metadata:
  project: Kingsford Hotel Bacolod — BMS
  date: 2026-04-28
basis: |
  Hotel + casino-lobby project. Trend logging strategy per Op#11:
  - 100% AI: temperature/humidity/pressure/flow are key tuning data; full trend.
  - 100% AO: control-loop diagnostics require AO trends.
  - 50% DI: status events trended (run-status, trip, H/O/A); raise from default 40%
    because casino MVAC requires audit-trail trend retention for IAQ regulation.
  - 100% DO: command actions trended for fault-tracing.
  - 80% HLI: VFD speed / chiller load / heat-pump efficiency points trended at
    higher rate than default 70% — Megaworld energy-management standard requires
    chiller plant ECPI / efficiency trending.
ai_pct: 100
ao_pct: 100
di_pct: 50
do_pct: 100
hli_pct: 80