# C1 — Contractor / Owner-Supplied Matrix

**Project:** Kingsford Hotel Bacolod — BMS
**Generated from:** A1-io-list.yaml
**Generator:** `_playbook/tools/generate-c1-co-matrix.py`

This matrix shows, per equipment class, which **BMS-side field devices** are supplied by which party. It is the contractual-scope-boundary view derived from the points list `C/O` column.

Suppliers:
- **BMS Contractor** — we (the proposing party) supply
- **ME Contractor** — Mechanical contractor supplies (typically valves, dampers, motorized actuators)
- **EE Contractor** — Electrical contractor supplies (power metering related — varies by project)
- **Equipment Supplier** — Manufacturer / Equipment vendor supplies (auxiliary contacts on motors/pumps, native equipment data via BACnet/Modbus, VFDs)
- **Owner** — Customer / building owner supplies

---

## Overall Summary

| Supplier | Total BMS I/O Points | Share |
|----------|---------------------:|------:|
| Equipment Supplier | 462 | 61.4% |
| BMS Contractor | 232 | 30.8% |
| ME Contractor | 59 | 7.8% |
| **Total** | **753** | **100%** |

---

## Per-Equipment-Class Breakdown

### Exhaust Fan (Toilet)  ·  53 units, 159 I/O points

**Instances:** TEF-1.1, TEF-1.2, TEF-1.3, TEF-1.4, TEF-2.1, TEF-2.3, TEF-2B.3, TEF-3A.1, TEF-3A.2, TEF-3B, TEF-3C.1, TEF-3C.2, TEF-3D.1, TEF-3D.10, TEF-3D.11, TEF-3D.12, TEF-3D.13, TEF-3D.14, TEF-3D.15, TEF-3D.16, TEF-3D.17, TEF-3D.18, TEF-3D.19, TEF-3D.2, TEF-3D.20, TEF-3D.3, TEF-3D.4, TEF-3D.5, TEF-3D.6, TEF-3D.7, TEF-3D.8, TEF-3D.9, TEF-B.1, TEF-B.10, TEF-B.11, TEF-B.12, TEF-B.13, TEF-B.14, TEF-B.15, TEF-B.16, TEF-B.2, TEF-B.3, TEF-B.4, TEF-B.5, TEF-B.6, TEF-B.7, TEF-B.8, TEF-B.9, TEF-GS.1, TEF-GS.2, TEF-RD.1, TEF-RD.2, TEF-RD.3

| Supplier | I/O Count | Provides |
|----------|----------:|----------|
| Equipment Supplier | 159 | Auxiliary Contact (159×) |

### Precooled Air Handling Unit  ·  7 units, 112 I/O points

**Instances:** PAHU-01, PAHU-02, PAHU-03, PAHU-04, PAHU-05, PAHU-06, PAHU-07

| Supplier | I/O Count | Provides |
|----------|----------:|----------|
| BMS Contractor | 56 | Duct Temp Sensor (21×), Air Flow Station (7×), 0-10V / 4-20 mA (7×), Duct RH Sensor (7×), Diff. Pressure Switch (7×), and 1 more types |
| Equipment Supplier | 42 | Auxiliary Contact (28×), VFD analog output (7×), BACnet/Modbus card (7×) |
| ME Contractor | 14 | Damper Actuator (7×), Electric Valve Actuator (7×) |

### Chiller (Package Water-Cooled)  ·  3 units, 84 I/O points

**Instances:** CH-1, CH-2, CH-3

| Supplier | I/O Count | Provides |
|----------|----------:|----------|
| Equipment Supplier | 57 | — (54×), BACnet/IP (3×) |
| BMS Contractor | 15 | Temperature Sensor (immersion) (12×), Relay output (3×) |
| ME Contractor | 12 | Auxiliary Contact (12×) |

### DOAS Unit  ·  3 units, 78 I/O points

**Instances:** DOAS-2F-CASINO, DOAS-RD1, DOAS-RD2

| Supplier | I/O Count | Provides |
|----------|----------:|----------|
| BMS Contractor | 36 | Duct Temp Sensor (12×), Duct RH Sensor (9×), 0-10V / 4-20 mA (6×), Air Flow Station (3×), Damper Actuator (3×), and 1 more types |
| Equipment Supplier | 36 | Auxiliary Contact (27×), VFD analog output (6×), BACnet/Modbus card (3×) |
| ME Contractor | 6 | Auxiliary Contact (3×), Electric Valve Actuator (3×) |

### AHU (Chilled-Water-Served)  ·  4 units, 64 I/O points

**Instances:** AHU-2F-1, AHU-B1-1, AHU-GF-1, AHU-GFM-1

| Supplier | I/O Count | Provides |
|----------|----------:|----------|
| BMS Contractor | 28 | Duct Temp Sensor (16×), CO2 Sensor (4×), 0-10V / 4-20 mA (4×), Diff. Pressure Switch (4×) |
| Equipment Supplier | 24 | Auxiliary Contact (16×), VFD analog output (4×), BACnet/Modbus card (4×) |
| ME Contractor | 12 | Damper Actuator (8×), Electric Valve Actuator (4×) |

### Steam Boiler  ·  2 units, 42 I/O points

**Instances:** SB-1, SB-2

| Supplier | I/O Count | Provides |
|----------|----------:|----------|
| Equipment Supplier | 26 | — (22×), Equipment Supplier level sensor (4×) |
| BMS Contractor | 16 | Pressure Transmitter (4×), Electric Valve Actuator (2×), Auxiliary Contact (2×), Temperature Sensor (2×), Temperature Sensor (high-temp) (2×), and 2 more types |

### Cooling Tower  ·  3 units, 36 I/O points

**Instances:** CT-1, CT-2, CT-3

| Supplier | I/O Count | Provides |
|----------|----------:|----------|
| BMS Contractor | 21 | Level Electrode (6×), Relay output (3×), 0-10V / 4-20 mA (3×), OA Temperature Sensor (3×), OA Humidity Sensor (3×), and 1 more types |
| Equipment Supplier | 9 | Auxiliary Contact (6×), VFD analog output (3×) |
| ME Contractor | 6 | Auxiliary Contact (6×) |

### AHU (Modulating CHW-served)  ·  2 units, 34 I/O points

**Instances:** AHU-2M.1, AHU-2M.2

| Supplier | I/O Count | Provides |
|----------|----------:|----------|
| BMS Contractor | 16 | Duct Temp Sensor (8×), CO2 Sensor (2×), 0-10V / 4-20 mA (2×), Diff. Pressure Switch (2×), CO Sensor (2×) |
| Equipment Supplier | 12 | Auxiliary Contact (8×), VFD analog output (2×), BACnet/Modbus card (2×) |
| ME Contractor | 6 | Damper Actuator (4×), Electric Valve Actuator (2×) |

### Primary CHW Pump  ·  3 units, 24 I/O points

**Instances:** PCHWP-1, PCHWP-2, PCHWP-3

| Supplier | I/O Count | Provides |
|----------|----------:|----------|
| Equipment Supplier | 18 | Auxiliary Contact (9×), VFD analog output / 4-20 mA (3×), Pressure Transmitter (3×), BACnet/Modbus card (3×) |
| BMS Contractor | 6 | 0-10V / 4-20 mA out (3×), Relay output (3×) |

### Exhaust Fan (General)  ·  8 units, 24 I/O points

**Instances:** EF-1, EF-1.2A, EF-1MR.1, EF-1STO.1, EF-LPG.1, EF-MRF.1, EF-RD.1, EF-RD.2

| Supplier | I/O Count | Provides |
|----------|----------:|----------|
| Equipment Supplier | 24 | Auxiliary Contact (24×) |

### Condenser Water Pump  ·  3 units, 18 I/O points

**Instances:** CWP-1, CWP-2, CWP-3

| Supplier | I/O Count | Provides |
|----------|----------:|----------|
| Equipment Supplier | 15 | Auxiliary Contact (9×), VFD analog output (3×), BACnet/Modbus card (3×) |
| BMS Contractor | 3 | Relay output (3×) |

### Heat Pump  ·  6 units, 18 I/O points

**Instances:** HP-HZ-1, HP-HZ-2, HP-HZ-3, HP-LZ-1, HP-LZ-2, HP-LZ-3

| Supplier | I/O Count | Provides |
|----------|----------:|----------|
| Equipment Supplier | 18 | Auxiliary Contact (18×) |

### Recirculating Pump  ·  6 units, 18 I/O points

**Instances:** RP-HZ-1, RP-HZ-2, RP-HZ-3, RP-LZ-1, RP-LZ-2, RP-LZ-3

| Supplier | I/O Count | Provides |
|----------|----------:|----------|
| Equipment Supplier | 18 | Auxiliary Contact (18×) |

### Multifunction Power Meter (Feeder)  ·  10 units, 10 I/O points

**Instances:** PM-CASINO-FB, PM-CHILLER-1, PM-CHILLER-2, PM-CHILLER-3, PM-ELEVATOR, PM-KITCHEN-2F, PM-LAUNDRY-LG, PM-LIGHTING-GUEST, PM-LOBBY-GF, PM-ROOFDECK-MECH

| Supplier | I/O Count | Provides |
|----------|----------:|----------|
| BMS Contractor | 10 | Modbus RTU/TCP (10×) |

### Calorifier (Hot Water Storage Tank)  ·  6 units, 6 I/O points

**Instances:** HWT-HZ-1, HWT-HZ-2, HWT-HZ-3, HWT-LZ-1, HWT-LZ-2, HWT-LZ-3

| Supplier | I/O Count | Provides |
|----------|----------:|----------|
| BMS Contractor | 6 | Temperature Sensor (6×) |

### CHW Bypass Header  ·  1 unit, 5 I/O points

**Instances:** CHW-BYPASS

| Supplier | I/O Count | Provides |
|----------|----------:|----------|
| BMS Contractor | 4 | Diff. Pressure Sensor (1×), Diff. Temp Sensor (1×), Electric Valve Actuator (1×), Position Feedback (1×) |
| ME Contractor | 1 | Auxiliary Contact (1×) |

### BTU Meter  ·  5 units, 5 I/O points

**Instances:** BTU-1, BTU-2, BTU-3, BTU-4, BTU-5

| Supplier | I/O Count | Provides |
|----------|----------:|----------|
| BMS Contractor | 5 | Modbus RTU/TCP (5×) |

### Cooling Tower (Common)  ·  1 unit, 4 I/O points

**Instances:** CT-COMMON

| Supplier | I/O Count | Provides |
|----------|----------:|----------|
| BMS Contractor | 2 | Temperature Sensor (2×) |
| ME Contractor | 2 | pH Sensor (1×), Conductivity Sensor (1×) |

### Ozone Generator (UV-light or Corona)  ·  2 units, 4 I/O points

**Instances:** ION-2F-1, ION-2F-2

| Supplier | I/O Count | Provides |
|----------|----------:|----------|
| Equipment Supplier | 4 | Auxiliary Contact (4×) |

### Hot Water Header Set  ·  1 unit, 3 I/O points

**Instances:** HW-HEADERS

| Supplier | I/O Count | Provides |
|----------|----------:|----------|
| BMS Contractor | 3 | Temperature Sensor (3×) |

### CHW Supply Main Header  ·  1 unit, 2 I/O points

**Instances:** CHW-HDR-S

| Supplier | I/O Count | Provides |
|----------|----------:|----------|
| BMS Contractor | 2 | Temperature Sensor (1×), Pressure Transmitter (1×) |

### CHW Return Main Header  ·  1 unit, 2 I/O points

**Instances:** CHW-HDR-R

| Supplier | I/O Count | Provides |
|----------|----------:|----------|
| BMS Contractor | 2 | Temperature Sensor (1×), Pressure Transmitter (1×) |

### Multifunction Power Meter (Main)  ·  1 unit, 1 I/O points

**Instances:** PM-MAIN

| Supplier | I/O Count | Provides |
|----------|----------:|----------|
| BMS Contractor | 1 | Modbus RTU/TCP (1×) |

---

## Notes for Proposal Inclusions/Exclusions

- BMS scope = BMS Contractor row(s) above. We supply these field devices, plus the BMS panels, controllers, network, head-end, programming, and T&C.
- Items marked **ME Contractor** or **Equipment Supplier** are **NOT in BMS supply scope** — they're supplied under Mechanical or Equipment contracts. BMS scope includes the *terminations* and *signal cables* to these devices, but not the devices themselves.
- This matrix feeds C3 (Inclusions / Exclusions / Clarifications) — the customer-facing summary of scope boundaries.