# A4 — Panel Schedule
# Generated from A1-io-list.yaml
#
metadata:
  project: "Kingsford Hotel Bacolod \u2014 BMS"
  generated_from: A1-io-list.yaml
  generator: _playbook/tools/generate-a4-panel-schedule.py
  controller_sizing_rule: 1 DDC controller per 40 physical I/O, +1 network gateway if Network drops present. Refine after Q-008 confirms wiring topology.
  power_estimate_basis: ~25W per controller, ~5W per network device. Excludes UPS/transformer overhead.
summary:
  total_panels: 13
  total_physical_io: 570
  total_hli_subpoints: 49
  total_network_drops: 0
  total_io_points: 619
  total_controllers_estimated: 21
  total_power_watts_estimated: 525
  panel_summary_table:
  - panel: BMS-PNL-AHU-2F
    location: 2F
    physical_io: 12
    network: 0
    controllers: 1
    power_w: 25
    equipment_count: 1
  - panel: BMS-PNL-AHU-RD
    location: RD
    physical_io: 44
    network: 0
    controllers: 2
    power_w: 50
    equipment_count: 2
  - panel: BMS-PNL-BOHAHU-2F
    location: 2F
    physical_io: 120
    network: 0
    controllers: 3
    power_w: 75
    equipment_count: 1
  - panel: BMS-PNL-BOILER-LG
    location: LG
    physical_io: 22
    network: 0
    controllers: 1
    power_w: 25
    equipment_count: 1
  - panel: BMS-PNL-CASINO-2F
    location: 2F
    physical_io: 30
    network: 0
    controllers: 1
    power_w: 25
    equipment_count: 2
  - panel: BMS-PNL-CHWPLANT-2F
    location: 2F
    physical_io: 121
    network: 0
    controllers: 4
    power_w: 100
    equipment_count: 4
  - panel: BMS-PNL-CT-RD
    location: RD
    physical_io: 35
    network: 0
    controllers: 1
    power_w: 25
    equipment_count: 1
  - panel: BMS-PNL-PLUMBING-LG
    location: LG
    physical_io: 18
    network: 0
    controllers: 1
    power_w: 25
    equipment_count: 4
  - panel: BMS-PNL-PLUMBING-RD
    location: RD
    physical_io: 12
    network: 0
    controllers: 1
    power_w: 25
    equipment_count: 3
  - panel: BMS-PNL-VENT-2F
    location: 2F
    physical_io: 39
    network: 0
    controllers: 1
    power_w: 25
    equipment_count: 1
  - panel: BMS-PNL-VENT-3F
    location: 3F
    physical_io: 81
    network: 0
    controllers: 3
    power_w: 75
    equipment_count: 1
  - panel: BMS-PNL-VENT-GF
    location: GF
    physical_io: 27
    network: 0
    controllers: 1
    power_w: 25
    equipment_count: 1
  - panel: BMS-PNL-VENT-RD
    location: RD
    physical_io: 9
    network: 0
    controllers: 1
    power_w: 25
    equipment_count: 1
panels:
- id: BMS-PNL-AHU-2F
  location: 2F
  system_scope:
  - "Air Handling \u2014 Pre-cooled"
  equipment_served:
    instance_count: 1
    instances:
    - PAHU-0.1
    by_class:
      Precooled Air Handling Unit: 16
  io_summary:
    physical_io: 12
    hli_subpoints: 4
    network_drops: 0
    total: 16
    by_type:
      AI: 6
      AO: 2
      DI: 4
      HLI: 4
    by_co:
      BMS Contractor: 8
      Equipment Supplier: 4
      ME Contractor: 4
  controller_estimate:
    ddc_controllers: 1
    network_gateway: 0
    total_controllers: 1
    rule: 1 DDC per 40 physical I/O, plus 1 network gateway if BACnet/Modbus integration on panel
  power_estimate_w: 25
  enclosure_assumption: Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
  notes: ''
- id: BMS-PNL-AHU-RD
  location: RD
  system_scope:
  - "Air Handling \u2014 Pre-cooled (Roofdeck)"
  - "Air Handling \u2014 Roofdeck AHU"
  equipment_served:
    instance_count: 2
    instances:
    - AHU-RD (with CHW mod valve)
    - "PAHU-RD (\xD72)"
    by_class:
      AHU (Chilled-Water-Served): 32
      Precooled Air Handling Unit: 14
  io_summary:
    physical_io: 44
    hli_subpoints: 2
    network_drops: 0
    total: 46
    by_type:
      AI: 20
      AO: 4
      DI: 14
      DO: 6
      HLI: 2
    by_co:
      BMS Contractor: 24
      Equipment Supplier: 2
      ME Contractor: 20
  controller_estimate:
    ddc_controllers: 2
    network_gateway: 0
    total_controllers: 2
    rule: 1 DDC per 40 physical I/O, plus 1 network gateway if BACnet/Modbus integration on panel
  power_estimate_w: 50
  enclosure_assumption: Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
  notes: ''
- id: BMS-PNL-BOHAHU-2F
  location: 2F
  system_scope:
  - "Air Handling \u2014 Basement / Podium BOH"
  equipment_served:
    instance_count: 1
    instances:
    - AHU-2/B.2/B.3/PP/CL/FRE/FRD
    by_class:
      AHU (Chilled-Water-Served): 140
  io_summary:
    physical_io: 120
    hli_subpoints: 20
    network_drops: 0
    total: 140
    by_type:
      AI: 70
      AO: 30
      DI: 20
      HLI: 20
    by_co:
      BMS Contractor: 100
      Equipment Supplier: 20
      ME Contractor: 20
  controller_estimate:
    ddc_controllers: 3
    network_gateway: 0
    total_controllers: 3
    rule: 1 DDC per 40 physical I/O, plus 1 network gateway if BACnet/Modbus integration on panel
  power_estimate_w: 75
  enclosure_assumption: Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
  notes: ''
- id: BMS-PNL-BOILER-LG
  location: LG
  system_scope:
  - Boiler / Laundry
  equipment_served:
    instance_count: 1
    instances:
    - SB-1 & SB-2
    by_class:
      Steam Boiler: 22
  io_summary:
    physical_io: 22
    hli_subpoints: 0
    network_drops: 0
    total: 22
    by_type:
      AI: 6
      DI: 14
      DO: 2
    by_co:
      BMS Contractor: 6
      ME Contractor: 16
  controller_estimate:
    ddc_controllers: 1
    network_gateway: 0
    total_controllers: 1
    rule: 1 DDC per 40 physical I/O, plus 1 network gateway if BACnet/Modbus integration on panel
  power_estimate_w: 25
  enclosure_assumption: Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
  notes: ''
- id: BMS-PNL-CASINO-2F
  location: 2F
  system_scope:
  - "Casino MVAC \u2014 Dedicated Outdoor Air"
  - "Casino MVAC \u2014 Smoke Sanitizer"
  equipment_served:
    instance_count: 2
    instances:
    - "DOAS (Casino) \u2014 2 units"
    - Sanitizer for AHU-2M.1/2M.2
    by_class:
      DOAS Unit: 30
      Ozone Generator (UV-light or Corona): 4
  io_summary:
    physical_io: 30
    hli_subpoints: 4
    network_drops: 0
    total: 34
    by_type:
      AI: 16
      AO: 6
      DI: 8
      HLI: 4
    by_co:
      BMS Contractor: 22
      Equipment Supplier: 8
      ME Contractor: 4
  controller_estimate:
    ddc_controllers: 1
    network_gateway: 0
    total_controllers: 1
    rule: 1 DDC per 40 physical I/O, plus 1 network gateway if BACnet/Modbus integration on panel
  power_estimate_w: 25
  enclosure_assumption: Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
  notes: ''
- id: BMS-PNL-CHWPLANT-2F
  location: 2F
  system_scope:
  - Chilled Water Plant
  equipment_served:
    instance_count: 4
    instances:
    - CDWP-1 to CDWP-3
    - CH-1 to CH-3
    - CHW Supply & Return Main Header
    - CHWP-1 to CHWP-3
    by_class:
      Chiller (Package Water-Cooled): 81
      Primary CHW Pump: 21
      Condenser Water Pump: 12
      CHW Supply Main Header: 7
  io_summary:
    physical_io: 121
    hli_subpoints: 0
    network_drops: 0
    total: 121
    by_type:
      AI: 33
      AO: 1
      DI: 81
      DO: 6
    by_co:
      BMS Contractor: 34
      ME Contractor: 87
  controller_estimate:
    ddc_controllers: 4
    network_gateway: 0
    total_controllers: 4
    rule: 1 DDC per 40 physical I/O, plus 1 network gateway if BACnet/Modbus integration on panel
  power_estimate_w: 100
  enclosure_assumption: Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
  notes: ''
- id: BMS-PNL-CT-RD
  location: RD
  system_scope:
  - "Heat Rejection \u2014 Cooling Tower"
  equipment_served:
    instance_count: 1
    instances:
    - CT-1 to CT-3
    by_class:
      Cooling Tower: 36
  io_summary:
    physical_io: 35
    hli_subpoints: 1
    network_drops: 0
    total: 36
    by_type:
      AI: 24
      DI: 8
      DO: 3
      HLI: 1
    by_co:
      BMS Contractor: 24
      Equipment Supplier: 1
      ME Contractor: 11
  controller_estimate:
    ddc_controllers: 1
    network_gateway: 0
    total_controllers: 1
    rule: 1 DDC per 40 physical I/O, plus 1 network gateway if BACnet/Modbus integration on panel
  power_estimate_w: 25
  enclosure_assumption: Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
  notes: ''
- id: BMS-PNL-PLUMBING-LG
  location: LG
  system_scope:
  - "Plumbing \u2014 Sanitary Hot Water"
  equipment_served:
    instance_count: 4
    instances:
    - "HP-LZ (\xD73)"
    - HW Supply & Return Header (LG)
    - "HWT-LZ (\xD73)"
    - "RP-LZ (\xD73)"
    by_class:
      Heat Pump: 9
      Recirculating Pump: 9
      CHW Supply Main Header: 6
      Calorifier (Hot Water Storage Tank): 3
  io_summary:
    physical_io: 18
    hli_subpoints: 9
    network_drops: 0
    total: 27
    by_type:
      AI: 9
      DI: 9
      HLI: 9
    by_co:
      BMS Contractor: 9
      Equipment Supplier: 9
      ME Contractor: 9
  controller_estimate:
    ddc_controllers: 1
    network_gateway: 0
    total_controllers: 1
    rule: 1 DDC per 40 physical I/O, plus 1 network gateway if BACnet/Modbus integration on panel
  power_estimate_w: 25
  enclosure_assumption: Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
  notes: ''
- id: BMS-PNL-PLUMBING-RD
  location: RD
  system_scope:
  - "Plumbing \u2014 Sanitary Hot Water"
  equipment_served:
    instance_count: 3
    instances:
    - "HP-HZ (\xD73)"
    - "HWT-HZ (\xD73)"
    - "RP-HZ (\xD73)"
    by_class:
      Heat Pump: 9
      Recirculating Pump: 9
      Calorifier (Hot Water Storage Tank): 3
  io_summary:
    physical_io: 12
    hli_subpoints: 9
    network_drops: 0
    total: 21
    by_type:
      AI: 3
      DI: 9
      HLI: 9
    by_co:
      BMS Contractor: 3
      Equipment Supplier: 9
      ME Contractor: 9
  controller_estimate:
    ddc_controllers: 1
    network_gateway: 0
    total_controllers: 1
    rule: 1 DDC per 40 physical I/O, plus 1 network gateway if BACnet/Modbus integration on panel
  power_estimate_w: 25
  enclosure_assumption: Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
  notes: ''
- id: BMS-PNL-VENT-2F
  location: 2F
  system_scope:
  - General Ventilation
  equipment_served:
    instance_count: 1
    instances:
    - TEF-2.1/2.3/2B.3 + EF-2B.1/2B.2/GS.1&GS.2 + EF-2.1 to 2.4 + EF-CHRx2
    by_class:
      Exhaust Fan (General): 39
  io_summary:
    physical_io: 39
    hli_subpoints: 0
    network_drops: 0
    total: 39
    by_type:
      DI: 39
    by_co:
      ME Contractor: 39
  controller_estimate:
    ddc_controllers: 1
    network_gateway: 0
    total_controllers: 1
    rule: 1 DDC per 40 physical I/O, plus 1 network gateway if BACnet/Modbus integration on panel
  power_estimate_w: 25
  enclosure_assumption: Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
  notes: ''
- id: BMS-PNL-VENT-3F
  location: 3F
  system_scope:
  - General Ventilation
  equipment_served:
    instance_count: 1
    instances:
    - TEF-3Ax2/3B/3Cx2/3Dx20 + others
    by_class:
      Exhaust Fan (General): 81
  io_summary:
    physical_io: 81
    hli_subpoints: 0
    network_drops: 0
    total: 81
    by_type:
      DI: 81
    by_co:
      ME Contractor: 81
  controller_estimate:
    ddc_controllers: 3
    network_gateway: 0
    total_controllers: 3
    rule: 1 DDC per 40 physical I/O, plus 1 network gateway if BACnet/Modbus integration on panel
  power_estimate_w: 75
  enclosure_assumption: Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
  notes: ''
- id: BMS-PNL-VENT-GF
  location: GF
  system_scope:
  - General Ventilation
  equipment_served:
    instance_count: 1
    instances:
    - TEF-1.1 to 1.4 + EF-1.2A/LPG.1/1MR.1/1STO.1/MRF.1
    by_class:
      Exhaust Fan (General): 27
  io_summary:
    physical_io: 27
    hli_subpoints: 0
    network_drops: 0
    total: 27
    by_type:
      DI: 27
    by_co:
      ME Contractor: 27
  controller_estimate:
    ddc_controllers: 1
    network_gateway: 0
    total_controllers: 1
    rule: 1 DDC per 40 physical I/O, plus 1 network gateway if BACnet/Modbus integration on panel
  power_estimate_w: 25
  enclosure_assumption: Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
  notes: ''
- id: BMS-PNL-VENT-RD
  location: RD
  system_scope:
  - General Ventilation
  equipment_served:
    instance_count: 1
    instances:
    - EF-RD.1/RD.2, EF-1
    by_class:
      Exhaust Fan (General): 9
  io_summary:
    physical_io: 9
    hli_subpoints: 0
    network_drops: 0
    total: 9
    by_type:
      DI: 9
    by_co:
      ME Contractor: 9
  controller_estimate:
    ddc_controllers: 1
    network_gateway: 0
    total_controllers: 1
    rule: 1 DDC per 40 physical I/O, plus 1 network gateway if BACnet/Modbus integration on panel
  power_estimate_w: 25
  enclosure_assumption: Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
  notes: ''