metadata:
  project: Kingsford Hotel Bacolod — BMS
  date: '2026-04-28'
  source: BMS-01 / BMS-02 / BMS-03 (TUEC Construction Bulletin Oct 2025) + MC Standards Part B Mechanical + Part C Plumbing (Megaworld DRC-004-2024 Revised BMS Standards Condotels)
  status: draft
  aggregation_strategy: 'per-instance (D-005, AB-Run-6 Patch A): every plant equipment unit enumerated; no zone-class aggregation in this run because the consultant''s points list explicitly tags every
    equipment by floor/area'
io_list:
- id: P-0001
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Entering Chilled Water Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0002
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Leaving Chilled Water Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0003
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Isolation Motorized Valve Status CHW Return & Supply
  type: DI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0004
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Entering Condenser Water Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0005
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Leaving Condenser Water Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0006
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Isolation Motorized Valve Status COW Return & Supply
  type: DI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0007
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Chilled Water Return Flow Metering
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0008
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Chilled Water Supply Flow Metering
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0009
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Condenser Water Supply Flow Metering
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0010
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Network drop (BACnet/IP — chiller plant manager gateway)
  type: Network
  field_device: Chiller PLC + BACnet gateway
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0011
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Chiller Compressor Pump On/Off Status
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0012
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Chiller Compressor Hand/Off/Auto Status
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0013
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Chiller Compressor Trip Alarm Status
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0014
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Motor Load Current
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0015
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Motor Consumption — KW / BTU Meter
  type: HLI
  field_device: Chiller PLC + BTU meter
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0016
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Winding Temperature
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0017
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Evaporator Approach Delta Temperature
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0018
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Evaporator Approach Delta Pressure
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0019
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Evaporator Refrigerant Pressure
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0020
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Evaporator Refrigerant Temperature
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0021
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Condenser Refrigerant Pressure
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0022
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Condenser Refrigerant Temperature
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0023
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Condenser Approach Delta Temperature
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0024
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Condenser Approach Delta Pressure
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0025
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Oil Sump Pressure
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0026
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Oil Sump Temperature
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0027
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Oil Pump Status (ON/OFF)
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0028
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Chiller Room
  point_description: Oil Pump Trip Status
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0029
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Entering Chilled Water Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0030
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Leaving Chilled Water Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0031
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Isolation Motorized Valve Status CHW Return & Supply
  type: DI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0032
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Entering Condenser Water Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0033
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Leaving Condenser Water Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0034
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Isolation Motorized Valve Status COW Return & Supply
  type: DI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0035
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Chilled Water Return Flow Metering
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0036
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Chilled Water Supply Flow Metering
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0037
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Condenser Water Supply Flow Metering
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0038
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Network drop (BACnet/IP — chiller plant manager gateway)
  type: Network
  field_device: Chiller PLC + BACnet gateway
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0039
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Chiller Compressor Pump On/Off Status
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0040
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Chiller Compressor Hand/Off/Auto Status
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0041
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Chiller Compressor Trip Alarm Status
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0042
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Motor Load Current
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0043
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Motor Consumption — KW / BTU Meter
  type: HLI
  field_device: Chiller PLC + BTU meter
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0044
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Winding Temperature
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0045
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Evaporator Approach Delta Temperature
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0046
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Evaporator Approach Delta Pressure
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0047
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Evaporator Refrigerant Pressure
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0048
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Evaporator Refrigerant Temperature
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0049
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Condenser Refrigerant Pressure
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0050
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Condenser Refrigerant Temperature
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0051
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Condenser Approach Delta Temperature
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0052
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Condenser Approach Delta Pressure
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0053
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Oil Sump Pressure
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0054
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Oil Sump Temperature
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0055
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Oil Pump Status (ON/OFF)
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0056
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Chiller Room
  point_description: Oil Pump Trip Status
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0057
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Entering Chilled Water Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0058
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Leaving Chilled Water Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0059
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Isolation Motorized Valve Status CHW Return & Supply
  type: DI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0060
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Entering Condenser Water Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0061
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Leaving Condenser Water Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0062
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Isolation Motorized Valve Status COW Return & Supply
  type: DI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0063
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Chilled Water Return Flow Metering
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0064
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Chilled Water Supply Flow Metering
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0065
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Condenser Water Supply Flow Metering
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0066
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Network drop (BACnet/IP — chiller plant manager gateway)
  type: Network
  field_device: Chiller PLC + BACnet gateway
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0067
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Chiller Compressor Pump On/Off Status
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0068
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Chiller Compressor Hand/Off/Auto Status
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0069
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Chiller Compressor Trip Alarm Status
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0070
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Motor Load Current
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0071
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Motor Consumption — KW / BTU Meter
  type: HLI
  field_device: Chiller PLC + BTU meter
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0072
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Winding Temperature
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0073
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Evaporator Approach Delta Temperature
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0074
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Evaporator Approach Delta Pressure
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0075
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Evaporator Refrigerant Pressure
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0076
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Evaporator Refrigerant Temperature
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0077
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Condenser Refrigerant Pressure
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0078
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Condenser Refrigerant Temperature
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0079
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Condenser Approach Delta Temperature
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0080
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Condenser Approach Delta Pressure
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0081
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Oil Sump Pressure
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0082
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Oil Sump Temperature
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0083
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Oil Pump Status (ON/OFF)
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0084
  system: AC
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Chiller Room
  point_description: Oil Pump Trip Status
  type: HLI
  field_device: Chiller PLC
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0085
  system: AC
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-1
  location: 2nd Level Chiller Room
  point_description: Pump On/Off Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0086
  system: AC
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-1
  location: 2nd Level Chiller Room
  point_description: Pump Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0087
  system: AC
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-1
  location: 2nd Level Chiller Room
  point_description: Pump Trip Alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0088
  system: AC
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-1
  location: 2nd Level Chiller Room
  point_description: Pump Start/Stop Command
  type: DO
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0089
  system: AC
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-1
  location: 2nd Level Chiller Room
  point_description: Chilled Water Supply Pressure
  type: AI
  field_device: Pressure Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0090
  system: AC
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-1
  location: 2nd Level Chiller Room
  point_description: VFD Speed (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0091
  system: AC
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-1
  location: 2nd Level Chiller Room
  point_description: VFD Speed Command (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0092
  system: AC
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-1
  location: 2nd Level Chiller Room
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0093
  system: AC
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-2
  location: 2nd Level Chiller Room
  point_description: Pump On/Off Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0094
  system: AC
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-2
  location: 2nd Level Chiller Room
  point_description: Pump Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0095
  system: AC
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-2
  location: 2nd Level Chiller Room
  point_description: Pump Trip Alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0096
  system: AC
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-2
  location: 2nd Level Chiller Room
  point_description: Pump Start/Stop Command
  type: DO
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0097
  system: AC
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-2
  location: 2nd Level Chiller Room
  point_description: Chilled Water Supply Pressure
  type: AI
  field_device: Pressure Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0098
  system: AC
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-2
  location: 2nd Level Chiller Room
  point_description: VFD Speed (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0099
  system: AC
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-2
  location: 2nd Level Chiller Room
  point_description: VFD Speed Command (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0100
  system: AC
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-2
  location: 2nd Level Chiller Room
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0101
  system: AC
  equipment_class: Primary CHW Pump (Standby)
  equipment_instance: PCHWP-3
  location: 2nd Level Chiller Room
  point_description: Pump On/Off Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0102
  system: AC
  equipment_class: Primary CHW Pump (Standby)
  equipment_instance: PCHWP-3
  location: 2nd Level Chiller Room
  point_description: Pump Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0103
  system: AC
  equipment_class: Primary CHW Pump (Standby)
  equipment_instance: PCHWP-3
  location: 2nd Level Chiller Room
  point_description: Pump Trip Alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0104
  system: AC
  equipment_class: Primary CHW Pump (Standby)
  equipment_instance: PCHWP-3
  location: 2nd Level Chiller Room
  point_description: Pump Start/Stop Command
  type: DO
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0105
  system: AC
  equipment_class: Secondary CHW Pump
  equipment_instance: SCHWP-1
  location: 2nd Level Chiller Room
  point_description: Pump On/Off Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0106
  system: AC
  equipment_class: Secondary CHW Pump
  equipment_instance: SCHWP-1
  location: 2nd Level Chiller Room
  point_description: Pump Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0107
  system: AC
  equipment_class: Secondary CHW Pump
  equipment_instance: SCHWP-1
  location: 2nd Level Chiller Room
  point_description: Pump Trip Alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0108
  system: AC
  equipment_class: Secondary CHW Pump
  equipment_instance: SCHWP-1
  location: 2nd Level Chiller Room
  point_description: Pump Start/Stop Command
  type: DO
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0109
  system: AC
  equipment_class: Secondary CHW Pump
  equipment_instance: SCHWP-1
  location: 2nd Level Chiller Room
  point_description: VFD Speed (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0110
  system: AC
  equipment_class: Secondary CHW Pump
  equipment_instance: SCHWP-1
  location: 2nd Level Chiller Room
  point_description: VFD Speed Command (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0111
  system: AC
  equipment_class: Secondary CHW Pump
  equipment_instance: SCHWP-1
  location: 2nd Level Chiller Room
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0112
  system: AC
  equipment_class: Secondary CHW Pump
  equipment_instance: SCHWP-2
  location: 2nd Level Chiller Room
  point_description: Pump On/Off Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0113
  system: AC
  equipment_class: Secondary CHW Pump
  equipment_instance: SCHWP-2
  location: 2nd Level Chiller Room
  point_description: Pump Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0114
  system: AC
  equipment_class: Secondary CHW Pump
  equipment_instance: SCHWP-2
  location: 2nd Level Chiller Room
  point_description: Pump Trip Alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0115
  system: AC
  equipment_class: Secondary CHW Pump
  equipment_instance: SCHWP-2
  location: 2nd Level Chiller Room
  point_description: Pump Start/Stop Command
  type: DO
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0116
  system: AC
  equipment_class: Secondary CHW Pump
  equipment_instance: SCHWP-2
  location: 2nd Level Chiller Room
  point_description: VFD Speed (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0117
  system: AC
  equipment_class: Secondary CHW Pump
  equipment_instance: SCHWP-2
  location: 2nd Level Chiller Room
  point_description: VFD Speed Command (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0118
  system: AC
  equipment_class: Secondary CHW Pump
  equipment_instance: SCHWP-2
  location: 2nd Level Chiller Room
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0119
  system: AC
  equipment_class: Secondary CHW Pump
  equipment_instance: SCHWP-3
  location: 2nd Level Chiller Room
  point_description: Pump On/Off Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0120
  system: AC
  equipment_class: Secondary CHW Pump
  equipment_instance: SCHWP-3
  location: 2nd Level Chiller Room
  point_description: Pump Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0121
  system: AC
  equipment_class: Secondary CHW Pump
  equipment_instance: SCHWP-3
  location: 2nd Level Chiller Room
  point_description: Pump Trip Alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0122
  system: AC
  equipment_class: Secondary CHW Pump
  equipment_instance: SCHWP-3
  location: 2nd Level Chiller Room
  point_description: Pump Start/Stop Command
  type: DO
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0123
  system: AC
  equipment_class: Secondary CHW Pump
  equipment_instance: SCHWP-3
  location: 2nd Level Chiller Room
  point_description: VFD Speed (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0124
  system: AC
  equipment_class: Secondary CHW Pump
  equipment_instance: SCHWP-3
  location: 2nd Level Chiller Room
  point_description: VFD Speed Command (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0125
  system: AC
  equipment_class: Secondary CHW Pump
  equipment_instance: SCHWP-3
  location: 2nd Level Chiller Room
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0126
  system: AC
  equipment_class: Condenser Water Pump
  equipment_instance: COWP-1
  location: 2nd Level Chiller Room
  point_description: Pump On/Off Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0127
  system: AC
  equipment_class: Condenser Water Pump
  equipment_instance: COWP-1
  location: 2nd Level Chiller Room
  point_description: Pump Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0128
  system: AC
  equipment_class: Condenser Water Pump
  equipment_instance: COWP-1
  location: 2nd Level Chiller Room
  point_description: Pump Trip Alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0129
  system: AC
  equipment_class: Condenser Water Pump
  equipment_instance: COWP-1
  location: 2nd Level Chiller Room
  point_description: Pump Start/Stop Command
  type: DO
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0130
  system: AC
  equipment_class: Condenser Water Pump
  equipment_instance: COWP-2
  location: 2nd Level Chiller Room
  point_description: Pump On/Off Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0131
  system: AC
  equipment_class: Condenser Water Pump
  equipment_instance: COWP-2
  location: 2nd Level Chiller Room
  point_description: Pump Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0132
  system: AC
  equipment_class: Condenser Water Pump
  equipment_instance: COWP-2
  location: 2nd Level Chiller Room
  point_description: Pump Trip Alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0133
  system: AC
  equipment_class: Condenser Water Pump
  equipment_instance: COWP-2
  location: 2nd Level Chiller Room
  point_description: Pump Start/Stop Command
  type: DO
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0134
  system: AC
  equipment_class: Condenser Water Pump
  equipment_instance: COWP-3
  location: 2nd Level Chiller Room
  point_description: Pump On/Off Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0135
  system: AC
  equipment_class: Condenser Water Pump
  equipment_instance: COWP-3
  location: 2nd Level Chiller Room
  point_description: Pump Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0136
  system: AC
  equipment_class: Condenser Water Pump
  equipment_instance: COWP-3
  location: 2nd Level Chiller Room
  point_description: Pump Trip Alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0137
  system: AC
  equipment_class: Condenser Water Pump
  equipment_instance: COWP-3
  location: 2nd Level Chiller Room
  point_description: Pump Start/Stop Command
  type: DO
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0138
  system: AC
  equipment_class: CHW Supply Main Header
  equipment_instance: CHW-SUP-HDR
  location: 2nd Level Chiller Room
  point_description: CHW Supply Main Header Pressure
  type: AI
  field_device: Pressure Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0139
  system: AC
  equipment_class: CHW Supply Main Header
  equipment_instance: CHW-SUP-HDR
  location: 2nd Level Chiller Room
  point_description: CHW Supply Main Header Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0140
  system: AC
  equipment_class: CHW Return Main Header
  equipment_instance: CHW-RET-HDR
  location: 2nd Level Chiller Room
  point_description: CHW Return Main Header Pressure
  type: AI
  field_device: Pressure Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0141
  system: AC
  equipment_class: CHW Return Main Header
  equipment_instance: CHW-RET-HDR
  location: 2nd Level Chiller Room
  point_description: CHW Return Main Header Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0142
  system: AC
  equipment_class: CHW Bypass Header
  equipment_instance: CHW-DIFF
  location: 2nd Level Chiller Room
  point_description: CHW Differential Pressure
  type: AI
  field_device: Diff. Pressure Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0143
  system: AC
  equipment_class: CHW Bypass Header
  equipment_instance: CHW-DIFF
  location: 2nd Level Chiller Room
  point_description: CHW Differential Temperature
  type: AI
  field_device: Diff. Pressure Sensor
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0144
  system: AC
  equipment_class: CHW Bypass Header
  equipment_instance: CHW-DIFF
  location: 2nd Level Chiller Room
  point_description: Isolation Motorized Valve Status CHW Bypass
  type: DI
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0145
  system: AC
  equipment_class: Condenser Water Header
  equipment_instance: CW-HDR
  location: Roof Deck CT Area
  point_description: Condenser Water Supply Header Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0146
  system: AC
  equipment_class: Condenser Water Header
  equipment_instance: CW-HDR
  location: Roof Deck CT Area
  point_description: Condenser Water Return Header Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0147
  system: AC
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roof Deck
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0148
  system: AC
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roof Deck
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0149
  system: AC
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roof Deck
  point_description: Fan Start/Stop Command
  type: DO
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0150
  system: AC
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roof Deck
  point_description: Level Alarm Low (CT Basin)
  type: DI
  field_device: Level Sensor / Electrode
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0151
  system: AC
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roof Deck
  point_description: Level Alarm High (CT Basin)
  type: DI
  field_device: Level Sensor / Electrode
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0152
  system: AC
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roof Deck
  point_description: Isolation Motorized Valve Status COW Return & Supply
  type: DI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0153
  system: AC
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roof Deck
  point_description: Blowdown Corrosion/Scale Monitoring
  type: AI
  field_device: pH Sensor / Conductivity Sensor
  c_o: ME Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0154
  system: AC
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roof Deck
  point_description: Motorized Blowdown Valve Status
  type: DI
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0155
  system: AC
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roof Deck
  point_description: Motorized Blowdown Valve Control
  type: DO
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0156
  system: AC
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roof Deck
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0157
  system: AC
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roof Deck
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0158
  system: AC
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roof Deck
  point_description: Fan Start/Stop Command
  type: DO
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0159
  system: AC
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roof Deck
  point_description: Level Alarm Low (CT Basin)
  type: DI
  field_device: Level Sensor / Electrode
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0160
  system: AC
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roof Deck
  point_description: Level Alarm High (CT Basin)
  type: DI
  field_device: Level Sensor / Electrode
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0161
  system: AC
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roof Deck
  point_description: Isolation Motorized Valve Status COW Return & Supply
  type: DI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0162
  system: AC
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roof Deck
  point_description: Blowdown Corrosion/Scale Monitoring
  type: AI
  field_device: pH Sensor / Conductivity Sensor
  c_o: ME Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0163
  system: AC
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roof Deck
  point_description: Motorized Blowdown Valve Status
  type: DI
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0164
  system: AC
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roof Deck
  point_description: Motorized Blowdown Valve Control
  type: DO
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0165
  system: AC
  equipment_class: Cooling Tower
  equipment_instance: CT-3
  location: Roof Deck
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0166
  system: AC
  equipment_class: Cooling Tower
  equipment_instance: CT-3
  location: Roof Deck
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0167
  system: AC
  equipment_class: Cooling Tower
  equipment_instance: CT-3
  location: Roof Deck
  point_description: Fan Start/Stop Command
  type: DO
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0168
  system: AC
  equipment_class: Cooling Tower
  equipment_instance: CT-3
  location: Roof Deck
  point_description: Level Alarm Low (CT Basin)
  type: DI
  field_device: Level Sensor / Electrode
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0169
  system: AC
  equipment_class: Cooling Tower
  equipment_instance: CT-3
  location: Roof Deck
  point_description: Level Alarm High (CT Basin)
  type: DI
  field_device: Level Sensor / Electrode
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0170
  system: AC
  equipment_class: Cooling Tower
  equipment_instance: CT-3
  location: Roof Deck
  point_description: Isolation Motorized Valve Status COW Return & Supply
  type: DI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0171
  system: AC
  equipment_class: Cooling Tower
  equipment_instance: CT-3
  location: Roof Deck
  point_description: Blowdown Corrosion/Scale Monitoring
  type: AI
  field_device: pH Sensor / Conductivity Sensor
  c_o: ME Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0172
  system: AC
  equipment_class: Cooling Tower
  equipment_instance: CT-3
  location: Roof Deck
  point_description: Motorized Blowdown Valve Status
  type: DI
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0173
  system: AC
  equipment_class: Cooling Tower
  equipment_instance: CT-3
  location: Roof Deck
  point_description: Motorized Blowdown Valve Control
  type: DO
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0174
  system: AC
  equipment_class: Cooling Tower (Common)
  equipment_instance: CT-COMMON
  location: Roof Deck
  point_description: Outside Air Temperature Monitoring
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0175
  system: AC
  equipment_class: Cooling Tower (Common)
  equipment_instance: CT-COMMON
  location: Roof Deck
  point_description: Outside Air Humidity Monitoring
  type: AI
  field_device: Humidity Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0176
  system: AC
  equipment_class: Cooling Tower (Common)
  equipment_instance: CT-COMMON
  location: Roof Deck
  point_description: Water Temp Monitoring (Condenser Return Header)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0177
  system: AC
  equipment_class: Cooling Tower (Common)
  equipment_instance: CT-COMMON
  location: Roof Deck
  point_description: Water Temp Monitoring (Condenser Supply Header)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0178
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Boiler Room
  point_description: Supply Steam Pressure
  type: AI
  field_device: Pressure Sensor
  c_o: BMS Contractor
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0179
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Boiler Room
  point_description: Low Water Level
  type: DI
  field_device: Level Sensor
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0180
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Boiler Room
  point_description: High Water Level
  type: DI
  field_device: Level Sensor
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0181
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Boiler Room
  point_description: Burner Power
  type: HLI
  field_device: Burner Controller
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0182
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Boiler Room
  point_description: Small Fire Control Signal
  type: HLI
  field_device: Burner Controller
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0183
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Boiler Room
  point_description: Big Fire Control Signal
  type: HLI
  field_device: Burner Controller
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0184
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Boiler Room
  point_description: Waterfeed Pump Status
  type: HLI
  field_device: Burner Controller
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0185
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Boiler Room
  point_description: Burner Status
  type: HLI
  field_device: Burner Controller
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0186
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Boiler Room
  point_description: Burner Fire Running Status
  type: HLI
  field_device: Burner Controller
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0187
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Boiler Room
  point_description: Blower Motor Status
  type: HLI
  field_device: Burner Controller
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0188
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Boiler Room
  point_description: Fuel Oil Pump Status
  type: HLI
  field_device: Burner Controller
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0189
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Boiler Room
  point_description: Motorized Valve Status Blowdown Water
  type: DI
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0190
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Boiler Room
  point_description: Motorized Valve Control Blowdown Water
  type: DO
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0191
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Boiler Room
  point_description: Feedwater Supply Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0192
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Boiler Room
  point_description: Fluegas Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0193
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Boiler Room
  point_description: Fluegas Oxygen Level
  type: AI
  field_device: Oxygen Sensor
  c_o: BMS Contractor
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0194
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Boiler Room
  point_description: Network drop (BACnet MS/TP — Burner Controller)
  type: Network
  field_device: Burner Controller gateway
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0195
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Boiler Room
  point_description: Supply Steam Pressure
  type: AI
  field_device: Pressure Sensor
  c_o: BMS Contractor
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0196
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Boiler Room
  point_description: Low Water Level
  type: DI
  field_device: Level Sensor
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0197
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Boiler Room
  point_description: High Water Level
  type: DI
  field_device: Level Sensor
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0198
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Boiler Room
  point_description: Burner Power
  type: HLI
  field_device: Burner Controller
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0199
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Boiler Room
  point_description: Small Fire Control Signal
  type: HLI
  field_device: Burner Controller
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0200
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Boiler Room
  point_description: Big Fire Control Signal
  type: HLI
  field_device: Burner Controller
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0201
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Boiler Room
  point_description: Waterfeed Pump Status
  type: HLI
  field_device: Burner Controller
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0202
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Boiler Room
  point_description: Burner Status
  type: HLI
  field_device: Burner Controller
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0203
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Boiler Room
  point_description: Burner Fire Running Status
  type: HLI
  field_device: Burner Controller
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0204
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Boiler Room
  point_description: Blower Motor Status
  type: HLI
  field_device: Burner Controller
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0205
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Boiler Room
  point_description: Fuel Oil Pump Status
  type: HLI
  field_device: Burner Controller
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0206
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Boiler Room
  point_description: Motorized Valve Status Blowdown Water
  type: DI
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0207
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Boiler Room
  point_description: Motorized Valve Control Blowdown Water
  type: DO
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0208
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Boiler Room
  point_description: Feedwater Supply Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0209
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Boiler Room
  point_description: Fluegas Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0210
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Boiler Room
  point_description: Fluegas Oxygen Level
  type: AI
  field_device: Oxygen Sensor
  c_o: BMS Contractor
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0211
  system: VENT
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Boiler Room
  point_description: Network drop (BACnet MS/TP — Burner Controller)
  type: Network
  field_device: Burner Controller gateway
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0212
  system: HWL
  equipment_class: Calorifier (Hot Water Storage Tank)
  equipment_instance: HWT-LZ
  location: Lower Ground HWL Room
  point_description: Tank Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0213
  system: HWL
  equipment_class: Calorifier (Hot Water Storage Tank)
  equipment_instance: HWT-HZ
  location: Roof Deck HWL Area
  point_description: Tank Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0214
  system: HWL
  equipment_class: Hot Water Header Set
  equipment_instance: HWH-LZ
  location: Lower Ground HWL Room
  point_description: Hot Water Supply Header Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0215
  system: HWL
  equipment_class: Hot Water Header Set
  equipment_instance: HWH-LZ
  location: Lower Ground HWL Room
  point_description: Make-Up Cold Water Header Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0216
  system: HWL
  equipment_class: Hot Water Header Set
  equipment_instance: HWH-LZ
  location: Lower Ground HWL Room
  point_description: Hot Water Return Header Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0217
  system: HWL
  equipment_class: Hot Water Header Set
  equipment_instance: HWH-HZ
  location: Roof Deck HWL Area
  point_description: Hot Water Supply Header Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0218
  system: HWL
  equipment_class: Hot Water Header Set
  equipment_instance: HWH-HZ
  location: Roof Deck HWL Area
  point_description: Make-Up Cold Water Header Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0219
  system: HWL
  equipment_class: Hot Water Header Set
  equipment_instance: HWH-HZ
  location: Roof Deck HWL Area
  point_description: Hot Water Return Header Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0220
  system: HWL
  equipment_class: Heat Pump
  equipment_instance: HP-LZ
  location: Lower Ground HWL Room
  point_description: Pump Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0221
  system: HWL
  equipment_class: Heat Pump
  equipment_instance: HP-LZ
  location: Lower Ground HWL Room
  point_description: Pump Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0222
  system: HWL
  equipment_class: Heat Pump
  equipment_instance: HP-LZ
  location: Lower Ground HWL Room
  point_description: Pump Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0223
  system: HWL
  equipment_class: Heat Pump
  equipment_instance: HP-HZ
  location: Roof Deck HWL Area
  point_description: Pump Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0224
  system: HWL
  equipment_class: Heat Pump
  equipment_instance: HP-HZ
  location: Roof Deck HWL Area
  point_description: Pump Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0225
  system: HWL
  equipment_class: Heat Pump
  equipment_instance: HP-HZ
  location: Roof Deck HWL Area
  point_description: Pump Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0226
  system: HWL
  equipment_class: Recirculating Pump
  equipment_instance: RP-LZ
  location: Lower Ground HWL Room
  point_description: Pump Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0227
  system: HWL
  equipment_class: Recirculating Pump
  equipment_instance: RP-LZ
  location: Lower Ground HWL Room
  point_description: Pump Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0228
  system: HWL
  equipment_class: Recirculating Pump
  equipment_instance: RP-LZ
  location: Lower Ground HWL Room
  point_description: Pump Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0229
  system: HWL
  equipment_class: Recirculating Pump
  equipment_instance: RP-HZ
  location: Roof Deck HWL Area
  point_description: Pump Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0230
  system: HWL
  equipment_class: Recirculating Pump
  equipment_instance: RP-HZ
  location: Roof Deck HWL Area
  point_description: Pump Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0231
  system: HWL
  equipment_class: Recirculating Pump
  equipment_instance: RP-HZ
  location: Roof Deck HWL Area
  point_description: Pump Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0232
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.1
  location: Roof Deck
  point_description: Temperature Monitoring (Outside — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0233
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.1
  location: Roof Deck
  point_description: Flow Monitoring (Outside — Supply Air)
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0234
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.1
  location: Roof Deck
  point_description: Humidity Monitoring (Outdoor — Supply Air)
  type: AI
  field_device: Humidity Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0235
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.1
  location: Roof Deck
  point_description: Outdoor Supply Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0236
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.1
  location: Roof Deck
  point_description: Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0237
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.1
  location: Roof Deck
  point_description: Recovery Wheel Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0238
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.1
  location: Roof Deck
  point_description: Recovery Wheel Motor Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0239
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.1
  location: Roof Deck
  point_description: Supply Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0240
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.1
  location: Roof Deck
  point_description: Supply Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0241
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.1
  location: Roof Deck
  point_description: Supply Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0242
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.1
  location: Roof Deck
  point_description: Supply Fan Variable Speed Monitoring (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0243
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.1
  location: Roof Deck
  point_description: Supply Fan Control (On/Off/Modulating) (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0244
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.1
  location: Roof Deck
  point_description: Temperature Monitoring (Indoor — Mixed Air)
  type: AI
  field_device: Temperature Sensor
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0245
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.1
  location: Roof Deck
  point_description: Humidity Monitoring (Indoor — Mixed Air)
  type: AI
  field_device: Humidity Sensor
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0246
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.1
  location: Roof Deck
  point_description: CHWS / Cooling Coil Valve Status
  type: AI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0247
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.1
  location: Roof Deck
  point_description: CHWS Valve Control (On/Off/Modulating)
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0248
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.1
  location: Roof Deck
  point_description: Temperature Monitoring (Indoor — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0249
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.1
  location: Roof Deck
  point_description: Humidity Monitoring (Indoor — Exhaust Air)
  type: AI
  field_device: Humidity Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0250
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.1
  location: Roof Deck
  point_description: Temperature Monitoring (Indoor — Exhaust Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0251
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.1
  location: Roof Deck
  point_description: Exhaust Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0252
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.1
  location: Roof Deck
  point_description: Exhaust Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0253
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.1
  location: Roof Deck
  point_description: Exhaust Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0254
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.1
  location: Roof Deck
  point_description: Exhaust Fan Variable Speed Monitoring (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0255
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.1
  location: Roof Deck
  point_description: Exhaust Fan Control (On/Off/Modulating) (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0256
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.1
  location: Roof Deck
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0257
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.2
  location: Roof Deck
  point_description: Temperature Monitoring (Outside — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0258
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.2
  location: Roof Deck
  point_description: Flow Monitoring (Outside — Supply Air)
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0259
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.2
  location: Roof Deck
  point_description: Humidity Monitoring (Outdoor — Supply Air)
  type: AI
  field_device: Humidity Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0260
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.2
  location: Roof Deck
  point_description: Outdoor Supply Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0261
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.2
  location: Roof Deck
  point_description: Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0262
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.2
  location: Roof Deck
  point_description: Recovery Wheel Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0263
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.2
  location: Roof Deck
  point_description: Recovery Wheel Motor Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0264
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.2
  location: Roof Deck
  point_description: Supply Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0265
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.2
  location: Roof Deck
  point_description: Supply Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0266
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.2
  location: Roof Deck
  point_description: Supply Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0267
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.2
  location: Roof Deck
  point_description: Supply Fan Variable Speed Monitoring (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0268
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.2
  location: Roof Deck
  point_description: Supply Fan Control (On/Off/Modulating) (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0269
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.2
  location: Roof Deck
  point_description: Temperature Monitoring (Indoor — Mixed Air)
  type: AI
  field_device: Temperature Sensor
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0270
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.2
  location: Roof Deck
  point_description: Humidity Monitoring (Indoor — Mixed Air)
  type: AI
  field_device: Humidity Sensor
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0271
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.2
  location: Roof Deck
  point_description: CHWS / Cooling Coil Valve Status
  type: AI
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0272
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.2
  location: Roof Deck
  point_description: CHWS Valve Control (On/Off/Modulating)
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0273
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.2
  location: Roof Deck
  point_description: Temperature Monitoring (Indoor — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0274
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.2
  location: Roof Deck
  point_description: Humidity Monitoring (Indoor — Exhaust Air)
  type: AI
  field_device: Humidity Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0275
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.2
  location: Roof Deck
  point_description: Temperature Monitoring (Indoor — Exhaust Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0276
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.2
  location: Roof Deck
  point_description: Exhaust Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0277
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.2
  location: Roof Deck
  point_description: Exhaust Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0278
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.2
  location: Roof Deck
  point_description: Exhaust Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0279
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.2
  location: Roof Deck
  point_description: Exhaust Fan Variable Speed Monitoring (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0280
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.2
  location: Roof Deck
  point_description: Exhaust Fan Control (On/Off/Modulating) (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0281
  system: VENT
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD.2
  location: Roof Deck
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0282
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-r.1
  location: Roof Deck
  point_description: Outdoor Supply Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0283
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-r.1
  location: Roof Deck
  point_description: Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0284
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-r.1
  location: Roof Deck
  point_description: Temperature Monitoring (Outside — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0285
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-r.1
  location: Roof Deck
  point_description: Flow Monitoring (Outside — Supply Air)
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0286
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-r.1
  location: Roof Deck
  point_description: CHWS Valve Control (On/Off/Modulating)
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0287
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-r.1
  location: Roof Deck
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0288
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-r.1
  location: Roof Deck
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0289
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-r.1
  location: Roof Deck
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0290
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-r.1
  location: Roof Deck
  point_description: Temperature Monitoring (Indoor — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0291
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-r.1
  location: Roof Deck
  point_description: Variable Speed Monitoring (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0292
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-r.1
  location: Roof Deck
  point_description: Fan Control (On/Off/Modulating) (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0293
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-r.1
  location: Roof Deck
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0294
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-r.2
  location: Roof Deck
  point_description: Outdoor Supply Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0295
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-r.2
  location: Roof Deck
  point_description: Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0296
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-r.2
  location: Roof Deck
  point_description: Temperature Monitoring (Outside — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0297
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-r.2
  location: Roof Deck
  point_description: Flow Monitoring (Outside — Supply Air)
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0298
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-r.2
  location: Roof Deck
  point_description: CHWS Valve Control (On/Off/Modulating)
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0299
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-r.2
  location: Roof Deck
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0300
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-r.2
  location: Roof Deck
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0301
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-r.2
  location: Roof Deck
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0302
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-r.2
  location: Roof Deck
  point_description: Temperature Monitoring (Indoor — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0303
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-r.2
  location: Roof Deck
  point_description: Variable Speed Monitoring (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0304
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-r.2
  location: Roof Deck
  point_description: Fan Control (On/Off/Modulating) (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0305
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-r.2
  location: Roof Deck
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0306
  system: VENT
  equipment_class: DOAS Unit (Casino — with CO/VOC)
  equipment_instance: DOAS-2M
  location: 2nd Mezzanine (Casino)
  point_description: Temperature Monitoring (Outside — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0307
  system: VENT
  equipment_class: DOAS Unit (Casino — with CO/VOC)
  equipment_instance: DOAS-2M
  location: 2nd Mezzanine (Casino)
  point_description: Flow Monitoring (Outside — Supply Air)
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0308
  system: VENT
  equipment_class: DOAS Unit (Casino — with CO/VOC)
  equipment_instance: DOAS-2M
  location: 2nd Mezzanine (Casino)
  point_description: Humidity Monitoring (Outdoor — Supply Air)
  type: AI
  field_device: Humidity Sensor
  c_o: BMS Contractor
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0309
  system: VENT
  equipment_class: DOAS Unit (Casino — with CO/VOC)
  equipment_instance: DOAS-2M
  location: 2nd Mezzanine (Casino)
  point_description: Outdoor Supply Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0310
  system: VENT
  equipment_class: DOAS Unit (Casino — with CO/VOC)
  equipment_instance: DOAS-2M
  location: 2nd Mezzanine (Casino)
  point_description: Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0311
  system: VENT
  equipment_class: DOAS Unit (Casino — with CO/VOC)
  equipment_instance: DOAS-2M
  location: 2nd Mezzanine (Casino)
  point_description: Recovery Wheel Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0312
  system: VENT
  equipment_class: DOAS Unit (Casino — with CO/VOC)
  equipment_instance: DOAS-2M
  location: 2nd Mezzanine (Casino)
  point_description: Recovery Wheel Motor Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0313
  system: VENT
  equipment_class: DOAS Unit (Casino — with CO/VOC)
  equipment_instance: DOAS-2M
  location: 2nd Mezzanine (Casino)
  point_description: Supply Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0314
  system: VENT
  equipment_class: DOAS Unit (Casino — with CO/VOC)
  equipment_instance: DOAS-2M
  location: 2nd Mezzanine (Casino)
  point_description: Supply Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0315
  system: VENT
  equipment_class: DOAS Unit (Casino — with CO/VOC)
  equipment_instance: DOAS-2M
  location: 2nd Mezzanine (Casino)
  point_description: Supply Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0316
  system: VENT
  equipment_class: DOAS Unit (Casino — with CO/VOC)
  equipment_instance: DOAS-2M
  location: 2nd Mezzanine (Casino)
  point_description: Supply Fan Variable Speed Monitoring (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0317
  system: VENT
  equipment_class: DOAS Unit (Casino — with CO/VOC)
  equipment_instance: DOAS-2M
  location: 2nd Mezzanine (Casino)
  point_description: Supply Fan Control (On/Off/Modulating) (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0318
  system: VENT
  equipment_class: DOAS Unit (Casino — with CO/VOC)
  equipment_instance: DOAS-2M
  location: 2nd Mezzanine (Casino)
  point_description: Temperature Monitoring (Indoor — Mixed Air)
  type: AI
  field_device: Temperature Sensor
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0319
  system: VENT
  equipment_class: DOAS Unit (Casino — with CO/VOC)
  equipment_instance: DOAS-2M
  location: 2nd Mezzanine (Casino)
  point_description: Humidity Monitoring (Indoor — Mixed Air)
  type: AI
  field_device: Humidity Sensor
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0320
  system: VENT
  equipment_class: DOAS Unit (Casino — with CO/VOC)
  equipment_instance: DOAS-2M
  location: 2nd Mezzanine (Casino)
  point_description: CHWS Valve Control (On/Off/Modulating)
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0321
  system: VENT
  equipment_class: DOAS Unit (Casino — with CO/VOC)
  equipment_instance: DOAS-2M
  location: 2nd Mezzanine (Casino)
  point_description: Carbon Dioxide (CO2) Sensor at Return Duct
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0322
  system: VENT
  equipment_class: DOAS Unit (Casino — with CO/VOC)
  equipment_instance: DOAS-2M
  location: 2nd Mezzanine (Casino)
  point_description: Carbon Monoxide (CO) Sensor at Return Duct (Casino)
  type: AI
  field_device: CO Sensor
  c_o: BMS Contractor
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0323
  system: VENT
  equipment_class: DOAS Unit (Casino — with CO/VOC)
  equipment_instance: DOAS-2M
  location: 2nd Mezzanine (Casino)
  point_description: Exhaust Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0324
  system: VENT
  equipment_class: DOAS Unit (Casino — with CO/VOC)
  equipment_instance: DOAS-2M
  location: 2nd Mezzanine (Casino)
  point_description: Exhaust Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0325
  system: VENT
  equipment_class: DOAS Unit (Casino — with CO/VOC)
  equipment_instance: DOAS-2M
  location: 2nd Mezzanine (Casino)
  point_description: Exhaust Fan Variable Speed Monitoring (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0326
  system: VENT
  equipment_class: DOAS Unit (Casino — with CO/VOC)
  equipment_instance: DOAS-2M
  location: 2nd Mezzanine (Casino)
  point_description: Exhaust Fan Control (On/Off/Modulating) (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0327
  system: VENT
  equipment_class: DOAS Unit (Casino — with CO/VOC)
  equipment_instance: DOAS-2M
  location: 2nd Mezzanine (Casino)
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0328
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.1
  location: 2nd Mezzanine (Casino)
  point_description: Indoor Return Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0329
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.1
  location: 2nd Mezzanine (Casino)
  point_description: Indoor Return Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0330
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.1
  location: 2nd Mezzanine (Casino)
  point_description: Indoor Return Air CO2 Level
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0331
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.1
  location: 2nd Mezzanine (Casino)
  point_description: Temperature Monitoring (Indoor — Return Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0332
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.1
  location: 2nd Mezzanine (Casino)
  point_description: Temperature Monitoring (Indoor — Mixed Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0333
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.1
  location: 2nd Mezzanine (Casino)
  point_description: Outdoor Supply Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0334
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.1
  location: 2nd Mezzanine (Casino)
  point_description: Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0335
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.1
  location: 2nd Mezzanine (Casino)
  point_description: Temperature Monitoring (Outside — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0336
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.1
  location: 2nd Mezzanine (Casino)
  point_description: Temperature Monitoring (Indoor — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0337
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.1
  location: 2nd Mezzanine (Casino)
  point_description: CHWS Valve Control (On/Off/Modulating)
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0338
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.1
  location: 2nd Mezzanine (Casino)
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0339
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.1
  location: 2nd Mezzanine (Casino)
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0340
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.1
  location: 2nd Mezzanine (Casino)
  point_description: Fan Variable Speed Monitoring (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0341
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.1
  location: 2nd Mezzanine (Casino)
  point_description: Fan Control On/Off/Modulating (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0342
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.1
  location: 2nd Mezzanine (Casino)
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0343
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.2
  location: 2nd Mezzanine (Casino)
  point_description: Indoor Return Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0344
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.2
  location: 2nd Mezzanine (Casino)
  point_description: Indoor Return Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0345
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.2
  location: 2nd Mezzanine (Casino)
  point_description: Indoor Return Air CO2 Level
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0346
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.2
  location: 2nd Mezzanine (Casino)
  point_description: Temperature Monitoring (Indoor — Return Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0347
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.2
  location: 2nd Mezzanine (Casino)
  point_description: Temperature Monitoring (Indoor — Mixed Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0348
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.2
  location: 2nd Mezzanine (Casino)
  point_description: Outdoor Supply Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0349
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.2
  location: 2nd Mezzanine (Casino)
  point_description: Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0350
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.2
  location: 2nd Mezzanine (Casino)
  point_description: Temperature Monitoring (Outside — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0351
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.2
  location: 2nd Mezzanine (Casino)
  point_description: Temperature Monitoring (Indoor — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0352
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.2
  location: 2nd Mezzanine (Casino)
  point_description: CHWS Valve Control (On/Off/Modulating)
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0353
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.2
  location: 2nd Mezzanine (Casino)
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0354
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.2
  location: 2nd Mezzanine (Casino)
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0355
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.2
  location: 2nd Mezzanine (Casino)
  point_description: Fan Variable Speed Monitoring (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0356
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.2
  location: 2nd Mezzanine (Casino)
  point_description: Fan Control On/Off/Modulating (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0357
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2M.2
  location: 2nd Mezzanine (Casino)
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0358
  system: AC
  equipment_class: Air Ionizer (Casino)
  equipment_instance: AIR-ION-2M.1
  location: 2nd Mezzanine (Casino)
  point_description: VOC Monitoring (Return Duct)
  type: AI
  field_device: VOC Sensor
  c_o: BMS Contractor
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0359
  system: AC
  equipment_class: Air Ionizer (Casino)
  equipment_instance: AIR-ION-2M.1
  location: 2nd Mezzanine (Casino)
  point_description: Air Ionizer Equipment Status
  type: DI
  field_device: Auxiliary Contact / Modbus
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0360
  system: AC
  equipment_class: Air Ionizer (Casino)
  equipment_instance: AIR-ION-2M.1
  location: 2nd Mezzanine (Casino)
  point_description: Air Ionizer Equipment Trip Status
  type: DI
  field_device: Auxiliary Contact / Modbus
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0361
  system: AC
  equipment_class: Air Ionizer (Casino)
  equipment_instance: AIR-ION-2M.1
  location: 2nd Mezzanine (Casino)
  point_description: Network drop (Modbus / BACnet MS-TP — Ionizer Controller)
  type: Network
  field_device: Ionizer Controller
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0362
  system: AC
  equipment_class: Air Ionizer (Casino)
  equipment_instance: AIR-ION-2M.2
  location: 2nd Mezzanine (Casino)
  point_description: VOC Monitoring (Return Duct)
  type: AI
  field_device: VOC Sensor
  c_o: BMS Contractor
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0363
  system: AC
  equipment_class: Air Ionizer (Casino)
  equipment_instance: AIR-ION-2M.2
  location: 2nd Mezzanine (Casino)
  point_description: Air Ionizer Equipment Status
  type: DI
  field_device: Auxiliary Contact / Modbus
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0364
  system: AC
  equipment_class: Air Ionizer (Casino)
  equipment_instance: AIR-ION-2M.2
  location: 2nd Mezzanine (Casino)
  point_description: Air Ionizer Equipment Trip Status
  type: DI
  field_device: Auxiliary Contact / Modbus
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0365
  system: AC
  equipment_class: Air Ionizer (Casino)
  equipment_instance: AIR-ION-2M.2
  location: 2nd Mezzanine (Casino)
  point_description: Network drop (Modbus / BACnet MS-TP — Ionizer Controller)
  type: Network
  field_device: Ionizer Controller
  c_o: Equipment Supplier
  panel: DDC-2M-CASINO
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0366
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.1
  location: 2nd Level BOH
  point_description: Indoor Return Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0367
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.1
  location: 2nd Level BOH
  point_description: Indoor Return Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0368
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.1
  location: 2nd Level BOH
  point_description: Indoor Return Air CO2 Level
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0369
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.1
  location: 2nd Level BOH
  point_description: Temperature Monitoring (Indoor — Return Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0370
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.1
  location: 2nd Level BOH
  point_description: Temperature Monitoring (Indoor — Mixed Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0371
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.1
  location: 2nd Level BOH
  point_description: Outdoor Supply Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0372
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.1
  location: 2nd Level BOH
  point_description: Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0373
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.1
  location: 2nd Level BOH
  point_description: Temperature Monitoring (Outside — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0374
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.1
  location: 2nd Level BOH
  point_description: Temperature Monitoring (Indoor — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0375
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.1
  location: 2nd Level BOH
  point_description: CHWS Valve Control (On/Off/Modulating)
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0376
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.1
  location: 2nd Level BOH
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0377
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.1
  location: 2nd Level BOH
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0378
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.1
  location: 2nd Level BOH
  point_description: Fan Variable Speed Monitoring (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0379
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.1
  location: 2nd Level BOH
  point_description: Fan Control On/Off/Modulating (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0380
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.1
  location: 2nd Level BOH
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0381
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.2
  location: 2nd Level BOH
  point_description: Indoor Return Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0382
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.2
  location: 2nd Level BOH
  point_description: Indoor Return Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0383
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.2
  location: 2nd Level BOH
  point_description: Indoor Return Air CO2 Level
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0384
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.2
  location: 2nd Level BOH
  point_description: Temperature Monitoring (Indoor — Return Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0385
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.2
  location: 2nd Level BOH
  point_description: Temperature Monitoring (Indoor — Mixed Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0386
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.2
  location: 2nd Level BOH
  point_description: Outdoor Supply Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0387
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.2
  location: 2nd Level BOH
  point_description: Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0388
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.2
  location: 2nd Level BOH
  point_description: Temperature Monitoring (Outside — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0389
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.2
  location: 2nd Level BOH
  point_description: Temperature Monitoring (Indoor — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0390
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.2
  location: 2nd Level BOH
  point_description: CHWS Valve Control (On/Off/Modulating)
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0391
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.2
  location: 2nd Level BOH
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0392
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.2
  location: 2nd Level BOH
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0393
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.2
  location: 2nd Level BOH
  point_description: Fan Variable Speed Monitoring (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0394
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.2
  location: 2nd Level BOH
  point_description: Fan Control On/Off/Modulating (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0395
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.2
  location: 2nd Level BOH
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0396
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.3
  location: 2nd Level BOH
  point_description: Indoor Return Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0397
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.3
  location: 2nd Level BOH
  point_description: Indoor Return Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0398
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.3
  location: 2nd Level BOH
  point_description: Indoor Return Air CO2 Level
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0399
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.3
  location: 2nd Level BOH
  point_description: Temperature Monitoring (Indoor — Return Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0400
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.3
  location: 2nd Level BOH
  point_description: Temperature Monitoring (Indoor — Mixed Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0401
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.3
  location: 2nd Level BOH
  point_description: Outdoor Supply Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0402
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.3
  location: 2nd Level BOH
  point_description: Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0403
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.3
  location: 2nd Level BOH
  point_description: Temperature Monitoring (Outside — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0404
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.3
  location: 2nd Level BOH
  point_description: Temperature Monitoring (Indoor — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0405
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.3
  location: 2nd Level BOH
  point_description: CHWS Valve Control (On/Off/Modulating)
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0406
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.3
  location: 2nd Level BOH
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0407
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.3
  location: 2nd Level BOH
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0408
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.3
  location: 2nd Level BOH
  point_description: Fan Variable Speed Monitoring (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0409
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.3
  location: 2nd Level BOH
  point_description: Fan Control On/Off/Modulating (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0410
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B.3
  location: 2nd Level BOH
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0411
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-PF
  location: 2nd Level Pre-Function
  point_description: Indoor Return Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0412
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-PF
  location: 2nd Level Pre-Function
  point_description: Indoor Return Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0413
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-PF
  location: 2nd Level Pre-Function
  point_description: Indoor Return Air CO2 Level
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0414
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-PF
  location: 2nd Level Pre-Function
  point_description: Temperature Monitoring (Indoor — Return Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0415
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-PF
  location: 2nd Level Pre-Function
  point_description: Temperature Monitoring (Indoor — Mixed Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0416
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-PF
  location: 2nd Level Pre-Function
  point_description: Outdoor Supply Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0417
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-PF
  location: 2nd Level Pre-Function
  point_description: Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0418
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-PF
  location: 2nd Level Pre-Function
  point_description: Temperature Monitoring (Outside — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0419
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-PF
  location: 2nd Level Pre-Function
  point_description: Temperature Monitoring (Indoor — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0420
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-PF
  location: 2nd Level Pre-Function
  point_description: CHWS Valve Control (On/Off/Modulating)
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0421
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-PF
  location: 2nd Level Pre-Function
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0422
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-PF
  location: 2nd Level Pre-Function
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0423
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-PF
  location: 2nd Level Pre-Function
  point_description: Fan Variable Speed Monitoring (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0424
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-PF
  location: 2nd Level Pre-Function
  point_description: Fan Control On/Off/Modulating (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0425
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-PF
  location: 2nd Level Pre-Function
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0426
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-EL
  location: 2nd Level Executive Lounge
  point_description: Indoor Return Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0427
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-EL
  location: 2nd Level Executive Lounge
  point_description: Indoor Return Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0428
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-EL
  location: 2nd Level Executive Lounge
  point_description: Indoor Return Air CO2 Level
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0429
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-EL
  location: 2nd Level Executive Lounge
  point_description: Temperature Monitoring (Indoor — Return Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0430
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-EL
  location: 2nd Level Executive Lounge
  point_description: Temperature Monitoring (Indoor — Mixed Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0431
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-EL
  location: 2nd Level Executive Lounge
  point_description: Outdoor Supply Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0432
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-EL
  location: 2nd Level Executive Lounge
  point_description: Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0433
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-EL
  location: 2nd Level Executive Lounge
  point_description: Temperature Monitoring (Outside — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0434
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-EL
  location: 2nd Level Executive Lounge
  point_description: Temperature Monitoring (Indoor — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0435
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-EL
  location: 2nd Level Executive Lounge
  point_description: CHWS Valve Control (On/Off/Modulating)
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0436
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-EL
  location: 2nd Level Executive Lounge
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0437
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-EL
  location: 2nd Level Executive Lounge
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0438
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-EL
  location: 2nd Level Executive Lounge
  point_description: Fan Variable Speed Monitoring (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0439
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-EL
  location: 2nd Level Executive Lounge
  point_description: Fan Control On/Off/Modulating (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0440
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-EL
  location: 2nd Level Executive Lounge
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0441
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR2
  location: 2nd Level Function Room 2
  point_description: Indoor Return Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0442
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR2
  location: 2nd Level Function Room 2
  point_description: Indoor Return Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0443
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR2
  location: 2nd Level Function Room 2
  point_description: Indoor Return Air CO2 Level
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0444
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR2
  location: 2nd Level Function Room 2
  point_description: Temperature Monitoring (Indoor — Return Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0445
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR2
  location: 2nd Level Function Room 2
  point_description: Temperature Monitoring (Indoor — Mixed Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0446
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR2
  location: 2nd Level Function Room 2
  point_description: Outdoor Supply Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0447
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR2
  location: 2nd Level Function Room 2
  point_description: Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0448
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR2
  location: 2nd Level Function Room 2
  point_description: Temperature Monitoring (Outside — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0449
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR2
  location: 2nd Level Function Room 2
  point_description: Temperature Monitoring (Indoor — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0450
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR2
  location: 2nd Level Function Room 2
  point_description: CHWS Valve Control (On/Off/Modulating)
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0451
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR2
  location: 2nd Level Function Room 2
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0452
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR2
  location: 2nd Level Function Room 2
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0453
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR2
  location: 2nd Level Function Room 2
  point_description: Fan Variable Speed Monitoring (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0454
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR2
  location: 2nd Level Function Room 2
  point_description: Fan Control On/Off/Modulating (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0455
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR2
  location: 2nd Level Function Room 2
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0456
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR3
  location: 2nd Level Function Room 3
  point_description: Indoor Return Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0457
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR3
  location: 2nd Level Function Room 3
  point_description: Indoor Return Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0458
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR3
  location: 2nd Level Function Room 3
  point_description: Indoor Return Air CO2 Level
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0459
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR3
  location: 2nd Level Function Room 3
  point_description: Temperature Monitoring (Indoor — Return Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0460
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR3
  location: 2nd Level Function Room 3
  point_description: Temperature Monitoring (Indoor — Mixed Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0461
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR3
  location: 2nd Level Function Room 3
  point_description: Outdoor Supply Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0462
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR3
  location: 2nd Level Function Room 3
  point_description: Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0463
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR3
  location: 2nd Level Function Room 3
  point_description: Temperature Monitoring (Outside — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0464
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR3
  location: 2nd Level Function Room 3
  point_description: Temperature Monitoring (Indoor — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0465
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR3
  location: 2nd Level Function Room 3
  point_description: CHWS Valve Control (On/Off/Modulating)
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0466
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR3
  location: 2nd Level Function Room 3
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0467
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR3
  location: 2nd Level Function Room 3
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0468
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR3
  location: 2nd Level Function Room 3
  point_description: Fan Variable Speed Monitoring (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0469
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR3
  location: 2nd Level Function Room 3
  point_description: Fan Control On/Off/Modulating (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0470
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-FR3
  location: 2nd Level Function Room 3
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0471
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.1
  location: 2nd Level BOH
  point_description: Outdoor Supply Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0472
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.1
  location: 2nd Level BOH
  point_description: Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0473
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.1
  location: 2nd Level BOH
  point_description: Temperature Monitoring (Outside — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0474
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.1
  location: 2nd Level BOH
  point_description: Flow Monitoring (Outside — Supply Air)
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0475
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.1
  location: 2nd Level BOH
  point_description: CHWS Valve Control (On/Off/Modulating)
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0476
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.1
  location: 2nd Level BOH
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0477
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.1
  location: 2nd Level BOH
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0478
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.1
  location: 2nd Level BOH
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0479
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.1
  location: 2nd Level BOH
  point_description: Temperature Monitoring (Indoor — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0480
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.1
  location: 2nd Level BOH
  point_description: Variable Speed Monitoring (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0481
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.1
  location: 2nd Level BOH
  point_description: Fan Control (On/Off/Modulating) (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0482
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.1
  location: 2nd Level BOH
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0483
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.2
  location: 2nd Level BOH
  point_description: Outdoor Supply Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0484
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.2
  location: 2nd Level BOH
  point_description: Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0485
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.2
  location: 2nd Level BOH
  point_description: Temperature Monitoring (Outside — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0486
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.2
  location: 2nd Level BOH
  point_description: Flow Monitoring (Outside — Supply Air)
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0487
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.2
  location: 2nd Level BOH
  point_description: CHWS Valve Control (On/Off/Modulating)
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0488
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.2
  location: 2nd Level BOH
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0489
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.2
  location: 2nd Level BOH
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0490
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.2
  location: 2nd Level BOH
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0491
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.2
  location: 2nd Level BOH
  point_description: Temperature Monitoring (Indoor — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0492
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.2
  location: 2nd Level BOH
  point_description: Variable Speed Monitoring (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0493
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.2
  location: 2nd Level BOH
  point_description: Fan Control (On/Off/Modulating) (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0494
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.2
  location: 2nd Level BOH
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0495
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.3
  location: 2nd Level BOH
  point_description: Outdoor Supply Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0496
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.3
  location: 2nd Level BOH
  point_description: Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0497
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.3
  location: 2nd Level BOH
  point_description: Temperature Monitoring (Outside — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0498
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.3
  location: 2nd Level BOH
  point_description: Flow Monitoring (Outside — Supply Air)
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0499
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.3
  location: 2nd Level BOH
  point_description: CHWS Valve Control (On/Off/Modulating)
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0500
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.3
  location: 2nd Level BOH
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0501
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.3
  location: 2nd Level BOH
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0502
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.3
  location: 2nd Level BOH
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0503
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.3
  location: 2nd Level BOH
  point_description: Temperature Monitoring (Indoor — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0504
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.3
  location: 2nd Level BOH
  point_description: Variable Speed Monitoring (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0505
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.3
  location: 2nd Level BOH
  point_description: Fan Control (On/Off/Modulating) (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0506
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-B.3
  location: 2nd Level BOH
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0507
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-PF
  location: 2nd Level Pre-Function
  point_description: Outdoor Supply Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0508
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-PF
  location: 2nd Level Pre-Function
  point_description: Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0509
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-PF
  location: 2nd Level Pre-Function
  point_description: Temperature Monitoring (Outside — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0510
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-PF
  location: 2nd Level Pre-Function
  point_description: Flow Monitoring (Outside — Supply Air)
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0511
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-PF
  location: 2nd Level Pre-Function
  point_description: CHWS Valve Control (On/Off/Modulating)
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0512
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-PF
  location: 2nd Level Pre-Function
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0513
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-PF
  location: 2nd Level Pre-Function
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0514
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-PF
  location: 2nd Level Pre-Function
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0515
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-PF
  location: 2nd Level Pre-Function
  point_description: Temperature Monitoring (Indoor — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0516
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-PF
  location: 2nd Level Pre-Function
  point_description: Variable Speed Monitoring (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0517
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-PF
  location: 2nd Level Pre-Function
  point_description: Fan Control (On/Off/Modulating) (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0518
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-PF
  location: 2nd Level Pre-Function
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0519
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-FR
  location: 2nd Level Function Rooms
  point_description: Outdoor Supply Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0520
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-FR
  location: 2nd Level Function Rooms
  point_description: Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0521
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-FR
  location: 2nd Level Function Rooms
  point_description: Temperature Monitoring (Outside — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0522
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-FR
  location: 2nd Level Function Rooms
  point_description: Flow Monitoring (Outside — Supply Air)
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0523
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-FR
  location: 2nd Level Function Rooms
  point_description: CHWS Valve Control (On/Off/Modulating)
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0524
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-FR
  location: 2nd Level Function Rooms
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0525
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-FR
  location: 2nd Level Function Rooms
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0526
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-FR
  location: 2nd Level Function Rooms
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0527
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-FR
  location: 2nd Level Function Rooms
  point_description: Temperature Monitoring (Indoor — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0528
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-FR
  location: 2nd Level Function Rooms
  point_description: Variable Speed Monitoring (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0529
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-FR
  location: 2nd Level Function Rooms
  point_description: Fan Control (On/Off/Modulating) (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0530
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-FR
  location: 2nd Level Function Rooms
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0531
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.1
  location: Ground Floor BOH
  point_description: Indoor Return Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0532
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.1
  location: Ground Floor BOH
  point_description: Indoor Return Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0533
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.1
  location: Ground Floor BOH
  point_description: Indoor Return Air CO2 Level
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0534
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.1
  location: Ground Floor BOH
  point_description: Temperature Monitoring (Indoor — Return Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0535
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.1
  location: Ground Floor BOH
  point_description: Temperature Monitoring (Indoor — Mixed Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0536
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.1
  location: Ground Floor BOH
  point_description: Outdoor Supply Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0537
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.1
  location: Ground Floor BOH
  point_description: Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0538
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.1
  location: Ground Floor BOH
  point_description: Temperature Monitoring (Outside — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0539
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.1
  location: Ground Floor BOH
  point_description: Temperature Monitoring (Indoor — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0540
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.1
  location: Ground Floor BOH
  point_description: CHWS Valve Control (On/Off/Modulating)
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0541
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.1
  location: Ground Floor BOH
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0542
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.1
  location: Ground Floor BOH
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0543
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.1
  location: Ground Floor BOH
  point_description: Fan Variable Speed Monitoring (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0544
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.1
  location: Ground Floor BOH
  point_description: Fan Control On/Off/Modulating (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0545
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.1
  location: Ground Floor BOH
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0546
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.2
  location: Ground Floor BOH
  point_description: Indoor Return Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0547
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.2
  location: Ground Floor BOH
  point_description: Indoor Return Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0548
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.2
  location: Ground Floor BOH
  point_description: Indoor Return Air CO2 Level
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0549
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.2
  location: Ground Floor BOH
  point_description: Temperature Monitoring (Indoor — Return Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0550
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.2
  location: Ground Floor BOH
  point_description: Temperature Monitoring (Indoor — Mixed Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0551
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.2
  location: Ground Floor BOH
  point_description: Outdoor Supply Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0552
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.2
  location: Ground Floor BOH
  point_description: Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0553
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.2
  location: Ground Floor BOH
  point_description: Temperature Monitoring (Outside — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0554
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.2
  location: Ground Floor BOH
  point_description: Temperature Monitoring (Indoor — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0555
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.2
  location: Ground Floor BOH
  point_description: CHWS Valve Control (On/Off/Modulating)
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0556
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.2
  location: Ground Floor BOH
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0557
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.2
  location: Ground Floor BOH
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0558
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.2
  location: Ground Floor BOH
  point_description: Fan Variable Speed Monitoring (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0559
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.2
  location: Ground Floor BOH
  point_description: Fan Control On/Off/Modulating (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0560
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.2
  location: Ground Floor BOH
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0561
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.3
  location: Ground Floor BOH
  point_description: Indoor Return Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0562
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.3
  location: Ground Floor BOH
  point_description: Indoor Return Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: ME Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0563
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.3
  location: Ground Floor BOH
  point_description: Indoor Return Air CO2 Level
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0564
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.3
  location: Ground Floor BOH
  point_description: Temperature Monitoring (Indoor — Return Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0565
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.3
  location: Ground Floor BOH
  point_description: Temperature Monitoring (Indoor — Mixed Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0566
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.3
  location: Ground Floor BOH
  point_description: Outdoor Supply Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0567
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.3
  location: Ground Floor BOH
  point_description: Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0568
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.3
  location: Ground Floor BOH
  point_description: Temperature Monitoring (Outside — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0569
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.3
  location: Ground Floor BOH
  point_description: Temperature Monitoring (Indoor — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0570
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.3
  location: Ground Floor BOH
  point_description: CHWS Valve Control (On/Off/Modulating)
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0571
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.3
  location: Ground Floor BOH
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0572
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.3
  location: Ground Floor BOH
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0573
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.3
  location: Ground Floor BOH
  point_description: Fan Variable Speed Monitoring (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0574
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.3
  location: Ground Floor BOH
  point_description: Fan Control On/Off/Modulating (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0575
  system: AC
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-1.3
  location: Ground Floor BOH
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0576
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-0.1
  location: Basement
  point_description: Outdoor Supply Air Motorized Damper Status
  type: AI
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0577
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-0.1
  location: Basement
  point_description: Outdoor Supply Air Motorized Damper Control (On/Off/Modulating)
  type: AO
  field_device: Damper Controller
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0578
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-0.1
  location: Basement
  point_description: Temperature Monitoring (Outside — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0579
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-0.1
  location: Basement
  point_description: Flow Monitoring (Outside — Supply Air)
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0580
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-0.1
  location: Basement
  point_description: CHWS Valve Control (On/Off/Modulating)
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0581
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-0.1
  location: Basement
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0582
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-0.1
  location: Basement
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0583
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-0.1
  location: Basement
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0584
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-0.1
  location: Basement
  point_description: Temperature Monitoring (Indoor — Supply Air)
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0585
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-0.1
  location: Basement
  point_description: Variable Speed Monitoring (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0586
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-0.1
  location: Basement
  point_description: Fan Control (On/Off/Modulating) (HLI)
  type: HLI
  field_device: VFD
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0587
  system: VENT
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-0.1
  location: Basement
  point_description: Network drop (BACnet MS/TP — VFD)
  type: Network
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0588
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-1.1
  location: GF Main Lobby Toilet
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0589
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-1.1
  location: GF Main Lobby Toilet
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0590
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-1.1
  location: GF Main Lobby Toilet
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0591
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-1.2
  location: GF Main Lobby Toilet
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0592
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-1.2
  location: GF Main Lobby Toilet
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0593
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-1.2
  location: GF Main Lobby Toilet
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0594
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-1.3
  location: GF Main Lobby Toilet
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0595
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-1.3
  location: GF Main Lobby Toilet
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0596
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-1.3
  location: GF Main Lobby Toilet
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0597
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-1.4
  location: GF Main Lobby Toilet
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0598
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-1.4
  location: GF Main Lobby Toilet
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0599
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-1.4
  location: GF Main Lobby Toilet
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0600
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-2.1
  location: 2nd Floor Toilet
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0601
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-2.1
  location: 2nd Floor Toilet
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0602
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-2.1
  location: 2nd Floor Toilet
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0603
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-2.2
  location: 2nd Floor Toilet
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0604
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-2.2
  location: 2nd Floor Toilet
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0605
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-2.2
  location: 2nd Floor Toilet
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0606
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-2B.3
  location: 2nd Floor BOH Toilet
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0607
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-2B.3
  location: 2nd Floor BOH Toilet
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0608
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-2B.3
  location: 2nd Floor BOH Toilet
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0609
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-2B.1
  location: 2nd Floor BOH
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0610
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-2B.1
  location: 2nd Floor BOH
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0611
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-2B.1
  location: 2nd Floor BOH
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0612
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-2B.2
  location: 2nd Floor BOH
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0613
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-2B.2
  location: 2nd Floor BOH
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0614
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-2B.2
  location: 2nd Floor BOH
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0615
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-GS.1
  location: 2nd Floor General Service
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0616
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-GS.1
  location: 2nd Floor General Service
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0617
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-GS.1
  location: 2nd Floor General Service
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0618
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-GS.2
  location: 2nd Floor General Service
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0619
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-GS.2
  location: 2nd Floor General Service
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0620
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-GS.2
  location: 2nd Floor General Service
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0621
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-2.1
  location: 2nd Floor
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0622
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-2.1
  location: 2nd Floor
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0623
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-2.1
  location: 2nd Floor
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0624
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-2.2
  location: 2nd Floor
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0625
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-2.2
  location: 2nd Floor
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0626
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-2.2
  location: 2nd Floor
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0627
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-2.3
  location: 2nd Floor
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0628
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-2.3
  location: 2nd Floor
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0629
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-2.3
  location: 2nd Floor
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0630
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-2.4
  location: 2nd Floor
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0631
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-2.4
  location: 2nd Floor
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0632
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-2.4
  location: 2nd Floor
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0633
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-OHRv2
  location: 2nd Floor OHR
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0634
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-OHRv2
  location: 2nd Floor OHR
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0635
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-OHRv2
  location: 2nd Floor OHR
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0636
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3A.1
  location: 3rd Floor Amenity Toilet
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0637
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3A.1
  location: 3rd Floor Amenity Toilet
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0638
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3A.1
  location: 3rd Floor Amenity Toilet
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0639
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3A.2
  location: 3rd Floor Amenity Toilet
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0640
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3A.2
  location: 3rd Floor Amenity Toilet
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0641
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3A.2
  location: 3rd Floor Amenity Toilet
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0642
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3B
  location: 3rd Floor Toilet
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0643
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3B
  location: 3rd Floor Toilet
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0644
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3B
  location: 3rd Floor Toilet
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0645
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3C.1
  location: 3rd Floor Toilet
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0646
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3C.1
  location: 3rd Floor Toilet
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0647
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3C.1
  location: 3rd Floor Toilet
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0648
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3C.2
  location: 3rd Floor Toilet
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0649
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3C.2
  location: 3rd Floor Toilet
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0650
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3C.2
  location: 3rd Floor Toilet
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0651
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-30.20
  location: 3rd Floor Toilet
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0652
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-30.20
  location: 3rd Floor Toilet
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0653
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-30.20
  location: 3rd Floor Toilet
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0654
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-3.1
  location: 3rd Floor
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0655
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-3.1
  location: 3rd Floor
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0656
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-3.1
  location: 3rd Floor
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0657
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-3.2
  location: 3rd Floor
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0658
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-3.2
  location: 3rd Floor
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0659
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-3.2
  location: 3rd Floor
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0660
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-3.3
  location: 3rd Floor
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0661
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-3.3
  location: 3rd Floor
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0662
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-3.3
  location: 3rd Floor
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0663
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-3.4
  location: 3rd Floor
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0664
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-3.4
  location: 3rd Floor
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0665
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-3.4
  location: 3rd Floor
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0666
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-3B-G
  location: 3rd Floor BOH
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0667
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-3B-G
  location: 3rd Floor BOH
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0668
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-3B-G
  location: 3rd Floor BOH
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0669
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-3C.1-G
  location: 3rd Floor
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0670
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-3C.1-G
  location: 3rd Floor
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0671
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-3C.1-G
  location: 3rd Floor
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-3F
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0672
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.1
  location: Basement Toilet
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0673
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.1
  location: Basement Toilet
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0674
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.1
  location: Basement Toilet
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0675
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.2
  location: Basement Toilet
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0676
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.2
  location: Basement Toilet
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0677
  system: VENT
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.2
  location: Basement Toilet
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0678
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-B.1
  location: Basement
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0679
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-B.1
  location: Basement
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0680
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-B.1
  location: Basement
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0681
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-B.2
  location: Basement
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0682
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-B.2
  location: Basement
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0683
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-B.2
  location: Basement
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0684
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-BS.1
  location: Basement Service
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0685
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-BS.1
  location: Basement Service
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0686
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-BS.1
  location: Basement Service
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0687
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-BS.2
  location: Basement Service
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0688
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-BS.2
  location: Basement Service
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0689
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-BS.2
  location: Basement Service
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0690
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-GL.1
  location: Basement Garbage Lobby
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0691
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-GL.1
  location: Basement Garbage Lobby
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0692
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-GL.1
  location: Basement Garbage Lobby
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0693
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-GL.2
  location: Basement Garbage Lobby
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0694
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-GL.2
  location: Basement Garbage Lobby
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0695
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-GL.2
  location: Basement Garbage Lobby
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0696
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-FOST.1
  location: Basement FOST Room
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0697
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-FOST.1
  location: Basement FOST Room
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0698
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-FOST.1
  location: Basement FOST Room
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0699
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-BR.1
  location: Basement Battery Room
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0700
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-BR.1
  location: Basement Battery Room
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0701
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-BR.1
  location: Basement Battery Room
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0702
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-BR.2
  location: Basement Battery Room
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0703
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-BR.2
  location: Basement Battery Room
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0704
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-BR.2
  location: Basement Battery Room
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0705
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-WS.1
  location: Basement Wash Service
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0706
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-WS.1
  location: Basement Wash Service
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0707
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-WS.1
  location: Basement Wash Service
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0708
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-MP.1
  location: Basement Mech / Pump
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0709
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-MP.1
  location: Basement Mech / Pump
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0710
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-MP.1
  location: Basement Mech / Pump
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0711
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-PR.1
  location: Basement Pump Room
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0712
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-PR.1
  location: Basement Pump Room
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0713
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-PR.1
  location: Basement Pump Room
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0714
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-PR.3
  location: Basement Pump Room
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0715
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-PR.3
  location: Basement Pump Room
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0716
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-PR.3
  location: Basement Pump Room
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0717
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-MFR.1
  location: Basement Main Fire Riser
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0718
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-MFR.1
  location: Basement Main Fire Riser
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0719
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-MFR.1
  location: Basement Main Fire Riser
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-B1-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0720
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-RD.1
  location: Roof Deck
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0721
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-RD.1
  location: Roof Deck
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0722
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-RD.1
  location: Roof Deck
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0723
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-RO.2
  location: Roof Deck
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0724
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-RO.2
  location: Roof Deck
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0725
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-RO.2
  location: Roof Deck
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0726
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-1
  location: Roof Deck
  point_description: Fan Motor Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0727
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-1
  location: Roof Deck
  point_description: Fan Motor Hand/Off/Auto Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0728
  system: VENT
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-1
  location: Roof Deck
  point_description: Fan Trip Alarm Status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  panel: DDC-RD-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0729
  system: EL
  equipment_class: Multifunction Power Meter (Main)
  equipment_instance: MPM-MAIN
  location: Lower Ground Main Switchroom
  point_description: Multifunction power meter — voltage / current / kW / kWh / power factor / harmonics
  type: HLI
  field_device: Multifunction Power Meter
  c_o: BMS Contractor
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0730
  system: EL
  equipment_class: Multifunction Power Meter (Main)
  equipment_instance: MPM-MAIN
  location: Lower Ground Main Switchroom
  point_description: Network drop (Modbus TCP — Power Meter)
  type: Network
  field_device: Multifunction Power Meter
  c_o: BMS Contractor
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0731
  system: EL
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: MPM-CHILLER
  location: 2nd Level Chiller MCC
  point_description: Multifunction power meter — voltage / current / kW / kWh / power factor
  type: HLI
  field_device: Multifunction Power Meter
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0732
  system: EL
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: MPM-CHILLER
  location: 2nd Level Chiller MCC
  point_description: Network drop (Modbus TCP — Power Meter)
  type: Network
  field_device: Multifunction Power Meter
  c_o: BMS Contractor
  panel: DDC-2F-CHILLER
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0733
  system: EL
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: MPM-AHU-2F
  location: 2nd Level AHU MCC
  point_description: Multifunction power meter — voltage / current / kW / kWh / power factor
  type: HLI
  field_device: Multifunction Power Meter
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0734
  system: EL
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: MPM-AHU-2F
  location: 2nd Level AHU MCC
  point_description: Network drop (Modbus TCP — Power Meter)
  type: Network
  field_device: Multifunction Power Meter
  c_o: BMS Contractor
  panel: DDC-2F-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0735
  system: EL
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: MPM-AHU-GF
  location: Ground Floor AHU MCC
  point_description: Multifunction power meter — voltage / current / kW / kWh / power factor
  type: HLI
  field_device: Multifunction Power Meter
  c_o: BMS Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0736
  system: EL
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: MPM-AHU-GF
  location: Ground Floor AHU MCC
  point_description: Network drop (Modbus TCP — Power Meter)
  type: Network
  field_device: Multifunction Power Meter
  c_o: BMS Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0737
  system: EL
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: MPM-LIGHT-A
  location: Lower Ground Lighting Panel A
  point_description: Multifunction power meter — voltage / current / kW / kWh / power factor
  type: HLI
  field_device: Multifunction Power Meter
  c_o: BMS Contractor
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0738
  system: EL
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: MPM-LIGHT-A
  location: Lower Ground Lighting Panel A
  point_description: Network drop (Modbus TCP — Power Meter)
  type: Network
  field_device: Multifunction Power Meter
  c_o: BMS Contractor
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0739
  system: EL
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: MPM-LIGHT-B
  location: Lower Ground Lighting Panel B
  point_description: Multifunction power meter — voltage / current / kW / kWh / power factor
  type: HLI
  field_device: Multifunction Power Meter
  c_o: BMS Contractor
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0740
  system: EL
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: MPM-LIGHT-B
  location: Lower Ground Lighting Panel B
  point_description: Network drop (Modbus TCP — Power Meter)
  type: Network
  field_device: Multifunction Power Meter
  c_o: BMS Contractor
  panel: DDC-LG-PLANT
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0741
  system: FDAS
  equipment_class: FACP Gateway
  equipment_instance: FACP-GW
  location: Ground Floor Fire Command Center
  point_description: Fire Alarm Common Alarm
  type: HLI
  field_device: FACP BACnet Gateway
  c_o: EE Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0742
  system: FDAS
  equipment_class: FACP Gateway
  equipment_instance: FACP-GW
  location: Ground Floor Fire Command Center
  point_description: Fire Alarm Common Trouble
  type: HLI
  field_device: FACP BACnet Gateway
  c_o: EE Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0743
  system: FDAS
  equipment_class: FACP Gateway
  equipment_instance: FACP-GW
  location: Ground Floor Fire Command Center
  point_description: Fire Alarm System Status
  type: HLI
  field_device: FACP BACnet Gateway
  c_o: EE Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
- id: P-0744
  system: FDAS
  equipment_class: FACP Gateway
  equipment_instance: FACP-GW
  location: Ground Floor Fire Command Center
  point_description: Network drop (BACnet/IP — FACP Gateway)
  type: Network
  field_device: FACP BACnet Gateway
  c_o: EE Contractor
  panel: DDC-GF-BOH
  source: BMS-01/02 + MC Standards ME/PL
  notes: ''
summary:
  total_points: 744
  total_instances: 109