# Instance: BMS Head-End — Kingsford BMS

**WBS leaves served:** 2.1.1, 2.1.2, 2.1.3, 2.1.4, 2.1.5, 2.1.6, 3.7.1, 3.7.2, 3.7.3, 3.7.4
**Module ref:** `_playbook/modules/bms/head-end.md`
**Project:** Kingsford Hotel Bacolod BMS

## Project-specific parameter values

- `server_count`: 2 (primary HE-SVR-01 + standby HE-SVR-02)
- `workstation_count`: 2 (HE-WS-01 chief engineer, HE-WS-02 front desk)
- `gfx_pc_count`: 1 (HE-GFX-01 + 55" display)
- `ups_size_kva`: 3
- `ups_runtime_min`: 30 (per BMS general spec on BMS-01)
- `license_seats`: 3 client connections (2 WS + 1 graphics PC)
- `server_room_location`: TBD (per Q-005, assumed Lower Ground or GF BOH)

## BOQ line items (Phase 6 input)

| WBS | Description | Qty | Unit | Reference |
|-----|-------------|-----|------|-----------|
| 2.1.1 | BMS Server (Primary) — dual-CPU, 16+ GB RAM, redundant PSU | 1 | each | A6: HE-SVR-01 |
| 2.1.1 | BMS Server (Standby, redundancy) | 1 | each | A6: HE-SVR-02 |
| 2.1.2 | Operator Workstation #1 (Chief Engineer) | 1 | each | A6: HE-WS-01 |
| 2.1.2 | Operator Workstation #2 (Front Desk) | 1 | each | A6: HE-WS-02 |
| 2.1.3 | Graphics PC + 55" Commercial Display | 1 | set | A6: HE-GFX-01 |
| 2.1.4 | UPS for Head-End (3 kVA, 30-min runtime) | 1 | each | A6: HE-UPS-01 |
| 2.1.5 | Software licenses (server + 3 client + energy module + graphics editor) | 1 | lot | A6: HE-SW-* |
| 2.1.6 | Server-room peripherals (KVM, console monitor, color laser printer, 19" rack) | 1 | lot | A6: HE-PRINTER-01, HE-RACK-01, HE-KVM-01, HE-MON-01 |
| 3.7.1 | Server install + image + license activation | 12 | hr | A6 module rate (6 hr × 2 servers) |
| 3.7.2 | Workstation install + image | 4 | hr | (2 hr × 2 WS) |
| 3.7.3 | UPS install + battery commissioning | 2 | hr | |
| 3.7.4 | Server-room build-out (rack, cable mgmt, labeling) | 8 | hr | |
| | **Total head-end install labor** | **26** | hr | (within B4 budget) |

## Open assumptions for this instance

- A6 line items reflect BMS general spec on BMS-01; brand selection per Q-013
- Server room location TBD per Q-005 — affects both this module and cabling-and-containment
- Software licensing model: perpetual (one-time) per A-008 commercial defaults

## Cross-references

- **Working docs:** A6 (head-end equipment), A5 (network — core switch is shared), A7 (power feed to UPS), B1 (programming hours include head-end software programming)
- **Assumptions:** A-008 (commercial), A-009 (schedule)
- **Clarifications:** Q-005 (server room location), Q-013 (brand)