# A3 — Cable Schedule
# Generated from A1-io-list.yaml; lengths per A-001
#
metadata:
  project: "Kingsford Hotel Bacolod \u2014 BMS"
  generated_from: A1-io-list.yaml
  generator: _playbook/tools/generate-a3-cable-schedule.py
  assumptions:
  - 'A-001: 30 m average panel-to-device run; 80 m trunk per floor'
  - Cable conductor count = (points + 2 spare), rounded up to standard 4/6/8/12 sizes
  - Cat6 for all BACnet/IP network drops
  - BACnet MS/TP backbone interconnects all BMS panels (refine after Q-008)
  - 240V single-phase power feed to each BMS panel @ 30 m default length
summary:
  total_field_cable_runs: 194
  total_field_cable_length_m: 3409
  total_trunk_cable_length_m: 1480
  total_power_feed_length_m: 144
  grand_total_cable_length_m: 5033
  field_cable_by_type_m:
    "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)": 3409
  field_cable_by_panel_m:
    BMS-PNL-2F-CASINO: 20
    BMS-PNL-B1: 19
    BMS-PNL-GF: 20
    BMS-PNL-LG-CHILLER: 33
    BMS-PNL-RD-CT: 11
    BMS-PNL-RD-MECH: 52
    BMS-PNL-LG-PLUMB: 13
    BMS-PNL-3F: 26
field_cables:
- id: C0001
  from: BMS-PNL-2F-CASINO
  to: AHU-2F-1 (BMS Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: common_area
  location: 2nd Floor BOH
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 5
    AO: 1
    DI: 1
  conductor_count_required: 8
  conductor_count_specified: 8
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 7
  carries_point_ids:
  - P0439
  - P0440
  - P0441
  - P0442
  - P0446
  - '...'
  notes: 7 I/O points carried, 8C cable; length 22 m (typical_range:boh_same_floor)
- id: C0002
  from: BMS-PNL-2F-CASINO
  to: AHU-2F-1 (Equipment Supplier)
  equipment_class: AHU (Chilled-Water-Served)
  system: common_area
  location: 2nd Floor BOH
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 4
    AI: 1
  conductor_count_required: 6
  conductor_count_specified: 6
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 5
  carries_point_ids:
  - P0437
  - P0444
  - P0445
  - P0447
  - P0448
  notes: 5 I/O points carried, 6C cable; length 22 m (typical_range:boh_same_floor)
- id: C0003
  from: BMS-PNL-2F-CASINO
  to: AHU-2F-1 (ME Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: common_area
  location: 2nd Floor BOH
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AO: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0438
  - P0443
  - P0449
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0004
  from: BMS-PNL-2F-CASINO
  to: AHU-2M.1 (BMS Contractor)
  equipment_class: AHU (Modulating CHW-served)
  system: casino_mvac
  location: 2nd Floor Casino MVAC Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 6
    AO: 1
    DI: 1
  conductor_count_required: 9
  conductor_count_specified: 12
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 8
  carries_point_ids:
  - P0373
  - P0374
  - P0375
  - P0376
  - P0380
  - '...'
  notes: 8 I/O points carried, 12C cable; length 22 m (typical_range:boh_same_floor)
- id: C0005
  from: BMS-PNL-2F-CASINO
  to: AHU-2M.1 (Equipment Supplier)
  equipment_class: AHU (Modulating CHW-served)
  system: casino_mvac
  location: 2nd Floor Casino MVAC Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 4
    AI: 1
  conductor_count_required: 6
  conductor_count_specified: 6
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 5
  carries_point_ids:
  - P0371
  - P0378
  - P0379
  - P0381
  - P0382
  notes: 5 I/O points carried, 6C cable; length 22 m (typical_range:boh_same_floor)
- id: C0006
  from: BMS-PNL-2F-CASINO
  to: AHU-2M.1 (ME Contractor)
  equipment_class: AHU (Modulating CHW-served)
  system: casino_mvac
  location: 2nd Floor Casino MVAC Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AO: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0372
  - P0377
  - P0383
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0007
  from: BMS-PNL-2F-CASINO
  to: AHU-2M.2 (BMS Contractor)
  equipment_class: AHU (Modulating CHW-served)
  system: casino_mvac
  location: 2nd Floor Casino MVAC Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 6
    AO: 1
    DI: 1
  conductor_count_required: 9
  conductor_count_specified: 12
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 8
  carries_point_ids:
  - P0390
  - P0391
  - P0392
  - P0393
  - P0397
  - '...'
  notes: 8 I/O points carried, 12C cable; length 22 m (typical_range:boh_same_floor)
- id: C0008
  from: BMS-PNL-2F-CASINO
  to: AHU-2M.2 (Equipment Supplier)
  equipment_class: AHU (Modulating CHW-served)
  system: casino_mvac
  location: 2nd Floor Casino MVAC Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 4
    AI: 1
  conductor_count_required: 6
  conductor_count_specified: 6
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 5
  carries_point_ids:
  - P0388
  - P0395
  - P0396
  - P0398
  - P0399
  notes: 5 I/O points carried, 6C cable; length 22 m (typical_range:boh_same_floor)
- id: C0009
  from: BMS-PNL-2F-CASINO
  to: AHU-2M.2 (ME Contractor)
  equipment_class: AHU (Modulating CHW-served)
  system: casino_mvac
  location: 2nd Floor Casino MVAC Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AO: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0389
  - P0394
  - P0400
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0010
  from: BMS-PNL-B1
  to: AHU-B1-1 (BMS Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: common_area
  location: Basement 1 BOH
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 5
    AO: 1
    DI: 1
  conductor_count_required: 8
  conductor_count_specified: 8
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 7
  carries_point_ids:
  - P0455
  - P0456
  - P0457
  - P0458
  - P0462
  - '...'
  notes: 7 I/O points carried, 8C cable; length 22 m (typical_range:boh_same_floor)
- id: C0011
  from: BMS-PNL-B1
  to: AHU-B1-1 (Equipment Supplier)
  equipment_class: AHU (Chilled-Water-Served)
  system: common_area
  location: Basement 1 BOH
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 4
    AI: 1
  conductor_count_required: 6
  conductor_count_specified: 6
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 5
  carries_point_ids:
  - P0453
  - P0460
  - P0461
  - P0463
  - P0464
  notes: 5 I/O points carried, 6C cable; length 22 m (typical_range:boh_same_floor)
- id: C0012
  from: BMS-PNL-B1
  to: AHU-B1-1 (ME Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: common_area
  location: Basement 1 BOH
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AO: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0454
  - P0459
  - P0465
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0013
  from: BMS-PNL-GF
  to: AHU-GF-1 (BMS Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: common_area
  location: Ground Floor BOH
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 5
    AO: 1
    DI: 1
  conductor_count_required: 8
  conductor_count_specified: 8
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 7
  carries_point_ids:
  - P0407
  - P0408
  - P0409
  - P0410
  - P0414
  - '...'
  notes: 7 I/O points carried, 8C cable; length 22 m (typical_range:boh_same_floor)
- id: C0014
  from: BMS-PNL-GF
  to: AHU-GF-1 (Equipment Supplier)
  equipment_class: AHU (Chilled-Water-Served)
  system: common_area
  location: Ground Floor BOH
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 4
    AI: 1
  conductor_count_required: 6
  conductor_count_specified: 6
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 5
  carries_point_ids:
  - P0405
  - P0412
  - P0413
  - P0415
  - P0416
  notes: 5 I/O points carried, 6C cable; length 22 m (typical_range:boh_same_floor)
- id: C0015
  from: BMS-PNL-GF
  to: AHU-GF-1 (ME Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: common_area
  location: Ground Floor BOH
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AO: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0406
  - P0411
  - P0417
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0016
  from: BMS-PNL-GF
  to: AHU-GFM-1 (BMS Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: common_area
  location: Ground Floor Mezzanine BOH
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 5
    AO: 1
    DI: 1
  conductor_count_required: 8
  conductor_count_specified: 8
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 7
  carries_point_ids:
  - P0423
  - P0424
  - P0425
  - P0426
  - P0430
  - '...'
  notes: 7 I/O points carried, 8C cable; length 22 m (typical_range:boh_same_floor)
- id: C0017
  from: BMS-PNL-GF
  to: AHU-GFM-1 (Equipment Supplier)
  equipment_class: AHU (Chilled-Water-Served)
  system: common_area
  location: Ground Floor Mezzanine BOH
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 4
    AI: 1
  conductor_count_required: 6
  conductor_count_specified: 6
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 5
  carries_point_ids:
  - P0421
  - P0428
  - P0429
  - P0431
  - P0432
  notes: 5 I/O points carried, 6C cable; length 22 m (typical_range:boh_same_floor)
- id: C0018
  from: BMS-PNL-GF
  to: AHU-GFM-1 (ME Contractor)
  equipment_class: AHU (Chilled-Water-Served)
  system: common_area
  location: Ground Floor Mezzanine BOH
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AO: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0422
  - P0427
  - P0433
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0019
  from: BMS-PNL-LG-CHILLER
  to: CH-1 (BMS Contractor)
  equipment_class: Chiller (Package Water-Cooled)
  system: chilled_water
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 4
    DO: 1
  conductor_count_required: 6
  conductor_count_specified: 6
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 5
  carries_point_ids:
  - P0019
  - P0020
  - P0021
  - P0022
  - P0028
  notes: 5 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0020
  from: BMS-PNL-LG-CHILLER
  to: CH-1 (ME Contractor)
  equipment_class: Chiller (Package Water-Cooled)
  system: chilled_water
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 4
  conductor_count_required: 5
  conductor_count_specified: 6
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 4
  carries_point_ids:
  - P0024
  - P0025
  - P0026
  - P0027
  notes: 4 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0021
  from: BMS-PNL-LG-CHILLER
  to: CH-2 (BMS Contractor)
  equipment_class: Chiller (Package Water-Cooled)
  system: chilled_water
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 4
    DO: 1
  conductor_count_required: 6
  conductor_count_specified: 6
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 5
  carries_point_ids:
  - P0061
  - P0062
  - P0063
  - P0064
  - P0070
  notes: 5 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0022
  from: BMS-PNL-LG-CHILLER
  to: CH-2 (ME Contractor)
  equipment_class: Chiller (Package Water-Cooled)
  system: chilled_water
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 4
  conductor_count_required: 5
  conductor_count_specified: 6
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 4
  carries_point_ids:
  - P0066
  - P0067
  - P0068
  - P0069
  notes: 4 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0023
  from: BMS-PNL-LG-CHILLER
  to: CH-3 (BMS Contractor)
  equipment_class: Chiller (Package Water-Cooled)
  system: chilled_water
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 4
    DO: 1
  conductor_count_required: 6
  conductor_count_specified: 6
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 5
  carries_point_ids:
  - P0103
  - P0104
  - P0105
  - P0106
  - P0112
  notes: 5 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0024
  from: BMS-PNL-LG-CHILLER
  to: CH-3 (ME Contractor)
  equipment_class: Chiller (Package Water-Cooled)
  system: chilled_water
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 4
  conductor_count_required: 5
  conductor_count_specified: 6
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 4
  carries_point_ids:
  - P0108
  - P0109
  - P0110
  - P0111
  notes: 4 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0025
  from: BMS-PNL-LG-CHILLER
  to: CHW-BYPASS (BMS Contractor)
  equipment_class: CHW Bypass Header
  system: chilled_water
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 3
    AO: 1
  conductor_count_required: 4
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 4
  carries_point_ids:
  - P0131
  - P0132
  - P0133
  - P0134
  notes: 4 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0026
  from: BMS-PNL-LG-CHILLER
  to: CHW-BYPASS (ME Contractor)
  equipment_class: CHW Bypass Header
  system: chilled_water
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 1
  conductor_count_required: 1
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0135
  notes: 1 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0027
  from: BMS-PNL-LG-CHILLER
  to: CHW-HDR-R (BMS Contractor)
  equipment_class: CHW Return Main Header
  system: chilled_water
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 2
  conductor_count_required: 2
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 2
  carries_point_ids:
  - P0129
  - P0130
  notes: 2 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0028
  from: BMS-PNL-LG-CHILLER
  to: CHW-HDR-S (BMS Contractor)
  equipment_class: CHW Supply Main Header
  system: chilled_water
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 2
  conductor_count_required: 2
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 2
  carries_point_ids:
  - P0127
  - P0128
  notes: 2 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0029
  from: BMS-PNL-RD-CT
  to: CT-1 (BMS Contractor)
  equipment_class: Cooling Tower
  system: condenser_water
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DO: 2
    AO: 1
    DI: 2
    AI: 2
  conductor_count_required: 7
  conductor_count_specified: 8
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 7
  carries_point_ids:
  - P0138
  - P0139
  - P0141
  - P0142
  - P0143
  - '...'
  notes: 7 I/O points carried, 8C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0030
  from: BMS-PNL-RD-CT
  to: CT-1 (Equipment Supplier)
  equipment_class: Cooling Tower
  system: condenser_water
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 2
    AI: 1
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0136
  - P0137
  - P0140
  notes: 3 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0031
  from: BMS-PNL-RD-CT
  to: CT-1 (ME Contractor)
  equipment_class: Cooling Tower
  system: condenser_water
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 2
  conductor_count_required: 2
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 2
  carries_point_ids:
  - P0145
  - P0146
  notes: 2 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0032
  from: BMS-PNL-RD-CT
  to: CT-2 (BMS Contractor)
  equipment_class: Cooling Tower
  system: condenser_water
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DO: 2
    AO: 1
    DI: 2
    AI: 2
  conductor_count_required: 7
  conductor_count_specified: 8
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 7
  carries_point_ids:
  - P0150
  - P0151
  - P0153
  - P0154
  - P0155
  - '...'
  notes: 7 I/O points carried, 8C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0033
  from: BMS-PNL-RD-CT
  to: CT-2 (Equipment Supplier)
  equipment_class: Cooling Tower
  system: condenser_water
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 2
    AI: 1
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0148
  - P0149
  - P0152
  notes: 3 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0034
  from: BMS-PNL-RD-CT
  to: CT-2 (ME Contractor)
  equipment_class: Cooling Tower
  system: condenser_water
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 2
  conductor_count_required: 2
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 2
  carries_point_ids:
  - P0157
  - P0158
  notes: 2 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0035
  from: BMS-PNL-RD-CT
  to: CT-3 (BMS Contractor)
  equipment_class: Cooling Tower
  system: condenser_water
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DO: 2
    AO: 1
    DI: 2
    AI: 2
  conductor_count_required: 7
  conductor_count_specified: 8
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 7
  carries_point_ids:
  - P0162
  - P0163
  - P0165
  - P0166
  - P0167
  - '...'
  notes: 7 I/O points carried, 8C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0036
  from: BMS-PNL-RD-CT
  to: CT-3 (Equipment Supplier)
  equipment_class: Cooling Tower
  system: condenser_water
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 2
    AI: 1
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0160
  - P0161
  - P0164
  notes: 3 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0037
  from: BMS-PNL-RD-CT
  to: CT-3 (ME Contractor)
  equipment_class: Cooling Tower
  system: condenser_water
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 2
  conductor_count_required: 2
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 2
  carries_point_ids:
  - P0169
  - P0170
  notes: 2 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0038
  from: BMS-PNL-RD-CT
  to: CT-COMMON (BMS Contractor)
  equipment_class: Cooling Tower (Common)
  system: condenser_water
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 2
  conductor_count_required: 2
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 2
  carries_point_ids:
  - P0172
  - P0173
  notes: 2 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0039
  from: BMS-PNL-RD-CT
  to: CT-COMMON (ME Contractor)
  equipment_class: Cooling Tower (Common)
  system: condenser_water
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 2
  conductor_count_required: 2
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 2
  carries_point_ids:
  - P0174
  - P0175
  notes: 2 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0040
  from: BMS-PNL-LG-CHILLER
  to: CWP-1 (BMS Contractor)
  equipment_class: Condenser Water Pump
  system: chilled_water
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DO: 1
  conductor_count_required: 1
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0040
  notes: 1 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0041
  from: BMS-PNL-LG-CHILLER
  to: CWP-1 (Equipment Supplier)
  equipment_class: Condenser Water Pump
  system: chilled_water
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
    AI: 1
  conductor_count_required: 4
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 4
  carries_point_ids:
  - P0037
  - P0038
  - P0039
  - P0041
  notes: 4 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0042
  from: BMS-PNL-LG-CHILLER
  to: CWP-2 (BMS Contractor)
  equipment_class: Condenser Water Pump
  system: chilled_water
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DO: 1
  conductor_count_required: 1
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0082
  notes: 1 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0043
  from: BMS-PNL-LG-CHILLER
  to: CWP-2 (Equipment Supplier)
  equipment_class: Condenser Water Pump
  system: chilled_water
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
    AI: 1
  conductor_count_required: 4
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 4
  carries_point_ids:
  - P0079
  - P0080
  - P0081
  - P0083
  notes: 4 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0044
  from: BMS-PNL-LG-CHILLER
  to: CWP-3 (BMS Contractor)
  equipment_class: Condenser Water Pump
  system: chilled_water
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DO: 1
  conductor_count_required: 1
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0124
  notes: 1 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0045
  from: BMS-PNL-LG-CHILLER
  to: CWP-3 (Equipment Supplier)
  equipment_class: Condenser Water Pump
  system: chilled_water
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
    AI: 1
  conductor_count_required: 4
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 4
  carries_point_ids:
  - P0121
  - P0122
  - P0123
  - P0125
  notes: 4 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0046
  from: BMS-PNL-2F-CASINO
  to: DOAS-2F-CASINO (BMS Contractor)
  equipment_class: DOAS Unit
  system: ventilation
  location: 2nd Floor Casino MVAC Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 8
    AO: 3
  conductor_count_required: 12
  conductor_count_specified: 12
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 11
  carries_point_ids:
  - P0233
  - P0234
  - P0235
  - P0237
  - P0244
  - '...'
  notes: 11 I/O points carried, 12C cable; length 22 m (typical_range:boh_same_floor)
- id: C0047
  from: BMS-PNL-2F-CASINO
  to: DOAS-2F-CASINO (Equipment Supplier)
  equipment_class: DOAS Unit
  system: ventilation
  location: 2nd Floor Casino MVAC Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 9
    AI: 2
  conductor_count_required: 12
  conductor_count_specified: 12
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 11
  carries_point_ids:
  - P0236
  - P0238
  - P0239
  - P0240
  - P0241
  - '...'
  notes: 11 I/O points carried, 12C cable; length 22 m (typical_range:boh_same_floor)
- id: C0048
  from: BMS-PNL-2F-CASINO
  to: DOAS-2F-CASINO (ME Contractor)
  equipment_class: DOAS Unit
  system: ventilation
  location: 2nd Floor Casino MVAC Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 1
    AO: 1
  conductor_count_required: 2
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 2
  carries_point_ids:
  - P0247
  - P0248
  notes: 2 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0049
  from: BMS-PNL-RD-MECH
  to: DOAS-RD1 (BMS Contractor)
  equipment_class: DOAS Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 8
    AO: 3
  conductor_count_required: 12
  conductor_count_specified: 12
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 11
  carries_point_ids:
  - P0181
  - P0182
  - P0183
  - P0185
  - P0192
  - '...'
  notes: 11 I/O points carried, 12C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0050
  from: BMS-PNL-RD-MECH
  to: DOAS-RD1 (Equipment Supplier)
  equipment_class: DOAS Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 9
    AI: 2
  conductor_count_required: 12
  conductor_count_specified: 12
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 11
  carries_point_ids:
  - P0184
  - P0186
  - P0187
  - P0188
  - P0189
  - '...'
  notes: 11 I/O points carried, 12C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0051
  from: BMS-PNL-RD-MECH
  to: DOAS-RD1 (ME Contractor)
  equipment_class: DOAS Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 1
    AO: 1
  conductor_count_required: 2
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 2
  carries_point_ids:
  - P0195
  - P0196
  notes: 2 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0052
  from: BMS-PNL-RD-MECH
  to: DOAS-RD2 (BMS Contractor)
  equipment_class: DOAS Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 8
    AO: 3
  conductor_count_required: 12
  conductor_count_specified: 12
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 11
  carries_point_ids:
  - P0207
  - P0208
  - P0209
  - P0211
  - P0218
  - '...'
  notes: 11 I/O points carried, 12C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0053
  from: BMS-PNL-RD-MECH
  to: DOAS-RD2 (Equipment Supplier)
  equipment_class: DOAS Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 9
    AI: 2
  conductor_count_required: 12
  conductor_count_specified: 12
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 11
  carries_point_ids:
  - P0210
  - P0212
  - P0213
  - P0214
  - P0215
  - '...'
  notes: 11 I/O points carried, 12C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0054
  from: BMS-PNL-RD-MECH
  to: DOAS-RD2 (ME Contractor)
  equipment_class: DOAS Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 1
    AO: 1
  conductor_count_required: 2
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 2
  carries_point_ids:
  - P0221
  - P0222
  notes: 2 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0055
  from: BMS-PNL-RD-MECH
  to: EF-1 (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: ventilation
  location: Roof Deck
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0653
  - P0654
  - P0655
  notes: 3 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0056
  from: BMS-PNL-GF
  to: EF-1.2A (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: ventilation
  location: Ground Floor Lobby
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0632
  - P0633
  - P0634
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0057
  from: BMS-PNL-GF
  to: EF-1MR.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: ventilation
  location: Ground Floor Lobby
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0638
  - P0639
  - P0640
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0058
  from: BMS-PNL-GF
  to: EF-1STO.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: ventilation
  location: Ground Floor Lobby
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0641
  - P0642
  - P0643
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0059
  from: BMS-PNL-GF
  to: EF-LPG.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: ventilation
  location: Ground Floor Lobby
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0635
  - P0636
  - P0637
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0060
  from: BMS-PNL-GF
  to: EF-MRF.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: ventilation
  location: Ground Floor Lobby
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0644
  - P0645
  - P0646
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0061
  from: BMS-PNL-RD-MECH
  to: EF-RD.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: ventilation
  location: Roof Deck
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0647
  - P0648
  - P0649
  notes: 3 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0062
  from: BMS-PNL-RD-MECH
  to: EF-RD.2 (Equipment Supplier)
  equipment_class: Exhaust Fan (General)
  system: ventilation
  location: Roof Deck
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0650
  - P0651
  - P0652
  notes: 3 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0063
  from: BMS-PNL-RD-MECH
  to: HP-HZ-1 (Equipment Supplier)
  equipment_class: Heat Pump
  system: hot_water
  location: Roof Deck HW Plant
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0678
  - P0679
  - P0680
  notes: 3 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0064
  from: BMS-PNL-RD-MECH
  to: HP-HZ-2 (Equipment Supplier)
  equipment_class: Heat Pump
  system: hot_water
  location: Roof Deck HW Plant
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0685
  - P0686
  - P0687
  notes: 3 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0065
  from: BMS-PNL-RD-MECH
  to: HP-HZ-3 (Equipment Supplier)
  equipment_class: Heat Pump
  system: hot_water
  location: Roof Deck HW Plant
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0692
  - P0693
  - P0694
  notes: 3 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0066
  from: BMS-PNL-LG-PLUMB
  to: HP-LZ-1 (Equipment Supplier)
  equipment_class: Heat Pump
  system: hot_water
  location: Lower Ground HW Plant
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0657
  - P0658
  - P0659
  notes: 3 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0067
  from: BMS-PNL-LG-PLUMB
  to: HP-LZ-2 (Equipment Supplier)
  equipment_class: Heat Pump
  system: hot_water
  location: Lower Ground HW Plant
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0664
  - P0665
  - P0666
  notes: 3 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0068
  from: BMS-PNL-LG-PLUMB
  to: HP-LZ-3 (Equipment Supplier)
  equipment_class: Heat Pump
  system: hot_water
  location: Lower Ground HW Plant
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0671
  - P0672
  - P0673
  notes: 3 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0069
  from: BMS-PNL-LG-PLUMB
  to: HW-HEADERS (BMS Contractor)
  equipment_class: Hot Water Header Set
  system: hot_water
  location: Lower Ground HW Plant
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0698
  - P0699
  - P0700
  notes: 3 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0070
  from: BMS-PNL-RD-MECH
  to: HWT-HZ-1 (BMS Contractor)
  equipment_class: Calorifier (Hot Water Storage Tank)
  system: hot_water
  location: Roof Deck HW Plant
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 1
  conductor_count_required: 1
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0677
  notes: 1 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0071
  from: BMS-PNL-RD-MECH
  to: HWT-HZ-2 (BMS Contractor)
  equipment_class: Calorifier (Hot Water Storage Tank)
  system: hot_water
  location: Roof Deck HW Plant
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 1
  conductor_count_required: 1
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0684
  notes: 1 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0072
  from: BMS-PNL-RD-MECH
  to: HWT-HZ-3 (BMS Contractor)
  equipment_class: Calorifier (Hot Water Storage Tank)
  system: hot_water
  location: Roof Deck HW Plant
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 1
  conductor_count_required: 1
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0691
  notes: 1 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0073
  from: BMS-PNL-LG-PLUMB
  to: HWT-LZ-1 (BMS Contractor)
  equipment_class: Calorifier (Hot Water Storage Tank)
  system: hot_water
  location: Lower Ground HW Plant
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 1
  conductor_count_required: 1
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0656
  notes: 1 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0074
  from: BMS-PNL-LG-PLUMB
  to: HWT-LZ-2 (BMS Contractor)
  equipment_class: Calorifier (Hot Water Storage Tank)
  system: hot_water
  location: Lower Ground HW Plant
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 1
  conductor_count_required: 1
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0663
  notes: 1 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0075
  from: BMS-PNL-LG-PLUMB
  to: HWT-LZ-3 (BMS Contractor)
  equipment_class: Calorifier (Hot Water Storage Tank)
  system: hot_water
  location: Lower Ground HW Plant
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 1
  conductor_count_required: 1
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0670
  notes: 1 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0076
  from: BMS-PNL-2F-CASINO
  to: ION-2F-1 (Equipment Supplier)
  equipment_class: Ozone Generator (UV-light or Corona)
  system: casino_mvac
  location: 2nd Floor Casino
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 2
  conductor_count_required: 2
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 2
  carries_point_ids:
  - P0469
  - P0470
  notes: 2 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0077
  from: BMS-PNL-2F-CASINO
  to: ION-2F-2 (Equipment Supplier)
  equipment_class: Ozone Generator (UV-light or Corona)
  system: casino_mvac
  location: 2nd Floor Casino
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 2
  conductor_count_required: 2
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 2
  carries_point_ids:
  - P0471
  - P0472
  notes: 2 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0078
  from: BMS-PNL-RD-MECH
  to: PAHU-01 (BMS Contractor)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 5
    AO: 1
    DI: 1
  conductor_count_required: 8
  conductor_count_specified: 8
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 7
  carries_point_ids:
  - P0259
  - P0260
  - P0268
  - P0269
  - P0270
  - '...'
  notes: 7 I/O points carried, 8C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0079
  from: BMS-PNL-RD-MECH
  to: PAHU-01 (Equipment Supplier)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 4
    AI: 1
  conductor_count_required: 6
  conductor_count_specified: 6
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 5
  carries_point_ids:
  - P0261
  - P0264
  - P0265
  - P0266
  - P0267
  notes: 5 I/O points carried, 6C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0080
  from: BMS-PNL-RD-MECH
  to: PAHU-01 (ME Contractor)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AO: 2
  conductor_count_required: 2
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 2
  carries_point_ids:
  - P0262
  - P0263
  notes: 2 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0081
  from: BMS-PNL-RD-MECH
  to: PAHU-02 (BMS Contractor)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 5
    AO: 1
    DI: 1
  conductor_count_required: 8
  conductor_count_specified: 8
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 7
  carries_point_ids:
  - P0275
  - P0276
  - P0284
  - P0285
  - P0286
  - '...'
  notes: 7 I/O points carried, 8C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0082
  from: BMS-PNL-RD-MECH
  to: PAHU-02 (Equipment Supplier)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 4
    AI: 1
  conductor_count_required: 6
  conductor_count_specified: 6
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 5
  carries_point_ids:
  - P0277
  - P0280
  - P0281
  - P0282
  - P0283
  notes: 5 I/O points carried, 6C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0083
  from: BMS-PNL-RD-MECH
  to: PAHU-02 (ME Contractor)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AO: 2
  conductor_count_required: 2
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 2
  carries_point_ids:
  - P0278
  - P0279
  notes: 2 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0084
  from: BMS-PNL-RD-MECH
  to: PAHU-03 (BMS Contractor)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 5
    AO: 1
    DI: 1
  conductor_count_required: 8
  conductor_count_specified: 8
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 7
  carries_point_ids:
  - P0291
  - P0292
  - P0300
  - P0301
  - P0302
  - '...'
  notes: 7 I/O points carried, 8C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0085
  from: BMS-PNL-RD-MECH
  to: PAHU-03 (Equipment Supplier)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 4
    AI: 1
  conductor_count_required: 6
  conductor_count_specified: 6
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 5
  carries_point_ids:
  - P0293
  - P0296
  - P0297
  - P0298
  - P0299
  notes: 5 I/O points carried, 6C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0086
  from: BMS-PNL-RD-MECH
  to: PAHU-03 (ME Contractor)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AO: 2
  conductor_count_required: 2
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 2
  carries_point_ids:
  - P0294
  - P0295
  notes: 2 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0087
  from: BMS-PNL-RD-MECH
  to: PAHU-04 (BMS Contractor)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 5
    AO: 1
    DI: 1
  conductor_count_required: 8
  conductor_count_specified: 8
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 7
  carries_point_ids:
  - P0307
  - P0308
  - P0316
  - P0317
  - P0318
  - '...'
  notes: 7 I/O points carried, 8C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0088
  from: BMS-PNL-RD-MECH
  to: PAHU-04 (Equipment Supplier)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 4
    AI: 1
  conductor_count_required: 6
  conductor_count_specified: 6
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 5
  carries_point_ids:
  - P0309
  - P0312
  - P0313
  - P0314
  - P0315
  notes: 5 I/O points carried, 6C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0089
  from: BMS-PNL-RD-MECH
  to: PAHU-04 (ME Contractor)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AO: 2
  conductor_count_required: 2
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 2
  carries_point_ids:
  - P0310
  - P0311
  notes: 2 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0090
  from: BMS-PNL-RD-MECH
  to: PAHU-05 (BMS Contractor)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 5
    AO: 1
    DI: 1
  conductor_count_required: 8
  conductor_count_specified: 8
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 7
  carries_point_ids:
  - P0323
  - P0324
  - P0332
  - P0333
  - P0334
  - '...'
  notes: 7 I/O points carried, 8C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0091
  from: BMS-PNL-RD-MECH
  to: PAHU-05 (Equipment Supplier)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 4
    AI: 1
  conductor_count_required: 6
  conductor_count_specified: 6
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 5
  carries_point_ids:
  - P0325
  - P0328
  - P0329
  - P0330
  - P0331
  notes: 5 I/O points carried, 6C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0092
  from: BMS-PNL-RD-MECH
  to: PAHU-05 (ME Contractor)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AO: 2
  conductor_count_required: 2
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 2
  carries_point_ids:
  - P0326
  - P0327
  notes: 2 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0093
  from: BMS-PNL-RD-MECH
  to: PAHU-06 (BMS Contractor)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 5
    AO: 1
    DI: 1
  conductor_count_required: 8
  conductor_count_specified: 8
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 7
  carries_point_ids:
  - P0339
  - P0340
  - P0348
  - P0349
  - P0350
  - '...'
  notes: 7 I/O points carried, 8C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0094
  from: BMS-PNL-RD-MECH
  to: PAHU-06 (Equipment Supplier)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 4
    AI: 1
  conductor_count_required: 6
  conductor_count_specified: 6
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 5
  carries_point_ids:
  - P0341
  - P0344
  - P0345
  - P0346
  - P0347
  notes: 5 I/O points carried, 6C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0095
  from: BMS-PNL-RD-MECH
  to: PAHU-06 (ME Contractor)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AO: 2
  conductor_count_required: 2
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 2
  carries_point_ids:
  - P0342
  - P0343
  notes: 2 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0096
  from: BMS-PNL-RD-MECH
  to: PAHU-07 (BMS Contractor)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 5
    AO: 1
    DI: 1
  conductor_count_required: 8
  conductor_count_specified: 8
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 7
  carries_point_ids:
  - P0355
  - P0356
  - P0364
  - P0365
  - P0366
  - '...'
  notes: 7 I/O points carried, 8C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0097
  from: BMS-PNL-RD-MECH
  to: PAHU-07 (Equipment Supplier)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 4
    AI: 1
  conductor_count_required: 6
  conductor_count_specified: 6
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 5
  carries_point_ids:
  - P0357
  - P0360
  - P0361
  - P0362
  - P0363
  notes: 5 I/O points carried, 6C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0098
  from: BMS-PNL-RD-MECH
  to: PAHU-07 (ME Contractor)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AO: 2
  conductor_count_required: 2
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 2
  carries_point_ids:
  - P0358
  - P0359
  notes: 2 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0099
  from: BMS-PNL-LG-CHILLER
  to: PCHWP-1 (BMS Contractor)
  equipment_class: Primary CHW Pump
  system: chilled_water
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AO: 1
    DO: 1
  conductor_count_required: 2
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 2
  carries_point_ids:
  - P0033
  - P0036
  notes: 2 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0100
  from: BMS-PNL-LG-CHILLER
  to: PCHWP-1 (Equipment Supplier)
  equipment_class: Primary CHW Pump
  system: chilled_water
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
    AI: 2
  conductor_count_required: 5
  conductor_count_specified: 6
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 5
  carries_point_ids:
  - P0029
  - P0030
  - P0031
  - P0032
  - P0034
  notes: 5 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0101
  from: BMS-PNL-LG-CHILLER
  to: PCHWP-2 (BMS Contractor)
  equipment_class: Primary CHW Pump
  system: chilled_water
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AO: 1
    DO: 1
  conductor_count_required: 2
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 2
  carries_point_ids:
  - P0075
  - P0078
  notes: 2 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0102
  from: BMS-PNL-LG-CHILLER
  to: PCHWP-2 (Equipment Supplier)
  equipment_class: Primary CHW Pump
  system: chilled_water
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
    AI: 2
  conductor_count_required: 5
  conductor_count_specified: 6
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 5
  carries_point_ids:
  - P0071
  - P0072
  - P0073
  - P0074
  - P0076
  notes: 5 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0103
  from: BMS-PNL-LG-CHILLER
  to: PCHWP-3 (BMS Contractor)
  equipment_class: Primary CHW Pump
  system: chilled_water
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AO: 1
    DO: 1
  conductor_count_required: 2
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 2
  carries_point_ids:
  - P0117
  - P0120
  notes: 2 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0104
  from: BMS-PNL-LG-CHILLER
  to: PCHWP-3 (Equipment Supplier)
  equipment_class: Primary CHW Pump
  system: chilled_water
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
    AI: 2
  conductor_count_required: 5
  conductor_count_specified: 6
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 5
  carries_point_ids:
  - P0113
  - P0114
  - P0115
  - P0116
  - P0118
  notes: 5 I/O points carried, 6C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0105
  from: BMS-PNL-RD-MECH
  to: RP-HZ-1 (Equipment Supplier)
  equipment_class: Recirculating Pump
  system: hot_water
  location: Roof Deck HW Plant
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0681
  - P0682
  - P0683
  notes: 3 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0106
  from: BMS-PNL-RD-MECH
  to: RP-HZ-2 (Equipment Supplier)
  equipment_class: Recirculating Pump
  system: hot_water
  location: Roof Deck HW Plant
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0688
  - P0689
  - P0690
  notes: 3 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0107
  from: BMS-PNL-RD-MECH
  to: RP-HZ-3 (Equipment Supplier)
  equipment_class: Recirculating Pump
  system: hot_water
  location: Roof Deck HW Plant
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0695
  - P0696
  - P0697
  notes: 3 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0108
  from: BMS-PNL-LG-PLUMB
  to: RP-LZ-1 (Equipment Supplier)
  equipment_class: Recirculating Pump
  system: hot_water
  location: Lower Ground HW Plant
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0660
  - P0661
  - P0662
  notes: 3 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0109
  from: BMS-PNL-LG-PLUMB
  to: RP-LZ-2 (Equipment Supplier)
  equipment_class: Recirculating Pump
  system: hot_water
  location: Lower Ground HW Plant
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0667
  - P0668
  - P0669
  notes: 3 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0110
  from: BMS-PNL-LG-PLUMB
  to: RP-LZ-3 (Equipment Supplier)
  equipment_class: Recirculating Pump
  system: hot_water
  location: Lower Ground HW Plant
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0674
  - P0675
  - P0676
  notes: 3 I/O points carried, 4C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0111
  from: BMS-PNL-LG-PLUMB
  to: SB-1 (BMS Contractor)
  equipment_class: Steam Boiler
  system: steam
  location: Lower Ground Laundry
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 5
    AO: 2
    DI: 1
  conductor_count_required: 9
  conductor_count_specified: 12
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 8
  carries_point_ids:
  - P0701
  - P0715
  - P0716
  - P0717
  - P0718
  - '...'
  notes: 8 I/O points carried, 12C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0112
  from: BMS-PNL-LG-PLUMB
  to: SB-2 (BMS Contractor)
  equipment_class: Steam Boiler
  system: steam
  location: Lower Ground Laundry
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    AI: 5
    AO: 2
    DI: 1
  conductor_count_required: 9
  conductor_count_specified: 12
  spare_basis: per-class spare strategy ()
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 8
  carries_point_ids:
  - P0722
  - P0736
  - P0737
  - P0738
  - P0739
  - '...'
  notes: 8 I/O points carried, 12C cable; length 12 m (typical_range:plant_room_same_room)
- id: C0113
  from: BMS-PNL-GF
  to: TEF-1.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: Ground Floor Lobby
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0488
  - P0489
  - P0490
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0114
  from: BMS-PNL-GF
  to: TEF-1.2 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: Ground Floor Lobby
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0491
  - P0492
  - P0493
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0115
  from: BMS-PNL-GF
  to: TEF-1.3 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: Ground Floor Lobby
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0494
  - P0495
  - P0496
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0116
  from: BMS-PNL-GF
  to: TEF-1.4 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: Ground Floor Lobby
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0497
  - P0498
  - P0499
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0117
  from: BMS-PNL-2F-CASINO
  to: TEF-2.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 2nd Floor BOH
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0473
  - P0474
  - P0475
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0118
  from: BMS-PNL-2F-CASINO
  to: TEF-2.3 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 2nd Floor BOH
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0476
  - P0477
  - P0478
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0119
  from: BMS-PNL-2F-CASINO
  to: TEF-2B.3 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 2nd Floor BOH
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0479
  - P0480
  - P0481
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0120
  from: BMS-PNL-3F
  to: TEF-3A.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 3rd Floor Amenity
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0500
  - P0501
  - P0502
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0121
  from: BMS-PNL-3F
  to: TEF-3A.2 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 3rd Floor Amenity
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0503
  - P0504
  - P0505
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0122
  from: BMS-PNL-3F
  to: TEF-3B (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 3rd Floor Amenity
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0506
  - P0507
  - P0508
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0123
  from: BMS-PNL-3F
  to: TEF-3C.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 3rd Floor Amenity
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0509
  - P0510
  - P0511
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0124
  from: BMS-PNL-3F
  to: TEF-3C.2 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 3rd Floor Amenity
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0512
  - P0513
  - P0514
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0125
  from: BMS-PNL-3F
  to: TEF-3D.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 3rd Floor Amenity
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0515
  - P0516
  - P0517
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0126
  from: BMS-PNL-3F
  to: TEF-3D.10 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 3rd Floor Amenity
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0542
  - P0543
  - P0544
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0127
  from: BMS-PNL-3F
  to: TEF-3D.11 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 3rd Floor Amenity
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0545
  - P0546
  - P0547
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0128
  from: BMS-PNL-3F
  to: TEF-3D.12 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 3rd Floor Amenity
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0548
  - P0549
  - P0550
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0129
  from: BMS-PNL-3F
  to: TEF-3D.13 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 3rd Floor Amenity
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0551
  - P0552
  - P0553
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0130
  from: BMS-PNL-3F
  to: TEF-3D.14 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 3rd Floor Amenity
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0554
  - P0555
  - P0556
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0131
  from: BMS-PNL-3F
  to: TEF-3D.15 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 3rd Floor Amenity
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0557
  - P0558
  - P0559
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0132
  from: BMS-PNL-3F
  to: TEF-3D.16 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 3rd Floor Amenity
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0560
  - P0561
  - P0562
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0133
  from: BMS-PNL-3F
  to: TEF-3D.17 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 3rd Floor Amenity
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0563
  - P0564
  - P0565
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0134
  from: BMS-PNL-3F
  to: TEF-3D.18 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 3rd Floor Amenity
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0566
  - P0567
  - P0568
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0135
  from: BMS-PNL-3F
  to: TEF-3D.19 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 3rd Floor Amenity
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0569
  - P0570
  - P0571
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0136
  from: BMS-PNL-3F
  to: TEF-3D.2 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 3rd Floor Amenity
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0518
  - P0519
  - P0520
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0137
  from: BMS-PNL-3F
  to: TEF-3D.20 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 3rd Floor Amenity
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0572
  - P0573
  - P0574
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0138
  from: BMS-PNL-3F
  to: TEF-3D.3 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 3rd Floor Amenity
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0521
  - P0522
  - P0523
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0139
  from: BMS-PNL-3F
  to: TEF-3D.4 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 3rd Floor Amenity
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0524
  - P0525
  - P0526
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0140
  from: BMS-PNL-3F
  to: TEF-3D.5 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 3rd Floor Amenity
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0527
  - P0528
  - P0529
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0141
  from: BMS-PNL-3F
  to: TEF-3D.6 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 3rd Floor Amenity
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0530
  - P0531
  - P0532
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0142
  from: BMS-PNL-3F
  to: TEF-3D.7 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 3rd Floor Amenity
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0533
  - P0534
  - P0535
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0143
  from: BMS-PNL-3F
  to: TEF-3D.8 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 3rd Floor Amenity
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0536
  - P0537
  - P0538
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0144
  from: BMS-PNL-3F
  to: TEF-3D.9 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: 3rd Floor Amenity
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0539
  - P0540
  - P0541
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0145
  from: BMS-PNL-B1
  to: TEF-B.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: Basement 1
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0575
  - P0576
  - P0577
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0146
  from: BMS-PNL-B1
  to: TEF-B.10 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: Basement 1
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0602
  - P0603
  - P0604
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0147
  from: BMS-PNL-B1
  to: TEF-B.11 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: Basement 1
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0605
  - P0606
  - P0607
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0148
  from: BMS-PNL-B1
  to: TEF-B.12 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: Basement 1
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0608
  - P0609
  - P0610
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0149
  from: BMS-PNL-B1
  to: TEF-B.13 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: Basement 1
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0611
  - P0612
  - P0613
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0150
  from: BMS-PNL-B1
  to: TEF-B.14 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: Basement 1
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0614
  - P0615
  - P0616
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0151
  from: BMS-PNL-B1
  to: TEF-B.15 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: Basement 1
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0617
  - P0618
  - P0619
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0152
  from: BMS-PNL-B1
  to: TEF-B.16 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: Basement 1
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0620
  - P0621
  - P0622
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0153
  from: BMS-PNL-B1
  to: TEF-B.2 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: Basement 1
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0578
  - P0579
  - P0580
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0154
  from: BMS-PNL-B1
  to: TEF-B.3 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: Basement 1
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0581
  - P0582
  - P0583
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0155
  from: BMS-PNL-B1
  to: TEF-B.4 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: Basement 1
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0584
  - P0585
  - P0586
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0156
  from: BMS-PNL-B1
  to: TEF-B.5 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: Basement 1
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0587
  - P0588
  - P0589
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0157
  from: BMS-PNL-B1
  to: TEF-B.6 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: Basement 1
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0590
  - P0591
  - P0592
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0158
  from: BMS-PNL-B1
  to: TEF-B.7 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: Basement 1
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0593
  - P0594
  - P0595
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0159
  from: BMS-PNL-B1
  to: TEF-B.8 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: Basement 1
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0596
  - P0597
  - P0598
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0160
  from: BMS-PNL-B1
  to: TEF-B.9 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: Basement 1
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0599
  - P0600
  - P0601
  notes: 3 I/O points carried, 4C cable; length 22 m (typical_range:boh_same_floor)
- id: C0161
  from: BMS-PNL-GF
  to: TEF-GS.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: Ground Floor
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 35
  length_method: typical_range:guestroom_corridor
  length_basis: 'Field cables from each floor''s BMS field panel (in electrical room) to

    corridor-mounted DOAS/PAHU sensors, exhaust-fan aux contacts, and

    duct-mounted sensors. Guestroom corridor length typical 25-40 m.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0482
  - P0483
  - P0484
  notes: 3 I/O points carried, 4C cable; length 35 m (typical_range:guestroom_corridor)
- id: C0162
  from: BMS-PNL-GF
  to: TEF-GS.2 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: Ground Floor
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 35
  length_method: typical_range:guestroom_corridor
  length_basis: 'Field cables from each floor''s BMS field panel (in electrical room) to

    corridor-mounted DOAS/PAHU sensors, exhaust-fan aux contacts, and

    duct-mounted sensors. Guestroom corridor length typical 25-40 m.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0485
  - P0486
  - P0487
  notes: 3 I/O points carried, 4C cable; length 35 m (typical_range:guestroom_corridor)
- id: C0163
  from: BMS-PNL-RD-MECH
  to: TEF-RD.1 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: Roof Deck
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0623
  - P0624
  - P0625
  notes: 3 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0164
  from: BMS-PNL-RD-MECH
  to: TEF-RD.2 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: Roof Deck
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0626
  - P0627
  - P0628
  notes: 3 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0165
  from: BMS-PNL-RD-MECH
  to: TEF-RD.3 (Equipment Supplier)
  equipment_class: Exhaust Fan (Toilet)
  system: ventilation
  location: Roof Deck
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  spec_source: rule:?
  spec_basis: ''
  by_class:
    DI: 3
  conductor_count_required: 3
  conductor_count_specified: 4
  spare_basis: per-class spare strategy ()
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 3
  carries_point_ids:
  - P0629
  - P0630
  - P0631
  notes: 3 I/O points carried, 4C cable; length 15 m (typical_range:roofdeck_plant_area)
- id: C0166
  from: BMS-PNL-LG-CHILLER
  to: CH-1 (Network)
  equipment_class: Chiller (Package Water-Cooled)
  system: chilled_water
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0023
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)"
- id: C0167
  from: BMS-PNL-LG-CHILLER
  to: CH-2 (Network)
  equipment_class: Chiller (Package Water-Cooled)
  system: chilled_water
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0065
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)"
- id: C0168
  from: BMS-PNL-LG-CHILLER
  to: CH-3 (Network)
  equipment_class: Chiller (Package Water-Cooled)
  system: chilled_water
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0107
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)"
- id: C0169
  from: BMS-PNL-LG-CHILLER
  to: BTU-1 (Network)
  equipment_class: BTU Meter
  system: btu_metering
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0176
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)"
- id: C0170
  from: BMS-PNL-LG-CHILLER
  to: BTU-2 (Network)
  equipment_class: BTU Meter
  system: btu_metering
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0177
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)"
- id: C0171
  from: BMS-PNL-LG-CHILLER
  to: BTU-3 (Network)
  equipment_class: BTU Meter
  system: btu_metering
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0178
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)"
- id: C0172
  from: BMS-PNL-LG-CHILLER
  to: BTU-4 (Network)
  equipment_class: BTU Meter
  system: btu_metering
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0179
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)"
- id: C0173
  from: BMS-PNL-LG-CHILLER
  to: BTU-5 (Network)
  equipment_class: BTU Meter
  system: btu_metering
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0180
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)"
- id: C0174
  from: BMS-PNL-RD-MECH
  to: DOAS-RD1 (Network)
  equipment_class: DOAS Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0206
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 15 m (typical_range:roofdeck_plant_area)"
- id: C0175
  from: BMS-PNL-RD-MECH
  to: DOAS-RD2 (Network)
  equipment_class: DOAS Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0232
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 15 m (typical_range:roofdeck_plant_area)"
- id: C0176
  from: BMS-PNL-2F-CASINO
  to: DOAS-2F-CASINO (Network)
  equipment_class: DOAS Unit
  system: ventilation
  location: 2nd Floor Casino MVAC Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0258
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 22 m (typical_range:boh_same_floor)"
- id: C0177
  from: BMS-PNL-RD-MECH
  to: PAHU-01 (Network)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0274
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 15 m (typical_range:roofdeck_plant_area)"
- id: C0178
  from: BMS-PNL-RD-MECH
  to: PAHU-02 (Network)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0290
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 15 m (typical_range:roofdeck_plant_area)"
- id: C0179
  from: BMS-PNL-RD-MECH
  to: PAHU-03 (Network)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0306
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 15 m (typical_range:roofdeck_plant_area)"
- id: C0180
  from: BMS-PNL-RD-MECH
  to: PAHU-04 (Network)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0322
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 15 m (typical_range:roofdeck_plant_area)"
- id: C0181
  from: BMS-PNL-RD-MECH
  to: PAHU-05 (Network)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0338
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 15 m (typical_range:roofdeck_plant_area)"
- id: C0182
  from: BMS-PNL-RD-MECH
  to: PAHU-06 (Network)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0354
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 15 m (typical_range:roofdeck_plant_area)"
- id: C0183
  from: BMS-PNL-RD-MECH
  to: PAHU-07 (Network)
  equipment_class: Precooled Air Handling Unit
  system: ventilation
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0370
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 15 m (typical_range:roofdeck_plant_area)"
- id: C0184
  from: BMS-PNL-GF
  to: PM-MAIN (Network)
  equipment_class: Multifunction Power Meter (Main)
  system: power_metering
  location: Main Switchgear Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0743
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)"
- id: C0185
  from: BMS-PNL-LG-CHILLER
  to: PM-CHILLER-1 (Network)
  equipment_class: Multifunction Power Meter (Feeder)
  system: power_metering
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0744
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)"
- id: C0186
  from: BMS-PNL-LG-CHILLER
  to: PM-CHILLER-2 (Network)
  equipment_class: Multifunction Power Meter (Feeder)
  system: power_metering
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0745
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)"
- id: C0187
  from: BMS-PNL-LG-CHILLER
  to: PM-CHILLER-3 (Network)
  equipment_class: Multifunction Power Meter (Feeder)
  system: power_metering
  location: 2nd Level Mechanical Room
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0746
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)"
- id: C0188
  from: BMS-PNL-2F-CASINO
  to: PM-CASINO-FB (Network)
  equipment_class: Multifunction Power Meter (Feeder)
  system: power_metering
  location: 2nd Floor Casino
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0747
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 22 m (typical_range:boh_same_floor)"
- id: C0189
  from: BMS-PNL-2F-CASINO
  to: PM-KITCHEN-2F (Network)
  equipment_class: Multifunction Power Meter (Feeder)
  system: power_metering
  location: 2nd Floor BOH
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0748
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 22 m (typical_range:boh_same_floor)"
- id: C0190
  from: BMS-PNL-GF
  to: PM-LOBBY-GF (Network)
  equipment_class: Multifunction Power Meter (Feeder)
  system: power_metering
  location: Ground Floor
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 35
  length_method: typical_range:guestroom_corridor
  length_basis: 'Field cables from each floor''s BMS field panel (in electrical room) to

    corridor-mounted DOAS/PAHU sensors, exhaust-fan aux contacts, and

    duct-mounted sensors. Guestroom corridor length typical 25-40 m.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0749
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 35 m (typical_range:guestroom_corridor)"
- id: C0191
  from: BMS-PNL-GF
  to: PM-ELEVATOR (Network)
  equipment_class: Multifunction Power Meter (Feeder)
  system: power_metering
  location: Ground Floor
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 35
  length_method: typical_range:guestroom_corridor
  length_basis: 'Field cables from each floor''s BMS field panel (in electrical room) to

    corridor-mounted DOAS/PAHU sensors, exhaust-fan aux contacts, and

    duct-mounted sensors. Guestroom corridor length typical 25-40 m.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0750
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 35 m (typical_range:guestroom_corridor)"
- id: C0192
  from: BMS-PNL-3F
  to: PM-LIGHTING-GUEST (Network)
  equipment_class: Multifunction Power Meter (Feeder)
  system: power_metering
  location: 3rd Floor Amenity
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 22
  length_method: typical_range:boh_same_floor
  length_basis: 'Back-of-house equipment (kitchen exhaust fans, basement EAS, lobby

    EAS, GF panels) on the same floor as BMS field panel. Spread across

    floor footprint; longer than plant-room same-room.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0751
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 22 m (typical_range:boh_same_floor)"
- id: C0193
  from: BMS-PNL-LG-PLUMB
  to: PM-LAUNDRY-LG (Network)
  equipment_class: Multifunction Power Meter (Feeder)
  system: power_metering
  location: Lower Ground Laundry
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 12
  length_method: typical_range:plant_room_same_room
  length_basis: 'Chiller-plant pumps, headers, BTU meters, and chillers are in the same

    Lower-Ground / 2nd-Level plant room as their BMS field panel. Cable

    lengths are short (panel-to-device 5-20 m). Industry typical 10-15 m;

    RtRx prior projects 12 m average.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0752
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 12 m (typical_range:plant_room_same_room)"
- id: C0194
  from: BMS-PNL-RD-MECH
  to: PM-ROOFDECK-MECH (Network)
  equipment_class: Multifunction Power Meter (Feeder)
  system: power_metering
  location: Roof Deck Mechanical
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP)"
  conductor_count_required: 4P (8 wires)
  conductor_count_specified: Cat6 patch + permanent link
  length_m: 15
  length_method: typical_range:roofdeck_plant_area
  length_basis: 'Roofdeck PAHU, cooling towers, calorifiers HZ, heat pumps HZ, recirc

    pumps HZ are in the roofdeck mechanical penthouse, with BMS field

    panel co-located. Slightly longer than chiller plant due to spread

    across roofdeck mechanical zone.

    '
  carries_io_points: 1
  carries_point_ids:
  - P0753
  notes: "BACnet/IP or Modbus TCP \u2014 Cat6 to equipment controller; length 15 m (typical_range:roofdeck_plant_area)"
trunk_cables:
- id: T0195
  from: BMS Server Room (head-end)
  to: All BMS panels at 2nd Floor
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP) \u2014 riser fiber + Cat6 trunk"
  length_m: 80
  notes: "Network trunk for 2nd Floor \u2014 fiber to floor switch + Cat6 distribution to floor's BMS panels"
- id: T0196
  from: BMS Server Room (head-end)
  to: All BMS panels at 3rd Floor
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP) \u2014 riser fiber + Cat6 trunk"
  length_m: 80
  notes: "Network trunk for 3rd Floor \u2014 fiber to floor switch + Cat6 distribution to floor's BMS panels"
- id: T0197
  from: BMS Server Room (head-end)
  to: All BMS panels at Basement
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP) \u2014 riser fiber + Cat6 trunk"
  length_m: 80
  notes: "Network trunk for Basement \u2014 fiber to floor switch + Cat6 distribution to floor's BMS panels"
- id: T0198
  from: BMS Server Room (head-end)
  to: All BMS panels at Ground
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP) \u2014 riser fiber + Cat6 trunk"
  length_m: 80
  notes: "Network trunk for Ground \u2014 fiber to floor switch + Cat6 distribution to floor's BMS panels"
- id: T0199
  from: BMS Server Room (head-end)
  to: All BMS panels at Lower Ground
  cable_type: "Cat6 4P \xD7 23 AWG U/UTP, FRLS jacket (BACnet/IP) \u2014 riser fiber + Cat6 trunk"
  length_m: 80
  notes: "Network trunk for Lower Ground \u2014 fiber to floor switch + Cat6 distribution to floor's BMS panels"
- id: T0200
  from: BMS Server Room (head-end)
  to: BMS panel controllers (per topology id ?)
  cable_type: "BACnet MS/TP shielded twisted-pair trunk, 1pr \xD7 22 AWG low-cap"
  length_m: 380
  length_method: agent_specified
  length_basis: ''
  notes: Backbone per agent's trunk_topology entry ?
- id: T0201
  from: BMS Server Room (head-end)
  to: BMS panel controllers (per topology id ?)
  cable_type: "BACnet MS/TP shielded twisted-pair trunk, 1pr \xD7 22 AWG low-cap"
  length_m: 700
  length_method: agent_specified
  length_basis: ''
  notes: Backbone per agent's trunk_topology entry ?
panel_power_feeds:
- id: P0202
  from: Local panelboard / EE-supplied feeder
  to: "BMS-PNL-2F-CASINO \u2014 BMS panel 240V power feed"
  cable_type: "3C \xD7 2.5 mm\xB2 FRLS (240V single-phase BMS panel power feed)"
  length_m: 18
  length_method: typical_range:panel_power_feed
  length_basis: '240V single-phase panel power feed from nearest electrical panel

    (EE-21..23 load schedules) to BMS field panel. Typical 15-25 m;

    depends on EE-panel siting per floor.

    '
  notes: 240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:panel_power_feed)
- id: P0203
  from: Local panelboard / EE-supplied feeder
  to: "BMS-PNL-3F \u2014 BMS panel 240V power feed"
  cable_type: "3C \xD7 2.5 mm\xB2 FRLS (240V single-phase BMS panel power feed)"
  length_m: 18
  length_method: typical_range:panel_power_feed
  length_basis: '240V single-phase panel power feed from nearest electrical panel

    (EE-21..23 load schedules) to BMS field panel. Typical 15-25 m;

    depends on EE-panel siting per floor.

    '
  notes: 240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:panel_power_feed)
- id: P0204
  from: Local panelboard / EE-supplied feeder
  to: "BMS-PNL-B1 \u2014 BMS panel 240V power feed"
  cable_type: "3C \xD7 2.5 mm\xB2 FRLS (240V single-phase BMS panel power feed)"
  length_m: 18
  length_method: typical_range:panel_power_feed
  length_basis: '240V single-phase panel power feed from nearest electrical panel

    (EE-21..23 load schedules) to BMS field panel. Typical 15-25 m;

    depends on EE-panel siting per floor.

    '
  notes: 240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:panel_power_feed)
- id: P0205
  from: Local panelboard / EE-supplied feeder
  to: "BMS-PNL-GF \u2014 BMS panel 240V power feed"
  cable_type: "3C \xD7 2.5 mm\xB2 FRLS (240V single-phase BMS panel power feed)"
  length_m: 18
  length_method: typical_range:panel_power_feed
  length_basis: '240V single-phase panel power feed from nearest electrical panel

    (EE-21..23 load schedules) to BMS field panel. Typical 15-25 m;

    depends on EE-panel siting per floor.

    '
  notes: 240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:panel_power_feed)
- id: P0206
  from: Local panelboard / EE-supplied feeder
  to: "BMS-PNL-LG-CHILLER \u2014 BMS panel 240V power feed"
  cable_type: "3C \xD7 2.5 mm\xB2 FRLS (240V single-phase BMS panel power feed)"
  length_m: 18
  length_method: typical_range:panel_power_feed
  length_basis: '240V single-phase panel power feed from nearest electrical panel

    (EE-21..23 load schedules) to BMS field panel. Typical 15-25 m;

    depends on EE-panel siting per floor.

    '
  notes: 240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:panel_power_feed)
- id: P0207
  from: Local panelboard / EE-supplied feeder
  to: "BMS-PNL-LG-PLUMB \u2014 BMS panel 240V power feed"
  cable_type: "3C \xD7 2.5 mm\xB2 FRLS (240V single-phase BMS panel power feed)"
  length_m: 18
  length_method: typical_range:panel_power_feed
  length_basis: '240V single-phase panel power feed from nearest electrical panel

    (EE-21..23 load schedules) to BMS field panel. Typical 15-25 m;

    depends on EE-panel siting per floor.

    '
  notes: 240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:panel_power_feed)
- id: P0208
  from: Local panelboard / EE-supplied feeder
  to: "BMS-PNL-RD-CT \u2014 BMS panel 240V power feed"
  cable_type: "3C \xD7 2.5 mm\xB2 FRLS (240V single-phase BMS panel power feed)"
  length_m: 18
  length_method: typical_range:panel_power_feed
  length_basis: '240V single-phase panel power feed from nearest electrical panel

    (EE-21..23 load schedules) to BMS field panel. Typical 15-25 m;

    depends on EE-panel siting per floor.

    '
  notes: 240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:panel_power_feed)
- id: P0209
  from: Local panelboard / EE-supplied feeder
  to: "BMS-PNL-RD-MECH \u2014 BMS panel 240V power feed"
  cable_type: "3C \xD7 2.5 mm\xB2 FRLS (240V single-phase BMS panel power feed)"
  length_m: 18
  length_method: typical_range:panel_power_feed
  length_basis: '240V single-phase panel power feed from nearest electrical panel

    (EE-21..23 load schedules) to BMS field panel. Typical 15-25 m;

    depends on EE-panel siting per floor.

    '
  notes: 240V single-phase 16A circuit to BMS panel; UPS-backed where in scope (A7); length 18 m (typical_range:panel_power_feed)