# B3 — Commissioning Point Inventory
#
metadata:
  project: "Kingsford Hotel Bacolod \u2014 BMS"
  generated_from: A1-io-list.yaml + A2-equipment-takeoff.yaml
  generator: _playbook/tools/generate-b1-b3-programming-and-commissioning.py
  rates:
    hrs_per_p2p_point: 0.15
    hrs_per_functional_test: 1.5
    hrs_per_integrated_test: 4.0
summary:
  p2p_points: 622
  functional_tests: 132
  integrated_tests: 8
  total_test_items: 762
tc_hours:
  point_to_point: 93.3
  functional_per_equipment: 198.0
  integrated_sequences: 32.0
  total_tc_hours: 323.3
  person_days_at_8hr: 40.4
p2p_breakdown_by_panel:
  BMS-PNL-RD-MECH: 185
  BMS-PNL-2F-CASINO: 84
  BMS-PNL-3F: 75
  BMS-PNL-LG-CHILLER: 72
  BMS-PNL-GF: 63
  BMS-PNL-B1: 63
  BMS-PNL-RD-CT: 40
  BMS-PNL-LG-PLUMB: 40
functional_test_inventory:
- equipment: AHU-2F-1
  equipment_class: AHU (Chilled-Water-Served)
  location: 2nd Floor BOH
- equipment: AHU-2M.1
  equipment_class: AHU (Modulating CHW-served)
  location: 2nd Floor Casino MVAC Room
- equipment: AHU-2M.2
  equipment_class: AHU (Modulating CHW-served)
  location: 2nd Floor Casino MVAC Room
- equipment: AHU-B1-1
  equipment_class: AHU (Chilled-Water-Served)
  location: Basement 1 BOH
- equipment: AHU-GF-1
  equipment_class: AHU (Chilled-Water-Served)
  location: Ground Floor BOH
- equipment: AHU-GFM-1
  equipment_class: AHU (Chilled-Water-Served)
  location: Ground Floor Mezzanine BOH
- equipment: BTU-1
  equipment_class: BTU Meter
  location: 2nd Level Mechanical Room
- equipment: BTU-2
  equipment_class: BTU Meter
  location: 2nd Level Mechanical Room
- equipment: BTU-3
  equipment_class: BTU Meter
  location: 2nd Level Mechanical Room
- equipment: BTU-4
  equipment_class: BTU Meter
  location: 2nd Level Mechanical Room
- equipment: BTU-5
  equipment_class: BTU Meter
  location: 2nd Level Mechanical Room
- equipment: CH-1
  equipment_class: Chiller (Package Water-Cooled)
  location: 2nd Level Mechanical Room
- equipment: CH-2
  equipment_class: Chiller (Package Water-Cooled)
  location: 2nd Level Mechanical Room
- equipment: CH-3
  equipment_class: Chiller (Package Water-Cooled)
  location: 2nd Level Mechanical Room
- equipment: CHW-BYPASS
  equipment_class: CHW Bypass Header
  location: 2nd Level Mechanical Room
- equipment: CHW-HDR-R
  equipment_class: CHW Return Main Header
  location: 2nd Level Mechanical Room
- equipment: CHW-HDR-S
  equipment_class: CHW Supply Main Header
  location: 2nd Level Mechanical Room
- equipment: CT-1
  equipment_class: Cooling Tower
  location: Roof Deck Mechanical
- equipment: CT-2
  equipment_class: Cooling Tower
  location: Roof Deck Mechanical
- equipment: CT-3
  equipment_class: Cooling Tower
  location: Roof Deck Mechanical
- equipment: CT-COMMON
  equipment_class: Cooling Tower (Common)
  location: Roof Deck Mechanical
- equipment: CWP-1
  equipment_class: Condenser Water Pump
  location: 2nd Level Mechanical Room
- equipment: CWP-2
  equipment_class: Condenser Water Pump
  location: 2nd Level Mechanical Room
- equipment: CWP-3
  equipment_class: Condenser Water Pump
  location: 2nd Level Mechanical Room
- equipment: DOAS-2F-CASINO
  equipment_class: DOAS Unit
  location: 2nd Floor Casino MVAC Room
- equipment: DOAS-RD1
  equipment_class: DOAS Unit
  location: Roof Deck Mechanical
- equipment: DOAS-RD2
  equipment_class: DOAS Unit
  location: Roof Deck Mechanical
- equipment: EF-1
  equipment_class: Exhaust Fan (General)
  location: Roof Deck
- equipment: EF-1.2A
  equipment_class: Exhaust Fan (General)
  location: Ground Floor Lobby
- equipment: EF-1MR.1
  equipment_class: Exhaust Fan (General)
  location: Ground Floor Lobby
- equipment: EF-1STO.1
  equipment_class: Exhaust Fan (General)
  location: Ground Floor Lobby
- equipment: EF-LPG.1
  equipment_class: Exhaust Fan (General)
  location: Ground Floor Lobby
- equipment: EF-MRF.1
  equipment_class: Exhaust Fan (General)
  location: Ground Floor Lobby
- equipment: EF-RD.1
  equipment_class: Exhaust Fan (General)
  location: Roof Deck
- equipment: EF-RD.2
  equipment_class: Exhaust Fan (General)
  location: Roof Deck
- equipment: HP-HZ-1
  equipment_class: Heat Pump
  location: Roof Deck HW Plant
- equipment: HP-HZ-2
  equipment_class: Heat Pump
  location: Roof Deck HW Plant
- equipment: HP-HZ-3
  equipment_class: Heat Pump
  location: Roof Deck HW Plant
- equipment: HP-LZ-1
  equipment_class: Heat Pump
  location: Lower Ground HW Plant
- equipment: HP-LZ-2
  equipment_class: Heat Pump
  location: Lower Ground HW Plant
- equipment: HP-LZ-3
  equipment_class: Heat Pump
  location: Lower Ground HW Plant
- equipment: HW-HEADERS
  equipment_class: Hot Water Header Set
  location: Lower Ground HW Plant
- equipment: HWT-HZ-1
  equipment_class: Calorifier (Hot Water Storage Tank)
  location: Roof Deck HW Plant
- equipment: HWT-HZ-2
  equipment_class: Calorifier (Hot Water Storage Tank)
  location: Roof Deck HW Plant
- equipment: HWT-HZ-3
  equipment_class: Calorifier (Hot Water Storage Tank)
  location: Roof Deck HW Plant
- equipment: HWT-LZ-1
  equipment_class: Calorifier (Hot Water Storage Tank)
  location: Lower Ground HW Plant
- equipment: HWT-LZ-2
  equipment_class: Calorifier (Hot Water Storage Tank)
  location: Lower Ground HW Plant
- equipment: HWT-LZ-3
  equipment_class: Calorifier (Hot Water Storage Tank)
  location: Lower Ground HW Plant
- equipment: ION-2F-1
  equipment_class: Ozone Generator (UV-light or Corona)
  location: 2nd Floor Casino
- equipment: ION-2F-2
  equipment_class: Ozone Generator (UV-light or Corona)
  location: 2nd Floor Casino
- equipment: PAHU-01
  equipment_class: Precooled Air Handling Unit
  location: Roof Deck Mechanical
- equipment: PAHU-02
  equipment_class: Precooled Air Handling Unit
  location: Roof Deck Mechanical
- equipment: PAHU-03
  equipment_class: Precooled Air Handling Unit
  location: Roof Deck Mechanical
- equipment: PAHU-04
  equipment_class: Precooled Air Handling Unit
  location: Roof Deck Mechanical
- equipment: PAHU-05
  equipment_class: Precooled Air Handling Unit
  location: Roof Deck Mechanical
- equipment: PAHU-06
  equipment_class: Precooled Air Handling Unit
  location: Roof Deck Mechanical
- equipment: PAHU-07
  equipment_class: Precooled Air Handling Unit
  location: Roof Deck Mechanical
- equipment: PCHWP-1
  equipment_class: Primary CHW Pump
  location: 2nd Level Mechanical Room
- equipment: PCHWP-2
  equipment_class: Primary CHW Pump
  location: 2nd Level Mechanical Room
- equipment: PCHWP-3
  equipment_class: Primary CHW Pump
  location: 2nd Level Mechanical Room
- equipment: PM-CASINO-FB
  equipment_class: Multifunction Power Meter (Feeder)
  location: 2nd Floor Casino
- equipment: PM-CHILLER-1
  equipment_class: Multifunction Power Meter (Feeder)
  location: 2nd Level Mechanical Room
- equipment: PM-CHILLER-2
  equipment_class: Multifunction Power Meter (Feeder)
  location: 2nd Level Mechanical Room
- equipment: PM-CHILLER-3
  equipment_class: Multifunction Power Meter (Feeder)
  location: 2nd Level Mechanical Room
- equipment: PM-ELEVATOR
  equipment_class: Multifunction Power Meter (Feeder)
  location: Ground Floor
- equipment: PM-KITCHEN-2F
  equipment_class: Multifunction Power Meter (Feeder)
  location: 2nd Floor BOH
- equipment: PM-LAUNDRY-LG
  equipment_class: Multifunction Power Meter (Feeder)
  location: Lower Ground Laundry
- equipment: PM-LIGHTING-GUEST
  equipment_class: Multifunction Power Meter (Feeder)
  location: 3rd Floor Amenity
- equipment: PM-LOBBY-GF
  equipment_class: Multifunction Power Meter (Feeder)
  location: Ground Floor
- equipment: PM-MAIN
  equipment_class: Multifunction Power Meter (Main)
  location: Main Switchgear Room
- equipment: PM-ROOFDECK-MECH
  equipment_class: Multifunction Power Meter (Feeder)
  location: Roof Deck Mechanical
- equipment: RP-HZ-1
  equipment_class: Recirculating Pump
  location: Roof Deck HW Plant
- equipment: RP-HZ-2
  equipment_class: Recirculating Pump
  location: Roof Deck HW Plant
- equipment: RP-HZ-3
  equipment_class: Recirculating Pump
  location: Roof Deck HW Plant
- equipment: RP-LZ-1
  equipment_class: Recirculating Pump
  location: Lower Ground HW Plant
- equipment: RP-LZ-2
  equipment_class: Recirculating Pump
  location: Lower Ground HW Plant
- equipment: RP-LZ-3
  equipment_class: Recirculating Pump
  location: Lower Ground HW Plant
- equipment: SB-1
  equipment_class: Steam Boiler
  location: Lower Ground Laundry
- equipment: SB-2
  equipment_class: Steam Boiler
  location: Lower Ground Laundry
- equipment: TEF-1.1
  equipment_class: Exhaust Fan (Toilet)
  location: Ground Floor Lobby
- equipment: TEF-1.2
  equipment_class: Exhaust Fan (Toilet)
  location: Ground Floor Lobby
- equipment: TEF-1.3
  equipment_class: Exhaust Fan (Toilet)
  location: Ground Floor Lobby
- equipment: TEF-1.4
  equipment_class: Exhaust Fan (Toilet)
  location: Ground Floor Lobby
- equipment: TEF-2.1
  equipment_class: Exhaust Fan (Toilet)
  location: 2nd Floor BOH
- equipment: TEF-2.3
  equipment_class: Exhaust Fan (Toilet)
  location: 2nd Floor BOH
- equipment: TEF-2B.3
  equipment_class: Exhaust Fan (Toilet)
  location: 2nd Floor BOH
- equipment: TEF-3A.1
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Amenity
- equipment: TEF-3A.2
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Amenity
- equipment: TEF-3B
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Amenity
- equipment: TEF-3C.1
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Amenity
- equipment: TEF-3C.2
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Amenity
- equipment: TEF-3D.1
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Amenity
- equipment: TEF-3D.10
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Amenity
- equipment: TEF-3D.11
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Amenity
- equipment: TEF-3D.12
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Amenity
- equipment: TEF-3D.13
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Amenity
- equipment: TEF-3D.14
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Amenity
- equipment: TEF-3D.15
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Amenity
- equipment: TEF-3D.16
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Amenity
- equipment: TEF-3D.17
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Amenity
- equipment: TEF-3D.18
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Amenity
- equipment: TEF-3D.19
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Amenity
- equipment: TEF-3D.2
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Amenity
- equipment: TEF-3D.20
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Amenity
- equipment: TEF-3D.3
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Amenity
- equipment: TEF-3D.4
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Amenity
- equipment: TEF-3D.5
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Amenity
- equipment: TEF-3D.6
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Amenity
- equipment: TEF-3D.7
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Amenity
- equipment: TEF-3D.8
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Amenity
- equipment: TEF-3D.9
  equipment_class: Exhaust Fan (Toilet)
  location: 3rd Floor Amenity
- equipment: TEF-B.1
  equipment_class: Exhaust Fan (Toilet)
  location: Basement 1
- equipment: TEF-B.10
  equipment_class: Exhaust Fan (Toilet)
  location: Basement 1
- equipment: TEF-B.11
  equipment_class: Exhaust Fan (Toilet)
  location: Basement 1
- equipment: TEF-B.12
  equipment_class: Exhaust Fan (Toilet)
  location: Basement 1
- equipment: TEF-B.13
  equipment_class: Exhaust Fan (Toilet)
  location: Basement 1
- equipment: TEF-B.14
  equipment_class: Exhaust Fan (Toilet)
  location: Basement 1
- equipment: TEF-B.15
  equipment_class: Exhaust Fan (Toilet)
  location: Basement 1
- equipment: TEF-B.16
  equipment_class: Exhaust Fan (Toilet)
  location: Basement 1
- equipment: TEF-B.2
  equipment_class: Exhaust Fan (Toilet)
  location: Basement 1
- equipment: TEF-B.3
  equipment_class: Exhaust Fan (Toilet)
  location: Basement 1
- equipment: TEF-B.4
  equipment_class: Exhaust Fan (Toilet)
  location: Basement 1
- equipment: TEF-B.5
  equipment_class: Exhaust Fan (Toilet)
  location: Basement 1
- equipment: TEF-B.6
  equipment_class: Exhaust Fan (Toilet)
  location: Basement 1
- equipment: TEF-B.7
  equipment_class: Exhaust Fan (Toilet)
  location: Basement 1
- equipment: TEF-B.8
  equipment_class: Exhaust Fan (Toilet)
  location: Basement 1
- equipment: TEF-B.9
  equipment_class: Exhaust Fan (Toilet)
  location: Basement 1
- equipment: TEF-GS.1
  equipment_class: Exhaust Fan (Toilet)
  location: Ground Floor
- equipment: TEF-GS.2
  equipment_class: Exhaust Fan (Toilet)
  location: Ground Floor
- equipment: TEF-RD.1
  equipment_class: Exhaust Fan (Toilet)
  location: Roof Deck
- equipment: TEF-RD.2
  equipment_class: Exhaust Fan (Toilet)
  location: Roof Deck
- equipment: TEF-RD.3
  equipment_class: Exhaust Fan (Toilet)
  location: Roof Deck
integrated_test_inventory:
- Chiller plant sequencing (chiller staging + CHW pump + COW pump + cooling tower fan)
- CHW differential pressure control (PCHWP VFD speed via header dP)
- AHU supply-air temperature control (modulating CHW valve loop)
- DOAS demand-controlled ventilation (CO2-based fresh air modulation)
- Hotwater system sequencing (heat pump + recirculating pump + tank temp)
- Boiler firing rate vs. steam pressure
- Cooling tower fan staging vs. condenser water temperature
- Energy savings algorithm verification (max-demand limiting + load shedding)
notes:
- 'P2P = point-to-point verification: every physical I/O calibrated, range-checked, polarity verified, scaled correctly.'
- 'Functional test: per-equipment sequence verification (e.g., does the AHU CHW valve modulate correctly to maintain supply air temp?).'
- 'Integrated test: cross-system sequence (e.g., chiller staging triggers correctly when load increases).'
- "Owner T&C / SAT: separate from this \u2014 handled in proposal as an item under 5.5 in WBS."