# A2 — Equipment Takeoff
# Generated from A1-io-list.yaml on $(date) — see metadata.generator
# Schema: see _playbook/checklists/working-documents.md (A2)
#
metadata:
  project: "Kingsford Hotel Bacolod \u2014 BMS"
  generated_from: A1-io-list.yaml
  generator: _playbook/tools/generate-a2-equipment-takeoff.py
  regenerate: Re-run the generator after A1 changes. Hand edits to make_model_assumed and notes can be preserved by editing equipment-class-defaults.yaml or adding per-instance overrides below.
summary:
  total_instances: 23
  by_equipment_class:
    Exhaust Fan (General): 4
    AHU (Chilled-Water-Served): 2
    CHW Supply Main Header: 2
    Heat Pump: 2
    Calorifier (Hot Water Storage Tank): 2
    Precooled Air Handling Unit: 2
    Recirculating Pump: 2
    Condenser Water Pump: 1
    Chiller (Package Water-Cooled): 1
    Primary CHW Pump: 1
    Cooling Tower: 1
    DOAS Unit: 1
    Steam Boiler: 1
    Ozone Generator (UV-light or Corona): 1
  by_location:
    2F: 9
    RD: 7
    LG: 5
    GF: 1
    3F: 1
  by_panel:
    BMS-PNL-CHWPLANT-2F: 4
    BMS-PNL-PLUMBING-LG: 4
    BMS-PNL-PLUMBING-RD: 3
    BMS-PNL-AHU-RD: 2
    BMS-PNL-CASINO-2F: 2
    BMS-PNL-BOHAHU-2F: 1
    BMS-PNL-CT-RD: 1
    BMS-PNL-VENT-RD: 1
    BMS-PNL-AHU-2F: 1
    BMS-PNL-BOILER-LG: 1
    BMS-PNL-VENT-GF: 1
    BMS-PNL-VENT-2F: 1
    BMS-PNL-VENT-3F: 1
  by_primary_co:
    ME Contractor: 11
    BMS Contractor: 9
    Equipment Supplier: 3
takeoff:
- id: AHU-2/B.2/B.3/PP/CL/FRE/FRD
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: 2F
  system: "Air Handling \u2014 Basement / Podium BOH"
  panel: BMS-PNL-BOHAHU-2F
  primary_co: BMS Contractor
  io_summary:
    physical_io: 120
    hli_subpoints: 20
    network_drops: 0
    total: 140
    by_type:
      AI: 70
      AO: 30
      DI: 20
      HLI: 20
    by_co:
      BMS Contractor: 100
      Equipment Supplier: 20
      ME Contractor: 20
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: AHU-RD (with CHW mod valve)
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: RD
  system: "Air Handling \u2014 Roofdeck AHU"
  panel: BMS-PNL-AHU-RD
  primary_co: BMS Contractor
  io_summary:
    physical_io: 32
    hli_subpoints: 0
    network_drops: 0
    total: 32
    by_type:
      AI: 16
      AO: 4
      DI: 8
      DO: 4
    by_co:
      BMS Contractor: 20
      ME Contractor: 12
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: CDWP-1 to CDWP-3
  equipment_class: Condenser Water Pump
  quantity: 1
  location: 2F
  system: Chilled Water Plant
  panel: BMS-PNL-CHWPLANT-2F
  primary_co: ME Contractor
  io_summary:
    physical_io: 12
    hli_subpoints: 0
    network_drops: 0
    total: 12
    by_type:
      DI: 9
      DO: 3
    by_co:
      ME Contractor: 12
  make_model_assumed: End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious)
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: BMS reads aux contacts; commands start via DO.
- id: CH-1 to CH-3
  equipment_class: Chiller (Package Water-Cooled)
  quantity: 1
  location: 2F
  system: Chilled Water Plant
  panel: BMS-PNL-CHWPLANT-2F
  primary_co: ME Contractor
  io_summary:
    physical_io: 81
    hli_subpoints: 0
    network_drops: 0
    total: 81
    by_type:
      AI: 27
      DI: 54
    by_co:
      BMS Contractor: 27
      ME Contractor: 54
  make_model_assumed: Tier-1 BACnet IP chiller (Trane/York/Carrier/Daikin), water-cooled centrifugal or screw, sized per design cooling load
  network_type: BACnet/IP
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: BMS reads via chiller's native BACnet gateway. BMS supplies external T-sensors on entering/leaving CHW & CW pipes.
- id: CHW Supply & Return Main Header
  equipment_class: CHW Supply Main Header
  quantity: 1
  location: 2F
  system: Chilled Water Plant
  panel: BMS-PNL-CHWPLANT-2F
  primary_co: BMS Contractor
  io_summary:
    physical_io: 7
    hli_subpoints: 0
    network_drops: 0
    total: 7
    by_type:
      AI: 6
      AO: 1
    by_co:
      BMS Contractor: 7
  make_model_assumed: BMS T+P sensors on CHW supply manifold
  network_type: Hardwired
  typical_supplier: BMS contractor
  notes: Field instrumentation only.
- id: CHWP-1 to CHWP-3
  equipment_class: Primary CHW Pump
  quantity: 1
  location: 2F
  system: Chilled Water Plant
  panel: BMS-PNL-CHWPLANT-2F
  primary_co: ME Contractor
  io_summary:
    physical_io: 21
    hli_subpoints: 0
    network_drops: 0
    total: 21
    by_type:
      DI: 18
      DO: 3
    by_co:
      ME Contractor: 21
  make_model_assumed: End-suction or split-case centrifugal with VFD, sized per design CHW flow
  network_type: Hardwired (BMS reads VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: VFD typically Equipment Supplier provided with BACnet card.
- id: CT-1 to CT-3
  equipment_class: Cooling Tower
  quantity: 1
  location: RD
  system: "Heat Rejection \u2014 Cooling Tower"
  panel: BMS-PNL-CT-RD
  primary_co: BMS Contractor
  io_summary:
    physical_io: 35
    hli_subpoints: 1
    network_drops: 0
    total: 36
    by_type:
      AI: 24
      DI: 8
      DO: 3
      HLI: 1
    by_co:
      BMS Contractor: 24
      Equipment Supplier: 1
      ME Contractor: 11
  make_model_assumed: Induced-draft counterflow open cooling tower (Marley/BAC/EVAPCO), sized per condenser water flow
  network_type: Hardwired
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: BMS supplies basin level sensors and condenser water header T-sensors.
- id: "DOAS (Casino) \u2014 2 units"
  equipment_class: DOAS Unit
  quantity: 1
  location: 2F
  system: "Casino MVAC \u2014 Dedicated Outdoor Air"
  panel: BMS-PNL-CASINO-2F
  primary_co: BMS Contractor
  io_summary:
    physical_io: 26
    hli_subpoints: 4
    network_drops: 0
    total: 30
    by_type:
      AI: 16
      AO: 6
      DI: 4
      HLI: 4
    by_co:
      BMS Contractor: 22
      Equipment Supplier: 4
      ME Contractor: 4
  make_model_assumed: Dedicated Outdoor Air System with energy recovery wheel, supply + exhaust fans, CHW coil
  network_type: BACnet/IP
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: Native BACnet controller typical. BMS supplies external sensors (OA T/RH/Flow, indoor T/RH, exhaust T) and modulating valve actuator.
- id: EF-RD.1/RD.2, EF-1
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: RD
  system: General Ventilation
  panel: BMS-PNL-VENT-RD
  primary_co: ME Contractor
  io_summary:
    physical_io: 9
    hli_subpoints: 0
    network_drops: 0
    total: 9
    by_type:
      DI: 9
    by_co:
      ME Contractor: 9
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: "HP-HZ (\xD73)"
  equipment_class: Heat Pump
  quantity: 1
  location: RD
  system: "Plumbing \u2014 Sanitary Hot Water"
  panel: BMS-PNL-PLUMBING-RD
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 0
    hli_subpoints: 9
    network_drops: 0
    total: 9
    by_type:
      HLI: 9
    by_co:
      Equipment Supplier: 9
  make_model_assumed: Air-source or water-source heat pump for hot water heating
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor / Equipment supplier
  notes: BMS reads pump status/HOA/trip via aux contacts.
- id: "HP-LZ (\xD73)"
  equipment_class: Heat Pump
  quantity: 1
  location: LG
  system: "Plumbing \u2014 Sanitary Hot Water"
  panel: BMS-PNL-PLUMBING-LG
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 0
    hli_subpoints: 9
    network_drops: 0
    total: 9
    by_type:
      HLI: 9
    by_co:
      Equipment Supplier: 9
  make_model_assumed: Air-source or water-source heat pump for hot water heating
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor / Equipment supplier
  notes: BMS reads pump status/HOA/trip via aux contacts.
- id: HW Supply & Return Header (LG)
  equipment_class: CHW Supply Main Header
  quantity: 1
  location: LG
  system: "Plumbing \u2014 Sanitary Hot Water"
  panel: BMS-PNL-PLUMBING-LG
  primary_co: BMS Contractor
  io_summary:
    physical_io: 6
    hli_subpoints: 0
    network_drops: 0
    total: 6
    by_type:
      AI: 6
    by_co:
      BMS Contractor: 6
  make_model_assumed: BMS T+P sensors on CHW supply manifold
  network_type: Hardwired
  typical_supplier: BMS contractor
  notes: Field instrumentation only.
- id: "HWT-HZ (\xD73)"
  equipment_class: Calorifier (Hot Water Storage Tank)
  quantity: 1
  location: RD
  system: "Plumbing \u2014 Sanitary Hot Water"
  panel: BMS-PNL-PLUMBING-RD
  primary_co: BMS Contractor
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      AI: 3
    by_co:
      BMS Contractor: 3
  make_model_assumed: Pressurised hot-water storage tank with internal coil, sized per design hot water demand
  network_type: Hardwired
  typical_supplier: Plumbing contractor
  notes: BMS supplies tank temperature sensor (immersion or strapped probe).
- id: "HWT-LZ (\xD73)"
  equipment_class: Calorifier (Hot Water Storage Tank)
  quantity: 1
  location: LG
  system: "Plumbing \u2014 Sanitary Hot Water"
  panel: BMS-PNL-PLUMBING-LG
  primary_co: BMS Contractor
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      AI: 3
    by_co:
      BMS Contractor: 3
  make_model_assumed: Pressurised hot-water storage tank with internal coil, sized per design hot water demand
  network_type: Hardwired
  typical_supplier: Plumbing contractor
  notes: BMS supplies tank temperature sensor (immersion or strapped probe).
- id: PAHU-0.1
  equipment_class: Precooled Air Handling Unit
  quantity: 1
  location: 2F
  system: "Air Handling \u2014 Pre-cooled"
  panel: BMS-PNL-AHU-2F
  primary_co: BMS Contractor
  io_summary:
    physical_io: 12
    hli_subpoints: 4
    network_drops: 0
    total: 16
    by_type:
      AI: 6
      AO: 2
      DI: 4
      HLI: 4
    by_co:
      BMS Contractor: 8
      Equipment Supplier: 4
      ME Contractor: 4
  make_model_assumed: Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust path
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: 'Precool function: cools outdoor air before it''s distributed to other systems. BMS supplies OA/supply T sensors.'
- id: "PAHU-RD (\xD72)"
  equipment_class: Precooled Air Handling Unit
  quantity: 1
  location: RD
  system: "Air Handling \u2014 Pre-cooled (Roofdeck)"
  panel: BMS-PNL-AHU-RD
  primary_co: ME Contractor
  io_summary:
    physical_io: 12
    hli_subpoints: 2
    network_drops: 0
    total: 14
    by_type:
      AI: 4
      DI: 6
      DO: 2
      HLI: 2
    by_co:
      BMS Contractor: 4
      Equipment Supplier: 2
      ME Contractor: 8
  make_model_assumed: Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust path
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: 'Precool function: cools outdoor air before it''s distributed to other systems. BMS supplies OA/supply T sensors.'
- id: "RP-HZ (\xD73)"
  equipment_class: Recirculating Pump
  quantity: 1
  location: RD
  system: "Plumbing \u2014 Sanitary Hot Water"
  panel: BMS-PNL-PLUMBING-RD
  primary_co: ME Contractor
  io_summary:
    physical_io: 9
    hli_subpoints: 0
    network_drops: 0
    total: 9
    by_type:
      DI: 9
    by_co:
      ME Contractor: 9
  make_model_assumed: Hot water recirculating pump, fixed-speed (typical for hotwater systems)
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor
  notes: BMS reads aux contacts only.
- id: "RP-LZ (\xD73)"
  equipment_class: Recirculating Pump
  quantity: 1
  location: LG
  system: "Plumbing \u2014 Sanitary Hot Water"
  panel: BMS-PNL-PLUMBING-LG
  primary_co: ME Contractor
  io_summary:
    physical_io: 9
    hli_subpoints: 0
    network_drops: 0
    total: 9
    by_type:
      DI: 9
    by_co:
      ME Contractor: 9
  make_model_assumed: Hot water recirculating pump, fixed-speed (typical for hotwater systems)
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor
  notes: BMS reads aux contacts only.
- id: SB-1 & SB-2
  equipment_class: Steam Boiler
  quantity: 1
  location: LG
  system: Boiler / Laundry
  panel: BMS-PNL-BOILER-LG
  primary_co: ME Contractor
  io_summary:
    physical_io: 22
    hli_subpoints: 0
    network_drops: 0
    total: 22
    by_type:
      AI: 6
      DI: 14
      DO: 2
    by_co:
      BMS Contractor: 6
      ME Contractor: 16
  make_model_assumed: Fire-tube steam boiler with multi-stage burner, fuel-oil fired (typical for hotel laundry)
  network_type: Hardwired
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: BMS supplies steam pressure, feedwater T, fluegas T+O2 sensors. Boiler equipment provides aux contacts for status/HOA/trip points.
- id: Sanitizer for AHU-2M.1/2M.2
  equipment_class: Ozone Generator (UV-light or Corona)
  quantity: 1
  location: 2F
  system: "Casino MVAC \u2014 Smoke Sanitizer"
  panel: BMS-PNL-CASINO-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 4
    hli_subpoints: 0
    network_drops: 0
    total: 4
    by_type:
      DI: 4
    by_co:
      Equipment Supplier: 4
  make_model_assumed: UV-light or corona-discharge ozone generator (paired with Casino AHU)
  network_type: Hardwired
  typical_supplier: Equipment supplier
  notes: Casino-specific air-treatment device. BMS monitors status/trip and reads VOC sensor (BMS-supplied).
- id: TEF-1.1 to 1.4 + EF-1.2A/LPG.1/1MR.1/1STO.1/MRF.1
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: GF
  system: General Ventilation
  panel: BMS-PNL-VENT-GF
  primary_co: ME Contractor
  io_summary:
    physical_io: 27
    hli_subpoints: 0
    network_drops: 0
    total: 27
    by_type:
      DI: 27
    by_co:
      ME Contractor: 27
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-2.1/2.3/2B.3 + EF-2B.1/2B.2/GS.1&GS.2 + EF-2.1 to 2.4 + EF-CHRx2
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 2F
  system: General Ventilation
  panel: BMS-PNL-VENT-2F
  primary_co: ME Contractor
  io_summary:
    physical_io: 39
    hli_subpoints: 0
    network_drops: 0
    total: 39
    by_type:
      DI: 39
    by_co:
      ME Contractor: 39
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: TEF-3Ax2/3B/3Cx2/3Dx20 + others
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 3F
  system: General Ventilation
  panel: BMS-PNL-VENT-3F
  primary_co: ME Contractor
  io_summary:
    physical_io: 81
    hli_subpoints: 0
    network_drops: 0
    total: 81
    by_type:
      DI: 81
    by_co:
      ME Contractor: 81
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."