metadata:
  project: Kingsford Hotel Bacolod — BMS
  date: 2026-04-28
  source: "A4 panel schedule + EE-21/22/23 + EE-24 power riser (Part 1 of 2)"
  status: draft

field_panels:
  total_panel_load_w: 525
  basis: "13 BMS field panels × ~25–35 W each (per A4 controller estimate). Each panel takes a 240V single-phase 16A breaker from the nearest panelboard (per A-018)."
  per_panel_load_w_typical: 35
  panel_count: 13

head_end:
  total_head_end_load_w: 1800
  basis: "1 server (~600 W) + 1 operator WS (~250 W) + 1 HMI (~200 W) + 2 secondary monitors (~120 W) + UPS overhead (~100 W) + KVM/printer (~100 W) + headroom (~430 W). 240V single-phase clean feed from MV/LV main + UPS bypass."

network_edge:
  total_edge_load_w: 240
  basis: "BMS edge switch ports (~6 managed L2 switches at ~30 W each) + small loads (~60 W). Distributed across riser + head-end rack."

summary:
  total_bms_load_w: 2565
  basis_summary: "Total BMS continuous load ~2.6 kW across 13 field panels + head-end + network edge. Coordination with EE contractor: dedicated 240V single-phase breakers at nearest panelboard for each BMS field panel; clean UPS-backed feed for head-end."