHU-B1 | 2nd Floor | Outdoor Damper Status | DI | Damper Controller | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0159 | VENT | Precooled Air Handling Unit | PAHU-B1 | 2nd Floor | Outdoor Damper Control | AO | Damper Controller | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0160 | VENT | Precooled Air Handling Unit | PAHU-B1 | 2nd Floor | CHWS Valve Status | DI | Electric Valve Actuator | ME Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0161 | VENT | Precooled Air Handling Unit | PAHU-B1 | 2nd Floor | CHWS Valve Control | AO | Electric Valve Actuator | ME Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0162 | VENT | Precooled Air Handling Unit | PAHU-B1 | 2nd Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0163 | VENT | Precooled Air Handling Unit | PAHU-B1 | 2nd Floor | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0164 | VENT | Precooled Air Handling Unit | PAHU-B1 | 2nd Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0165 | VENT | Precooled Air Handling Unit | PAHU-B1 | 2nd Floor | Fan VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0166 | VENT | Precooled Air Handling Unit | PAHU-B1 | 2nd Floor | Fan Control | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0167 | VENT | Precooled Air Handling Unit | PAHU-B1 | 2nd Floor | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0168 | VENT | Precooled Air Handling Unit | PAHU-B1 | 2nd Floor | BACnet/IP drop | Network | RJ45 to edge switch | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0169 | VENT | Precooled Air Handling Unit | PAHU-B2 | 2nd Floor | Outside Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0170 | VENT | Precooled Air Handling Unit | PAHU-B2 | 2nd Floor | Outside Supply Air Flow | AI | Flow Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0171 | VENT | Precooled Air Handling Unit | PAHU-B2 | 2nd Floor | Outdoor Supply Air Humidity | AI | Humidity Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0172 | VENT | Precooled Air Handling Unit | PAHU-B2 | 2nd Floor | Outdoor Damper Status | DI | Damper Controller | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0173 | VENT | Precooled Air Handling Unit | PAHU-B2 | 2nd Floor | Outdoor Damper Control | AO | Damper Controller | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0174 | VENT | Precooled Air Handling Unit | PAHU-B2 | 2nd Floor | CHWS Valve Status | DI | Electric Valve Actuator | ME Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0175 | VENT | Precooled Air Handling Unit | PAHU-B2 | 2nd Floor | CHWS Valve Control | AO | Electric Valve Actuator | ME Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0176 | VENT | Precooled Air Handling Unit | PAHU-B2 | 2nd Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0177 | VENT | Precooled Air Handling Unit | PAHU-B2 | 2nd Floor | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0178 | VENT | Precooled Air Handling Unit | PAHU-B2 | 2nd Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0179 | VENT | Precooled Air Handling Unit | PAHU-B2 | 2nd Floor | Fan VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0180 | VENT | Precooled Air Handling Unit | PAHU-B2 | 2nd Floor | Fan Control | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0181 | VENT | Precooled Air Handling Unit | PAHU-B2 | 2nd Floor | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0182 | VENT | Precooled Air Handling Unit | PAHU-B2 | 2nd Floor | BACnet/IP drop | Network | RJ45 to edge switch | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0183 | VENT | Precooled Air Handling Unit | PAHU-B3 | 2nd Floor | Outside Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0184 | VENT | Precooled Air Handling Unit | PAHU-B3 | 2nd Floor | Outside Supply Air Flow | AI | Flow Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0185 | VENT | Precooled Air Handling Unit | PAHU-B3 | 2nd Floor | Outdoor Supply Air Humidity | AI | Humidity Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0186 | VENT | Precooled Air Handling Unit | PAHU-B3 | 2nd Floor | Outdoor Damper Status | DI | Damper Controller | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0187 | VENT | Precooled Air Handling Unit | PAHU-B3 | 2nd Floor | Outdoor Damper Control | AO | Damper Controller | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0188 | VENT | Precooled Air Handling Unit | PAHU-B3 | 2nd Floor | CHWS Valve Status | DI | Electric Valve Actuator | ME Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0189 | VENT | Precooled Air Handling Unit | PAHU-B3 | 2nd Floor | CHWS Valve Control | AO | Electric Valve Actuator | ME Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0190 | VENT | Precooled Air Handling Unit | PAHU-B3 | 2nd Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0191 | VENT | Precooled Air Handling Unit | PAHU-B3 | 2nd Floor | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0192 | VENT | Precooled Air Handling Unit | PAHU-B3 | 2nd Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0193 | VENT | Precooled Air Handling Unit | PAHU-B3 | 2nd Floor | Fan VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0194 | VENT | Precooled Air Handling Unit | PAHU-B3 | 2nd Floor | Fan Control | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0195 | VENT | Precooled Air Handling Unit | PAHU-B3 | 2nd Floor | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0196 | VENT | Precooled Air Handling Unit | PAHU-B3 | 2nd Floor | BACnet/IP drop | Network | RJ45 to edge switch | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0197 | VENT | Precooled Air Handling Unit | PAHU-PF | 2nd Floor | Outside Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0198 | VENT | Precooled Air Handling Unit | PAHU-PF | 2nd Floor | Outside Supply Air Flow | AI | Flow Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0199 | VENT | Precooled Air Handling Unit | PAHU-PF | 2nd Floor | Outdoor Supply Air Humidity | AI | Humidity Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0200 | VENT | Precooled Air Handling Unit | PAHU-PF | 2nd Floor | Outdoor Damper Status | DI | Damper Controller | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0201 | VENT | Precooled Air Handling Unit | PAHU-PF | 2nd Floor | Outdoor Damper Control | AO | Damper Controller | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0202 | VENT | Precooled Air Handling Unit | PAHU-PF | 2nd Floor | CHWS Valve Status | DI | Electric Valve Actuator | ME Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0203 | VENT | Precooled Air Handling Unit | PAHU-PF | 2nd Floor | CHWS Valve Control | AO | Electric Valve Actuator | ME Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0204 | VENT | Precooled Air Handling Unit | PAHU-PF | 2nd Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0205 | VENT | Precooled Air Handling Unit | PAHU-PF | 2nd Floor | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0206 | VENT | Precooled Air Handling Unit | PAHU-PF | 2nd Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0207 | VENT | Precooled Air Handling Unit | PAHU-PF | 2nd Floor | Fan VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0208 | VENT | Precooled Air Handling Unit | PAHU-PF | 2nd Floor | Fan Control | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0209 | VENT | Precooled Air Handling Unit | PAHU-PF | 2nd Floor | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0210 | VENT | Precooled Air Handling Unit | PAHU-PF | 2nd Floor | BACnet/IP drop | Network | RJ45 to edge switch | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0211 | VENT | Precooled Air Handling Unit | PAHU-FR | 2nd Floor | Outside Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0212 | VENT | Precooled Air Handling Unit | PAHU-FR | 2nd Floor | Outside Supply Air Flow | AI | Flow Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0213 | VENT | Precooled Air Handling Unit | PAHU-FR | 2nd Floor | Outdoor Supply Air Humidity | AI | Humidity Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0214 | VENT | Precooled Air Handling Unit | PAHU-FR | 2nd Floor | Outdoor Damper Status | DI | Damper Controller | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0215 | VENT | Precooled Air Handling Unit | PAHU-FR | 2nd Floor | Outdoor Damper Control | AO | Damper Controller | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0216 | VENT | Precooled Air Handling Unit | PAHU-FR | 2nd Floor | CHWS Valve Status | DI | Electric Valve Actuator | ME Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0217 | VENT | Precooled Air Handling Unit | PAHU-FR | 2nd Floor | CHWS Valve Control | AO | Electric Valve Actuator | ME Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0218 | VENT | Precooled Air Handling Unit | PAHU-FR | 2nd Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0219 | VENT | Precooled Air Handling Unit | PAHU-FR | 2nd Floor | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0220 | VENT | Precooled Air Handling Unit | PAHU-FR | 2nd Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0221 | VENT | Precooled Air Handling Unit | PAHU-FR | 2nd Floor | Fan VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0222 | VENT | Precooled Air Handling Unit | PAHU-FR | 2nd Floor | Fan Control | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0223 | VENT | Precooled Air Handling Unit | PAHU-FR | 2nd Floor | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0224 | VENT | Precooled Air Handling Unit | PAHU-FR | 2nd Floor | BACnet/IP drop | Network | RJ45 to edge switch | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0225 | AC | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor (Casino) | Indoor Return Air Damper Status | DI | Damper Controller | ME Contractor | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0226 | AC | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor (Casino) | Indoor Return Air Damper Control | AO | Damper Controller | ME Contractor | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0227 | AC | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor (Casino) | Indoor Return Air CO2 | AI | CO2 Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0228 | AC | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor (Casino) | Indoor Return Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0229 | AC | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor (Casino) | CHWS Valve Control | AO | Electric Valve Actuator | ME Contractor | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0230 | AC | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor (Casino) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0231 | AC | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor (Casino) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0232 | AC | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor (Casino) | Fan VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0233 | AC | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor (Casino) | Fan Control | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0234 | AC | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor (Casino) | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0235 | AC | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor (Casino) | Indoor Mixed Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0236 | AC | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor (Casino) | Outdoor Damper Status | DI | Damper Controller | Equipment Supplier | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0237 | AC | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor (Casino) | Outdoor Damper Control | AO | Damper Controller | Equipment Supplier | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0238 | AC | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor (Casino) | Outside Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0239 | AC | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor (Casino) | Outdoor Air Humidity (Casino) | AI | Humidity Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0240 | AC | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor (Casino) | Indoor Mixed Air Humidity | AI | Humidity Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0241 | AC | AHU (Modulating CHW-served) | AHU-2M.1 | 2nd Floor (Casino) | Return Air CO sensor (Casino) | AI | CO Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0242 | AC | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor (Casino) | Indoor Return Air Damper Status | DI | Damper Controller | ME Contractor | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0243 | AC | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor (Casino) | Indoor Return Air Damper Control | AO | Damper Controller | ME Contractor | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0244 | AC | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor (Casino) | Indoor Return Air CO2 | AI | CO2 Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0245 | AC | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor (Casino) | Indoor Return Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0246 | AC | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor (Casino) | CHWS Valve Control | AO | Electric Valve Actuator | ME Contractor | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0247 | AC | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor (Casino) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0248 | AC | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor (Casino) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0249 | AC | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor (Casino) | Fan VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0250 | AC | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor (Casino) | Fan Control | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0251 | AC | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor (Casino) | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0252 | AC | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor (Casino) | Indoor Mixed Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0253 | AC | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor (Casino) | Outdoor Damper Status | DI | Damper Controller | Equipment Supplier | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0254 | AC | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor (Casino) | Outdoor Damper Control | AO | Damper Controller | Equipment Supplier | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0255 | AC | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor (Casino) | Outside Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0256 | AC | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor (Casino) | Outdoor Air Humidity (Casino) | AI | Humidity Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0257 | AC | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor (Casino) | Indoor Mixed Air Humidity | AI | Humidity Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0258 | AC | AHU (Modulating CHW-served) | AHU-2M.2 | 2nd Floor (Casino) | Return Air CO sensor (Casino) | AI | CO Sensor | BMS Contractor | DRC-004-2024 AC/AHU (Modulating CHW-served) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0259 | VENT | DOAS Unit | DOAS-2M | 2nd Floor (Casino) | Outside Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0260 | VENT | DOAS Unit | DOAS-2M | 2nd Floor (Casino) | Outside Supply Air Flow | AI | Flow Sensor | BMS Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0261 | VENT | DOAS Unit | DOAS-2M | 2nd Floor (Casino) | Outdoor Supply Air Humidity | AI | Humidity Sensor | BMS Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0262 | VENT | DOAS Unit | DOAS-2M | 2nd Floor (Casino) | Outdoor Supply Air Motorized Damper Status | DI | Damper Controller | ME Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0263 | VENT | DOAS Unit | DOAS-2M | 2nd Floor (Casino) | Outdoor Supply Air Motorized Damper Control | AO | Damper Controller | ME Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0264 | VENT | DOAS Unit | DOAS-2M | 2nd Floor (Casino) | Recovery Wheel Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0265 | VENT | DOAS Unit | DOAS-2M | 2nd Floor (Casino) | Recovery Wheel Motor Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0266 | VENT | DOAS Unit | DOAS-2M | 2nd Floor (Casino) | Supply Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0267 | VENT | DOAS Unit | DOAS-2M | 2nd Floor (Casino) | Supply Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0268 | VENT | DOAS Unit | DOAS-2M | 2nd Floor (Casino) | Supply Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0269 | VENT | DOAS Unit | DOAS-2M | 2nd Floor (Casino) | Supply Fan VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0270 | VENT | DOAS Unit | DOAS-2M | 2nd Floor (Casino) | Supply Fan Control | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0271 | VENT | DOAS Unit | DOAS-2M | 2nd Floor (Casino) | Indoor Mixed Air Temperature | AI | Temperature Sensor | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0272 | VENT | DOAS Unit | DOAS-2M | 2nd Floor (Casino) | Indoor Mixed Air Humidity | AI | Humidity Sensor | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0273 | VENT | DOAS Unit | DOAS-2M | 2nd Floor (Casino) | CHWS Cooling Coil Valve Status | DI | Electric Valve Actuator | ME Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0274 | VENT | DOAS Unit | DOAS-2M | 2nd Floor (Casino) | CHWS Valve Control | AO | Electric Valve Actuator | ME Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0275 | VENT | DOAS Unit | DOAS-2M | 2nd Floor (Casino) | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0276 | VENT | DOAS Unit | DOAS-2M | 2nd Floor (Casino) | Indoor Exhaust Air Humidity | AI | Humidity Sensor | BMS Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0277 | VENT | DOAS Unit | DOAS-2M | 2nd Floor (Casino) | Indoor Exhaust Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0278 | VENT | DOAS Unit | DOAS-2M | 2nd Floor (Casino) | Exhaust Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0279 | VENT | DOAS Unit | DOAS-2M | 2nd Floor (Casino) | Exhaust Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0280 | VENT | DOAS Unit | DOAS-2M | 2nd Floor (Casino) | Exhaust Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0281 | VENT | DOAS Unit | DOAS-2M | 2nd Floor (Casino) | Exhaust Fan VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0282 | VENT | DOAS Unit | DOAS-2M | 2nd Floor (Casino) | Exhaust Fan Control | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0283 | VENT | DOAS Unit | DOAS-2M | 2nd Floor (Casino) | BACnet/IP drop | Network | RJ45 to edge switch | BMS Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0284 | VENT | DOAS Unit | DOAS-RD.1 | Roofdeck | Outside Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0285 | VENT | DOAS Unit | DOAS-RD.1 | Roofdeck | Outside Supply Air Flow | AI | Flow Sensor | BMS Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0286 | VENT | DOAS Unit | DOAS-RD.1 | Roofdeck | Outdoor Supply Air Humidity | AI | Humidity Sensor | BMS Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0287 | VENT | DOAS Unit | DOAS-RD.1 | Roofdeck | Outdoor Supply Air Motorized Damper Status | DI | Damper Controller | ME Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0288 | VENT | DOAS Unit | DOAS-RD.1 | Roofdeck | Outdoor Supply Air Motorized Damper Control | AO | Damper Controller | ME Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0289 | VENT | DOAS Unit | DOAS-RD.1 | Roofdeck | Recovery Wheel Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0290 | VENT | DOAS Unit | DOAS-RD.1 | Roofdeck | Recovery Wheel Motor Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0291 | VENT | DOAS Unit | DOAS-RD.1 | Roofdeck | Supply Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0292 | VENT | DOAS Unit | DOAS-RD.1 | Roofdeck | Supply Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0293 | VENT | DOAS Unit | DOAS-RD.1 | Roofdeck | Supply Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0294 | VENT | DOAS Unit | DOAS-RD.1 | Roofdeck | Supply Fan VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0295 | VENT | DOAS Unit | DOAS-RD.1 | Roofdeck | Supply Fan Control | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0296 | VENT | DOAS Unit | DOAS-RD.1 | Roofdeck | Indoor Mixed Air Temperature | AI | Temperature Sensor | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0297 | VENT | DOAS Unit | DOAS-RD.1 | Roofdeck | Indoor Mixed Air Humidity | AI | Humidity Sensor | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0298 | VENT | DOAS Unit | DOAS-RD.1 | Roofdeck | CHWS Cooling Coil Valve Status | DI | Electric Valve Actuator | ME Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0299 | VENT | DOAS Unit | DOAS-RD.1 | Roofdeck | CHWS Valve Control | AO | Electric Valve Actuator | ME Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0300 | VENT | DOAS Unit | DOAS-RD.1 | Roofdeck | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0301 | VENT | DOAS Unit | DOAS-RD.1 | Roofdeck | Indoor Exhaust Air Humidity | AI | Humidity Sensor | BMS Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0302 | VENT | DOAS Unit | DOAS-RD.1 | Roofdeck | Indoor Exhaust Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0303 | VENT | DOAS Unit | DOAS-RD.1 | Roofdeck | Exhaust Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0304 | VENT | DOAS Unit | DOAS-RD.1 | Roofdeck | Exhaust Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0305 | VENT | DOAS Unit | DOAS-RD.1 | Roofdeck | Exhaust Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0306 | VENT | DOAS Unit | DOAS-RD.1 | Roofdeck | Exhaust Fan VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0307 | VENT | DOAS Unit | DOAS-RD.1 | Roofdeck | Exhaust Fan Control | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0308 | VENT | DOAS Unit | DOAS-RD.1 | Roofdeck | BACnet/IP drop | Network | RJ45 to edge switch | BMS Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0309 | VENT | DOAS Unit | DOAS-RD.2 | Roofdeck | Outside Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0310 | VENT | DOAS Unit | DOAS-RD.2 | Roofdeck | Outside Supply Air Flow | AI | Flow Sensor | BMS Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0311 | VENT | DOAS Unit | DOAS-RD.2 | Roofdeck | Outdoor Supply Air Humidity | AI | Humidity Sensor | BMS Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0312 | VENT | DOAS Unit | DOAS-RD.2 | Roofdeck | Outdoor Supply Air Motorized Damper Status | DI | Damper Controller | ME Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0313 | VENT | DOAS Unit | DOAS-RD.2 | Roofdeck | Outdoor Supply Air Motorized Damper Control | AO | Damper Controller | ME Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0314 | VENT | DOAS Unit | DOAS-RD.2 | Roofdeck | Recovery Wheel Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0315 | VENT | DOAS Unit | DOAS-RD.2 | Roofdeck | Recovery Wheel Motor Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0316 | VENT | DOAS Unit | DOAS-RD.2 | Roofdeck | Supply Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0317 | VENT | DOAS Unit | DOAS-RD.2 | Roofdeck | Supply Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0318 | VENT | DOAS Unit | DOAS-RD.2 | Roofdeck | Supply Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0319 | VENT | DOAS Unit | DOAS-RD.2 | Roofdeck | Supply Fan VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0320 | VENT | DOAS Unit | DOAS-RD.2 | Roofdeck | Supply Fan Control | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0321 | VENT | DOAS Unit | DOAS-RD.2 | Roofdeck | Indoor Mixed Air Temperature | AI | Temperature Sensor | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0322 | VENT | DOAS Unit | DOAS-RD.2 | Roofdeck | Indoor Mixed Air Humidity | AI | Humidity Sensor | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0323 | VENT | DOAS Unit | DOAS-RD.2 | Roofdeck | CHWS Cooling Coil Valve Status | DI | Electric Valve Actuator | ME Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0324 | VENT | DOAS Unit | DOAS-RD.2 | Roofdeck | CHWS Valve Control | AO | Electric Valve Actuator | ME Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0325 | VENT | DOAS Unit | DOAS-RD.2 | Roofdeck | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0326 | VENT | DOAS Unit | DOAS-RD.2 | Roofdeck | Indoor Exhaust Air Humidity | AI | Humidity Sensor | BMS Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0327 | VENT | DOAS Unit | DOAS-RD.2 | Roofdeck | Indoor Exhaust Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0328 | VENT | DOAS Unit | DOAS-RD.2 | Roofdeck | Exhaust Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0329 | VENT | DOAS Unit | DOAS-RD.2 | Roofdeck | Exhaust Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0330 | VENT | DOAS Unit | DOAS-RD.2 | Roofdeck | Exhaust Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0331 | VENT | DOAS Unit | DOAS-RD.2 | Roofdeck | Exhaust Fan VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0332 | VENT | DOAS Unit | DOAS-RD.2 | Roofdeck | Exhaust Fan Control | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0333 | VENT | DOAS Unit | DOAS-RD.2 | Roofdeck | BACnet/IP drop | Network | RJ45 to edge switch | BMS Contractor | DRC-004-2024 VENT/DOAS Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0334 | VENT | Precooled Air Handling Unit | PAHU-RD.1 | Roofdeck | Outside Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0335 | VENT | Precooled Air Handling Unit | PAHU-RD.1 | Roofdeck | Outside Supply Air Flow | AI | Flow Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0336 | VENT | Precooled Air Handling Unit | PAHU-RD.1 | Roofdeck | Outdoor Supply Air Humidity | AI | Humidity Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0337 | VENT | Precooled Air Handling Unit | PAHU-RD.1 | Roofdeck | Outdoor Damper Status | DI | Damper Controller | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0338 | VENT | Precooled Air Handling Unit | PAHU-RD.1 | Roofdeck | Outdoor Damper Control | AO | Damper Controller | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0339 | VENT | Precooled Air Handling Unit | PAHU-RD.1 | Roofdeck | CHWS Valve Status | DI | Electric Valve Actuator | ME Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0340 | VENT | Precooled Air Handling Unit | PAHU-RD.1 | Roofdeck | CHWS Valve Control | AO | Electric Valve Actuator | ME Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0341 | VENT | Precooled Air Handling Unit | PAHU-RD.1 | Roofdeck | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0342 | VENT | Precooled Air Handling Unit | PAHU-RD.1 | Roofdeck | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0343 | VENT | Precooled Air Handling Unit | PAHU-RD.1 | Roofdeck | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0344 | VENT | Precooled Air Handling Unit | PAHU-RD.1 | Roofdeck | Fan VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0345 | VENT | Precooled Air Handling Unit | PAHU-RD.1 | Roofdeck | Fan Control | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0346 | VENT | Precooled Air Handling Unit | PAHU-RD.1 | Roofdeck | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0347 | VENT | Precooled Air Handling Unit | PAHU-RD.1 | Roofdeck | BACnet/IP drop | Network | RJ45 to edge switch | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0348 | VENT | Precooled Air Handling Unit | PAHU-RD.2 | Roofdeck | Outside Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0349 | VENT | Precooled Air Handling Unit | PAHU-RD.2 | Roofdeck | Outside Supply Air Flow | AI | Flow Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0350 | VENT | Precooled Air Handling Unit | PAHU-RD.2 | Roofdeck | Outdoor Supply Air Humidity | AI | Humidity Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0351 | VENT | Precooled Air Handling Unit | PAHU-RD.2 | Roofdeck | Outdoor Damper Status | DI | Damper Controller | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0352 | VENT | Precooled Air Handling Unit | PAHU-RD.2 | Roofdeck | Outdoor Damper Control | AO | Damper Controller | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0353 | VENT | Precooled Air Handling Unit | PAHU-RD.2 | Roofdeck | CHWS Valve Status | DI | Electric Valve Actuator | ME Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0354 | VENT | Precooled Air Handling Unit | PAHU-RD.2 | Roofdeck | CHWS Valve Control | AO | Electric Valve Actuator | ME Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0355 | VENT | Precooled Air Handling Unit | PAHU-RD.2 | Roofdeck | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0356 | VENT | Precooled Air Handling Unit | PAHU-RD.2 | Roofdeck | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0357 | VENT | Precooled Air Handling Unit | PAHU-RD.2 | Roofdeck | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0358 | VENT | Precooled Air Handling Unit | PAHU-RD.2 | Roofdeck | Fan VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0359 | VENT | Precooled Air Handling Unit | PAHU-RD.2 | Roofdeck | Fan Control | HLI | VFD | Equipment Supplier | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0360 | VENT | Precooled Air Handling Unit | PAHU-RD.2 | Roofdeck | Indoor Supply Air Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0361 | VENT | Precooled Air Handling Unit | PAHU-RD.2 | Roofdeck | BACnet/IP drop | Network | RJ45 to edge switch | BMS Contractor | DRC-004-2024 VENT/Precooled Air Handling Unit | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0362 | AC | Ozone Generator (UV-light or Corona) | ION-2M.1 | 2nd Floor (Casino) | Equipment Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Ozone Generator (UV-light or Corona) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0363 | AC | Ozone Generator (UV-light or Corona) | ION-2M.1 | 2nd Floor (Casino) | Equipment Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Ozone Generator (UV-light or Corona) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0364 | AC | Ozone Generator (UV-light or Corona) | ION-2M.1 | 2nd Floor (Casino) | VOC Monitoring | AI | VOC Sensor | BMS Contractor | DRC-004-2024 AC/Ozone Generator (UV-light or Corona) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0365 | AC | Ozone Generator (UV-light or Corona) | ION-2M.2 | 2nd Floor (Casino) | Equipment Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Ozone Generator (UV-light or Corona) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0366 | AC | Ozone Generator (UV-light or Corona) | ION-2M.2 | 2nd Floor (Casino) | Equipment Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Ozone Generator (UV-light or Corona) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0367 | AC | Ozone Generator (UV-light or Corona) | ION-2M.2 | 2nd Floor (Casino) | VOC Monitoring | AI | VOC Sensor | BMS Contractor | DRC-004-2024 AC/Ozone Generator (UV-light or Corona) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0368 | VENT | Exhaust Fan (Toilet) | TEF-1.1 | Ground Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0369 | VENT | Exhaust Fan (Toilet) | TEF-1.1 | Ground Floor | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0370 | VENT | Exhaust Fan (Toilet) | TEF-1.1 | Ground Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0371 | VENT | Exhaust Fan (Toilet) | TEF-1.2 | Ground Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0372 | VENT | Exhaust Fan (Toilet) | TEF-1.2 | Ground Floor | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0373 | VENT | Exhaust Fan (Toilet) | TEF-1.2 | Ground Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0374 | VENT | Exhaust Fan (Toilet) | TEF-1.3 | Ground Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0375 | VENT | Exhaust Fan (Toilet) | TEF-1.3 | Ground Floor | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0376 | VENT | Exhaust Fan (Toilet) | TEF-1.3 | Ground Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0377 | VENT | Exhaust Fan (Toilet) | TEF-1.4 | Ground Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0378 | VENT | Exhaust Fan (Toilet) | TEF-1.4 | Ground Floor | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0379 | VENT | Exhaust Fan (Toilet) | TEF-1.4 | Ground Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0380 | VENT | Exhaust Fan (General) | EF-1.2A | Ground Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0381 | VENT | Exhaust Fan (General) | EF-1.2A | Ground Floor | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0382 | VENT | Exhaust Fan (General) | EF-1.2A | Ground Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0383 | VENT | Exhaust Fan (General) | EF-LPG.1 | Ground Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0384 | VENT | Exhaust Fan (General) | EF-LPG.1 | Ground Floor | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0385 | VENT | Exhaust Fan (General) | EF-LPG.1 | Ground Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0386 | VENT | Exhaust Fan (General) | EF-1MR.1 | Ground Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0387 | VENT | Exhaust Fan (General) | EF-1MR.1 | Ground Floor | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0388 | VENT | Exhaust Fan (General) | EF-1MR.1 | Ground Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0389 | VENT | Exhaust Fan (General) | EF-1ST0.1 | Ground Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0390 | VENT | Exhaust Fan (General) | EF-1ST0.1 | Ground Floor | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0391 | VENT | Exhaust Fan (General) | EF-1ST0.1 | Ground Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0392 | VENT | Exhaust Fan (General) | EF-MRF.1 | Ground Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0393 | VENT | Exhaust Fan (General) | EF-MRF.1 | Ground Floor | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0394 | VENT | Exhaust Fan (General) | EF-MRF.1 | Ground Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-GF | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0395 | VENT | Exhaust Fan (Toilet) | TEF-2.1 | 2nd Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0396 | VENT | Exhaust Fan (Toilet) | TEF-2.1 | 2nd Floor | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0397 | VENT | Exhaust Fan (Toilet) | TEF-2.1 | 2nd Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0398 | VENT | Exhaust Fan (Toilet) | TEF-2.3 | 2nd Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0399 | VENT | Exhaust Fan (Toilet) | TEF-2.3 | 2nd Floor | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0400 | VENT | Exhaust Fan (Toilet) | TEF-2.3 | 2nd Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0401 | VENT | Exhaust Fan (Toilet) | TEF-2B.3 | 2nd Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0402 | VENT | Exhaust Fan (Toilet) | TEF-2B.3 | 2nd Floor | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0403 | VENT | Exhaust Fan (Toilet) | TEF-2B.3 | 2nd Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0404 | VENT | Exhaust Fan (General) | EF-2B.1 | 2nd Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0405 | VENT | Exhaust Fan (General) | EF-2B.1 | 2nd Floor | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0406 | VENT | Exhaust Fan (General) | EF-2B.1 | 2nd Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0407 | VENT | Exhaust Fan (General) | EF-2B.2 | 2nd Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0408 | VENT | Exhaust Fan (General) | EF-2B.2 | 2nd Floor | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0409 | VENT | Exhaust Fan (General) | EF-2B.2 | 2nd Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0410 | VENT | Exhaust Fan (General) | EF-GS.1 | 2nd Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0411 | VENT | Exhaust Fan (General) | EF-GS.1 | 2nd Floor | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0412 | VENT | Exhaust Fan (General) | EF-GS.1 | 2nd Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0413 | VENT | Exhaust Fan (General) | EF-GS.2 | 2nd Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0414 | VENT | Exhaust Fan (General) | EF-GS.2 | 2nd Floor | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0415 | VENT | Exhaust Fan (General) | EF-GS.2 | 2nd Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0416 | VENT | Exhaust Fan (General) | EF-2.1 | 2nd Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0417 | VENT | Exhaust Fan (General) | EF-2.1 | 2nd Floor | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0418 | VENT | Exhaust Fan (General) | EF-2.1 | 2nd Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0419 | VENT | Exhaust Fan (General) | EF-2.2 | 2nd Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0420 | VENT | Exhaust Fan (General) | EF-2.2 | 2nd Floor | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0421 | VENT | Exhaust Fan (General) | EF-2.2 | 2nd Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0422 | VENT | Exhaust Fan (General) | EF-2.3 | 2nd Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0423 | VENT | Exhaust Fan (General) | EF-2.3 | 2nd Floor | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0424 | VENT | Exhaust Fan (General) | EF-2.3 | 2nd Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0425 | VENT | Exhaust Fan (General) | EF-2.4 | 2nd Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0426 | VENT | Exhaust Fan (General) | EF-2.4 | 2nd Floor | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0427 | VENT | Exhaust Fan (General) | EF-2.4 | 2nd Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0428 | VENT | Exhaust Fan (General) | EF-CHR.1 | 2nd Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0429 | VENT | Exhaust Fan (General) | EF-CHR.1 | 2nd Floor | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0430 | VENT | Exhaust Fan (General) | EF-CHR.1 | 2nd Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0431 | VENT | Exhaust Fan (General) | EF-CHR.2 | 2nd Floor | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0432 | VENT | Exhaust Fan (General) | EF-CHR.2 | 2nd Floor | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0433 | VENT | Exhaust Fan (General) | EF-CHR.2 | 2nd Floor | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-2F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0434 | VENT | Exhaust Fan (Toilet) | TEF-3A.1 | 3rd Floor (Amenity) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0435 | VENT | Exhaust Fan (Toilet) | TEF-3A.1 | 3rd Floor (Amenity) | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0436 | VENT | Exhaust Fan (Toilet) | TEF-3A.1 | 3rd Floor (Amenity) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0437 | VENT | Exhaust Fan (Toilet) | TEF-3A.2 | 3rd Floor (Amenity) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0438 | VENT | Exhaust Fan (Toilet) | TEF-3A.2 | 3rd Floor (Amenity) | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0439 | VENT | Exhaust Fan (Toilet) | TEF-3A.2 | 3rd Floor (Amenity) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0440 | VENT | Exhaust Fan (Toilet) | TEF-3B.1 | 3rd Floor (Amenity) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0441 | VENT | Exhaust Fan (Toilet) | TEF-3B.1 | 3rd Floor (Amenity) | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0442 | VENT | Exhaust Fan (Toilet) | TEF-3B.1 | 3rd Floor (Amenity) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0443 | VENT | Exhaust Fan (Toilet) | TEF-3C.1 | 3rd Floor (Amenity) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0444 | VENT | Exhaust Fan (Toilet) | TEF-3C.1 | 3rd Floor (Amenity) | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0445 | VENT | Exhaust Fan (Toilet) | TEF-3C.1 | 3rd Floor (Amenity) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0446 | VENT | Exhaust Fan (Toilet) | TEF-3C.2 | 3rd Floor (Amenity) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0447 | VENT | Exhaust Fan (Toilet) | TEF-3C.2 | 3rd Floor (Amenity) | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0448 | VENT | Exhaust Fan (Toilet) | TEF-3C.2 | 3rd Floor (Amenity) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0449 | VENT | Exhaust Fan (Toilet) | TEF-3D.1 | 3rd Floor (Guestroom) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0450 | VENT | Exhaust Fan (Toilet) | TEF-3D.1 | 3rd Floor (Guestroom) | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0451 | VENT | Exhaust Fan (Toilet) | TEF-3D.1 | 3rd Floor (Guestroom) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0452 | VENT | Exhaust Fan (Toilet) | TEF-3D.2 | 3rd Floor (Guestroom) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0453 | VENT | Exhaust Fan (Toilet) | TEF-3D.2 | 3rd Floor (Guestroom) | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0454 | VENT | Exhaust Fan (Toilet) | TEF-3D.2 | 3rd Floor (Guestroom) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0455 | VENT | Exhaust Fan (Toilet) | TEF-3D.3 | 3rd Floor (Guestroom) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0456 | VENT | Exhaust Fan (Toilet) | TEF-3D.3 | 3rd Floor (Guestroom) | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0457 | VENT | Exhaust Fan (Toilet) | TEF-3D.3 | 3rd Floor (Guestroom) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0458 | VENT | Exhaust Fan (Toilet) | TEF-3D.4 | 3rd Floor (Guestroom) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0459 | VENT | Exhaust Fan (Toilet) | TEF-3D.4 | 3rd Floor (Guestroom) | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0460 | VENT | Exhaust Fan (Toilet) | TEF-3D.4 | 3rd Floor (Guestroom) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0461 | VENT | Exhaust Fan (Toilet) | TEF-3D.5 | 3rd Floor (Guestroom) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0462 | VENT | Exhaust Fan (Toilet) | TEF-3D.5 | 3rd Floor (Guestroom) | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0463 | VENT | Exhaust Fan (Toilet) | TEF-3D.5 | 3rd Floor (Guestroom) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0464 | VENT | Exhaust Fan (Toilet) | TEF-3D.6 | 3rd Floor (Guestroom) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0465 | VENT | Exhaust Fan (Toilet) | TEF-3D.6 | 3rd Floor (Guestroom) | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0466 | VENT | Exhaust Fan (Toilet) | TEF-3D.6 | 3rd Floor (Guestroom) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0467 | VENT | Exhaust Fan (Toilet) | TEF-3D.7 | 3rd Floor (Guestroom) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0468 | VENT | Exhaust Fan (Toilet) | TEF-3D.7 | 3rd Floor (Guestroom) | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0469 | VENT | Exhaust Fan (Toilet) | TEF-3D.7 | 3rd Floor (Guestroom) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0470 | VENT | Exhaust Fan (Toilet) | TEF-3D.8 | 3rd Floor (Guestroom) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0471 | VENT | Exhaust Fan (Toilet) | TEF-3D.8 | 3rd Floor (Guestroom) | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0472 | VENT | Exhaust Fan (Toilet) | TEF-3D.8 | 3rd Floor (Guestroom) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0473 | VENT | Exhaust Fan (Toilet) | TEF-3D.9 | 3rd Floor (Guestroom) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0474 | VENT | Exhaust Fan (Toilet) | TEF-3D.9 | 3rd Floor (Guestroom) | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0475 | VENT | Exhaust Fan (Toilet) | TEF-3D.9 | 3rd Floor (Guestroom) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0476 | VENT | Exhaust Fan (Toilet) | TEF-3D.10 | 3rd Floor (Guestroom) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0477 | VENT | Exhaust Fan (Toilet) | TEF-3D.10 | 3rd Floor (Guestroom) | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0478 | VENT | Exhaust Fan (Toilet) | TEF-3D.10 | 3rd Floor (Guestroom) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0479 | VENT | Exhaust Fan (Toilet) | TEF-3D.11 | 3rd Floor (Guestroom) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0480 | VENT | Exhaust Fan (Toilet) | TEF-3D.11 | 3rd Floor (Guestroom) | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0481 | VENT | Exhaust Fan (Toilet) | TEF-3D.11 | 3rd Floor (Guestroom) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0482 | VENT | Exhaust Fan (Toilet) | TEF-3D.12 | 3rd Floor (Guestroom) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0483 | VENT | Exhaust Fan (Toilet) | TEF-3D.12 | 3rd Floor (Guestroom) | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0484 | VENT | Exhaust Fan (Toilet) | TEF-3D.12 | 3rd Floor (Guestroom) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0485 | VENT | Exhaust Fan (Toilet) | TEF-3D.13 | 3rd Floor (Guestroom) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0486 | VENT | Exhaust Fan (Toilet) | TEF-3D.13 | 3rd Floor (Guestroom) | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0487 | VENT | Exhaust Fan (Toilet) | TEF-3D.13 | 3rd Floor (Guestroom) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0488 | VENT | Exhaust Fan (Toilet) | TEF-3D.14 | 3rd Floor (Guestroom) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0489 | VENT | Exhaust Fan (Toilet) | TEF-3D.14 | 3rd Floor (Guestroom) | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0490 | VENT | Exhaust Fan (Toilet) | TEF-3D.14 | 3rd Floor (Guestroom) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0491 | VENT | Exhaust Fan (Toilet) | TEF-3D.15 | 3rd Floor (Guestroom) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0492 | VENT | Exhaust Fan (Toilet) | TEF-3D.15 | 3rd Floor (Guestroom) | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0493 | VENT | Exhaust Fan (Toilet) | TEF-3D.15 | 3rd Floor (Guestroom) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0494 | VENT | Exhaust Fan (Toilet) | TEF-3D.16 | 3rd Floor (Guestroom) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0495 | VENT | Exhaust Fan (Toilet) | TEF-3D.16 | 3rd Floor (Guestroom) | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0496 | VENT | Exhaust Fan (Toilet) | TEF-3D.16 | 3rd Floor (Guestroom) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0497 | VENT | Exhaust Fan (Toilet) | TEF-3D.17 | 3rd Floor (Guestroom) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0498 | VENT | Exhaust Fan (Toilet) | TEF-3D.17 | 3rd Floor (Guestroom) | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0499 | VENT | Exhaust Fan (Toilet) | TEF-3D.17 | 3rd Floor (Guestroom) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0500 | VENT | Exhaust Fan (Toilet) | TEF-3D.18 | 3rd Floor (Guestroom) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0501 | VENT | Exhaust Fan (Toilet) | TEF-3D.18 | 3rd Floor (Guestroom) | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0502 | VENT | Exhaust Fan (Toilet) | TEF-3D.18 | 3rd Floor (Guestroom) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0503 | VENT | Exhaust Fan (Toilet) | TEF-3D.19 | 3rd Floor (Guestroom) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0504 | VENT | Exhaust Fan (Toilet) | TEF-3D.19 | 3rd Floor (Guestroom) | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0505 | VENT | Exhaust Fan (Toilet) | TEF-3D.19 | 3rd Floor (Guestroom) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0506 | VENT | Exhaust Fan (Toilet) | TEF-3D.20 | 3rd Floor (Guestroom) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0507 | VENT | Exhaust Fan (Toilet) | TEF-3D.20 | 3rd Floor (Guestroom) | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0508 | VENT | Exhaust Fan (Toilet) | TEF-3D.20 | 3rd Floor (Guestroom) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (Toilet) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0509 | VENT | Exhaust Fan (General) | EF-3GE.1 | 3rd Floor (Amenity) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0510 | VENT | Exhaust Fan (General) | EF-3GE.1 | 3rd Floor (Amenity) | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0511 | VENT | Exhaust Fan (General) | EF-3GE.1 | 3rd Floor (Amenity) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0512 | VENT | Exhaust Fan (General) | EF-3GE.2 | 3rd Floor (Amenity) | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0513 | VENT | Exhaust Fan (General) | EF-3GE.2 | 3rd Floor (Amenity) | Fan HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0514 | VENT | Exhaust Fan (General) | EF-3GE.2 | 3rd Floor (Amenity) | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Exhaust Fan (General) | FCP-3F | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0515 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | Entering Chilled Water Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0516 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | Leaving Chilled Water Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0517 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | CHW Isolation Valve Status (Return) | DI | Electric Valve Actuator | ME Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0518 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | CHW Isolation Valve Status (Supply) | DI | Electric Valve Actuator | ME Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0519 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | Evaporator Approach dT | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0520 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | Evaporator Approach dP | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0521 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | Evaporator Refrigerant Pressure | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0522 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | Evaporator Refrigerant Temperature | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0523 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | Oil Sump Pressure | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0524 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | Oil Sump Temperature | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0525 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | Oil Pump Status | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0526 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | Oil Pump Trip | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0527 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | Compressor Status | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0528 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | Compressor HOA Status | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0529 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | Compressor Trip | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0530 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | Motor Load Current | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0531 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | Motor kW / BTU Meter | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0532 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | Winding Temperature | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0533 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | Condenser Refrigerant Pressure | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0534 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | Condenser Refrigerant Temperature | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0535 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | Condenser Approach dT | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0536 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | Condenser Approach dP | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0537 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | COW Isolation Valve Status (Return) | DI | Electric Valve Actuator | ME Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0538 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | COW Isolation Valve Status (Supply) | DI | Electric Valve Actuator | ME Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0539 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | Entering Condenser Water Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0540 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | Leaving Condenser Water Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0541 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | CHW Return Flow | AI | Flow Sensor | BMS Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0542 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | CHW Supply Flow | AI | Flow Sensor | BMS Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0543 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | COW Supply Flow | AI | Flow Sensor | BMS Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0544 | AC | Chiller (Package Water-Cooled) | CH-1 | 2nd Floor (Plant Room) | BACnet/IP gateway | Network | Chiller native BACnet | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0545 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | Entering Chilled Water Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0546 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | Leaving Chilled Water Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0547 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | CHW Isolation Valve Status (Return) | DI | Electric Valve Actuator | ME Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0548 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | CHW Isolation Valve Status (Supply) | DI | Electric Valve Actuator | ME Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0549 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | Evaporator Approach dT | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0550 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | Evaporator Approach dP | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0551 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | Evaporator Refrigerant Pressure | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0552 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | Evaporator Refrigerant Temperature | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0553 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | Oil Sump Pressure | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0554 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | Oil Sump Temperature | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0555 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | Oil Pump Status | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0556 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | Oil Pump Trip | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0557 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | Compressor Status | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0558 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | Compressor HOA Status | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0559 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | Compressor Trip | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0560 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | Motor Load Current | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0561 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | Motor kW / BTU Meter | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0562 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | Winding Temperature | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0563 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | Condenser Refrigerant Pressure | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0564 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | Condenser Refrigerant Temperature | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0565 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | Condenser Approach dT | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0566 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | Condenser Approach dP | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0567 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | COW Isolation Valve Status (Return) | DI | Electric Valve Actuator | ME Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0568 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | COW Isolation Valve Status (Supply) | DI | Electric Valve Actuator | ME Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0569 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | Entering Condenser Water Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0570 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | Leaving Condenser Water Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0571 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | CHW Return Flow | AI | Flow Sensor | BMS Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0572 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | CHW Supply Flow | AI | Flow Sensor | BMS Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0573 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | COW Supply Flow | AI | Flow Sensor | BMS Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0574 | AC | Chiller (Package Water-Cooled) | CH-2 | 2nd Floor (Plant Room) | BACnet/IP gateway | Network | Chiller native BACnet | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0575 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | Entering Chilled Water Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0576 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | Leaving Chilled Water Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0577 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | CHW Isolation Valve Status (Return) | DI | Electric Valve Actuator | ME Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0578 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | CHW Isolation Valve Status (Supply) | DI | Electric Valve Actuator | ME Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0579 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | Evaporator Approach dT | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0580 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | Evaporator Approach dP | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0581 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | Evaporator Refrigerant Pressure | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0582 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | Evaporator Refrigerant Temperature | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0583 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | Oil Sump Pressure | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0584 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | Oil Sump Temperature | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0585 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | Oil Pump Status | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0586 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | Oil Pump Trip | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0587 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | Compressor Status | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0588 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | Compressor HOA Status | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0589 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | Compressor Trip | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0590 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | Motor Load Current | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0591 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | Motor kW / BTU Meter | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0592 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | Winding Temperature | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0593 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | Condenser Refrigerant Pressure | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0594 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | Condenser Refrigerant Temperature | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0595 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | Condenser Approach dT | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0596 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | Condenser Approach dP | HLI | Chiller Native | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0597 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | COW Isolation Valve Status (Return) | DI | Electric Valve Actuator | ME Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0598 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | COW Isolation Valve Status (Supply) | DI | Electric Valve Actuator | ME Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0599 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | Entering Condenser Water Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0600 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | Leaving Condenser Water Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0601 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | CHW Return Flow | AI | Flow Sensor | BMS Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0602 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | CHW Supply Flow | AI | Flow Sensor | BMS Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0603 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | COW Supply Flow | AI | Flow Sensor | BMS Contractor | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0604 | AC | Chiller (Package Water-Cooled) | CH-3 | 2nd Floor (Plant Room) | BACnet/IP gateway | Network | Chiller native BACnet | Equipment Supplier | DRC-004-2024 AC/Chiller (Package Water-Cooled) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0605 | AC | Primary CHW Pump | PCHW-1 | 2nd Floor (Plant Room) | CHW Supply Pressure | AI | Pressure Sensor | Equipment Supplier | DRC-004-2024 AC/Primary CHW Pump | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0606 | AC | Primary CHW Pump | PCHW-1 | 2nd Floor (Plant Room) | On/Off Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Primary CHW Pump | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0607 | AC | Primary CHW Pump | PCHW-1 | 2nd Floor (Plant Room) | HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Primary CHW Pump | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0608 | AC | Primary CHW Pump | PCHW-1 | 2nd Floor (Plant Room) | VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/Primary CHW Pump | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0609 | AC | Primary CHW Pump | PCHW-1 | 2nd Floor (Plant Room) | Trip Alarm | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Primary CHW Pump | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0610 | AC | Primary CHW Pump | PCHW-2 | 2nd Floor (Plant Room) | CHW Supply Pressure | AI | Pressure Sensor | Equipment Supplier | DRC-004-2024 AC/Primary CHW Pump | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0611 | AC | Primary CHW Pump | PCHW-2 | 2nd Floor (Plant Room) | On/Off Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Primary CHW Pump | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0612 | AC | Primary CHW Pump | PCHW-2 | 2nd Floor (Plant Room) | HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Primary CHW Pump | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0613 | AC | Primary CHW Pump | PCHW-2 | 2nd Floor (Plant Room) | VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/Primary CHW Pump | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0614 | AC | Primary CHW Pump | PCHW-2 | 2nd Floor (Plant Room) | Trip Alarm | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Primary CHW Pump | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0615 | AC | Primary CHW Pump | PCHW-3 | 2nd Floor (Plant Room) | CHW Supply Pressure | AI | Pressure Sensor | Equipment Supplier | DRC-004-2024 AC/Primary CHW Pump | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0616 | AC | Primary CHW Pump | PCHW-3 | 2nd Floor (Plant Room) | On/Off Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Primary CHW Pump | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0617 | AC | Primary CHW Pump | PCHW-3 | 2nd Floor (Plant Room) | HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Primary CHW Pump | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0618 | AC | Primary CHW Pump | PCHW-3 | 2nd Floor (Plant Room) | VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/Primary CHW Pump | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0619 | AC | Primary CHW Pump | PCHW-3 | 2nd Floor (Plant Room) | Trip Alarm | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Primary CHW Pump | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0620 | AC | Primary CHW Pump (Standby) | PCHW-S | 2nd Floor (Plant Room) | CHW Supply Pressure | AI | Pressure Sensor | Equipment Supplier | DRC-004-2024 AC/Primary CHW Pump (Standby) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0621 | AC | Primary CHW Pump (Standby) | PCHW-S | 2nd Floor (Plant Room) | On/Off Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Primary CHW Pump (Standby) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0622 | AC | Primary CHW Pump (Standby) | PCHW-S | 2nd Floor (Plant Room) | HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Primary CHW Pump (Standby) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0623 | AC | Primary CHW Pump (Standby) | PCHW-S | 2nd Floor (Plant Room) | VFD Speed | HLI | VFD | Equipment Supplier | DRC-004-2024 AC/Primary CHW Pump (Standby) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0624 | AC | Primary CHW Pump (Standby) | PCHW-S | 2nd Floor (Plant Room) | Trip Alarm | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Primary CHW Pump (Standby) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0625 | AC | Condenser Water Pump | PCOW-1 | 2nd Floor (Plant Room) | On/Off Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Condenser Water Pump | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0626 | AC | Condenser Water Pump | PCOW-1 | 2nd Floor (Plant Room) | HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Condenser Water Pump | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0627 | AC | Condenser Water Pump | PCOW-1 | 2nd Floor (Plant Room) | Trip Alarm | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Condenser Water Pump | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0628 | AC | Condenser Water Pump | PCOW-2 | 2nd Floor (Plant Room) | On/Off Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Condenser Water Pump | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0629 | AC | Condenser Water Pump | PCOW-2 | 2nd Floor (Plant Room) | HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Condenser Water Pump | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0630 | AC | Condenser Water Pump | PCOW-2 | 2nd Floor (Plant Room) | Trip Alarm | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Condenser Water Pump | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0631 | AC | Condenser Water Pump | PCOW-3 | 2nd Floor (Plant Room) | On/Off Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Condenser Water Pump | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0632 | AC | Condenser Water Pump | PCOW-3 | 2nd Floor (Plant Room) | HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Condenser Water Pump | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0633 | AC | Condenser Water Pump | PCOW-3 | 2nd Floor (Plant Room) | Trip Alarm | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Condenser Water Pump | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0634 | AC | Cooling Tower | CT-1 | Roofdeck | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Cooling Tower | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0635 | AC | Cooling Tower | CT-1 | Roofdeck | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Cooling Tower | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0636 | AC | Cooling Tower | CT-1 | Roofdeck | Basin Low Level | DI | Level Sensor | BMS Contractor | DRC-004-2024 AC/Cooling Tower | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0637 | AC | Cooling Tower | CT-1 | Roofdeck | Basin High Level | DI | Level Sensor | BMS Contractor | DRC-004-2024 AC/Cooling Tower | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0638 | AC | Cooling Tower | CT-1 | Roofdeck | COW Isolation Valve Status (Return) | DI | Electric Valve Actuator | ME Contractor | DRC-004-2024 AC/Cooling Tower | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0639 | AC | Cooling Tower | CT-1 | Roofdeck | Blowdown Corrosion/Scale (pH) | AI | pH/Cond Sensor | ME Contractor | DRC-004-2024 AC/Cooling Tower | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0640 | AC | Cooling Tower | CT-1 | Roofdeck | Blowdown Valve Control | AO | Electric Valve Actuator | BMS Contractor | DRC-004-2024 AC/Cooling Tower | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0641 | AC | Cooling Tower | CT-2 | Roofdeck | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Cooling Tower | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0642 | AC | Cooling Tower | CT-2 | Roofdeck | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Cooling Tower | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0643 | AC | Cooling Tower | CT-2 | Roofdeck | Basin Low Level | DI | Level Sensor | BMS Contractor | DRC-004-2024 AC/Cooling Tower | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0644 | AC | Cooling Tower | CT-2 | Roofdeck | Basin High Level | DI | Level Sensor | BMS Contractor | DRC-004-2024 AC/Cooling Tower | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0645 | AC | Cooling Tower | CT-2 | Roofdeck | COW Isolation Valve Status (Return) | DI | Electric Valve Actuator | ME Contractor | DRC-004-2024 AC/Cooling Tower | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0646 | AC | Cooling Tower | CT-2 | Roofdeck | Blowdown Corrosion/Scale (pH) | AI | pH/Cond Sensor | ME Contractor | DRC-004-2024 AC/Cooling Tower | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0647 | AC | Cooling Tower | CT-2 | Roofdeck | Blowdown Valve Control | AO | Electric Valve Actuator | BMS Contractor | DRC-004-2024 AC/Cooling Tower | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0648 | AC | Cooling Tower | CT-3 | Roofdeck | Fan Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Cooling Tower | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0649 | AC | Cooling Tower | CT-3 | Roofdeck | Fan Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 AC/Cooling Tower | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0650 | AC | Cooling Tower | CT-3 | Roofdeck | Basin Low Level | DI | Level Sensor | BMS Contractor | DRC-004-2024 AC/Cooling Tower | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0651 | AC | Cooling Tower | CT-3 | Roofdeck | Basin High Level | DI | Level Sensor | BMS Contractor | DRC-004-2024 AC/Cooling Tower | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0652 | AC | Cooling Tower | CT-3 | Roofdeck | COW Isolation Valve Status (Return) | DI | Electric Valve Actuator | ME Contractor | DRC-004-2024 AC/Cooling Tower | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0653 | AC | Cooling Tower | CT-3 | Roofdeck | Blowdown Corrosion/Scale (pH) | AI | pH/Cond Sensor | ME Contractor | DRC-004-2024 AC/Cooling Tower | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0654 | AC | Cooling Tower | CT-3 | Roofdeck | Blowdown Valve Control | AO | Electric Valve Actuator | BMS Contractor | DRC-004-2024 AC/Cooling Tower | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0655 | AC | Cooling Tower (Common) | CT-COMMON | Roofdeck | Outside Air Temperature (CT area) | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/Cooling Tower (Common) | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0656 | AC | Cooling Tower (Common) | CT-COMMON | Roofdeck | Outside Air Humidity (CT area) | AI | Humidity Sensor | BMS Contractor | DRC-004-2024 AC/Cooling Tower (Common) | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0657 | AC | Cooling Tower (Common) | CT-COMMON | Roofdeck | Condenser Return Header Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/Cooling Tower (Common) | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0658 | AC | Cooling Tower (Common) | CT-COMMON | Roofdeck | Condenser Supply Header Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/Cooling Tower (Common) | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0659 | AC | CHW Supply Main Header | CHW-HDR-S | 2nd Floor (Plant Room) | CHW Supply Header Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/CHW Supply Main Header | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0660 | AC | CHW Supply Main Header | CHW-HDR-S | 2nd Floor (Plant Room) | CHW Supply Header Pressure | AI | Pressure Sensor | BMS Contractor | DRC-004-2024 AC/CHW Supply Main Header | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0661 | AC | CHW Return Main Header | CHW-HDR-R | 2nd Floor (Plant Room) | CHW Return Header Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/CHW Return Main Header | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0662 | AC | CHW Return Main Header | CHW-HDR-R | 2nd Floor (Plant Room) | CHW Return Header Pressure | AI | Pressure Sensor | BMS Contractor | DRC-004-2024 AC/CHW Return Main Header | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0663 | AC | CHW Bypass Header | CHW-BYPASS | 2nd Floor (Plant Room) | Differential Pressure | AI | Diff. Pressure Sensor | BMS Contractor | DRC-004-2024 AC/CHW Bypass Header | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0664 | AC | CHW Bypass Header | CHW-BYPASS | 2nd Floor (Plant Room) | Differential Temperature | AI | Diff. Temp Sensor | BMS Contractor | DRC-004-2024 AC/CHW Bypass Header | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0665 | AC | CHW Bypass Header | CHW-BYPASS | 2nd Floor (Plant Room) | CHW Bypass Valve Status | DI | Electric Valve Actuator | BMS Contractor | DRC-004-2024 AC/CHW Bypass Header | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0666 | AC | CHW Bypass Header | CHW-BYPASS | 2nd Floor (Plant Room) | CHW Bypass Valve Control | AO | Electric Valve Actuator | BMS Contractor | DRC-004-2024 AC/CHW Bypass Header | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0667 | AC | Condenser Water Header | COW-HDR | Roofdeck | Condenser Supply Header Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/Condenser Water Header | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0668 | AC | Condenser Water Header | COW-HDR | Roofdeck | Condenser Return Header Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 AC/Condenser Water Header | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0669 | VENT | Steam Boiler | BLR-1 | Lower Ground | Supply Steam Pressure | AI | Pressure Sensor | BMS Contractor | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0670 | VENT | Steam Boiler | BLR-1 | Lower Ground | Low Water Level | DI | Level Sensor | Equipment Supplier | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0671 | VENT | Steam Boiler | BLR-1 | Lower Ground | High Water Level | DI | Level Sensor | Equipment Supplier | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0672 | VENT | Steam Boiler | BLR-1 | Lower Ground | Burner Power | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0673 | VENT | Steam Boiler | BLR-1 | Lower Ground | Small Fire Control | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0674 | VENT | Steam Boiler | BLR-1 | Lower Ground | Big Fire Control | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0675 | VENT | Steam Boiler | BLR-1 | Lower Ground | Feedwater Pump Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0676 | VENT | Steam Boiler | BLR-1 | Lower Ground | Burner Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0677 | VENT | Steam Boiler | BLR-1 | Lower Ground | Burner Fire Running | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0678 | VENT | Steam Boiler | BLR-1 | Lower Ground | Blower Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0679 | VENT | Steam Boiler | BLR-1 | Lower Ground | Fuel Oil Pump Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0680 | VENT | Steam Boiler | BLR-1 | Lower Ground | Blowdown Valve Status | DI | Electric Valve Actuator | BMS Contractor | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0681 | VENT | Steam Boiler | BLR-1 | Lower Ground | Blowdown Valve Control | AO | Electric Valve Actuator | BMS Contractor | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0682 | VENT | Steam Boiler | BLR-1 | Lower Ground | Feedwater Supply Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0683 | VENT | Steam Boiler | BLR-1 | Lower Ground | Fluegas Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0684 | VENT | Steam Boiler | BLR-1 | Lower Ground | Fluegas Oxygen Level | AI | Oxygen Sensor | BMS Contractor | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0685 | VENT | Steam Boiler | BLR-2 | Lower Ground | Supply Steam Pressure | AI | Pressure Sensor | BMS Contractor | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0686 | VENT | Steam Boiler | BLR-2 | Lower Ground | Low Water Level | DI | Level Sensor | Equipment Supplier | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0687 | VENT | Steam Boiler | BLR-2 | Lower Ground | High Water Level | DI | Level Sensor | Equipment Supplier | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0688 | VENT | Steam Boiler | BLR-2 | Lower Ground | Burner Power | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0689 | VENT | Steam Boiler | BLR-2 | Lower Ground | Small Fire Control | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0690 | VENT | Steam Boiler | BLR-2 | Lower Ground | Big Fire Control | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0691 | VENT | Steam Boiler | BLR-2 | Lower Ground | Feedwater Pump Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0692 | VENT | Steam Boiler | BLR-2 | Lower Ground | Burner Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0693 | VENT | Steam Boiler | BLR-2 | Lower Ground | Burner Fire Running | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0694 | VENT | Steam Boiler | BLR-2 | Lower Ground | Blower Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0695 | VENT | Steam Boiler | BLR-2 | Lower Ground | Fuel Oil Pump Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0696 | VENT | Steam Boiler | BLR-2 | Lower Ground | Blowdown Valve Status | DI | Electric Valve Actuator | BMS Contractor | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0697 | VENT | Steam Boiler | BLR-2 | Lower Ground | Blowdown Valve Control | AO | Electric Valve Actuator | BMS Contractor | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0698 | VENT | Steam Boiler | BLR-2 | Lower Ground | Feedwater Supply Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0699 | VENT | Steam Boiler | BLR-2 | Lower Ground | Fluegas Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0700 | VENT | Steam Boiler | BLR-2 | Lower Ground | Fluegas Oxygen Level | AI | Oxygen Sensor | BMS Contractor | DRC-004-2024 VENT/Steam Boiler | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0701 | HWL | Calorifier (Hot Water Storage Tank) | HWT-LZ.1 | Lower Ground | Tank Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 HWL/Calorifier (Hot Water Storage Tank) | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0702 | HWL | Calorifier (Hot Water Storage Tank) | HWT-LZ.2 | Lower Ground | Tank Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 HWL/Calorifier (Hot Water Storage Tank) | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0703 | HWL | Calorifier (Hot Water Storage Tank) | HWT-LZ.3 | Lower Ground | Tank Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 HWL/Calorifier (Hot Water Storage Tank) | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0704 | HWL | Calorifier (Hot Water Storage Tank) | HWT-HZ.1 | Roofdeck | Tank Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 HWL/Calorifier (Hot Water Storage Tank) | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0705 | HWL | Calorifier (Hot Water Storage Tank) | HWT-HZ.2 | Roofdeck | Tank Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 HWL/Calorifier (Hot Water Storage Tank) | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0706 | HWL | Calorifier (Hot Water Storage Tank) | HWT-HZ.3 | Roofdeck | Tank Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 HWL/Calorifier (Hot Water Storage Tank) | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0707 | HWL | Hot Water Header Set | HW-HDR-LZ | Lower Ground | Hot Water Supply Header Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 HWL/Hot Water Header Set | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0708 | HWL | Hot Water Header Set | HW-HDR-LZ | Lower Ground | Hot Water Return Header Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 HWL/Hot Water Header Set | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0709 | HWL | Hot Water Header Set | HW-HDR-LZ | Lower Ground | Make-Up Cold Water Header Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 HWL/Hot Water Header Set | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0710 | HWL | Hot Water Header Set | HW-HDR-HZ | Roofdeck | Hot Water Supply Header Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 HWL/Hot Water Header Set | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0711 | HWL | Hot Water Header Set | HW-HDR-HZ | Roofdeck | Hot Water Return Header Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 HWL/Hot Water Header Set | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0712 | HWL | Hot Water Header Set | HW-HDR-HZ | Roofdeck | Make-Up Cold Water Header Temperature | AI | Temperature Sensor | BMS Contractor | DRC-004-2024 HWL/Hot Water Header Set | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0713 | HWL | Heat Pump | HP-LZ.1 | Lower Ground | Pump Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Heat Pump | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0714 | HWL | Heat Pump | HP-LZ.1 | Lower Ground | Pump HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Heat Pump | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0715 | HWL | Heat Pump | HP-LZ.1 | Lower Ground | Pump Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Heat Pump | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0716 | HWL | Heat Pump | HP-LZ.2 | Lower Ground | Pump Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Heat Pump | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0717 | HWL | Heat Pump | HP-LZ.2 | Lower Ground | Pump HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Heat Pump | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0718 | HWL | Heat Pump | HP-LZ.2 | Lower Ground | Pump Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Heat Pump | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0719 | HWL | Heat Pump | HP-LZ.3 | Lower Ground | Pump Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Heat Pump | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0720 | HWL | Heat Pump | HP-LZ.3 | Lower Ground | Pump HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Heat Pump | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0721 | HWL | Heat Pump | HP-LZ.3 | Lower Ground | Pump Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Heat Pump | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0722 | HWL | Heat Pump | HP-HZ.1 | Roofdeck | Pump Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Heat Pump | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0723 | HWL | Heat Pump | HP-HZ.1 | Roofdeck | Pump HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Heat Pump | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0724 | HWL | Heat Pump | HP-HZ.1 | Roofdeck | Pump Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Heat Pump | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0725 | HWL | Heat Pump | HP-HZ.2 | Roofdeck | Pump Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Heat Pump | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0726 | HWL | Heat Pump | HP-HZ.2 | Roofdeck | Pump HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Heat Pump | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0727 | HWL | Heat Pump | HP-HZ.2 | Roofdeck | Pump Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Heat Pump | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0728 | HWL | Heat Pump | HP-HZ.3 | Roofdeck | Pump Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Heat Pump | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0729 | HWL | Heat Pump | HP-HZ.3 | Roofdeck | Pump HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Heat Pump | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0730 | HWL | Heat Pump | HP-HZ.3 | Roofdeck | Pump Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Heat Pump | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0731 | HWL | Recirculating Pump | RP-LZ.1 | Lower Ground | Pump Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Recirculating Pump | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0732 | HWL | Recirculating Pump | RP-LZ.1 | Lower Ground | Pump HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Recirculating Pump | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0733 | HWL | Recirculating Pump | RP-LZ.1 | Lower Ground | Pump Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Recirculating Pump | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0734 | HWL | Recirculating Pump | RP-LZ.2 | Lower Ground | Pump Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Recirculating Pump | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0735 | HWL | Recirculating Pump | RP-LZ.2 | Lower Ground | Pump HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Recirculating Pump | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0736 | HWL | Recirculating Pump | RP-LZ.2 | Lower Ground | Pump Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Recirculating Pump | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0737 | HWL | Recirculating Pump | RP-LZ.3 | Lower Ground | Pump Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Recirculating Pump | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0738 | HWL | Recirculating Pump | RP-LZ.3 | Lower Ground | Pump HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Recirculating Pump | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0739 | HWL | Recirculating Pump | RP-LZ.3 | Lower Ground | Pump Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Recirculating Pump | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0740 | HWL | Recirculating Pump | RP-HZ.1 | Roofdeck | Pump Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Recirculating Pump | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0741 | HWL | Recirculating Pump | RP-HZ.1 | Roofdeck | Pump HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Recirculating Pump | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0742 | HWL | Recirculating Pump | RP-HZ.1 | Roofdeck | Pump Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Recirculating Pump | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0743 | HWL | Recirculating Pump | RP-HZ.2 | Roofdeck | Pump Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Recirculating Pump | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0744 | HWL | Recirculating Pump | RP-HZ.2 | Roofdeck | Pump HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Recirculating Pump | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0745 | HWL | Recirculating Pump | RP-HZ.2 | Roofdeck | Pump Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Recirculating Pump | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0746 | HWL | Recirculating Pump | RP-HZ.3 | Roofdeck | Pump Motor Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Recirculating Pump | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0747 | HWL | Recirculating Pump | RP-HZ.3 | Roofdeck | Pump HOA Status | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Recirculating Pump | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0748 | HWL | Recirculating Pump | RP-HZ.3 | Roofdeck | Pump Trip | DI | Auxiliary Contact | Equipment Supplier | DRC-004-2024 HWL/Recirculating Pump | FCP-RD | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0749 | EE | Multifunction Power Meter (Main) | PM-MAIN | 2nd Floor (Plant Room) | Multifunction Power Meter (Modbus) | Network | Modbus RTU meter | BMS Contractor | DRC-004-2024 EE/Multifunction Power Meter (Main) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0750 | EE | Multifunction Power Meter (Main) | PM-GEN | 2nd Floor (Plant Room) | Multifunction Power Meter (Modbus) | Network | Modbus RTU meter | BMS Contractor | DRC-004-2024 EE/Multifunction Power Meter (Main) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0751 | EE | Multifunction Power Meter (Feeder) | PM-MCC-CHILLER | 2nd Floor (Plant Room) | Multifunction Power Meter (Modbus) | Network | Modbus RTU meter | BMS Contractor | DRC-004-2024 EE/Multifunction Power Meter (Feeder) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0752 | EE | Multifunction Power Meter (Feeder) | PM-MCC-CT | 2nd Floor (Plant Room) | Multifunction Power Meter (Modbus) | Network | Modbus RTU meter | BMS Contractor | DRC-004-2024 EE/Multifunction Power Meter (Feeder) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0753 | EE | Multifunction Power Meter (Feeder) | PM-MCC-BOILER | 2nd Floor (Plant Room) | Multifunction Power Meter (Modbus) | Network | Modbus RTU meter | BMS Contractor | DRC-004-2024 EE/Multifunction Power Meter (Feeder) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0754 | EE | Multifunction Power Meter (Feeder) | PM-MCC-FIRE-PUMP | 2nd Floor (Plant Room) | Multifunction Power Meter (Modbus) | Network | Modbus RTU meter | BMS Contractor | DRC-004-2024 EE/Multifunction Power Meter (Feeder) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0755 | EE | Multifunction Power Meter (Feeder) | PM-MCC-MDP-1 | 2nd Floor (Plant Room) | Multifunction Power Meter (Modbus) | Network | Modbus RTU meter | BMS Contractor | DRC-004-2024 EE/Multifunction Power Meter (Feeder) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0756 | EE | Multifunction Power Meter (Feeder) | PM-MCC-MDP-2 | 2nd Floor (Plant Room) | Multifunction Power Meter (Modbus) | Network | Modbus RTU meter | BMS Contractor | DRC-004-2024 EE/Multifunction Power Meter (Feeder) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0757 | EE | Multifunction Power Meter (Feeder) | PM-MCC-MDP-3 | 2nd Floor (Plant Room) | Multifunction Power Meter (Modbus) | Network | Modbus RTU meter | BMS Contractor | DRC-004-2024 EE/Multifunction Power Meter (Feeder) | MCP-PLANT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0758 | EE | Multifunction Power Meter (Main) | GEN-1 | Basement (Genset) | Generator Run Status | DI | Auxiliary Contact | EE Contractor | DRC-004-2024 EE/Multifunction Power Meter (Main) | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0759 | EE | Multifunction Power Meter (Main) | GEN-1 | Basement (Genset) | Generator Common Trip | DI | Auxiliary Contact | EE Contractor | DRC-004-2024 EE/Multifunction Power Meter (Main) | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0760 | EE | Multifunction Power Meter (Main) | GEN-1 | Basement (Genset) | Generator Common Alarm | DI | Auxiliary Contact | EE Contractor | DRC-004-2024 EE/Multifunction Power Meter (Main) | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0761 | EE | Multifunction Power Meter (Main) | ATS-1 | Basement (Genset) | ATS Position (Mains/Gen) | DI | Auxiliary Contact | EE Contractor | DRC-004-2024 EE/Multifunction Power Meter (Main) | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |
| P0762 | EE | Multifunction Power Meter (Main) | ATS-1 | Basement (Genset) | ATS Trip | DI | Auxiliary Contact | EE Contractor | DRC-004-2024 EE/Multifunction Power Meter (Main) | FCP-BSMT | Synthesized from DRC-004-2024 (DRC standards) + TUEC BMS-01..03 (quantities) | |