# B3 — Commissioning Point Inventory
#
metadata:
  project: "Kingsford Hotel Bacolod \u2014 BMS"
  generated_from: A1-io-list.yaml + A2-equipment-takeoff.yaml
  generator: _playbook/tools/generate-b1-b3-programming-and-commissioning.py
  rates:
    hrs_per_p2p_point: 0.15
    hrs_per_functional_test: 1.5
    hrs_per_integrated_test: 4.0
summary:
  p2p_points: 561
  functional_tests: 109
  integrated_tests: 8
  total_test_items: 678
tc_hours:
  point_to_point: 84.1
  functional_per_equipment: 163.5
  integrated_sequences: 32.0
  total_tc_hours: 279.6
  person_days_at_8hr: 35.0
p2p_breakdown_by_panel:
  DDC-2F-BOH: 165
  DDC-RD-PLANT: 110
  DDC-2F-CHILLER: 72
  DDC-B1-BOH: 57
  DDC-GF-BOH: 48
  DDC-2M-CASINO: 47
  DDC-3F: 36
  DDC-LG-PLANT: 26
functional_test_inventory:
- equipment: AHU-1.1
  equipment_class: AHU (Chilled-Water-Served)
  location: Ground Floor BOH
- equipment: AHU-1.2
  equipment_class: AHU (Chilled-Water-Served)
  location: Ground Floor BOH
- equipment: AHU-1.3
  equipment_class: AHU (Chilled-Water-Served)
  location: Ground Floor BOH
- equipment: AHU-2M.1
  equipment_class: AHU (Chilled-Water-Served)
  location: 2nd Mezzanine (Casino)
- equipment: AHU-2M.2
  equipment_class: AHU (Chilled-Water-Served)
  location: 2nd Mezzanine (Casino)
- equipment: AHU-B.1
  equipment_class: AHU (Chilled-Water-Served)
  location: 2nd Level BOH
- equipment: AHU-B.2
  equipment_class: AHU (Chilled-Water-Served)
  location: 2nd Level BOH
- equipment: AHU-B.3
  equipment_class: AHU (Chilled-Water-Served)
  location: 2nd Level BOH
- equipment: AHU-EL
  equipment_class: AHU (Chilled-Water-Served)
  location: 2nd Level Executive Lounge
- equipment: AHU-FR2
  equipment_class: AHU (Chilled-Water-Served)
  location: 2nd Level Function Room 2
- equipment: AHU-FR3
  equipment_class: AHU (Chilled-Water-Served)
  location: 2nd Level Function Room 3
- equipment: AHU-PF
  equipment_class: AHU (Chilled-Water-Served)
  location: 2nd Level Pre-Function
- equipment: AIR-ION-2M.1
  equipment_class: Air Ionizer (Casino)
  location: 2nd Mezzanine (Casino)
- equipment: AIR-ION-2M.2
  equipment_class: Air Ionizer (Casino)
  location: 2nd Mezzanine (Casino)
- equipment: CH-1
  equipment_class: Chiller (Package Water-Cooled)
  location: 2nd Level Chiller Room
- equipment: CH-2
  equipment_class: Chiller (Package Water-Cooled)
  location: 2nd Level Chiller Room
- equipment: CH-3
  equipment_class: Chiller (Package Water-Cooled)
  location: 2nd Level Chiller Room
- equipment: CHW-DIFF
  equipment_class: CHW Bypass Header
  location: 2nd Level Chiller Room
- equipment: CHW-RET-HDR
  equipment_class: CHW Return Main Header
  location: 2nd Level Chiller Room
- equipment: CHW-SUP-HDR
  equipment_class: CHW Supply Main Header
  location: 2nd Level Chiller Room
- equipment: COWP-1
  equipment_class: Condenser Water Pump
  location: 2nd Level Chiller Room
- equipment: COWP-2
  equipment_class: Condenser Water Pump
  location: 2nd Level Chiller Room
- equipment: COWP-3
  equipment_class: Condenser Water Pump
  location: 2nd Level Chiller Room
- equipment: CT-1
  equipment_class: Cooling Tower
  location: Roof Deck
- equipment: CT-2
  equipment_class: Cooling Tower
  location: Roof Deck
- equipment: CT-3
  equipment_class: Cooling Tower
  location: Roof Deck
- equipment: CT-COMMON
  equipment_class: Cooling Tower (Common)
  location: Roof Deck
- equipment: CW-HDR
  equipment_class: Condenser Water Header
  location: Roof Deck CT Area
- equipment: DOAS-2M
  equipment_class: "DOAS Unit (Casino \u2014 with CO/VOC)"
  location: 2nd Mezzanine (Casino)
- equipment: DOAS-RD.1
  equipment_class: DOAS Unit
  location: Roof Deck
- equipment: DOAS-RD.2
  equipment_class: DOAS Unit
  location: Roof Deck
- equipment: EF-1
  equipment_class: Exhaust Fan (General)
  location: Roof Deck
- equipment: EF-2.1
  equipment_class: Exhaust Fan (General)
  location: 2nd Floor
- equipment: EF-2.2
  equipment_class: Exhaust Fan (General)
  location: 2nd Floor
- equipment: EF-2.3
  equipment_class: Exhaust Fan (General)
  location: 2nd Floor
- equipment: EF-2.4
  equipment_class: Exhaust Fan (General)
  location: 2nd Floor
- equipment: EF-2B.1
  equipment_class: Exhaust Fan (General)
  location: 2nd Floor BOH
- equipment: EF-2B.2
  equipment_class: Exhaust Fan (General)
  location: 2nd Floor BOH
- equipment: EF-3.1
  equipment_class: Exhaust Fan (General)
  location: 3rd Floor
- equipment: EF-3.2
  equipment_class: Exhaust Fan (General)
  location: 3rd Floor
- equipment: EF-3.3
  equipment_class: Exhaust Fan (General)
  location: 3rd Floor
- equipment: EF-3.4
  equipment_class: Exhaust Fan (General)
  location: 3rd Floor
- equipment: EF-3B-G
  equipment_class: Exhaust Fan (General)
  location: 3rd Floor BOH
- equipment: EF-3C.1-G
  equipment_class: Exhaust Fan (General)
  location: 3rd Floor
- equipment: EF-B.1
  equipment_class: Exhaust Fan (General)
  location: Basement
- equipment: EF-B.2
  equipment_class: Exhaust Fan (General)
  location: Basement
- equipment: EF-BR.1
  equipment_class: Exhaust Fan (General)
  location: Basement Battery Room
- equipment: EF-BR.2
  equipment_class: Exhaust Fan (General)
  location: Basement Battery Room
- equipment: EF-BS.1
  equipment_class: Exhaust Fan (General)
  location: Basement Service
- equipment: EF-BS.2
  equipment_class: Exhaust Fan (General)
  location: Basement Service
- equipment: EF-FOST.1
  equipment_class: Exhaust Fan (General)
  location: Basement FOST Room
- equipment: EF-GL.1
  equipment_class: Exhaust Fan (General)
  location: Basement Garbage Lobby
- equipment: EF-GL.2
  equipment_class: Exhaust Fan (General)
  location: Basement Garbage Lobby
- equipment: EF-GS.1
  equipment_class: Exhaust Fan (General)
  location: 2nd Floor General Service
- equipment: EF-GS.2
  equipment_class: Exhaust Fan (General)
  location: 2nd Floor General Service
- equipment: EF-MFR.1
  equipment_class: Exhaust Fan (General)
  location: Basement Main Fire Riser
- equipment: EF-MP.1
  equipment_class: Exhaust Fan (General)
  location: Basement Mech / Pump
- equipment: EF-OHRv2
  equipment_class: Exhaust Fan (General)
  location: 2nd Floor OHR
- equipment: EF-PR.1
  equipment_class: Exhaust Fan (General)
  location: Basement Pump Room
- equipment: EF-PR.3
  equipment_class: Exhaust Fan (General)
  location: Basement Pump Room
- equipment: EF-RD.1
  equipment_class: Exhaust Fan (General)
  location: Roof Deck
- equipment: EF-RO.2
  equipment_class: Exhaust Fan (General)
  location: Roof Deck
- equipment: EF-WS.1
  equipment_class: Exhaust Fan (General)
  location: Basement Wash Service
- equipment: FACP-GW
  equipment_class: FACP Gateway
  location: Ground Floor Fire Command Center
- equipment: HP-HZ
  equipment_class: Heat Pump
  location: Roof Deck HWL Area
- equipment: HP-LZ
  equipment_class: Heat Pump
  location: Lower Ground HWL Room
- equipment: HWH-HZ
  equipment_class: Hot Water Header Set
  location: Roof Deck HWL Area
- equipment: HWH-LZ
  equipment_class: Hot Water Header Set
  location: Lower Ground HWL Room
- equipment: HWT-HZ
  equipment_class: Calorifier (Hot Water Storage Tank)
  location: Roof Deck HWL Area
- equipment: HWT-LZ
  equipment_class: Calorifier (Hot Water Storage Tank)
  location: Lower Ground HWL Room
- equipment: MPM-AHU-2F
  equipment_class: Multifunction Power Meter (Feeder)
  location: 2nd Level AHU MCC
- equipment: MPM-AHU-GF
  equipment_class: Multifunction Power Meter (Feeder)
  location: Ground Floor AHU MCC
- equipment: MPM-CHILLER
  equipment_class: Multifunction Power Meter (Feeder)
  location: 2nd Level Chiller MCC
- equipment: MPM-LIGHT-A
  equipment_class: Multifunction Power Meter (Feeder)
  location: Lower Ground Lighting Panel A
- equipment: MPM-LIGHT-B
  equipment_class: Multifunction Power Meter (Feeder)
  location: Lower Ground Lighting Panel B
- equipment: MPM-MAIN
  equipment_class: Multifunction Power Meter (Main)
  location: Lower Ground Main Switchroom
- equipment: PAHU-0.1
  equipment_class: Precooled Air Handling Unit
  location: Basement
- equipment: PAHU-B.1
  equipment_class: Precooled Air Handling Unit
  location: 2nd Level BOH
- equipment: PAHU-B.2
  equipment_class: Precooled Air Handling Unit
  location: 2nd Level BOH
- equipment: PAHU-B.3
  equipment_class: Precooled Air Handling Unit
  location: 2nd Level BOH
- equipment: PAHU-FR
  equipment_class: Precooled Air Handling Unit
  location: 2nd Level Function Rooms
- equipment: PAHU-PF
  equipment_class: Precooled Air Handling Unit
  location: 2nd Level Pre-Function
- equipment: PAHU-r.1
  equipment_class: Precooled Air Handling Unit
  location: Roof Deck
- equipment: PAHU-r.2
  equipment_class: Precooled Air Handling Unit
  location: Roof Deck
- equipment: PCHWP-1
  equipment_class: Primary CHW Pump
  location: 2nd Level Chiller Room
- equipment: PCHWP-2
  equipment_class: Primary CHW Pump
  location: 2nd Level Chiller Room
- equipment: PCHWP-3
  equipment_class: Primary CHW Pump (Standby)
  location: 2nd Level Chiller Room
- equipment: RP-HZ
  equipment_class: Recirculating Pump
  location: Roof Deck HWL Area
- equipment: RP-LZ
  equipment_class: Recirculating Pump
  location: Lower Ground HWL Room
- equipment: SB-1
  equipment_class: Steam Boiler
  location: Lower Ground Boiler Room
- equipment: SB-2
  equipment_class: Steam Boiler
  location: Lower Ground Boiler Room
- equipment: SCHWP-1
  equipment_class: Secondary CHW Pump
  location: 2nd Level Chiller Room
- equipment: SCHWP-2
  equipment_class: Secondary CHW Pump
  location: 2nd Level Chiller Room
- equipment: SCHWP-3
  equipment_class: Secondary CHW Pump
  location: 2nd Level Chiller Room
- equipment: TEF-1.1
  equipment_class: Exhaust Fan (Toilet)
  location: GF Main Lobby Toilet
- equipment: TEF-1.2
  equipment_class: Exhaust Fan (Toilet)
  location: GF Main Lobby Toilet
- equipment: TEF-1.3
  equipment_class: Exhaust Fan (Toilet)
  location: GF Main Lobby Toilet
- equipment: TEF-1.4
  equipment_class: Exhaust Fan (Toilet)
  location: GF Main Lobby Toilet
- equipment: TEF-2.1
  equipment_class: Exhaust Fan (Toilet)
  location: 2nd Floor Toilet
- equipment: TEF-2.2
  equipment_class: Exhaust Fan (Toilet)
  location: 2nd Floor Toilet
- equipment: TEF-2B.3
  equipment_class: Exhaust Fan (Toilet)
  location: 2nd Floor BOH Toilet
- equipment: TEF-30.20
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Toilet
- equipment: TEF-3A.1
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Amenity Toilet
- equipment: TEF-3A.2
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Amenity Toilet
- equipment: TEF-3B
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Toilet
- equipment: TEF-3C.1
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Toilet
- equipment: TEF-3C.2
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Toilet
- equipment: TEF-B.1
  equipment_class: Exhaust Fan (Toilet)
  location: Basement Toilet
- equipment: TEF-B.2
  equipment_class: Exhaust Fan (Toilet)
  location: Basement Toilet
integrated_test_inventory:
- Chiller plant sequencing (chiller staging + CHW pump + COW pump + cooling tower fan)
- CHW differential pressure control (PCHWP VFD speed via header dP)
- AHU supply-air temperature control (modulating CHW valve loop)
- DOAS demand-controlled ventilation (CO2-based fresh air modulation)
- Hotwater system sequencing (heat pump + recirculating pump + tank temp)
- Boiler firing rate vs. steam pressure
- Cooling tower fan staging vs. condenser water temperature
- Energy savings algorithm verification (max-demand limiting + load shedding)
notes:
- 'P2P = point-to-point verification: every physical I/O calibrated, range-checked, polarity verified, scaled correctly.'
- 'Functional test: per-equipment sequence verification (e.g., does the AHU CHW valve modulate correctly to maintain supply air temp?).'
- 'Integrated test: cross-system sequence (e.g., chiller staging triggers correctly when load increases).'
- "Owner T&C / SAT: separate from this \u2014 handled in proposal as an item under 5.5 in WBS."