# A2 — Equipment Takeoff
# Generated from A1-io-list.yaml on $(date) — see metadata.generator
# Schema: see _playbook/checklists/working-documents.md (A2)
#
metadata:
  project: "Kingsford Hotel Bacolod \u2014 BMS"
  generated_from: A1-io-list.yaml
  generator: _playbook/tools/generate-a2-equipment-takeoff.py
  regenerate: Re-run the generator after A1 changes. Hand edits to make_model_assumed and notes can be preserved by editing equipment-class-defaults.yaml or adding per-instance overrides below.
summary:
  total_instances: 109
  by_equipment_class:
    Exhaust Fan (General): 32
    Exhaust Fan (Toilet): 15
    AHU (Chilled-Water-Served): 12
    Precooled Air Handling Unit: 8
    Multifunction Power Meter (Feeder): 5
    Chiller (Package Water-Cooled): 3
    Condenser Water Pump: 3
    Cooling Tower: 3
    Secondary CHW Pump: 3
    Air Ionizer (Casino): 2
    DOAS Unit: 2
    Heat Pump: 2
    Hot Water Header Set: 2
    Calorifier (Hot Water Storage Tank): 2
    Primary CHW Pump: 2
    Recirculating Pump: 2
    Steam Boiler: 2
    CHW Bypass Header: 1
    CHW Return Main Header: 1
    CHW Supply Main Header: 1
    Cooling Tower (Common): 1
    Condenser Water Header: 1
    "DOAS Unit (Casino \u2014 with CO/VOC)": 1
    FACP Gateway: 1
    Multifunction Power Meter (Main): 1
    Primary CHW Pump (Standby): 1
  by_location:
    2nd Level Chiller Room: 15
    Roof Deck: 11
    2nd Level BOH: 6
    2nd Mezzanine (Casino): 5
    3rd Floor: 5
    2nd Floor: 4
    Roof Deck HWL Area: 4
    Lower Ground HWL Room: 4
    GF Main Lobby Toilet: 4
    3rd Floor Toilet: 4
    Ground Floor BOH: 3
    Basement: 3
    2nd Level Pre-Function: 2
    2nd Floor BOH: 2
    Basement Battery Room: 2
    Basement Service: 2
    Basement Garbage Lobby: 2
    2nd Floor General Service: 2
    Basement Pump Room: 2
    Lower Ground Boiler Room: 2
    2nd Floor Toilet: 2
    3rd Floor Amenity Toilet: 2
    Basement Toilet: 2
    2nd Level Executive Lounge: 1
    2nd Level Function Room 2: 1
    2nd Level Function Room 3: 1
    Roof Deck CT Area: 1
    3rd Floor BOH: 1
    Basement FOST Room: 1
    Basement Main Fire Riser: 1
    Basement Mech / Pump: 1
    2nd Floor OHR: 1
    Basement Wash Service: 1
    Ground Floor Fire Command Center: 1
    2nd Level AHU MCC: 1
    Ground Floor AHU MCC: 1
    2nd Level Chiller MCC: 1
    Lower Ground Lighting Panel A: 1
    Lower Ground Lighting Panel B: 1
    Lower Ground Main Switchroom: 1
    2nd Level Function Rooms: 1
    2nd Floor BOH Toilet: 1
  by_panel:
    DDC-2F-BOH: 25
    DDC-B1-BOH: 17
    DDC-2F-CHILLER: 16
    DDC-RD-PLANT: 16
    DDC-3F: 12
    DDC-GF-BOH: 9
    DDC-LG-PLANT: 9
    DDC-2M-CASINO: 5
  by_primary_co:
    Equipment Supplier: 90
    BMS Contractor: 18
    EE Contractor: 1
takeoff:
- id: AHU-1.1
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: Ground Floor BOH
  system: AC
  panel: DDC-GF-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 12
    hli_subpoints: 2
    network_drops: 1
    total: 15
    by_type:
      AI: 7
      AO: 3
      DI: 2
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 7
      ME Contractor: 3
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: AHU-1.2
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: Ground Floor BOH
  system: AC
  panel: DDC-GF-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 12
    hli_subpoints: 2
    network_drops: 1
    total: 15
    by_type:
      AI: 7
      AO: 3
      DI: 2
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 7
      ME Contractor: 3
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: AHU-1.3
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: Ground Floor BOH
  system: AC
  panel: DDC-GF-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 12
    hli_subpoints: 2
    network_drops: 1
    total: 15
    by_type:
      AI: 7
      AO: 3
      DI: 2
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 7
      ME Contractor: 3
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: AHU-2M.1
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: 2nd Mezzanine (Casino)
  system: AC
  panel: DDC-2M-CASINO
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 12
    hli_subpoints: 2
    network_drops: 1
    total: 15
    by_type:
      AI: 7
      AO: 3
      DI: 2
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 7
      ME Contractor: 3
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: AHU-2M.2
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: 2nd Mezzanine (Casino)
  system: AC
  panel: DDC-2M-CASINO
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 12
    hli_subpoints: 2
    network_drops: 1
    total: 15
    by_type:
      AI: 7
      AO: 3
      DI: 2
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 7
      ME Contractor: 3
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: AHU-B.1
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: 2nd Level BOH
  system: AC
  panel: DDC-2F-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 12
    hli_subpoints: 2
    network_drops: 1
    total: 15
    by_type:
      AI: 7
      AO: 3
      DI: 2
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 7
      ME Contractor: 3
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: AHU-B.2
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: 2nd Level BOH
  system: AC
  panel: DDC-2F-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 12
    hli_subpoints: 2
    network_drops: 1
    total: 15
    by_type:
      AI: 7
      AO: 3
      DI: 2
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 7
      ME Contractor: 3
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: AHU-B.3
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: 2nd Level BOH
  system: AC
  panel: DDC-2F-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 12
    hli_subpoints: 2
    network_drops: 1
    total: 15
    by_type:
      AI: 7
      AO: 3
      DI: 2
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 7
      ME Contractor: 3
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: AHU-EL
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: 2nd Level Executive Lounge
  system: AC
  panel: DDC-2F-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 12
    hli_subpoints: 2
    network_drops: 1
    total: 15
    by_type:
      AI: 7
      AO: 3
      DI: 2
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 7
      ME Contractor: 3
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: AHU-FR2
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: 2nd Level Function Room 2
  system: AC
  panel: DDC-2F-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 12
    hli_subpoints: 2
    network_drops: 1
    total: 15
    by_type:
      AI: 7
      AO: 3
      DI: 2
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 7
      ME Contractor: 3
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: AHU-FR3
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: 2nd Level Function Room 3
  system: AC
  panel: DDC-2F-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 12
    hli_subpoints: 2
    network_drops: 1
    total: 15
    by_type:
      AI: 7
      AO: 3
      DI: 2
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 7
      ME Contractor: 3
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: AHU-PF
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: 2nd Level Pre-Function
  system: AC
  panel: DDC-2F-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 12
    hli_subpoints: 2
    network_drops: 1
    total: 15
    by_type:
      AI: 7
      AO: 3
      DI: 2
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 7
      ME Contractor: 3
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: AIR-ION-2M.1
  equipment_class: Air Ionizer (Casino)
  quantity: 1
  location: 2nd Mezzanine (Casino)
  system: AC
  panel: DDC-2M-CASINO
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 1
    total: 4
    by_type:
      AI: 1
      DI: 2
      Network: 1
    by_co:
      BMS Contractor: 1
      Equipment Supplier: 3
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: AIR-ION-2M.2
  equipment_class: Air Ionizer (Casino)
  quantity: 1
  location: 2nd Mezzanine (Casino)
  system: AC
  panel: DDC-2M-CASINO
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 1
    total: 4
    by_type:
      AI: 1
      DI: 2
      Network: 1
    by_co:
      BMS Contractor: 1
      Equipment Supplier: 3
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: CH-1
  equipment_class: Chiller (Package Water-Cooled)
  quantity: 1
  location: 2nd Level Chiller Room
  system: AC
  panel: DDC-2F-CHILLER
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 9
    hli_subpoints: 18
    network_drops: 1
    total: 28
    by_type:
      AI: 7
      DI: 2
      HLI: 18
      Network: 1
    by_co:
      BMS Contractor: 7
      Equipment Supplier: 19
      ME Contractor: 2
  make_model_assumed: Tier-1 BACnet IP chiller (Trane/York/Carrier/Daikin), water-cooled centrifugal or screw, sized per design cooling load
  network_type: BACnet/IP
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: BMS reads via chiller's native BACnet gateway. BMS supplies external T-sensors on entering/leaving CHW & CW pipes.
- id: CH-2
  equipment_class: Chiller (Package Water-Cooled)
  quantity: 1
  location: 2nd Level Chiller Room
  system: AC
  panel: DDC-2F-CHILLER
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 9
    hli_subpoints: 18
    network_drops: 1
    total: 28
    by_type:
      AI: 7
      DI: 2
      HLI: 18
      Network: 1
    by_co:
      BMS Contractor: 7
      Equipment Supplier: 19
      ME Contractor: 2
  make_model_assumed: Tier-1 BACnet IP chiller (Trane/York/Carrier/Daikin), water-cooled centrifugal or screw, sized per design cooling load
  network_type: BACnet/IP
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: BMS reads via chiller's native BACnet gateway. BMS supplies external T-sensors on entering/leaving CHW & CW pipes.
- id: CH-3
  equipment_class: Chiller (Package Water-Cooled)
  quantity: 1
  location: 2nd Level Chiller Room
  system: AC
  panel: DDC-2F-CHILLER
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 9
    hli_subpoints: 18
    network_drops: 1
    total: 28
    by_type:
      AI: 7
      DI: 2
      HLI: 18
      Network: 1
    by_co:
      BMS Contractor: 7
      Equipment Supplier: 19
      ME Contractor: 2
  make_model_assumed: Tier-1 BACnet IP chiller (Trane/York/Carrier/Daikin), water-cooled centrifugal or screw, sized per design cooling load
  network_type: BACnet/IP
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: BMS reads via chiller's native BACnet gateway. BMS supplies external T-sensors on entering/leaving CHW & CW pipes.
- id: CHW-DIFF
  equipment_class: CHW Bypass Header
  quantity: 1
  location: 2nd Level Chiller Room
  system: AC
  panel: DDC-2F-CHILLER
  primary_co: BMS Contractor
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      AI: 2
      DI: 1
    by_co:
      BMS Contractor: 3
  make_model_assumed: BMS dP/dT sensors + motorized bypass valve (BMS-supplied)
  network_type: Hardwired
  typical_supplier: BMS contractor
  notes: BMS controls bypass valve to maintain CHW differential.
- id: CHW-RET-HDR
  equipment_class: CHW Return Main Header
  quantity: 1
  location: 2nd Level Chiller Room
  system: AC
  panel: DDC-2F-CHILLER
  primary_co: BMS Contractor
  io_summary:
    physical_io: 2
    hli_subpoints: 0
    network_drops: 0
    total: 2
    by_type:
      AI: 2
    by_co:
      BMS Contractor: 2
  make_model_assumed: BMS T+P sensors on CHW return manifold
  network_type: Hardwired
  typical_supplier: BMS contractor
  notes: Field instrumentation only.
- id: CHW-SUP-HDR
  equipment_class: CHW Supply Main Header
  quantity: 1
  location: 2nd Level Chiller Room
  system: AC
  panel: DDC-2F-CHILLER
  primary_co: BMS Contractor
  io_summary:
    physical_io: 2
    hli_subpoints: 0
    network_drops: 0
    total: 2
    by_type:
      AI: 2
    by_co:
      BMS Contractor: 2
  make_model_assumed: BMS T+P sensors on CHW supply manifold
  network_type: Hardwired
  typical_supplier: BMS contractor
  notes: Field instrumentation only.
- id: COWP-1
  equipment_class: Condenser Water Pump
  quantity: 1
  location: 2nd Level Chiller Room
  system: AC
  panel: DDC-2F-CHILLER
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 4
    hli_subpoints: 0
    network_drops: 0
    total: 4
    by_type:
      DI: 3
      DO: 1
    by_co:
      Equipment Supplier: 4
  make_model_assumed: End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious)
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: BMS reads aux contacts; commands start via DO.
- id: COWP-2
  equipment_class: Condenser Water Pump
  quantity: 1
  location: 2nd Level Chiller Room
  system: AC
  panel: DDC-2F-CHILLER
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 4
    hli_subpoints: 0
    network_drops: 0
    total: 4
    by_type:
      DI: 3
      DO: 1
    by_co:
      Equipment Supplier: 4
  make_model_assumed: End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious)
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: BMS reads aux contacts; commands start via DO.
- id: COWP-3
  equipment_class: Condenser Water Pump
  quantity: 1
  location: 2nd Level Chiller Room
  system: AC
  panel: DDC-2F-CHILLER
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 4
    hli_subpoints: 0
    network_drops: 0
    total: 4
    by_type:
      DI: 3
      DO: 1
    by_co:
      Equipment Supplier: 4
  make_model_assumed: End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious)
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: BMS reads aux contacts; commands start via DO.
- id: CT-1
  equipment_class: Cooling Tower
  quantity: 1
  location: Roof Deck
  system: AC
  panel: DDC-RD-PLANT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 9
    hli_subpoints: 0
    network_drops: 0
    total: 9
    by_type:
      AI: 1
      DI: 6
      DO: 2
    by_co:
      BMS Contractor: 4
      Equipment Supplier: 3
      ME Contractor: 2
  make_model_assumed: Induced-draft counterflow open cooling tower (Marley/BAC/EVAPCO), sized per condenser water flow
  network_type: Hardwired
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: BMS supplies basin level sensors and condenser water header T-sensors.
- id: CT-2
  equipment_class: Cooling Tower
  quantity: 1
  location: Roof Deck
  system: AC
  panel: DDC-RD-PLANT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 9
    hli_subpoints: 0
    network_drops: 0
    total: 9
    by_type:
      AI: 1
      DI: 6
      DO: 2
    by_co:
      BMS Contractor: 4
      Equipment Supplier: 3
      ME Contractor: 2
  make_model_assumed: Induced-draft counterflow open cooling tower (Marley/BAC/EVAPCO), sized per condenser water flow
  network_type: Hardwired
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: BMS supplies basin level sensors and condenser water header T-sensors.
- id: CT-3
  equipment_class: Cooling Tower
  quantity: 1
  location: Roof Deck
  system: AC
  panel: DDC-RD-PLANT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 9
    hli_subpoints: 0
    network_drops: 0
    total: 9
    by_type:
      AI: 1
      DI: 6
      DO: 2
    by_co:
      BMS Contractor: 4
      Equipment Supplier: 3
      ME Contractor: 2
  make_model_assumed: Induced-draft counterflow open cooling tower (Marley/BAC/EVAPCO), sized per condenser water flow
  network_type: Hardwired
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: BMS supplies basin level sensors and condenser water header T-sensors.
- id: CT-COMMON
  equipment_class: Cooling Tower (Common)
  quantity: 1
  location: Roof Deck
  system: AC
  panel: DDC-RD-PLANT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 4
    hli_subpoints: 0
    network_drops: 0
    total: 4
    by_type:
      AI: 4
    by_co:
      BMS Contractor: 4
  make_model_assumed: Common BMS sensors at cooling tower area (OA T/RH, condenser headers)
  network_type: Hardwired
  typical_supplier: BMS contractor
  notes: "Field instrumentation only \u2014 no equipment per se."
- id: CW-HDR
  equipment_class: Condenser Water Header
  quantity: 1
  location: Roof Deck CT Area
  system: AC
  panel: DDC-RD-PLANT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 2
    hli_subpoints: 0
    network_drops: 0
    total: 2
    by_type:
      AI: 2
    by_co:
      BMS Contractor: 2
  make_model_assumed: BMS T sensors on condenser water headers at roofdeck
  network_type: Hardwired
  typical_supplier: BMS contractor
  notes: Field instrumentation only.
- id: DOAS-2M
  equipment_class: "DOAS Unit (Casino \u2014 with CO/VOC)"
  quantity: 1
  location: 2nd Mezzanine (Casino)
  system: VENT
  panel: DDC-2M-CASINO
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 17
    hli_subpoints: 4
    network_drops: 1
    total: 22
    by_type:
      AI: 8
      AO: 2
      DI: 7
      HLI: 4
      Network: 1
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 14
      ME Contractor: 3
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: DOAS-RD.1
  equipment_class: DOAS Unit
  quantity: 1
  location: Roof Deck
  system: VENT
  panel: DDC-RD-PLANT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 20
    hli_subpoints: 4
    network_drops: 1
    total: 25
    by_type:
      AI: 10
      AO: 2
      DI: 8
      HLI: 4
      Network: 1
    by_co:
      BMS Contractor: 6
      Equipment Supplier: 15
      ME Contractor: 4
  make_model_assumed: Dedicated Outdoor Air System with energy recovery wheel, supply + exhaust fans, CHW coil
  network_type: BACnet/IP
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: Native BACnet controller typical. BMS supplies external sensors (OA T/RH/Flow, indoor T/RH, exhaust T) and modulating valve actuator.
- id: DOAS-RD.2
  equipment_class: DOAS Unit
  quantity: 1
  location: Roof Deck
  system: VENT
  panel: DDC-RD-PLANT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 20
    hli_subpoints: 4
    network_drops: 1
    total: 25
    by_type:
      AI: 10
      AO: 2
      DI: 8
      HLI: 4
      Network: 1
    by_co:
      BMS Contractor: 6
      Equipment Supplier: 15
      ME Contractor: 4
  make_model_assumed: Dedicated Outdoor Air System with energy recovery wheel, supply + exhaust fans, CHW coil
  network_type: BACnet/IP
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: Native BACnet controller typical. BMS supplies external sensors (OA T/RH/Flow, indoor T/RH, exhaust T) and modulating valve actuator.
- id: EF-1
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: Roof Deck
  system: VENT
  panel: DDC-RD-PLANT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-2.1
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 2nd Floor
  system: VENT
  panel: DDC-2F-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-2.2
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 2nd Floor
  system: VENT
  panel: DDC-2F-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-2.3
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 2nd Floor
  system: VENT
  panel: DDC-2F-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-2.4
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 2nd Floor
  system: VENT
  panel: DDC-2F-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-2B.1
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 2nd Floor BOH
  system: VENT
  panel: DDC-2F-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-2B.2
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 2nd Floor BOH
  system: VENT
  panel: DDC-2F-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-3.1
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 3rd Floor
  system: VENT
  panel: DDC-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-3.2
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 3rd Floor
  system: VENT
  panel: DDC-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-3.3
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 3rd Floor
  system: VENT
  panel: DDC-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-3.4
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 3rd Floor
  system: VENT
  panel: DDC-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-3B-G
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 3rd Floor BOH
  system: VENT
  panel: DDC-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-3C.1-G
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 3rd Floor
  system: VENT
  panel: DDC-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-B.1
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: Basement
  system: VENT
  panel: DDC-B1-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-B.2
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: Basement
  system: VENT
  panel: DDC-B1-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-BR.1
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: Basement Battery Room
  system: VENT
  panel: DDC-B1-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-BR.2
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: Basement Battery Room
  system: VENT
  panel: DDC-B1-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-BS.1
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: Basement Service
  system: VENT
  panel: DDC-B1-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-BS.2
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: Basement Service
  system: VENT
  panel: DDC-B1-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-FOST.1
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: Basement FOST Room
  system: VENT
  panel: DDC-B1-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-GL.1
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: Basement Garbage Lobby
  system: VENT
  panel: DDC-B1-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-GL.2
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: Basement Garbage Lobby
  system: VENT
  panel: DDC-B1-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-GS.1
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 2nd Floor General Service
  system: VENT
  panel: DDC-2F-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-GS.2
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 2nd Floor General Service
  system: VENT
  panel: DDC-2F-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-MFR.1
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: Basement Main Fire Riser
  system: VENT
  panel: DDC-B1-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-MP.1
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: Basement Mech / Pump
  system: VENT
  panel: DDC-B1-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-OHRv2
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 2nd Floor OHR
  system: VENT
  panel: DDC-2F-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-PR.1
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: Basement Pump Room
  system: VENT
  panel: DDC-B1-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-PR.3
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: Basement Pump Room
  system: VENT
  panel: DDC-B1-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-RD.1
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: Roof Deck
  system: VENT
  panel: DDC-RD-PLANT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-RO.2
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: Roof Deck
  system: VENT
  panel: DDC-RD-PLANT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EF-WS.1
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: Basement Wash Service
  system: VENT
  panel: DDC-B1-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: FACP-GW
  equipment_class: FACP Gateway
  quantity: 1
  location: Ground Floor Fire Command Center
  system: FDAS
  panel: DDC-GF-BOH
  primary_co: EE Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 3
    network_drops: 1
    total: 4
    by_type:
      HLI: 3
      Network: 1
    by_co:
      EE Contractor: 4
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: HP-HZ
  equipment_class: Heat Pump
  quantity: 1
  location: Roof Deck HWL Area
  system: HWL
  panel: DDC-RD-PLANT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Air-source or water-source heat pump for hot water heating
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor / Equipment supplier
  notes: BMS reads pump status/HOA/trip via aux contacts.
- id: HP-LZ
  equipment_class: Heat Pump
  quantity: 1
  location: Lower Ground HWL Room
  system: HWL
  panel: DDC-LG-PLANT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Air-source or water-source heat pump for hot water heating
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor / Equipment supplier
  notes: BMS reads pump status/HOA/trip via aux contacts.
- id: HWH-HZ
  equipment_class: Hot Water Header Set
  quantity: 1
  location: Roof Deck HWL Area
  system: HWL
  panel: DDC-RD-PLANT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      AI: 3
    by_co:
      BMS Contractor: 3
  make_model_assumed: Hot water supply/return manifolds with BMS T sensors and make-up cold water T sensor
  network_type: Hardwired
  typical_supplier: BMS contractor
  notes: Field instrumentation on existing piping.
- id: HWH-LZ
  equipment_class: Hot Water Header Set
  quantity: 1
  location: Lower Ground HWL Room
  system: HWL
  panel: DDC-LG-PLANT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      AI: 3
    by_co:
      BMS Contractor: 3
  make_model_assumed: Hot water supply/return manifolds with BMS T sensors and make-up cold water T sensor
  network_type: Hardwired
  typical_supplier: BMS contractor
  notes: Field instrumentation on existing piping.
- id: HWT-HZ
  equipment_class: Calorifier (Hot Water Storage Tank)
  quantity: 1
  location: Roof Deck HWL Area
  system: HWL
  panel: DDC-RD-PLANT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 1
    hli_subpoints: 0
    network_drops: 0
    total: 1
    by_type:
      AI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Pressurised hot-water storage tank with internal coil, sized per design hot water demand
  network_type: Hardwired
  typical_supplier: Plumbing contractor
  notes: BMS supplies tank temperature sensor (immersion or strapped probe).
- id: HWT-LZ
  equipment_class: Calorifier (Hot Water Storage Tank)
  quantity: 1
  location: Lower Ground HWL Room
  system: HWL
  panel: DDC-LG-PLANT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 1
    hli_subpoints: 0
    network_drops: 0
    total: 1
    by_type:
      AI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Pressurised hot-water storage tank with internal coil, sized per design hot water demand
  network_type: Hardwired
  typical_supplier: Plumbing contractor
  notes: BMS supplies tank temperature sensor (immersion or strapped probe).
- id: MPM-AHU-2F
  equipment_class: Multifunction Power Meter (Feeder)
  quantity: 1
  location: 2nd Level AHU MCC
  system: EL
  panel: DDC-2F-BOH
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 1
    network_drops: 1
    total: 2
    by_type:
      HLI: 1
      Network: 1
    by_co:
      BMS Contractor: 2
  make_model_assumed: Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)
  network_type: Modbus RTU
  typical_supplier: BMS contractor
  notes: Daisy-chained on Modbus bus(es) back to BMS gateway.
- id: MPM-AHU-GF
  equipment_class: Multifunction Power Meter (Feeder)
  quantity: 1
  location: Ground Floor AHU MCC
  system: EL
  panel: DDC-GF-BOH
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 1
    network_drops: 1
    total: 2
    by_type:
      HLI: 1
      Network: 1
    by_co:
      BMS Contractor: 2
  make_model_assumed: Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)
  network_type: Modbus RTU
  typical_supplier: BMS contractor
  notes: Daisy-chained on Modbus bus(es) back to BMS gateway.
- id: MPM-CHILLER
  equipment_class: Multifunction Power Meter (Feeder)
  quantity: 1
  location: 2nd Level Chiller MCC
  system: EL
  panel: DDC-2F-CHILLER
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 1
    network_drops: 1
    total: 2
    by_type:
      HLI: 1
      Network: 1
    by_co:
      BMS Contractor: 2
  make_model_assumed: Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)
  network_type: Modbus RTU
  typical_supplier: BMS contractor
  notes: Daisy-chained on Modbus bus(es) back to BMS gateway.
- id: MPM-LIGHT-A
  equipment_class: Multifunction Power Meter (Feeder)
  quantity: 1
  location: Lower Ground Lighting Panel A
  system: EL
  panel: DDC-LG-PLANT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 1
    network_drops: 1
    total: 2
    by_type:
      HLI: 1
      Network: 1
    by_co:
      BMS Contractor: 2
  make_model_assumed: Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)
  network_type: Modbus RTU
  typical_supplier: BMS contractor
  notes: Daisy-chained on Modbus bus(es) back to BMS gateway.
- id: MPM-LIGHT-B
  equipment_class: Multifunction Power Meter (Feeder)
  quantity: 1
  location: Lower Ground Lighting Panel B
  system: EL
  panel: DDC-LG-PLANT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 1
    network_drops: 1
    total: 2
    by_type:
      HLI: 1
      Network: 1
    by_co:
      BMS Contractor: 2
  make_model_assumed: Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)
  network_type: Modbus RTU
  typical_supplier: BMS contractor
  notes: Daisy-chained on Modbus bus(es) back to BMS gateway.
- id: MPM-MAIN
  equipment_class: Multifunction Power Meter (Main)
  quantity: 1
  location: Lower Ground Main Switchroom
  system: EL
  panel: DDC-LG-PLANT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 1
    network_drops: 1
    total: 2
    by_type:
      HLI: 1
      Network: 1
    by_co:
      BMS Contractor: 2
  make_model_assumed: Multifunction power meter with Modbus output (Schneider PM-series, ABB M2M, Siemens SENTRON), main switchgear class
  network_type: Modbus RTU/TCP
  typical_supplier: BMS contractor
  notes: Mounted in main switchgear or on dedicated BMS-side panel.
- id: PAHU-0.1
  equipment_class: Precooled Air Handling Unit
  quantity: 1
  location: Basement
  system: VENT
  panel: DDC-B1-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 9
    hli_subpoints: 2
    network_drops: 1
    total: 12
    by_type:
      AI: 4
      AO: 2
      DI: 3
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 3
      Equipment Supplier: 8
      ME Contractor: 1
  make_model_assumed: Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust path
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: 'Precool function: cools outdoor air before it''s distributed to other systems. BMS supplies OA/supply T sensors.'
- id: PAHU-B.1
  equipment_class: Precooled Air Handling Unit
  quantity: 1
  location: 2nd Level BOH
  system: VENT
  panel: DDC-2F-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 9
    hli_subpoints: 2
    network_drops: 1
    total: 12
    by_type:
      AI: 4
      AO: 2
      DI: 3
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 3
      Equipment Supplier: 8
      ME Contractor: 1
  make_model_assumed: Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust path
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: 'Precool function: cools outdoor air before it''s distributed to other systems. BMS supplies OA/supply T sensors.'
- id: PAHU-B.2
  equipment_class: Precooled Air Handling Unit
  quantity: 1
  location: 2nd Level BOH
  system: VENT
  panel: DDC-2F-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 9
    hli_subpoints: 2
    network_drops: 1
    total: 12
    by_type:
      AI: 4
      AO: 2
      DI: 3
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 3
      Equipment Supplier: 8
      ME Contractor: 1
  make_model_assumed: Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust path
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: 'Precool function: cools outdoor air before it''s distributed to other systems. BMS supplies OA/supply T sensors.'
- id: PAHU-B.3
  equipment_class: Precooled Air Handling Unit
  quantity: 1
  location: 2nd Level BOH
  system: VENT
  panel: DDC-2F-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 9
    hli_subpoints: 2
    network_drops: 1
    total: 12
    by_type:
      AI: 4
      AO: 2
      DI: 3
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 3
      Equipment Supplier: 8
      ME Contractor: 1
  make_model_assumed: Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust path
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: 'Precool function: cools outdoor air before it''s distributed to other systems. BMS supplies OA/supply T sensors.'
- id: PAHU-FR
  equipment_class: Precooled Air Handling Unit
  quantity: 1
  location: 2nd Level Function Rooms
  system: VENT
  panel: DDC-2F-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 9
    hli_subpoints: 2
    network_drops: 1
    total: 12
    by_type:
      AI: 4
      AO: 2
      DI: 3
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 3
      Equipment Supplier: 8
      ME Contractor: 1
  make_model_assumed: Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust path
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: 'Precool function: cools outdoor air before it''s distributed to other systems. BMS supplies OA/supply T sensors.'
- id: PAHU-PF
  equipment_class: Precooled Air Handling Unit
  quantity: 1
  location: 2nd Level Pre-Function
  system: VENT
  panel: DDC-2F-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 9
    hli_subpoints: 2
    network_drops: 1
    total: 12
    by_type:
      AI: 4
      AO: 2
      DI: 3
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 3
      Equipment Supplier: 8
      ME Contractor: 1
  make_model_assumed: Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust path
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: 'Precool function: cools outdoor air before it''s distributed to other systems. BMS supplies OA/supply T sensors.'
- id: PAHU-r.1
  equipment_class: Precooled Air Handling Unit
  quantity: 1
  location: Roof Deck
  system: VENT
  panel: DDC-RD-PLANT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 9
    hli_subpoints: 2
    network_drops: 1
    total: 12
    by_type:
      AI: 4
      AO: 2
      DI: 3
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 3
      Equipment Supplier: 8
      ME Contractor: 1
  make_model_assumed: Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust path
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: 'Precool function: cools outdoor air before it''s distributed to other systems. BMS supplies OA/supply T sensors.'
- id: PAHU-r.2
  equipment_class: Precooled Air Handling Unit
  quantity: 1
  location: Roof Deck
  system: VENT
  panel: DDC-RD-PLANT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 9
    hli_subpoints: 2
    network_drops: 1
    total: 12
    by_type:
      AI: 4
      AO: 2
      DI: 3
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 3
      Equipment Supplier: 8
      ME Contractor: 1
  make_model_assumed: Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust path
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: 'Precool function: cools outdoor air before it''s distributed to other systems. BMS supplies OA/supply T sensors.'
- id: PCHWP-1
  equipment_class: Primary CHW Pump
  quantity: 1
  location: 2nd Level Chiller Room
  system: AC
  panel: DDC-2F-CHILLER
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 5
    hli_subpoints: 2
    network_drops: 1
    total: 8
    by_type:
      AI: 1
      DI: 3
      DO: 1
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 1
      Equipment Supplier: 7
  make_model_assumed: End-suction or split-case centrifugal with VFD, sized per design CHW flow
  network_type: Hardwired (BMS reads VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: VFD typically Equipment Supplier provided with BACnet card.
- id: PCHWP-2
  equipment_class: Primary CHW Pump
  quantity: 1
  location: 2nd Level Chiller Room
  system: AC
  panel: DDC-2F-CHILLER
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 5
    hli_subpoints: 2
    network_drops: 1
    total: 8
    by_type:
      AI: 1
      DI: 3
      DO: 1
      HLI: 2
      Network: 1
    by_co:
      BMS Contractor: 1
      Equipment Supplier: 7
  make_model_assumed: End-suction or split-case centrifugal with VFD, sized per design CHW flow
  network_type: Hardwired (BMS reads VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: VFD typically Equipment Supplier provided with BACnet card.
- id: PCHWP-3
  equipment_class: Primary CHW Pump (Standby)
  quantity: 1
  location: 2nd Level Chiller Room
  system: AC
  panel: DDC-2F-CHILLER
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 4
    hli_subpoints: 0
    network_drops: 0
    total: 4
    by_type:
      DI: 3
      DO: 1
    by_co:
      Equipment Supplier: 4
  make_model_assumed: Same as Primary CHW Pump (1 standby for N+1 redundancy)
  network_type: Hardwired (BMS reads VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: Standby unit per A-CHW-001.
- id: RP-HZ
  equipment_class: Recirculating Pump
  quantity: 1
  location: Roof Deck HWL Area
  system: HWL
  panel: DDC-RD-PLANT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Hot water recirculating pump, fixed-speed (typical for hotwater systems)
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor
  notes: BMS reads aux contacts only.
- id: RP-LZ
  equipment_class: Recirculating Pump
  quantity: 1
  location: Lower Ground HWL Room
  system: HWL
  panel: DDC-LG-PLANT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Hot water recirculating pump, fixed-speed (typical for hotwater systems)
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor
  notes: BMS reads aux contacts only.
- id: SB-1
  equipment_class: Steam Boiler
  quantity: 1
  location: Lower Ground Boiler Room
  system: VENT
  panel: DDC-LG-PLANT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 8
    hli_subpoints: 8
    network_drops: 1
    total: 17
    by_type:
      AI: 4
      DI: 3
      DO: 1
      HLI: 8
      Network: 1
    by_co:
      BMS Contractor: 6
      Equipment Supplier: 11
  make_model_assumed: Fire-tube steam boiler with multi-stage burner, fuel-oil fired (typical for hotel laundry)
  network_type: Hardwired
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: BMS supplies steam pressure, feedwater T, fluegas T+O2 sensors. Boiler equipment provides aux contacts for status/HOA/trip points.
- id: SB-2
  equipment_class: Steam Boiler
  quantity: 1
  location: Lower Ground Boiler Room
  system: VENT
  panel: DDC-LG-PLANT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 8
    hli_subpoints: 8
    network_drops: 1
    total: 17
    by_type:
      AI: 4
      DI: 3
      DO: 1
      HLI: 8
      Network: 1
    by_co:
      BMS Contractor: 6
      Equipment Supplier: 11
  make_model_assumed: Fire-tube steam boiler with multi-stage burner, fuel-oil fired (typical for hotel laundry)
  network_type: Hardwired
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: BMS supplies steam pressure, feedwater T, fluegas T+O2 sensors. Boiler equipment provides aux contacts for status/HOA/trip points.
- id: SCHWP-1
  equipment_class: Secondary CHW Pump
  quantity: 1
  location: 2nd Level Chiller Room
  system: AC
  panel: DDC-2F-CHILLER
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 4
    hli_subpoints: 2
    network_drops: 1
    total: 7
    by_type:
      DI: 3
      DO: 1
      HLI: 2
      Network: 1
    by_co:
      Equipment Supplier: 7
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: SCHWP-2
  equipment_class: Secondary CHW Pump
  quantity: 1
  location: 2nd Level Chiller Room
  system: AC
  panel: DDC-2F-CHILLER
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 4
    hli_subpoints: 2
    network_drops: 1
    total: 7
    by_type:
      DI: 3
      DO: 1
      HLI: 2
      Network: 1
    by_co:
      Equipment Supplier: 7
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: SCHWP-3
  equipment_class: Secondary CHW Pump
  quantity: 1
  location: 2nd Level Chiller Room
  system: AC
  panel: DDC-2F-CHILLER
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 4
    hli_subpoints: 2
    network_drops: 1
    total: 7
    by_type:
      DI: 3
      DO: 1
      HLI: 2
      Network: 1
    by_co:
      Equipment Supplier: 7
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: TEF-1.1
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: GF Main Lobby Toilet
  system: VENT
  panel: DDC-GF-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-1.2
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: GF Main Lobby Toilet
  system: VENT
  panel: DDC-GF-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-1.3
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: GF Main Lobby Toilet
  system: VENT
  panel: DDC-GF-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-1.4
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: GF Main Lobby Toilet
  system: VENT
  panel: DDC-GF-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-2.1
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 2nd Floor Toilet
  system: VENT
  panel: DDC-2F-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-2.2
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 2nd Floor Toilet
  system: VENT
  panel: DDC-2F-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-2B.3
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 2nd Floor BOH Toilet
  system: VENT
  panel: DDC-2F-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-30.20
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor Toilet
  system: VENT
  panel: DDC-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3A.1
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor Amenity Toilet
  system: VENT
  panel: DDC-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3A.2
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor Amenity Toilet
  system: VENT
  panel: DDC-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3B
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor Toilet
  system: VENT
  panel: DDC-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3C.1
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor Toilet
  system: VENT
  panel: DDC-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3C.2
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: 3rd Floor Toilet
  system: VENT
  panel: DDC-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-B.1
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: Basement Toilet
  system: VENT
  panel: DDC-B1-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-B.2
  equipment_class: Exhaust Fan (Toilet)
  quantity: 1
  location: Basement Toilet
  system: VENT
  panel: DDC-B1-BOH
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line or roof-mounted toilet exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."