metadata:
  project: Kingsford Hotel Bacolod — BMS (AB-Run-6)
  skeleton_emitted_by: generate-a3-cable-schedule.py --emit-skeleton
  next_step: 'Annotate each route: set method to ''measured'' (with length_m + drawing_ref
    + breakdown) OR ''typical_range'' (with typical_range_key referencing the typical_ranges
    block you author below per measure-cable-routes sub-routine).'
  annotated_by: _scripts/annotate-a3-routes.py
  annotation_basis: 'Per-context reasoned typical ranges per Operating Principle #11.
    Drawing-availability triage in 03-doc-inventory.md committed all routes to typical-range
    method (no measurable architectural floor plans provided; ECE auxiliary footprints
    + EE-24 riser used only for context calibration).'
typical_ranges:
  mstp_riser_2f_to_rd:
    length_m: 250
    applies_to: BACnet MS/TP field backbone routed via service-core IDF stack (west end of building per ECE auxiliary layouts) plus horizontal BOH-corridor segments connecting all 8 BMS panels (DDC-2F-CHILLER, DDC-2F-BOH, DDC-2M-CASINO, DDC-RD-PLANT, DDC-LG-PLANT, DDC-GF-BOH, DDC-B1-BOH, DDC-3F).
    basis: "Vertical span B1 → RD ≈ 13 floors × 4.5 m = 58.5 m. 8 horizontal panel-side segments at ~25 m each = 200 m. Routing factor 25% for tray sag + reserve = ~325 m. Refined to 250 m typical reflecting that not every panel sits at the same vertical line — some share corridor segments."
    sources: ["EE-24 power riser", "ECE-05..ECE-15 service-core IDF stack", "industry typical for hospitality service-core MS/TP backbone"]
    breakdown:
      horizontal_m: 200
      vertical_m: 50
  bacnet_ip_backbone_riser:
    length_m: 150
    applies_to: BACnet/IP backbone — fibre riser from head-end at Lower Ground to per-floor IDF edge switches, plus Cat6 horizontal trunk to each DDC field panel.
    basis: "Vertical fibre run LG → RD ≈ 13 floors × 4.5 m = 58.5 m. 8 horizontal Cat6 trunk segments at ~5 m each = 40 m. Plus 50 m reserve for service-core routing complexity. Total ~150 m typical."
    sources: ["EE-24 power riser", "ECE auxiliary IDF stack"]
    breakdown:
      horizontal_m: 40
      vertical_m: 60
      cornering_m: 50
  plant_room_chiller_2f:
    length_m: 12
    applies_to: Field cables from DDC-2F-CHILLER to chillers, primary/secondary CHW
      pumps, condenser-water pumps, CHW supply/return/bypass headers — all in or directly
      adjacent to the 2F chiller room.
    basis: 'Industry-typical plant-room same-room run with allowances for tray drop
      + cornering + 0.5 m terminations on each end. Baseline: chiller room ~10×8 m
      envelope; longest run from panel corner to far chiller skid ≈ 10 m + 1 m vertical
      drop + 1 m termination tails.'
    sources:
    - MC Standards ME chiller block
    - BMS-01 Chilled Water System I/O matrix
    - industry typical for hospitality chiller plant 1500-3000 RT
    breakdown:
      horizontal_m: 9
      vertical_m: 1
      terminations_m: 1
      cornering_m: 1
  plant_room_lg_boiler_hwl:
    length_m: 12
    applies_to: Field cables from DDC-LG-PLANT to steam boilers SB-1/SB-2, calorifier
      HWT-LZ, heat pump HP-LZ, recirculating pump RP-LZ, hot-water header set HWH-LZ
      — all in or directly adjacent to the Lower Ground boiler/HWL plant room.
    basis: Industry-typical plant-room same-room run. Boiler room and HWL plant adjacent
      on Lower Ground; combined envelope ~12×8 m with panel central. Longest run ≈
      9 m horizontal + 1 m vertical drop + 1 m termination + 1 m cornering.
    sources:
    - MC Standards ME boiler block
    - MC Standards PL
    - BMS-01 boiler-laundry table
    - industry typical
    breakdown:
      horizontal_m: 9
      vertical_m: 1
      terminations_m: 1
      cornering_m: 1
  plant_room_rd_plant:
    length_m: 15
    applies_to: Field cables from DDC-RD-PLANT to cooling towers CT-1/CT-2/CT-3, common
      CT sensors, condenser water headers, DOAS-RD, PAHU-r, calorifier HWT-HZ, heat
      pump HP-HZ, recirculating pump RP-HZ, hot-water header set HWH-HZ — Roof Deck
      plant area.
    basis: Roof-deck plant area is more spread out than indoor plant rooms (cooling
      towers separated for thermal isolation, calorifiers in adjacent enclosure).
      Allow 15 m typical with breakdown 12 m horizontal + 1.5 m vertical drop + 1
      m termination + 0.5 m cornering. Roof Deck exhaust fans (EF-RD.1, EF-RO.2, EF-1)
      also covered by this panel — same envelope.
    sources:
    - BMS-02 Cooling Tower table
    - MC Standards ME CT block
    - MC Standards PL
    - industry typical for rooftop plant
    breakdown:
      horizontal_m: 12
      vertical_m: 1.5
      terminations_m: 1
      cornering_m: 0.5
  casino_2m_localized:
    length_m: 18
    applies_to: Field cables from DDC-2M-CASINO to DOAS-2M, AHU-2M.1/2M.2, Air Ionizers
      — Casino 2nd Mezzanine equipment localized in casino MEP zone.
    basis: Casino mezzanine plant zone is mid-sized; AHU and DOAS spread across the
      2M MEP corridor with the panel central. Allow 18 m typical (15 horizontal +
      1.5 vertical + 1 termination + 0.5 cornering).
    sources:
    - BMS-02 Casino MVAC table
    breakdown:
      horizontal_m: 15
      vertical_m: 1.5
      terminations_m: 1
      cornering_m: 0.5
  boh_2f:
    length_m: 25
    applies_to: Field cables from DDC-2F-BOH to AHU-B.1/B.2/B.3, AHU-PF, AHU-EL, AHU-FR2,
      AHU-FR3, PAHU-B.1/B.2/B.3, PAHU-PF, PAHU-FR, and 2F exhaust fans (TEF-2.1/2.2,
      TEF-2B.3, EF-2B.1/2B.2, EF-GS.1/GS.2, EF-2.1..2.4, EF-OHRv2).
    basis: 2nd Floor BOH zone is large (function-room program + multiple AHU rooms
      + service areas); panel sited near 2F service-core IDF on the west end. Average
      run from panel to BOH AHU/PAHU rooms ≈ 22 m horizontal + 1 m vertical (slab
      pen) + 1 m termination + 1 m cornering.
    sources:
    - BMS-01 Basement-Podium BOH AHU/PAHU table
    - ECE-08 2F auxiliary layout
    - industry-typical service-core to remote-AHU run
    breakdown:
      horizontal_m: 22
      vertical_m: 1
      terminations_m: 1
      cornering_m: 1
  boh_gf:
    length_m: 25
    applies_to: Field cables from DDC-GF-BOH to AHU-1.1/1.2/1.3 (Ground Floor BOH
      AHU), GF main-lobby toilet exhaust fans TEF-1.1..1.4, and FACP gateway at the
      Fire Command Center.
    basis: Ground Floor includes lobby + F&B + retail + BOH; AHUs are spread across
      BOH zones, FACP at FCC near main entrance. Average run from panel (service-core
      IDF) to remote AHU ≈ 22 m horizontal + 1 m vertical + 1 m termination + 1 m
      cornering.
    sources:
    - BMS-01 BOH AHU table
    - ECE-07 GF + Mezz layout
    - industry-typical
    breakdown:
      horizontal_m: 22
      vertical_m: 1
      terminations_m: 1
      cornering_m: 1
  boh_b1:
    length_m: 28
    applies_to: Field cables from DDC-B1-BOH to PAHU-0.1, basement toilet exhaust
      TEF-B.1/B.2, and basement general exhaust EF-B.1/B.2/EF-BS.1/2/EF-GL.1/2/EF-FOST.1/EF-BR.1/2/EF-WS.1/EF-MP.1/EF-PR.1/3/EF-MFR.1.
    basis: Basement-1 has parking + service + multiple equipment rooms (sewage, fuel,
      pump, battery, mechanical); fans are widely scattered. Panel sited near B1 service-core
      IDF / mechanical room. Average run 25 m horizontal + 1 m vertical + 1 m termination
      + 1 m cornering = 28 m.
    sources:
    - BMS-01 Basement General Ventilation block (long fan tag list)
    - ECE-05/06 B1 layouts (multiple equipment rooms incl fuel/sewage tanks per insets)
    breakdown:
      horizontal_m: 25
      vertical_m: 1
      terminations_m: 1
      cornering_m: 1
  amenity_3f:
    length_m: 35
    applies_to: Field cables from DDC-3F to 3rd Floor amenity / first-guestroom-floor
      toilet exhaust TEF-3A/3B/3C/30.20 and general exhaust EF-3.1..3.4/EF-3B-G/EF-3C.1-G
      — long double-loaded corridor floor with pool/amenity zone.
    basis: 3rd Floor is amenity + first guestroom floor with a long corridor (~75-90
      m visible in ECE-09). Field devices distributed along corridor and at amenity-zone
      perimeter. Panel sited at service-core west end. Average run ≈ 32 m horizontal
      + 1 m vertical + 1 m termination + 1 m cornering.
    sources:
    - BMS-01 General Ventilation 3rd Floor block
    - ECE-09 3F PABX/FDAS layout (corridor scale calibrated against doorway = 900
      mm per A-011)
    breakdown:
      horizontal_m: 32
      vertical_m: 1
      terminations_m: 1
      cornering_m: 1
  panel_power_feed_local:
    length_m: 10
    applies_to: 240V single-phase power feed from local floor distribution panelboard
      (DBV-BMS / DBV-MECH per EE-24) to BMS DDC field panel.
    basis: Each BMS DDC panel sits adjacent to the floor's electrical closet / IDF.
      Industry typical 8-12 m from the floor distribution panelboard breaker to the
      BMS panel. Allow 10 m with breakdown 7 m horizontal + 1.5 m vertical drop +
      1 m termination + 0.5 m cornering.
    sources:
    - EE-24 power riser (Q-014 vector re-export pending for per-circuit IDs)
    - industry typical for service-core panel-to-panel
    breakdown:
      horizontal_m: 7
      vertical_m: 1.5
      terminations_m: 1
      cornering_m: 0.5
routes:
- from: DDC-GF-BOH
  to: AHU-1.1 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_gf
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 5
  notes: ''
- from: DDC-GF-BOH
  to: AHU-1.1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_gf
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 1
    AO: 1
    DI: 2
  notes: ''
- from: DDC-GF-BOH
  to: AHU-1.1 (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_gf
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 1
    AO: 2
  notes: ''
- from: DDC-GF-BOH
  to: AHU-1.2 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_gf
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 5
  notes: ''
- from: DDC-GF-BOH
  to: AHU-1.2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_gf
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 1
    AO: 1
    DI: 2
  notes: ''
- from: DDC-GF-BOH
  to: AHU-1.2 (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_gf
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 1
    AO: 2
  notes: ''
- from: DDC-GF-BOH
  to: AHU-1.3 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_gf
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 5
  notes: ''
- from: DDC-GF-BOH
  to: AHU-1.3 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_gf
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 1
    AO: 1
    DI: 2
  notes: ''
- from: DDC-GF-BOH
  to: AHU-1.3 (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_gf
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 1
    AO: 2
  notes: ''
- from: DDC-2M-CASINO
  to: AHU-2M.1 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: casino_2m_localized
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 5
  notes: ''
- from: DDC-2M-CASINO
  to: AHU-2M.1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: casino_2m_localized
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 1
    AO: 1
    DI: 2
  notes: ''
- from: DDC-2M-CASINO
  to: AHU-2M.1 (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: casino_2m_localized
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 1
    AO: 2
  notes: ''
- from: DDC-2M-CASINO
  to: AHU-2M.2 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: casino_2m_localized
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 5
  notes: ''
- from: DDC-2M-CASINO
  to: AHU-2M.2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: casino_2m_localized
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 1
    AO: 1
    DI: 2
  notes: ''
- from: DDC-2M-CASINO
  to: AHU-2M.2 (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: casino_2m_localized
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 1
    AO: 2
  notes: ''
- from: DDC-2F-BOH
  to: AHU-B.1 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 5
  notes: ''
- from: DDC-2F-BOH
  to: AHU-B.1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 1
    AO: 1
    DI: 2
  notes: ''
- from: DDC-2F-BOH
  to: AHU-B.1 (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 1
    AO: 2
  notes: ''
- from: DDC-2F-BOH
  to: AHU-B.2 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 5
  notes: ''
- from: DDC-2F-BOH
  to: AHU-B.2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 1
    AO: 1
    DI: 2
  notes: ''
- from: DDC-2F-BOH
  to: AHU-B.2 (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 1
    AO: 2
  notes: ''
- from: DDC-2F-BOH
  to: AHU-B.3 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 5
  notes: ''
- from: DDC-2F-BOH
  to: AHU-B.3 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 1
    AO: 1
    DI: 2
  notes: ''
- from: DDC-2F-BOH
  to: AHU-B.3 (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 1
    AO: 2
  notes: ''
- from: DDC-2F-BOH
  to: AHU-EL (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 5
  notes: ''
- from: DDC-2F-BOH
  to: AHU-EL (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 1
    AO: 1
    DI: 2
  notes: ''
- from: DDC-2F-BOH
  to: AHU-EL (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 1
    AO: 2
  notes: ''
- from: DDC-2F-BOH
  to: AHU-FR2 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 5
  notes: ''
- from: DDC-2F-BOH
  to: AHU-FR2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 1
    AO: 1
    DI: 2
  notes: ''
- from: DDC-2F-BOH
  to: AHU-FR2 (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 1
    AO: 2
  notes: ''
- from: DDC-2F-BOH
  to: AHU-FR3 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 5
  notes: ''
- from: DDC-2F-BOH
  to: AHU-FR3 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 1
    AO: 1
    DI: 2
  notes: ''
- from: DDC-2F-BOH
  to: AHU-FR3 (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 1
    AO: 2
  notes: ''
- from: DDC-2F-BOH
  to: AHU-PF (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 5
  notes: ''
- from: DDC-2F-BOH
  to: AHU-PF (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 1
    AO: 1
    DI: 2
  notes: ''
- from: DDC-2F-BOH
  to: AHU-PF (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  by_class:
    AI: 1
    AO: 2
  notes: ''
- from: DDC-2M-CASINO
  to: AIR-ION-2M.1 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: casino_2m_localized
  system: AC
  equipment_class: Air Ionizer (Casino)
  by_class:
    AI: 1
  notes: ''
- from: DDC-2M-CASINO
  to: AIR-ION-2M.1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: casino_2m_localized
  system: AC
  equipment_class: Air Ionizer (Casino)
  by_class:
    DI: 2
  notes: ''
- from: DDC-2M-CASINO
  to: AIR-ION-2M.2 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: casino_2m_localized
  system: AC
  equipment_class: Air Ionizer (Casino)
  by_class:
    AI: 1
  notes: ''
- from: DDC-2M-CASINO
  to: AIR-ION-2M.2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: casino_2m_localized
  system: AC
  equipment_class: Air Ionizer (Casino)
  by_class:
    DI: 2
  notes: ''
- from: DDC-2F-CHILLER
  to: CH-1 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  by_class:
    AI: 7
  notes: ''
- from: DDC-2F-CHILLER
  to: CH-1 (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  by_class:
    DI: 2
  notes: ''
- from: DDC-2F-CHILLER
  to: CH-2 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  by_class:
    AI: 7
  notes: ''
- from: DDC-2F-CHILLER
  to: CH-2 (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  by_class:
    DI: 2
  notes: ''
- from: DDC-2F-CHILLER
  to: CH-3 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  by_class:
    AI: 7
  notes: ''
- from: DDC-2F-CHILLER
  to: CH-3 (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  by_class:
    DI: 2
  notes: ''
- from: DDC-2F-CHILLER
  to: CHW-DIFF (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: CHW Bypass Header
  by_class:
    AI: 2
    DI: 1
  notes: ''
- from: DDC-2F-CHILLER
  to: CHW-RET-HDR (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: CHW Return Main Header
  by_class:
    AI: 2
  notes: ''
- from: DDC-2F-CHILLER
  to: CHW-SUP-HDR (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: CHW Supply Main Header
  by_class:
    AI: 2
  notes: ''
- from: DDC-2F-CHILLER
  to: COWP-1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: Condenser Water Pump
  by_class:
    DI: 3
    DO: 1
  notes: ''
- from: DDC-2F-CHILLER
  to: COWP-2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: Condenser Water Pump
  by_class:
    DI: 3
    DO: 1
  notes: ''
- from: DDC-2F-CHILLER
  to: COWP-3 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: Condenser Water Pump
  by_class:
    DI: 3
    DO: 1
  notes: ''
- from: DDC-RD-PLANT
  to: CT-1 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: AC
  equipment_class: Cooling Tower
  by_class:
    DI: 3
    DO: 1
  notes: ''
- from: DDC-RD-PLANT
  to: CT-1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: AC
  equipment_class: Cooling Tower
  by_class:
    DI: 2
    DO: 1
  notes: ''
- from: DDC-RD-PLANT
  to: CT-1 (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: AC
  equipment_class: Cooling Tower
  by_class:
    DI: 1
    AI: 1
  notes: ''
- from: DDC-RD-PLANT
  to: CT-2 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: AC
  equipment_class: Cooling Tower
  by_class:
    DI: 3
    DO: 1
  notes: ''
- from: DDC-RD-PLANT
  to: CT-2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: AC
  equipment_class: Cooling Tower
  by_class:
    DI: 2
    DO: 1
  notes: ''
- from: DDC-RD-PLANT
  to: CT-2 (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: AC
  equipment_class: Cooling Tower
  by_class:
    DI: 1
    AI: 1
  notes: ''
- from: DDC-RD-PLANT
  to: CT-3 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: AC
  equipment_class: Cooling Tower
  by_class:
    DI: 3
    DO: 1
  notes: ''
- from: DDC-RD-PLANT
  to: CT-3 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: AC
  equipment_class: Cooling Tower
  by_class:
    DI: 2
    DO: 1
  notes: ''
- from: DDC-RD-PLANT
  to: CT-3 (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: AC
  equipment_class: Cooling Tower
  by_class:
    DI: 1
    AI: 1
  notes: ''
- from: DDC-RD-PLANT
  to: CT-COMMON (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: AC
  equipment_class: Cooling Tower (Common)
  by_class:
    AI: 4
  notes: ''
- from: DDC-RD-PLANT
  to: CW-HDR (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: AC
  equipment_class: Condenser Water Header
  by_class:
    AI: 2
  notes: ''
- from: DDC-2M-CASINO
  to: DOAS-2M (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: casino_2m_localized
  system: VENT
  equipment_class: DOAS Unit (Casino — with CO/VOC)
  by_class:
    AI: 5
  notes: ''
- from: DDC-2M-CASINO
  to: DOAS-2M (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: casino_2m_localized
  system: VENT
  equipment_class: DOAS Unit (Casino — with CO/VOC)
  by_class:
    DI: 7
    AI: 2
  notes: ''
- from: DDC-2M-CASINO
  to: DOAS-2M (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: casino_2m_localized
  system: VENT
  equipment_class: DOAS Unit (Casino — with CO/VOC)
  by_class:
    AI: 1
    AO: 2
  notes: ''
- from: DDC-RD-PLANT
  to: DOAS-RD.1 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: VENT
  equipment_class: DOAS Unit
  by_class:
    AI: 6
  notes: ''
- from: DDC-RD-PLANT
  to: DOAS-RD.1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: VENT
  equipment_class: DOAS Unit
  by_class:
    DI: 8
    AI: 2
  notes: ''
- from: DDC-RD-PLANT
  to: DOAS-RD.1 (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: VENT
  equipment_class: DOAS Unit
  by_class:
    AI: 2
    AO: 2
  notes: ''
- from: DDC-RD-PLANT
  to: DOAS-RD.2 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: VENT
  equipment_class: DOAS Unit
  by_class:
    AI: 6
  notes: ''
- from: DDC-RD-PLANT
  to: DOAS-RD.2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: VENT
  equipment_class: DOAS Unit
  by_class:
    DI: 8
    AI: 2
  notes: ''
- from: DDC-RD-PLANT
  to: DOAS-RD.2 (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: VENT
  equipment_class: DOAS Unit
  by_class:
    AI: 2
    AO: 2
  notes: ''
- from: DDC-RD-PLANT
  to: EF-1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-2F-BOH
  to: EF-2.1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-2F-BOH
  to: EF-2.2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-2F-BOH
  to: EF-2.3 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-2F-BOH
  to: EF-2.4 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-2F-BOH
  to: EF-2B.1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-2F-BOH
  to: EF-2B.2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-3F
  to: EF-3.1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: amenity_3f
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-3F
  to: EF-3.2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: amenity_3f
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-3F
  to: EF-3.3 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: amenity_3f
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-3F
  to: EF-3.4 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: amenity_3f
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-3F
  to: EF-3B-G (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: amenity_3f
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-3F
  to: EF-3C.1-G (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: amenity_3f
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-B1-BOH
  to: EF-B.1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_b1
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-B1-BOH
  to: EF-B.2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_b1
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-B1-BOH
  to: EF-BR.1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_b1
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-B1-BOH
  to: EF-BR.2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_b1
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-B1-BOH
  to: EF-BS.1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_b1
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-B1-BOH
  to: EF-BS.2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_b1
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-B1-BOH
  to: EF-FOST.1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_b1
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-B1-BOH
  to: EF-GL.1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_b1
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-B1-BOH
  to: EF-GL.2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_b1
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-2F-BOH
  to: EF-GS.1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-2F-BOH
  to: EF-GS.2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-B1-BOH
  to: EF-MFR.1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_b1
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-B1-BOH
  to: EF-MP.1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_b1
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-2F-BOH
  to: EF-OHRv2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-B1-BOH
  to: EF-PR.1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_b1
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-B1-BOH
  to: EF-PR.3 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_b1
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-RD-PLANT
  to: EF-RD.1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-RD-PLANT
  to: EF-RO.2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-B1-BOH
  to: EF-WS.1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_b1
  system: VENT
  equipment_class: Exhaust Fan (General)
  by_class:
    DI: 3
  notes: ''
- from: DDC-RD-PLANT
  to: HP-HZ (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: HWL
  equipment_class: Heat Pump
  by_class:
    DI: 3
  notes: ''
- from: DDC-LG-PLANT
  to: HP-LZ (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_lg_boiler_hwl
  system: HWL
  equipment_class: Heat Pump
  by_class:
    DI: 3
  notes: ''
- from: DDC-RD-PLANT
  to: HWH-HZ (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: HWL
  equipment_class: Hot Water Header Set
  by_class:
    AI: 3
  notes: ''
- from: DDC-LG-PLANT
  to: HWH-LZ (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_lg_boiler_hwl
  system: HWL
  equipment_class: Hot Water Header Set
  by_class:
    AI: 3
  notes: ''
- from: DDC-RD-PLANT
  to: HWT-HZ (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: HWL
  equipment_class: Calorifier (Hot Water Storage Tank)
  by_class:
    AI: 1
  notes: ''
- from: DDC-LG-PLANT
  to: HWT-LZ (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_lg_boiler_hwl
  system: HWL
  equipment_class: Calorifier (Hot Water Storage Tank)
  by_class:
    AI: 1
  notes: ''
- from: DDC-B1-BOH
  to: PAHU-0.1 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_b1
  system: VENT
  equipment_class: Precooled Air Handling Unit
  by_class:
    AI: 3
  notes: ''
- from: DDC-B1-BOH
  to: PAHU-0.1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_b1
  system: VENT
  equipment_class: Precooled Air Handling Unit
  by_class:
    AI: 1
    AO: 1
    DI: 3
  notes: ''
- from: DDC-B1-BOH
  to: PAHU-0.1 (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_b1
  system: VENT
  equipment_class: Precooled Air Handling Unit
  by_class:
    AO: 1
  notes: ''
- from: DDC-2F-BOH
  to: PAHU-B.1 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Precooled Air Handling Unit
  by_class:
    AI: 3
  notes: ''
- from: DDC-2F-BOH
  to: PAHU-B.1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Precooled Air Handling Unit
  by_class:
    AI: 1
    AO: 1
    DI: 3
  notes: ''
- from: DDC-2F-BOH
  to: PAHU-B.1 (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Precooled Air Handling Unit
  by_class:
    AO: 1
  notes: ''
- from: DDC-2F-BOH
  to: PAHU-B.2 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Precooled Air Handling Unit
  by_class:
    AI: 3
  notes: ''
- from: DDC-2F-BOH
  to: PAHU-B.2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Precooled Air Handling Unit
  by_class:
    AI: 1
    AO: 1
    DI: 3
  notes: ''
- from: DDC-2F-BOH
  to: PAHU-B.2 (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Precooled Air Handling Unit
  by_class:
    AO: 1
  notes: ''
- from: DDC-2F-BOH
  to: PAHU-B.3 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Precooled Air Handling Unit
  by_class:
    AI: 3
  notes: ''
- from: DDC-2F-BOH
  to: PAHU-B.3 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Precooled Air Handling Unit
  by_class:
    AI: 1
    AO: 1
    DI: 3
  notes: ''
- from: DDC-2F-BOH
  to: PAHU-B.3 (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Precooled Air Handling Unit
  by_class:
    AO: 1
  notes: ''
- from: DDC-2F-BOH
  to: PAHU-FR (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Precooled Air Handling Unit
  by_class:
    AI: 3
  notes: ''
- from: DDC-2F-BOH
  to: PAHU-FR (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Precooled Air Handling Unit
  by_class:
    AI: 1
    AO: 1
    DI: 3
  notes: ''
- from: DDC-2F-BOH
  to: PAHU-FR (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Precooled Air Handling Unit
  by_class:
    AO: 1
  notes: ''
- from: DDC-2F-BOH
  to: PAHU-PF (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Precooled Air Handling Unit
  by_class:
    AI: 3
  notes: ''
- from: DDC-2F-BOH
  to: PAHU-PF (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Precooled Air Handling Unit
  by_class:
    AI: 1
    AO: 1
    DI: 3
  notes: ''
- from: DDC-2F-BOH
  to: PAHU-PF (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Precooled Air Handling Unit
  by_class:
    AO: 1
  notes: ''
- from: DDC-RD-PLANT
  to: PAHU-r.1 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: VENT
  equipment_class: Precooled Air Handling Unit
  by_class:
    AI: 3
  notes: ''
- from: DDC-RD-PLANT
  to: PAHU-r.1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: VENT
  equipment_class: Precooled Air Handling Unit
  by_class:
    AI: 1
    AO: 1
    DI: 3
  notes: ''
- from: DDC-RD-PLANT
  to: PAHU-r.1 (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: VENT
  equipment_class: Precooled Air Handling Unit
  by_class:
    AO: 1
  notes: ''
- from: DDC-RD-PLANT
  to: PAHU-r.2 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: VENT
  equipment_class: Precooled Air Handling Unit
  by_class:
    AI: 3
  notes: ''
- from: DDC-RD-PLANT
  to: PAHU-r.2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: VENT
  equipment_class: Precooled Air Handling Unit
  by_class:
    AI: 1
    AO: 1
    DI: 3
  notes: ''
- from: DDC-RD-PLANT
  to: PAHU-r.2 (ME Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: VENT
  equipment_class: Precooled Air Handling Unit
  by_class:
    AO: 1
  notes: ''
- from: DDC-2F-CHILLER
  to: PCHWP-1 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: Primary CHW Pump
  by_class:
    AI: 1
  notes: ''
- from: DDC-2F-CHILLER
  to: PCHWP-1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: Primary CHW Pump
  by_class:
    DI: 3
    DO: 1
  notes: ''
- from: DDC-2F-CHILLER
  to: PCHWP-2 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: Primary CHW Pump
  by_class:
    AI: 1
  notes: ''
- from: DDC-2F-CHILLER
  to: PCHWP-2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: Primary CHW Pump
  by_class:
    DI: 3
    DO: 1
  notes: ''
- from: DDC-2F-CHILLER
  to: PCHWP-3 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: Primary CHW Pump (Standby)
  by_class:
    DI: 3
    DO: 1
  notes: ''
- from: DDC-RD-PLANT
  to: RP-HZ (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: HWL
  equipment_class: Recirculating Pump
  by_class:
    DI: 3
  notes: ''
- from: DDC-LG-PLANT
  to: RP-LZ (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_lg_boiler_hwl
  system: HWL
  equipment_class: Recirculating Pump
  by_class:
    DI: 3
  notes: ''
- from: DDC-LG-PLANT
  to: SB-1 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_lg_boiler_hwl
  system: VENT
  equipment_class: Steam Boiler
  by_class:
    AI: 4
    DI: 1
    DO: 1
  notes: ''
- from: DDC-LG-PLANT
  to: SB-1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_lg_boiler_hwl
  system: VENT
  equipment_class: Steam Boiler
  by_class:
    DI: 2
  notes: ''
- from: DDC-LG-PLANT
  to: SB-2 (BMS Contractor)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_lg_boiler_hwl
  system: VENT
  equipment_class: Steam Boiler
  by_class:
    AI: 4
    DI: 1
    DO: 1
  notes: ''
- from: DDC-LG-PLANT
  to: SB-2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_lg_boiler_hwl
  system: VENT
  equipment_class: Steam Boiler
  by_class:
    DI: 2
  notes: ''
- from: DDC-2F-CHILLER
  to: SCHWP-1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: Secondary CHW Pump
  by_class:
    DI: 3
    DO: 1
  notes: ''
- from: DDC-2F-CHILLER
  to: SCHWP-2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: Secondary CHW Pump
  by_class:
    DI: 3
    DO: 1
  notes: ''
- from: DDC-2F-CHILLER
  to: SCHWP-3 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: Secondary CHW Pump
  by_class:
    DI: 3
    DO: 1
  notes: ''
- from: DDC-GF-BOH
  to: TEF-1.1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_gf
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  by_class:
    DI: 3
  notes: ''
- from: DDC-GF-BOH
  to: TEF-1.2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_gf
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  by_class:
    DI: 3
  notes: ''
- from: DDC-GF-BOH
  to: TEF-1.3 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_gf
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  by_class:
    DI: 3
  notes: ''
- from: DDC-GF-BOH
  to: TEF-1.4 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_gf
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  by_class:
    DI: 3
  notes: ''
- from: DDC-2F-BOH
  to: TEF-2.1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  by_class:
    DI: 3
  notes: ''
- from: DDC-2F-BOH
  to: TEF-2.2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  by_class:
    DI: 3
  notes: ''
- from: DDC-2F-BOH
  to: TEF-2B.3 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  by_class:
    DI: 3
  notes: ''
- from: DDC-3F
  to: TEF-30.20 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: amenity_3f
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  by_class:
    DI: 3
  notes: ''
- from: DDC-3F
  to: TEF-3A.1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: amenity_3f
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  by_class:
    DI: 3
  notes: ''
- from: DDC-3F
  to: TEF-3A.2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: amenity_3f
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  by_class:
    DI: 3
  notes: ''
- from: DDC-3F
  to: TEF-3B (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: amenity_3f
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  by_class:
    DI: 3
  notes: ''
- from: DDC-3F
  to: TEF-3C.1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: amenity_3f
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  by_class:
    DI: 3
  notes: ''
- from: DDC-3F
  to: TEF-3C.2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: amenity_3f
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  by_class:
    DI: 3
  notes: ''
- from: DDC-B1-BOH
  to: TEF-B.1 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_b1
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  by_class:
    DI: 3
  notes: ''
- from: DDC-B1-BOH
  to: TEF-B.2 (Equipment Supplier)
  method: typical_range
  length_m: null
  typical_range_key: boh_b1
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  by_class:
    DI: 3
  notes: ''
- from: DDC-2F-CHILLER
  to: CH-1 (Network)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  notes: Network drop
- from: DDC-2F-CHILLER
  to: CH-2 (Network)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  notes: Network drop
- from: DDC-2F-CHILLER
  to: CH-3 (Network)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  notes: Network drop
- from: DDC-2F-CHILLER
  to: PCHWP-1 (Network)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: Primary CHW Pump
  notes: Network drop
- from: DDC-2F-CHILLER
  to: PCHWP-2 (Network)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: Primary CHW Pump
  notes: Network drop
- from: DDC-2F-CHILLER
  to: SCHWP-1 (Network)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: Secondary CHW Pump
  notes: Network drop
- from: DDC-2F-CHILLER
  to: SCHWP-2 (Network)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: Secondary CHW Pump
  notes: Network drop
- from: DDC-2F-CHILLER
  to: SCHWP-3 (Network)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: AC
  equipment_class: Secondary CHW Pump
  notes: Network drop
- from: DDC-LG-PLANT
  to: SB-1 (Network)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_lg_boiler_hwl
  system: VENT
  equipment_class: Steam Boiler
  notes: Network drop
- from: DDC-LG-PLANT
  to: SB-2 (Network)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_lg_boiler_hwl
  system: VENT
  equipment_class: Steam Boiler
  notes: Network drop
- from: DDC-RD-PLANT
  to: DOAS-RD.1 (Network)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: VENT
  equipment_class: DOAS Unit
  notes: Network drop
- from: DDC-RD-PLANT
  to: DOAS-RD.2 (Network)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: VENT
  equipment_class: DOAS Unit
  notes: Network drop
- from: DDC-RD-PLANT
  to: PAHU-r.1 (Network)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: VENT
  equipment_class: Precooled Air Handling Unit
  notes: Network drop
- from: DDC-RD-PLANT
  to: PAHU-r.2 (Network)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_rd_plant
  system: VENT
  equipment_class: Precooled Air Handling Unit
  notes: Network drop
- from: DDC-2M-CASINO
  to: DOAS-2M (Network)
  method: typical_range
  length_m: null
  typical_range_key: casino_2m_localized
  system: VENT
  equipment_class: DOAS Unit (Casino — with CO/VOC)
  notes: Network drop
- from: DDC-2M-CASINO
  to: AHU-2M.1 (Network)
  method: typical_range
  length_m: null
  typical_range_key: casino_2m_localized
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  notes: Network drop
- from: DDC-2M-CASINO
  to: AHU-2M.2 (Network)
  method: typical_range
  length_m: null
  typical_range_key: casino_2m_localized
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  notes: Network drop
- from: DDC-2M-CASINO
  to: AIR-ION-2M.1 (Network)
  method: typical_range
  length_m: null
  typical_range_key: casino_2m_localized
  system: AC
  equipment_class: Air Ionizer (Casino)
  notes: Network drop
- from: DDC-2M-CASINO
  to: AIR-ION-2M.2 (Network)
  method: typical_range
  length_m: null
  typical_range_key: casino_2m_localized
  system: AC
  equipment_class: Air Ionizer (Casino)
  notes: Network drop
- from: DDC-2F-BOH
  to: AHU-B.1 (Network)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  notes: Network drop
- from: DDC-2F-BOH
  to: AHU-B.2 (Network)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  notes: Network drop
- from: DDC-2F-BOH
  to: AHU-B.3 (Network)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  notes: Network drop
- from: DDC-2F-BOH
  to: AHU-PF (Network)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  notes: Network drop
- from: DDC-2F-BOH
  to: AHU-EL (Network)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  notes: Network drop
- from: DDC-2F-BOH
  to: AHU-FR2 (Network)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  notes: Network drop
- from: DDC-2F-BOH
  to: AHU-FR3 (Network)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  notes: Network drop
- from: DDC-2F-BOH
  to: PAHU-B.1 (Network)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Precooled Air Handling Unit
  notes: Network drop
- from: DDC-2F-BOH
  to: PAHU-B.2 (Network)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Precooled Air Handling Unit
  notes: Network drop
- from: DDC-2F-BOH
  to: PAHU-B.3 (Network)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Precooled Air Handling Unit
  notes: Network drop
- from: DDC-2F-BOH
  to: PAHU-PF (Network)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Precooled Air Handling Unit
  notes: Network drop
- from: DDC-2F-BOH
  to: PAHU-FR (Network)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: VENT
  equipment_class: Precooled Air Handling Unit
  notes: Network drop
- from: DDC-GF-BOH
  to: AHU-1.1 (Network)
  method: typical_range
  length_m: null
  typical_range_key: boh_gf
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  notes: Network drop
- from: DDC-GF-BOH
  to: AHU-1.2 (Network)
  method: typical_range
  length_m: null
  typical_range_key: boh_gf
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  notes: Network drop
- from: DDC-GF-BOH
  to: AHU-1.3 (Network)
  method: typical_range
  length_m: null
  typical_range_key: boh_gf
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  notes: Network drop
- from: DDC-B1-BOH
  to: PAHU-0.1 (Network)
  method: typical_range
  length_m: null
  typical_range_key: boh_b1
  system: VENT
  equipment_class: Precooled Air Handling Unit
  notes: Network drop
- from: DDC-LG-PLANT
  to: MPM-MAIN (Network)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_lg_boiler_hwl
  system: EL
  equipment_class: Multifunction Power Meter (Main)
  notes: Network drop
- from: DDC-2F-CHILLER
  to: MPM-CHILLER (Network)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_chiller_2f
  system: EL
  equipment_class: Multifunction Power Meter (Feeder)
  notes: Network drop
- from: DDC-2F-BOH
  to: MPM-AHU-2F (Network)
  method: typical_range
  length_m: null
  typical_range_key: boh_2f
  system: EL
  equipment_class: Multifunction Power Meter (Feeder)
  notes: Network drop
- from: DDC-GF-BOH
  to: MPM-AHU-GF (Network)
  method: typical_range
  length_m: null
  typical_range_key: boh_gf
  system: EL
  equipment_class: Multifunction Power Meter (Feeder)
  notes: Network drop
- from: DDC-LG-PLANT
  to: MPM-LIGHT-A (Network)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_lg_boiler_hwl
  system: EL
  equipment_class: Multifunction Power Meter (Feeder)
  notes: Network drop
- from: DDC-LG-PLANT
  to: MPM-LIGHT-B (Network)
  method: typical_range
  length_m: null
  typical_range_key: plant_room_lg_boiler_hwl
  system: EL
  equipment_class: Multifunction Power Meter (Feeder)
  notes: Network drop
- from: DDC-GF-BOH
  to: FACP-GW (Network)
  method: typical_range
  length_m: null
  typical_range_key: boh_gf
  system: FDAS
  equipment_class: FACP Gateway
  notes: Network drop
- from: Local panelboard / EE-supplied feeder
  to: DDC-2F-BOH — BMS panel 240V power feed
  method: typical_range
  length_m: null
  typical_range_key: panel_power_feed_local
  notes: Panel power feed
- from: Local panelboard / EE-supplied feeder
  to: DDC-2F-CHILLER — BMS panel 240V power feed
  method: typical_range
  length_m: null
  typical_range_key: panel_power_feed_local
  notes: Panel power feed
- from: Local panelboard / EE-supplied feeder
  to: DDC-2M-CASINO — BMS panel 240V power feed
  method: typical_range
  length_m: null
  typical_range_key: panel_power_feed_local
  notes: Panel power feed
- from: Local panelboard / EE-supplied feeder
  to: DDC-3F — BMS panel 240V power feed
  method: typical_range
  length_m: null
  typical_range_key: panel_power_feed_local
  notes: Panel power feed
- from: Local panelboard / EE-supplied feeder
  to: DDC-B1-BOH — BMS panel 240V power feed
  method: typical_range
  length_m: null
  typical_range_key: panel_power_feed_local
  notes: Panel power feed
- from: Local panelboard / EE-supplied feeder
  to: DDC-GF-BOH — BMS panel 240V power feed
  method: typical_range
  length_m: null
  typical_range_key: panel_power_feed_local
  notes: Panel power feed
- from: Local panelboard / EE-supplied feeder
  to: DDC-LG-PLANT — BMS panel 240V power feed
  method: typical_range
  length_m: null
  typical_range_key: panel_power_feed_local
  notes: Panel power feed
- from: Local panelboard / EE-supplied feeder
  to: DDC-RD-PLANT — BMS panel 240V power feed
  method: typical_range
  length_m: null
  typical_range_key: panel_power_feed_local
  notes: Panel power feed