# 2.7.3 — Cable Field Control

**Module:** [bms/cabling-and-containment](../../../_playbook/modules/bms/cabling-and-containment.md)
**WBS leaf:** 2.7.3
**Project:** Kingsford Hotel Bacolod — BMS (AB-Run-6)
**Date:** 2026-04-28

### Project-specific values
- **Spec:** 4C × 1.5 mm² shielded FRLS for BMS-supplied signals (`bms_signal_default`); 4C × 1.5 mm² FRLS unshielded for equipment-supplier aux contacts (`equipment_aux_default`); 4C × 1.5 mm² FRLS for ME-actuator status/control (`me_actuator_default`); Modbus 1pr × 22 AWG shielded for EE metering (`ee_metering_default`).
- **Total field cable:** ~5,170 m per A3 `Grand total cable length`.
- **References:** A3 cable schedule, A3 cable-spec rules.