# 2.3.5 — Panels Floor Misc

**Module:** [bms/controller-panel](../../../_playbook/modules/bms/controller-panel.md)
**WBS leaf:** 2.3.5
**Project:** Kingsford Hotel Bacolod — BMS (AB-Run-6)
**Date:** 2026-04-28

### Project-specific values
- **Panels:** DDC-2F-BOH, DDC-GF-BOH, DDC-B1-BOH, DDC-3F (4 floor BMS DDC panels).
- **Equipment served:** 2F BOH AHU/PAHU + 2F exhaust fans (DDC-2F-BOH); GF AHU-1.x + Lobby exhaust + FACP-GW (DDC-GF-BOH); PAHU-0.1 + 16 basement exhaust fans (DDC-B1-BOH); 3F amenity + guestroom exhaust fans (DDC-3F).
- **Controllers (per panel):** typically 2 DDC controllers each.
- **I/O modules:** sized per-panel from A1 quantities + spare strategy; average 2 AI / 1 AO / 3 DI / 1 DO per panel.
- **Power feeds:** DBV-MECH-2F-BOH / DBV-MECH-GF / DBV-MECH-B1 / DBV-MECH-3F (TBC Q-014); 16-20A each.
- **Network drops:** Cat6 to per-floor IDF.
- **References:** A4 rows, BMS-01 BOH AHU + Basement General Ventilation + 2F + 3F General Ventilation tables.