metadata:
  project: Kingsford Hotel Bacolod — BMS
  date: '2026-04-28'
  source:
  - 00-customer-inputs/BMS Points list (TUEC).pdf BMS-01/02/03
  - 00-customer-inputs/MC Standards - ME Points list.pdf (Part B)
  - 00-customer-inputs/MC Standards - PL Points list.pdf (Part C)
  status: draft
  totals:
    total_points: 753
    by_type:
      AI: 170
      AO: 68
      DI: 369
      DO: 15
      HLI: 102
      Network: 29
    by_equipment_class:
      Exhaust Fan (Toilet): 159
      Precooled Air Handling Unit: 112
      Chiller (Package Water-Cooled): 84
      DOAS Unit: 78
      AHU (Chilled-Water-Served): 64
      Steam Boiler: 42
      Cooling Tower: 36
      AHU (Modulating CHW-served): 34
      Primary CHW Pump: 24
      Exhaust Fan (General): 24
      Condenser Water Pump: 18
      Heat Pump: 18
      Recirculating Pump: 18
      Multifunction Power Meter (Feeder): 10
      Calorifier (Hot Water Storage Tank): 6
      CHW Bypass Header: 5
      BTU Meter: 5
      Cooling Tower (Common): 4
      Ozone Generator (UV-light or Corona): 4
      Hot Water Header Set: 3
      CHW Supply Main Header: 2
      CHW Return Main Header: 2
      Multifunction Power Meter (Main): 1
io_list:
- id: P0001
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Compressor on/off status
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0002
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Compressor H/O/A status
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0003
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Compressor trip alarm
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0004
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Motor load current
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0005
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Motor consumption (kW)
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0006
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Motor winding temperature
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0007
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Oil sump pressure
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0008
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Oil sump temperature
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0009
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Oil pump on/off status
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0010
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Oil pump trip
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0011
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Evaporator approach delta-T
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0012
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Evaporator approach delta-P
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0013
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Evaporator refrigerant pressure
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0014
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Evaporator refrigerant temperature
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0015
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Condenser refrigerant pressure
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0016
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Condenser refrigerant temperature
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0017
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Condenser approach delta-T
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0018
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Condenser approach delta-P
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0019
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Entering CHW temperature
  type: AI
  field_device: Temperature Sensor (immersion)
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0020
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Leaving CHW temperature
  type: AI
  field_device: Temperature Sensor (immersion)
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0021
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Entering condenser water temperature
  type: AI
  field_device: Temperature Sensor (immersion)
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0022
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Leaving condenser water temperature
  type: AI
  field_device: Temperature Sensor (immersion)
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0023
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Chiller native BACnet/IP gateway
  type: Network
  field_device: BACnet/IP
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0024
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: CHW Supply isolation valve status
  type: DI
  field_device: Auxiliary Contact
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0025
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: CHW Return isolation valve status
  type: DI
  field_device: Auxiliary Contact
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0026
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Condenser Water Supply isolation valve status
  type: DI
  field_device: Auxiliary Contact
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0027
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Condenser Water Return isolation valve status
  type: DI
  field_device: Auxiliary Contact
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0028
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Start permissive
  type: DO
  field_device: Relay output
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0029
  system: chilled_water
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Pump motor on/off status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0030
  system: chilled_water
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Pump motor H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0031
  system: chilled_water
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Pump motor trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0032
  system: chilled_water
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: VFD speed feedback
  type: AI
  field_device: VFD analog output / 4-20 mA
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0033
  system: chilled_water
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: VFD speed command
  type: AO
  field_device: 0-10V / 4-20 mA out
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0034
  system: chilled_water
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: CHW supply pressure (per pump)
  type: AI
  field_device: Pressure Transmitter
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0035
  system: chilled_water
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: VFD network HLI (run hours, fault, kWh)
  type: HLI
  field_device: BACnet/Modbus card
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0036
  system: chilled_water
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Pump start command
  type: DO
  field_device: Relay output
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0037
  system: chilled_water
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Pump motor on/off status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0038
  system: chilled_water
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Pump motor H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0039
  system: chilled_water
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Pump motor trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0040
  system: chilled_water
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Pump start command
  type: DO
  field_device: Relay output
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0041
  system: chilled_water
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Pump VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0042
  system: chilled_water
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: VFD network HLI
  type: HLI
  field_device: BACnet/Modbus card
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0043
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Compressor on/off status
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0044
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Compressor H/O/A status
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0045
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Compressor trip alarm
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0046
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Motor load current
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0047
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Motor consumption (kW)
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0048
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Motor winding temperature
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0049
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Oil sump pressure
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0050
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Oil sump temperature
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0051
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Oil pump on/off status
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0052
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Oil pump trip
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0053
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Evaporator approach delta-T
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0054
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Evaporator approach delta-P
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0055
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Evaporator refrigerant pressure
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0056
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Evaporator refrigerant temperature
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0057
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Condenser refrigerant pressure
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0058
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Condenser refrigerant temperature
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0059
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Condenser approach delta-T
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0060
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Condenser approach delta-P
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0061
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Entering CHW temperature
  type: AI
  field_device: Temperature Sensor (immersion)
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0062
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Leaving CHW temperature
  type: AI
  field_device: Temperature Sensor (immersion)
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0063
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Entering condenser water temperature
  type: AI
  field_device: Temperature Sensor (immersion)
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0064
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Leaving condenser water temperature
  type: AI
  field_device: Temperature Sensor (immersion)
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0065
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Chiller native BACnet/IP gateway
  type: Network
  field_device: BACnet/IP
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0066
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: CHW Supply isolation valve status
  type: DI
  field_device: Auxiliary Contact
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0067
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: CHW Return isolation valve status
  type: DI
  field_device: Auxiliary Contact
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0068
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Condenser Water Supply isolation valve status
  type: DI
  field_device: Auxiliary Contact
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0069
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Condenser Water Return isolation valve status
  type: DI
  field_device: Auxiliary Contact
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0070
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Start permissive
  type: DO
  field_device: Relay output
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0071
  system: chilled_water
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Pump motor on/off status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0072
  system: chilled_water
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Pump motor H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0073
  system: chilled_water
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Pump motor trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0074
  system: chilled_water
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: VFD speed feedback
  type: AI
  field_device: VFD analog output / 4-20 mA
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0075
  system: chilled_water
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: VFD speed command
  type: AO
  field_device: 0-10V / 4-20 mA out
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0076
  system: chilled_water
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: CHW supply pressure (per pump)
  type: AI
  field_device: Pressure Transmitter
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0077
  system: chilled_water
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: VFD network HLI (run hours, fault, kWh)
  type: HLI
  field_device: BACnet/Modbus card
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0078
  system: chilled_water
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Pump start command
  type: DO
  field_device: Relay output
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0079
  system: chilled_water
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Pump motor on/off status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0080
  system: chilled_water
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Pump motor H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0081
  system: chilled_water
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Pump motor trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0082
  system: chilled_water
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Pump start command
  type: DO
  field_device: Relay output
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0083
  system: chilled_water
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Pump VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0084
  system: chilled_water
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: VFD network HLI
  type: HLI
  field_device: BACnet/Modbus card
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0085
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Compressor on/off status
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0086
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Compressor H/O/A status
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0087
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Compressor trip alarm
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0088
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Motor load current
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0089
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Motor consumption (kW)
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0090
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Motor winding temperature
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0091
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Oil sump pressure
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0092
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Oil sump temperature
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0093
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Oil pump on/off status
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0094
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Oil pump trip
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0095
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Evaporator approach delta-T
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0096
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Evaporator approach delta-P
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0097
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Evaporator refrigerant pressure
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0098
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Evaporator refrigerant temperature
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0099
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Condenser refrigerant pressure
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0100
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Condenser refrigerant temperature
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0101
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Condenser approach delta-T
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0102
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Condenser approach delta-P
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0103
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Entering CHW temperature
  type: AI
  field_device: Temperature Sensor (immersion)
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0104
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Leaving CHW temperature
  type: AI
  field_device: Temperature Sensor (immersion)
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0105
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Entering condenser water temperature
  type: AI
  field_device: Temperature Sensor (immersion)
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0106
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Leaving condenser water temperature
  type: AI
  field_device: Temperature Sensor (immersion)
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0107
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Chiller native BACnet/IP gateway
  type: Network
  field_device: BACnet/IP
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0108
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: CHW Supply isolation valve status
  type: DI
  field_device: Auxiliary Contact
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0109
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: CHW Return isolation valve status
  type: DI
  field_device: Auxiliary Contact
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0110
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Condenser Water Supply isolation valve status
  type: DI
  field_device: Auxiliary Contact
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0111
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Condenser Water Return isolation valve status
  type: DI
  field_device: Auxiliary Contact
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0112
  system: chilled_water
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Start permissive
  type: DO
  field_device: Relay output
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0113
  system: chilled_water
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Pump motor on/off status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0114
  system: chilled_water
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Pump motor H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0115
  system: chilled_water
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Pump motor trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0116
  system: chilled_water
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: VFD speed feedback
  type: AI
  field_device: VFD analog output / 4-20 mA
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0117
  system: chilled_water
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: VFD speed command
  type: AO
  field_device: 0-10V / 4-20 mA out
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0118
  system: chilled_water
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: CHW supply pressure (per pump)
  type: AI
  field_device: Pressure Transmitter
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0119
  system: chilled_water
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: VFD network HLI (run hours, fault, kWh)
  type: HLI
  field_device: BACnet/Modbus card
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0120
  system: chilled_water
  equipment_class: Primary CHW Pump
  equipment_instance: PCHWP-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Pump start command
  type: DO
  field_device: Relay output
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0121
  system: chilled_water
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Pump motor on/off status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0122
  system: chilled_water
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Pump motor H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0123
  system: chilled_water
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Pump motor trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0124
  system: chilled_water
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Pump start command
  type: DO
  field_device: Relay output
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0125
  system: chilled_water
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Pump VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0126
  system: chilled_water
  equipment_class: Condenser Water Pump
  equipment_instance: CWP-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: VFD network HLI
  type: HLI
  field_device: BACnet/Modbus card
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0127
  system: chilled_water
  equipment_class: CHW Supply Main Header
  equipment_instance: CHW-HDR-S
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: CHW supply header temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0128
  system: chilled_water
  equipment_class: CHW Supply Main Header
  equipment_instance: CHW-HDR-S
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: CHW supply header pressure
  type: AI
  field_device: Pressure Transmitter
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0129
  system: chilled_water
  equipment_class: CHW Return Main Header
  equipment_instance: CHW-HDR-R
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: CHW return header temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0130
  system: chilled_water
  equipment_class: CHW Return Main Header
  equipment_instance: CHW-HDR-R
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: CHW return header pressure
  type: AI
  field_device: Pressure Transmitter
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0131
  system: chilled_water
  equipment_class: CHW Bypass Header
  equipment_instance: CHW-BYPASS
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: CHW differential pressure
  type: AI
  field_device: Diff. Pressure Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0132
  system: chilled_water
  equipment_class: CHW Bypass Header
  equipment_instance: CHW-BYPASS
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: CHW differential temperature
  type: AI
  field_device: Diff. Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0133
  system: chilled_water
  equipment_class: CHW Bypass Header
  equipment_instance: CHW-BYPASS
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Bypass motorized valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0134
  system: chilled_water
  equipment_class: CHW Bypass Header
  equipment_instance: CHW-BYPASS
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Bypass motorized valve feedback
  type: AI
  field_device: Position Feedback
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0135
  system: chilled_water
  equipment_class: CHW Bypass Header
  equipment_instance: CHW-BYPASS
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Bypass valve status
  type: DI
  field_device: Auxiliary Contact
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0136
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0137
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0138
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Fan start command
  type: DO
  field_device: Relay output
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0139
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Fan VFD speed command
  type: AO
  field_device: 0-10V / 4-20 mA
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0140
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0141
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Basin level low alarm
  type: DI
  field_device: Level Electrode
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0142
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Basin level high alarm
  type: DI
  field_device: Level Electrode
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0143
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Outside air temperature (local)
  type: AI
  field_device: OA Temperature Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0144
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Outside air humidity (local)
  type: AI
  field_device: OA Humidity Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0145
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: CT supply isolation valve status
  type: DI
  field_device: Auxiliary Contact
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0146
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: CT return isolation valve status
  type: DI
  field_device: Auxiliary Contact
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0147
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Motorized blowdown valve control
  type: DO
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0148
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0149
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0150
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Fan start command
  type: DO
  field_device: Relay output
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0151
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Fan VFD speed command
  type: AO
  field_device: 0-10V / 4-20 mA
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0152
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0153
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Basin level low alarm
  type: DI
  field_device: Level Electrode
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0154
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Basin level high alarm
  type: DI
  field_device: Level Electrode
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0155
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Outside air temperature (local)
  type: AI
  field_device: OA Temperature Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0156
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Outside air humidity (local)
  type: AI
  field_device: OA Humidity Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0157
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: CT supply isolation valve status
  type: DI
  field_device: Auxiliary Contact
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0158
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: CT return isolation valve status
  type: DI
  field_device: Auxiliary Contact
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0159
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Motorized blowdown valve control
  type: DO
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0160
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-3
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0161
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-3
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0162
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-3
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Fan start command
  type: DO
  field_device: Relay output
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0163
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-3
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Fan VFD speed command
  type: AO
  field_device: 0-10V / 4-20 mA
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0164
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-3
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0165
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-3
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Basin level low alarm
  type: DI
  field_device: Level Electrode
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0166
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-3
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Basin level high alarm
  type: DI
  field_device: Level Electrode
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0167
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-3
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Outside air temperature (local)
  type: AI
  field_device: OA Temperature Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0168
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-3
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Outside air humidity (local)
  type: AI
  field_device: OA Humidity Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0169
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-3
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: CT supply isolation valve status
  type: DI
  field_device: Auxiliary Contact
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0170
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-3
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: CT return isolation valve status
  type: DI
  field_device: Auxiliary Contact
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0171
  system: condenser_water
  equipment_class: Cooling Tower
  equipment_instance: CT-3
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Motorized blowdown valve control
  type: DO
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0172
  system: condenser_water
  equipment_class: Cooling Tower (Common)
  equipment_instance: CT-COMMON
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Condenser supply header temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0173
  system: condenser_water
  equipment_class: Cooling Tower (Common)
  equipment_instance: CT-COMMON
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Condenser return header temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0174
  system: condenser_water
  equipment_class: Cooling Tower (Common)
  equipment_instance: CT-COMMON
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Condenser water pH (corrosion)
  type: AI
  field_device: pH Sensor
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0175
  system: condenser_water
  equipment_class: Cooling Tower (Common)
  equipment_instance: CT-COMMON
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-CT
  point_description: Condenser water conductivity (scale)
  type: AI
  field_device: Conductivity Sensor
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0176
  system: btu_metering
  equipment_class: BTU Meter
  equipment_instance: BTU-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: BTU meter (energy reading)
  type: Network
  field_device: Modbus RTU/TCP
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0177
  system: btu_metering
  equipment_class: BTU Meter
  equipment_instance: BTU-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: BTU meter (energy reading)
  type: Network
  field_device: Modbus RTU/TCP
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0178
  system: btu_metering
  equipment_class: BTU Meter
  equipment_instance: BTU-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: BTU meter (energy reading)
  type: Network
  field_device: Modbus RTU/TCP
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0179
  system: btu_metering
  equipment_class: BTU Meter
  equipment_instance: BTU-4
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: BTU meter (energy reading)
  type: Network
  field_device: Modbus RTU/TCP
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0180
  system: btu_metering
  equipment_class: BTU Meter
  equipment_instance: BTU-5
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: BTU meter (energy reading)
  type: Network
  field_device: Modbus RTU/TCP
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0181
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Outside SA temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0182
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Outside SA flow
  type: AI
  field_device: Air Flow Station
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0183
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Outside SA humidity
  type: AI
  field_device: Duct RH Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0184
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: OA motorized damper status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0185
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: OA motorized damper command
  type: AO
  field_device: Damper Actuator
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0186
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Recovery wheel motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0187
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Recovery wheel trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0188
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Supply fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0189
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Supply fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0190
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Supply fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0191
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Supply fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0192
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Supply fan VFD speed command
  type: AO
  field_device: 0-10V / 4-20 mA
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0193
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Mixed air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0194
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Mixed air humidity
  type: AI
  field_device: Duct RH Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0195
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: CHWS / cooling-coil valve status
  type: DI
  field_device: Auxiliary Contact
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0196
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: CHWS / cooling-coil valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0197
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Indoor supply air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0198
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Indoor exhaust air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0199
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Indoor exhaust air humidity
  type: AI
  field_device: Duct RH Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0200
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Exhaust fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0201
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Exhaust fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0202
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Exhaust fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0203
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Exhaust fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0204
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Exhaust fan VFD speed command
  type: AO
  field_device: 0-10V / 4-20 mA
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0205
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: DOAS network HLI (VFDs, kWh)
  type: HLI
  field_device: BACnet/Modbus card
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0206
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD1
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: DOAS network drop
  type: Network
  field_device: BACnet/IP
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0207
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Outside SA temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0208
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Outside SA flow
  type: AI
  field_device: Air Flow Station
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0209
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Outside SA humidity
  type: AI
  field_device: Duct RH Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0210
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: OA motorized damper status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0211
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: OA motorized damper command
  type: AO
  field_device: Damper Actuator
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0212
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Recovery wheel motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0213
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Recovery wheel trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0214
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Supply fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0215
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Supply fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0216
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Supply fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0217
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Supply fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0218
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Supply fan VFD speed command
  type: AO
  field_device: 0-10V / 4-20 mA
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0219
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Mixed air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0220
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Mixed air humidity
  type: AI
  field_device: Duct RH Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0221
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: CHWS / cooling-coil valve status
  type: DI
  field_device: Auxiliary Contact
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0222
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: CHWS / cooling-coil valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0223
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Indoor supply air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0224
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Indoor exhaust air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0225
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Indoor exhaust air humidity
  type: AI
  field_device: Duct RH Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0226
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Exhaust fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0227
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Exhaust fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0228
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Exhaust fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0229
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Exhaust fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0230
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Exhaust fan VFD speed command
  type: AO
  field_device: 0-10V / 4-20 mA
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0231
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: DOAS network HLI (VFDs, kWh)
  type: HLI
  field_device: BACnet/Modbus card
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0232
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD2
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: DOAS network drop
  type: Network
  field_device: BACnet/IP
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0233
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F-CASINO
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Outside SA temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0234
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F-CASINO
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Outside SA flow
  type: AI
  field_device: Air Flow Station
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0235
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F-CASINO
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Outside SA humidity
  type: AI
  field_device: Duct RH Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0236
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F-CASINO
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: OA motorized damper status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0237
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F-CASINO
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: OA motorized damper command
  type: AO
  field_device: Damper Actuator
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0238
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F-CASINO
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Recovery wheel motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0239
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F-CASINO
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Recovery wheel trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0240
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F-CASINO
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Supply fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0241
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F-CASINO
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Supply fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0242
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F-CASINO
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Supply fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0243
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F-CASINO
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Supply fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0244
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F-CASINO
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Supply fan VFD speed command
  type: AO
  field_device: 0-10V / 4-20 mA
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0245
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F-CASINO
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Mixed air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0246
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F-CASINO
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Mixed air humidity
  type: AI
  field_device: Duct RH Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0247
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F-CASINO
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: CHWS / cooling-coil valve status
  type: DI
  field_device: Auxiliary Contact
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0248
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F-CASINO
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: CHWS / cooling-coil valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0249
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F-CASINO
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Indoor supply air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0250
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F-CASINO
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Indoor exhaust air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0251
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F-CASINO
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Indoor exhaust air humidity
  type: AI
  field_device: Duct RH Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0252
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F-CASINO
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Exhaust fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0253
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F-CASINO
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Exhaust fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0254
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F-CASINO
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Exhaust fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0255
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F-CASINO
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Exhaust fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0256
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F-CASINO
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Exhaust fan VFD speed command
  type: AO
  field_device: 0-10V / 4-20 mA
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0257
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F-CASINO
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: DOAS network HLI (VFDs, kWh)
  type: HLI
  field_device: BACnet/Modbus card
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0258
  system: ventilation
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F-CASINO
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: DOAS network drop
  type: Network
  field_device: BACnet/IP
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0259
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-01
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Outside SA temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0260
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-01
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Outside SA flow
  type: AI
  field_device: Air Flow Station
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0261
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-01
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: OA motorized damper status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0262
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-01
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: OA motorized damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0263
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-01
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: CHWS / cooling-coil valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0264
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-01
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0265
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-01
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0266
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-01
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0267
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-01
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0268
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-01
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan VFD speed command
  type: AO
  field_device: 0-10V / 4-20 mA
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0269
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-01
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Indoor supply air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0270
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-01
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Mixed air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0271
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-01
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Mixed air humidity
  type: AI
  field_device: Duct RH Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0272
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-01
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Filter differential pressure (high)
  type: DI
  field_device: Diff. Pressure Switch
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0273
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-01
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: PAHU network HLI
  type: HLI
  field_device: BACnet/Modbus card
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0274
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-01
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: PAHU network drop
  type: Network
  field_device: BACnet/IP
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0275
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-02
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Outside SA temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0276
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-02
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Outside SA flow
  type: AI
  field_device: Air Flow Station
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0277
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-02
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: OA motorized damper status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0278
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-02
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: OA motorized damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0279
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-02
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: CHWS / cooling-coil valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0280
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-02
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0281
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-02
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0282
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-02
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0283
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-02
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0284
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-02
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan VFD speed command
  type: AO
  field_device: 0-10V / 4-20 mA
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0285
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-02
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Indoor supply air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0286
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-02
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Mixed air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0287
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-02
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Mixed air humidity
  type: AI
  field_device: Duct RH Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0288
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-02
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Filter differential pressure (high)
  type: DI
  field_device: Diff. Pressure Switch
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0289
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-02
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: PAHU network HLI
  type: HLI
  field_device: BACnet/Modbus card
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0290
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-02
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: PAHU network drop
  type: Network
  field_device: BACnet/IP
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0291
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-03
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Outside SA temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0292
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-03
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Outside SA flow
  type: AI
  field_device: Air Flow Station
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0293
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-03
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: OA motorized damper status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0294
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-03
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: OA motorized damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0295
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-03
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: CHWS / cooling-coil valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0296
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-03
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0297
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-03
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0298
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-03
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0299
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-03
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0300
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-03
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan VFD speed command
  type: AO
  field_device: 0-10V / 4-20 mA
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0301
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-03
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Indoor supply air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0302
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-03
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Mixed air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0303
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-03
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Mixed air humidity
  type: AI
  field_device: Duct RH Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0304
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-03
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Filter differential pressure (high)
  type: DI
  field_device: Diff. Pressure Switch
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0305
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-03
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: PAHU network HLI
  type: HLI
  field_device: BACnet/Modbus card
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0306
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-03
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: PAHU network drop
  type: Network
  field_device: BACnet/IP
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0307
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-04
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Outside SA temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0308
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-04
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Outside SA flow
  type: AI
  field_device: Air Flow Station
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0309
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-04
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: OA motorized damper status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0310
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-04
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: OA motorized damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0311
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-04
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: CHWS / cooling-coil valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0312
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-04
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0313
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-04
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0314
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-04
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0315
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-04
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0316
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-04
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan VFD speed command
  type: AO
  field_device: 0-10V / 4-20 mA
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0317
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-04
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Indoor supply air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0318
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-04
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Mixed air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0319
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-04
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Mixed air humidity
  type: AI
  field_device: Duct RH Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0320
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-04
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Filter differential pressure (high)
  type: DI
  field_device: Diff. Pressure Switch
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0321
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-04
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: PAHU network HLI
  type: HLI
  field_device: BACnet/Modbus card
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0322
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-04
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: PAHU network drop
  type: Network
  field_device: BACnet/IP
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0323
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-05
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Outside SA temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0324
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-05
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Outside SA flow
  type: AI
  field_device: Air Flow Station
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0325
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-05
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: OA motorized damper status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0326
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-05
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: OA motorized damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0327
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-05
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: CHWS / cooling-coil valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0328
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-05
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0329
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-05
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0330
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-05
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0331
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-05
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0332
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-05
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan VFD speed command
  type: AO
  field_device: 0-10V / 4-20 mA
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0333
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-05
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Indoor supply air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0334
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-05
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Mixed air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0335
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-05
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Mixed air humidity
  type: AI
  field_device: Duct RH Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0336
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-05
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Filter differential pressure (high)
  type: DI
  field_device: Diff. Pressure Switch
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0337
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-05
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: PAHU network HLI
  type: HLI
  field_device: BACnet/Modbus card
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0338
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-05
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: PAHU network drop
  type: Network
  field_device: BACnet/IP
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0339
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-06
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Outside SA temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0340
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-06
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Outside SA flow
  type: AI
  field_device: Air Flow Station
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0341
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-06
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: OA motorized damper status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0342
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-06
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: OA motorized damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0343
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-06
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: CHWS / cooling-coil valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0344
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-06
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0345
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-06
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0346
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-06
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0347
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-06
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0348
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-06
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan VFD speed command
  type: AO
  field_device: 0-10V / 4-20 mA
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0349
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-06
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Indoor supply air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0350
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-06
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Mixed air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0351
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-06
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Mixed air humidity
  type: AI
  field_device: Duct RH Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0352
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-06
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Filter differential pressure (high)
  type: DI
  field_device: Diff. Pressure Switch
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0353
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-06
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: PAHU network HLI
  type: HLI
  field_device: BACnet/Modbus card
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0354
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-06
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: PAHU network drop
  type: Network
  field_device: BACnet/IP
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0355
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-07
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Outside SA temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0356
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-07
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Outside SA flow
  type: AI
  field_device: Air Flow Station
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0357
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-07
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: OA motorized damper status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0358
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-07
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: OA motorized damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0359
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-07
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: CHWS / cooling-coil valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0360
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-07
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0361
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-07
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0362
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-07
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0363
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-07
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0364
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-07
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Fan VFD speed command
  type: AO
  field_device: 0-10V / 4-20 mA
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0365
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-07
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Indoor supply air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0366
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-07
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Mixed air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0367
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-07
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Mixed air humidity
  type: AI
  field_device: Duct RH Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0368
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-07
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Filter differential pressure (high)
  type: DI
  field_device: Diff. Pressure Switch
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0369
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-07
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: PAHU network HLI
  type: HLI
  field_device: BACnet/Modbus card
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0370
  system: ventilation
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-07
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: PAHU network drop
  type: Network
  field_device: BACnet/IP
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0371
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.1
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Return air motorized damper status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0372
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.1
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Return air motorized damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0373
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.1
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Return air CO2 (DCV)
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0374
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.1
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Return air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0375
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.1
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Mixed air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0376
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.1
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Supply air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0377
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.1
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: CHWS valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0378
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.1
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0379
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.1
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0380
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.1
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Fan VFD speed command
  type: AO
  field_device: 0-10V / 4-20 mA
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0381
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.1
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0382
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.1
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: OA motorized damper status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0383
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.1
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: OA motorized damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0384
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.1
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Outside SA temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0385
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.1
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Filter differential pressure
  type: DI
  field_device: Diff. Pressure Switch
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0386
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.1
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: AHU network HLI
  type: HLI
  field_device: BACnet/Modbus card
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0387
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.1
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Casino return-air CO sensor
  type: AI
  field_device: CO Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0388
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.2
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Return air motorized damper status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0389
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.2
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Return air motorized damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0390
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.2
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Return air CO2 (DCV)
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0391
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.2
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Return air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0392
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.2
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Mixed air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0393
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.2
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Supply air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0394
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.2
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: CHWS valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0395
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.2
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0396
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.2
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0397
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.2
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Fan VFD speed command
  type: AO
  field_device: 0-10V / 4-20 mA
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0398
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.2
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0399
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.2
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: OA motorized damper status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0400
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.2
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: OA motorized damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0401
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.2
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Outside SA temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0402
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.2
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Filter differential pressure
  type: DI
  field_device: Diff. Pressure Switch
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0403
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.2
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: AHU network HLI
  type: HLI
  field_device: BACnet/Modbus card
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0404
  system: casino_mvac
  equipment_class: AHU (Modulating CHW-served)
  equipment_instance: AHU-2M.2
  location: 2nd Floor Casino MVAC Room
  panel: BMS-PNL-2F-CASINO
  point_description: Casino return-air CO sensor
  type: AI
  field_device: CO Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0405
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-1
  location: Ground Floor BOH
  panel: BMS-PNL-GF
  point_description: Return air motorized damper status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0406
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-1
  location: Ground Floor BOH
  panel: BMS-PNL-GF
  point_description: Return air motorized damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0407
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-1
  location: Ground Floor BOH
  panel: BMS-PNL-GF
  point_description: Return air CO2 (DCV)
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0408
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-1
  location: Ground Floor BOH
  panel: BMS-PNL-GF
  point_description: Return air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0409
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-1
  location: Ground Floor BOH
  panel: BMS-PNL-GF
  point_description: Mixed air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0410
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-1
  location: Ground Floor BOH
  panel: BMS-PNL-GF
  point_description: Supply air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0411
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-1
  location: Ground Floor BOH
  panel: BMS-PNL-GF
  point_description: CHWS valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0412
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-1
  location: Ground Floor BOH
  panel: BMS-PNL-GF
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0413
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-1
  location: Ground Floor BOH
  panel: BMS-PNL-GF
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0414
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-1
  location: Ground Floor BOH
  panel: BMS-PNL-GF
  point_description: Fan VFD speed command
  type: AO
  field_device: 0-10V / 4-20 mA
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0415
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-1
  location: Ground Floor BOH
  panel: BMS-PNL-GF
  point_description: Fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0416
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-1
  location: Ground Floor BOH
  panel: BMS-PNL-GF
  point_description: OA motorized damper status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0417
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-1
  location: Ground Floor BOH
  panel: BMS-PNL-GF
  point_description: OA motorized damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0418
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-1
  location: Ground Floor BOH
  panel: BMS-PNL-GF
  point_description: Outside SA temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0419
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-1
  location: Ground Floor BOH
  panel: BMS-PNL-GF
  point_description: Filter differential pressure
  type: DI
  field_device: Diff. Pressure Switch
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0420
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GF-1
  location: Ground Floor BOH
  panel: BMS-PNL-GF
  point_description: AHU network HLI
  type: HLI
  field_device: BACnet/Modbus card
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0421
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GFM-1
  location: Ground Floor Mezzanine BOH
  panel: BMS-PNL-GF
  point_description: Return air motorized damper status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0422
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GFM-1
  location: Ground Floor Mezzanine BOH
  panel: BMS-PNL-GF
  point_description: Return air motorized damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0423
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GFM-1
  location: Ground Floor Mezzanine BOH
  panel: BMS-PNL-GF
  point_description: Return air CO2 (DCV)
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0424
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GFM-1
  location: Ground Floor Mezzanine BOH
  panel: BMS-PNL-GF
  point_description: Return air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0425
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GFM-1
  location: Ground Floor Mezzanine BOH
  panel: BMS-PNL-GF
  point_description: Mixed air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0426
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GFM-1
  location: Ground Floor Mezzanine BOH
  panel: BMS-PNL-GF
  point_description: Supply air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0427
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GFM-1
  location: Ground Floor Mezzanine BOH
  panel: BMS-PNL-GF
  point_description: CHWS valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0428
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GFM-1
  location: Ground Floor Mezzanine BOH
  panel: BMS-PNL-GF
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0429
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GFM-1
  location: Ground Floor Mezzanine BOH
  panel: BMS-PNL-GF
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0430
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GFM-1
  location: Ground Floor Mezzanine BOH
  panel: BMS-PNL-GF
  point_description: Fan VFD speed command
  type: AO
  field_device: 0-10V / 4-20 mA
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0431
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GFM-1
  location: Ground Floor Mezzanine BOH
  panel: BMS-PNL-GF
  point_description: Fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0432
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GFM-1
  location: Ground Floor Mezzanine BOH
  panel: BMS-PNL-GF
  point_description: OA motorized damper status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0433
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GFM-1
  location: Ground Floor Mezzanine BOH
  panel: BMS-PNL-GF
  point_description: OA motorized damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0434
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GFM-1
  location: Ground Floor Mezzanine BOH
  panel: BMS-PNL-GF
  point_description: Outside SA temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0435
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GFM-1
  location: Ground Floor Mezzanine BOH
  panel: BMS-PNL-GF
  point_description: Filter differential pressure
  type: DI
  field_device: Diff. Pressure Switch
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0436
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-GFM-1
  location: Ground Floor Mezzanine BOH
  panel: BMS-PNL-GF
  point_description: AHU network HLI
  type: HLI
  field_device: BACnet/Modbus card
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0437
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-1
  location: 2nd Floor BOH
  panel: BMS-PNL-2F-CASINO
  point_description: Return air motorized damper status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0438
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-1
  location: 2nd Floor BOH
  panel: BMS-PNL-2F-CASINO
  point_description: Return air motorized damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0439
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-1
  location: 2nd Floor BOH
  panel: BMS-PNL-2F-CASINO
  point_description: Return air CO2 (DCV)
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0440
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-1
  location: 2nd Floor BOH
  panel: BMS-PNL-2F-CASINO
  point_description: Return air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0441
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-1
  location: 2nd Floor BOH
  panel: BMS-PNL-2F-CASINO
  point_description: Mixed air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0442
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-1
  location: 2nd Floor BOH
  panel: BMS-PNL-2F-CASINO
  point_description: Supply air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0443
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-1
  location: 2nd Floor BOH
  panel: BMS-PNL-2F-CASINO
  point_description: CHWS valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0444
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-1
  location: 2nd Floor BOH
  panel: BMS-PNL-2F-CASINO
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0445
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-1
  location: 2nd Floor BOH
  panel: BMS-PNL-2F-CASINO
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0446
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-1
  location: 2nd Floor BOH
  panel: BMS-PNL-2F-CASINO
  point_description: Fan VFD speed command
  type: AO
  field_device: 0-10V / 4-20 mA
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0447
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-1
  location: 2nd Floor BOH
  panel: BMS-PNL-2F-CASINO
  point_description: Fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0448
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-1
  location: 2nd Floor BOH
  panel: BMS-PNL-2F-CASINO
  point_description: OA motorized damper status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0449
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-1
  location: 2nd Floor BOH
  panel: BMS-PNL-2F-CASINO
  point_description: OA motorized damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0450
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-1
  location: 2nd Floor BOH
  panel: BMS-PNL-2F-CASINO
  point_description: Outside SA temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0451
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-1
  location: 2nd Floor BOH
  panel: BMS-PNL-2F-CASINO
  point_description: Filter differential pressure
  type: DI
  field_device: Diff. Pressure Switch
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0452
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-2F-1
  location: 2nd Floor BOH
  panel: BMS-PNL-2F-CASINO
  point_description: AHU network HLI
  type: HLI
  field_device: BACnet/Modbus card
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0453
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B1-1
  location: Basement 1 BOH
  panel: BMS-PNL-B1
  point_description: Return air motorized damper status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0454
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B1-1
  location: Basement 1 BOH
  panel: BMS-PNL-B1
  point_description: Return air motorized damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0455
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B1-1
  location: Basement 1 BOH
  panel: BMS-PNL-B1
  point_description: Return air CO2 (DCV)
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0456
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B1-1
  location: Basement 1 BOH
  panel: BMS-PNL-B1
  point_description: Return air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0457
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B1-1
  location: Basement 1 BOH
  panel: BMS-PNL-B1
  point_description: Mixed air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0458
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B1-1
  location: Basement 1 BOH
  panel: BMS-PNL-B1
  point_description: Supply air temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0459
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B1-1
  location: Basement 1 BOH
  panel: BMS-PNL-B1
  point_description: CHWS valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0460
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B1-1
  location: Basement 1 BOH
  panel: BMS-PNL-B1
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0461
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B1-1
  location: Basement 1 BOH
  panel: BMS-PNL-B1
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0462
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B1-1
  location: Basement 1 BOH
  panel: BMS-PNL-B1
  point_description: Fan VFD speed command
  type: AO
  field_device: 0-10V / 4-20 mA
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0463
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B1-1
  location: Basement 1 BOH
  panel: BMS-PNL-B1
  point_description: Fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0464
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B1-1
  location: Basement 1 BOH
  panel: BMS-PNL-B1
  point_description: OA motorized damper status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0465
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B1-1
  location: Basement 1 BOH
  panel: BMS-PNL-B1
  point_description: OA motorized damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0466
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B1-1
  location: Basement 1 BOH
  panel: BMS-PNL-B1
  point_description: Outside SA temperature
  type: AI
  field_device: Duct Temp Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0467
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B1-1
  location: Basement 1 BOH
  panel: BMS-PNL-B1
  point_description: Filter differential pressure
  type: DI
  field_device: Diff. Pressure Switch
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0468
  system: common_area
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-B1-1
  location: Basement 1 BOH
  panel: BMS-PNL-B1
  point_description: AHU network HLI
  type: HLI
  field_device: BACnet/Modbus card
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0469
  system: casino_mvac
  equipment_class: Ozone Generator (UV-light or Corona)
  equipment_instance: ION-2F-1
  location: 2nd Floor Casino
  panel: BMS-PNL-2F-CASINO
  point_description: Ionizer run status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0470
  system: casino_mvac
  equipment_class: Ozone Generator (UV-light or Corona)
  equipment_instance: ION-2F-1
  location: 2nd Floor Casino
  panel: BMS-PNL-2F-CASINO
  point_description: Ionizer fault status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0471
  system: casino_mvac
  equipment_class: Ozone Generator (UV-light or Corona)
  equipment_instance: ION-2F-2
  location: 2nd Floor Casino
  panel: BMS-PNL-2F-CASINO
  point_description: Ionizer run status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0472
  system: casino_mvac
  equipment_class: Ozone Generator (UV-light or Corona)
  equipment_instance: ION-2F-2
  location: 2nd Floor Casino
  panel: BMS-PNL-2F-CASINO
  point_description: Ionizer fault status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0473
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-2.1
  location: 2nd Floor BOH
  panel: BMS-PNL-2F-CASINO
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0474
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-2.1
  location: 2nd Floor BOH
  panel: BMS-PNL-2F-CASINO
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0475
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-2.1
  location: 2nd Floor BOH
  panel: BMS-PNL-2F-CASINO
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0476
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-2.3
  location: 2nd Floor BOH
  panel: BMS-PNL-2F-CASINO
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0477
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-2.3
  location: 2nd Floor BOH
  panel: BMS-PNL-2F-CASINO
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0478
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-2.3
  location: 2nd Floor BOH
  panel: BMS-PNL-2F-CASINO
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0479
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-2B.3
  location: 2nd Floor BOH
  panel: BMS-PNL-2F-CASINO
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0480
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-2B.3
  location: 2nd Floor BOH
  panel: BMS-PNL-2F-CASINO
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0481
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-2B.3
  location: 2nd Floor BOH
  panel: BMS-PNL-2F-CASINO
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0482
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-GS.1
  location: Ground Floor
  panel: BMS-PNL-GF
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0483
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-GS.1
  location: Ground Floor
  panel: BMS-PNL-GF
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0484
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-GS.1
  location: Ground Floor
  panel: BMS-PNL-GF
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0485
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-GS.2
  location: Ground Floor
  panel: BMS-PNL-GF
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0486
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-GS.2
  location: Ground Floor
  panel: BMS-PNL-GF
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0487
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-GS.2
  location: Ground Floor
  panel: BMS-PNL-GF
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0488
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-1.1
  location: Ground Floor Lobby
  panel: BMS-PNL-GF
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0489
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-1.1
  location: Ground Floor Lobby
  panel: BMS-PNL-GF
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0490
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-1.1
  location: Ground Floor Lobby
  panel: BMS-PNL-GF
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0491
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-1.2
  location: Ground Floor Lobby
  panel: BMS-PNL-GF
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0492
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-1.2
  location: Ground Floor Lobby
  panel: BMS-PNL-GF
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0493
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-1.2
  location: Ground Floor Lobby
  panel: BMS-PNL-GF
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0494
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-1.3
  location: Ground Floor Lobby
  panel: BMS-PNL-GF
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0495
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-1.3
  location: Ground Floor Lobby
  panel: BMS-PNL-GF
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0496
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-1.3
  location: Ground Floor Lobby
  panel: BMS-PNL-GF
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0497
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-1.4
  location: Ground Floor Lobby
  panel: BMS-PNL-GF
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0498
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-1.4
  location: Ground Floor Lobby
  panel: BMS-PNL-GF
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0499
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-1.4
  location: Ground Floor Lobby
  panel: BMS-PNL-GF
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0500
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3A.1
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0501
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3A.1
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0502
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3A.1
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0503
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3A.2
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0504
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3A.2
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0505
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3A.2
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0506
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3B
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0507
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3B
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0508
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3B
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0509
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3C.1
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0510
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3C.1
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0511
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3C.1
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0512
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3C.2
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0513
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3C.2
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0514
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3C.2
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0515
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.1
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0516
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.1
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0517
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.1
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0518
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.2
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0519
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.2
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0520
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.2
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0521
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.3
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0522
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.3
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0523
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.3
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0524
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.4
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0525
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.4
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0526
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.4
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0527
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.5
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0528
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.5
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0529
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.5
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0530
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.6
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0531
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.6
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0532
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.6
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0533
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.7
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0534
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.7
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0535
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.7
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0536
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.8
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0537
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.8
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0538
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.8
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0539
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.9
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0540
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.9
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0541
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.9
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0542
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.10
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0543
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.10
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0544
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.10
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0545
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.11
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0546
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.11
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0547
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.11
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0548
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.12
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0549
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.12
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0550
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.12
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0551
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.13
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0552
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.13
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0553
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.13
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0554
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.14
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0555
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.14
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0556
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.14
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0557
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.15
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0558
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.15
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0559
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.15
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0560
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.16
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0561
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.16
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0562
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.16
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0563
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.17
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0564
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.17
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0565
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.17
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0566
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.18
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0567
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.18
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0568
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.18
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0569
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.19
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0570
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.19
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0571
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.19
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0572
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.20
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0573
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.20
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0574
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-3D.20
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0575
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.1
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0576
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.1
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0577
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.1
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0578
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.2
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0579
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.2
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0580
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.2
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0581
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.3
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0582
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.3
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0583
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.3
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0584
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.4
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0585
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.4
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0586
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.4
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0587
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.5
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0588
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.5
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0589
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.5
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0590
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.6
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0591
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.6
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0592
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.6
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0593
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.7
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0594
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.7
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0595
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.7
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0596
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.8
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0597
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.8
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0598
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.8
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0599
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.9
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0600
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.9
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0601
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.9
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0602
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.10
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0603
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.10
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0604
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.10
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0605
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.11
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0606
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.11
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0607
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.11
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0608
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.12
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0609
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.12
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0610
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.12
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0611
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.13
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0612
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.13
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0613
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.13
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0614
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.14
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0615
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.14
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0616
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.14
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0617
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.15
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0618
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.15
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0619
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.15
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0620
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.16
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0621
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.16
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0622
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-B.16
  location: Basement 1
  panel: BMS-PNL-B1
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0623
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-RD.1
  location: Roof Deck
  panel: BMS-PNL-RD-MECH
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0624
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-RD.1
  location: Roof Deck
  panel: BMS-PNL-RD-MECH
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0625
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-RD.1
  location: Roof Deck
  panel: BMS-PNL-RD-MECH
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0626
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-RD.2
  location: Roof Deck
  panel: BMS-PNL-RD-MECH
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0627
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-RD.2
  location: Roof Deck
  panel: BMS-PNL-RD-MECH
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0628
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-RD.2
  location: Roof Deck
  panel: BMS-PNL-RD-MECH
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0629
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-RD.3
  location: Roof Deck
  panel: BMS-PNL-RD-MECH
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0630
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-RD.3
  location: Roof Deck
  panel: BMS-PNL-RD-MECH
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0631
  system: ventilation
  equipment_class: Exhaust Fan (Toilet)
  equipment_instance: TEF-RD.3
  location: Roof Deck
  panel: BMS-PNL-RD-MECH
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0632
  system: ventilation
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-1.2A
  location: Ground Floor Lobby
  panel: BMS-PNL-GF
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0633
  system: ventilation
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-1.2A
  location: Ground Floor Lobby
  panel: BMS-PNL-GF
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0634
  system: ventilation
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-1.2A
  location: Ground Floor Lobby
  panel: BMS-PNL-GF
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0635
  system: ventilation
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-LPG.1
  location: Ground Floor Lobby
  panel: BMS-PNL-GF
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0636
  system: ventilation
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-LPG.1
  location: Ground Floor Lobby
  panel: BMS-PNL-GF
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0637
  system: ventilation
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-LPG.1
  location: Ground Floor Lobby
  panel: BMS-PNL-GF
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0638
  system: ventilation
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-1MR.1
  location: Ground Floor Lobby
  panel: BMS-PNL-GF
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0639
  system: ventilation
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-1MR.1
  location: Ground Floor Lobby
  panel: BMS-PNL-GF
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0640
  system: ventilation
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-1MR.1
  location: Ground Floor Lobby
  panel: BMS-PNL-GF
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0641
  system: ventilation
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-1STO.1
  location: Ground Floor Lobby
  panel: BMS-PNL-GF
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0642
  system: ventilation
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-1STO.1
  location: Ground Floor Lobby
  panel: BMS-PNL-GF
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0643
  system: ventilation
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-1STO.1
  location: Ground Floor Lobby
  panel: BMS-PNL-GF
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0644
  system: ventilation
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-MRF.1
  location: Ground Floor Lobby
  panel: BMS-PNL-GF
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0645
  system: ventilation
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-MRF.1
  location: Ground Floor Lobby
  panel: BMS-PNL-GF
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0646
  system: ventilation
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-MRF.1
  location: Ground Floor Lobby
  panel: BMS-PNL-GF
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0647
  system: ventilation
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-RD.1
  location: Roof Deck
  panel: BMS-PNL-RD-MECH
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0648
  system: ventilation
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-RD.1
  location: Roof Deck
  panel: BMS-PNL-RD-MECH
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0649
  system: ventilation
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-RD.1
  location: Roof Deck
  panel: BMS-PNL-RD-MECH
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0650
  system: ventilation
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-RD.2
  location: Roof Deck
  panel: BMS-PNL-RD-MECH
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0651
  system: ventilation
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-RD.2
  location: Roof Deck
  panel: BMS-PNL-RD-MECH
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0652
  system: ventilation
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-RD.2
  location: Roof Deck
  panel: BMS-PNL-RD-MECH
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0653
  system: ventilation
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-1
  location: Roof Deck
  panel: BMS-PNL-RD-MECH
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0654
  system: ventilation
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-1
  location: Roof Deck
  panel: BMS-PNL-RD-MECH
  point_description: Fan H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0655
  system: ventilation
  equipment_class: Exhaust Fan (General)
  equipment_instance: EF-1
  location: Roof Deck
  panel: BMS-PNL-RD-MECH
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0656
  system: hot_water
  equipment_class: Calorifier (Hot Water Storage Tank)
  equipment_instance: HWT-LZ-1
  location: Lower Ground HW Plant
  panel: BMS-PNL-LG-PLUMB
  point_description: Tank temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0657
  system: hot_water
  equipment_class: Heat Pump
  equipment_instance: HP-LZ-1
  location: Lower Ground HW Plant
  panel: BMS-PNL-LG-PLUMB
  point_description: Pump motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0658
  system: hot_water
  equipment_class: Heat Pump
  equipment_instance: HP-LZ-1
  location: Lower Ground HW Plant
  panel: BMS-PNL-LG-PLUMB
  point_description: Pump motor H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0659
  system: hot_water
  equipment_class: Heat Pump
  equipment_instance: HP-LZ-1
  location: Lower Ground HW Plant
  panel: BMS-PNL-LG-PLUMB
  point_description: Pump motor trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0660
  system: hot_water
  equipment_class: Recirculating Pump
  equipment_instance: RP-LZ-1
  location: Lower Ground HW Plant
  panel: BMS-PNL-LG-PLUMB
  point_description: Pump motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0661
  system: hot_water
  equipment_class: Recirculating Pump
  equipment_instance: RP-LZ-1
  location: Lower Ground HW Plant
  panel: BMS-PNL-LG-PLUMB
  point_description: Pump motor H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0662
  system: hot_water
  equipment_class: Recirculating Pump
  equipment_instance: RP-LZ-1
  location: Lower Ground HW Plant
  panel: BMS-PNL-LG-PLUMB
  point_description: Pump motor trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0663
  system: hot_water
  equipment_class: Calorifier (Hot Water Storage Tank)
  equipment_instance: HWT-LZ-2
  location: Lower Ground HW Plant
  panel: BMS-PNL-LG-PLUMB
  point_description: Tank temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0664
  system: hot_water
  equipment_class: Heat Pump
  equipment_instance: HP-LZ-2
  location: Lower Ground HW Plant
  panel: BMS-PNL-LG-PLUMB
  point_description: Pump motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0665
  system: hot_water
  equipment_class: Heat Pump
  equipment_instance: HP-LZ-2
  location: Lower Ground HW Plant
  panel: BMS-PNL-LG-PLUMB
  point_description: Pump motor H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0666
  system: hot_water
  equipment_class: Heat Pump
  equipment_instance: HP-LZ-2
  location: Lower Ground HW Plant
  panel: BMS-PNL-LG-PLUMB
  point_description: Pump motor trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0667
  system: hot_water
  equipment_class: Recirculating Pump
  equipment_instance: RP-LZ-2
  location: Lower Ground HW Plant
  panel: BMS-PNL-LG-PLUMB
  point_description: Pump motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0668
  system: hot_water
  equipment_class: Recirculating Pump
  equipment_instance: RP-LZ-2
  location: Lower Ground HW Plant
  panel: BMS-PNL-LG-PLUMB
  point_description: Pump motor H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0669
  system: hot_water
  equipment_class: Recirculating Pump
  equipment_instance: RP-LZ-2
  location: Lower Ground HW Plant
  panel: BMS-PNL-LG-PLUMB
  point_description: Pump motor trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0670
  system: hot_water
  equipment_class: Calorifier (Hot Water Storage Tank)
  equipment_instance: HWT-LZ-3
  location: Lower Ground HW Plant
  panel: BMS-PNL-LG-PLUMB
  point_description: Tank temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0671
  system: hot_water
  equipment_class: Heat Pump
  equipment_instance: HP-LZ-3
  location: Lower Ground HW Plant
  panel: BMS-PNL-LG-PLUMB
  point_description: Pump motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0672
  system: hot_water
  equipment_class: Heat Pump
  equipment_instance: HP-LZ-3
  location: Lower Ground HW Plant
  panel: BMS-PNL-LG-PLUMB
  point_description: Pump motor H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0673
  system: hot_water
  equipment_class: Heat Pump
  equipment_instance: HP-LZ-3
  location: Lower Ground HW Plant
  panel: BMS-PNL-LG-PLUMB
  point_description: Pump motor trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0674
  system: hot_water
  equipment_class: Recirculating Pump
  equipment_instance: RP-LZ-3
  location: Lower Ground HW Plant
  panel: BMS-PNL-LG-PLUMB
  point_description: Pump motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0675
  system: hot_water
  equipment_class: Recirculating Pump
  equipment_instance: RP-LZ-3
  location: Lower Ground HW Plant
  panel: BMS-PNL-LG-PLUMB
  point_description: Pump motor H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0676
  system: hot_water
  equipment_class: Recirculating Pump
  equipment_instance: RP-LZ-3
  location: Lower Ground HW Plant
  panel: BMS-PNL-LG-PLUMB
  point_description: Pump motor trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0677
  system: hot_water
  equipment_class: Calorifier (Hot Water Storage Tank)
  equipment_instance: HWT-HZ-1
  location: Roof Deck HW Plant
  panel: BMS-PNL-RD-MECH
  point_description: Tank temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0678
  system: hot_water
  equipment_class: Heat Pump
  equipment_instance: HP-HZ-1
  location: Roof Deck HW Plant
  panel: BMS-PNL-RD-MECH
  point_description: Pump motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0679
  system: hot_water
  equipment_class: Heat Pump
  equipment_instance: HP-HZ-1
  location: Roof Deck HW Plant
  panel: BMS-PNL-RD-MECH
  point_description: Pump motor H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0680
  system: hot_water
  equipment_class: Heat Pump
  equipment_instance: HP-HZ-1
  location: Roof Deck HW Plant
  panel: BMS-PNL-RD-MECH
  point_description: Pump motor trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0681
  system: hot_water
  equipment_class: Recirculating Pump
  equipment_instance: RP-HZ-1
  location: Roof Deck HW Plant
  panel: BMS-PNL-RD-MECH
  point_description: Pump motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0682
  system: hot_water
  equipment_class: Recirculating Pump
  equipment_instance: RP-HZ-1
  location: Roof Deck HW Plant
  panel: BMS-PNL-RD-MECH
  point_description: Pump motor H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0683
  system: hot_water
  equipment_class: Recirculating Pump
  equipment_instance: RP-HZ-1
  location: Roof Deck HW Plant
  panel: BMS-PNL-RD-MECH
  point_description: Pump motor trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0684
  system: hot_water
  equipment_class: Calorifier (Hot Water Storage Tank)
  equipment_instance: HWT-HZ-2
  location: Roof Deck HW Plant
  panel: BMS-PNL-RD-MECH
  point_description: Tank temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0685
  system: hot_water
  equipment_class: Heat Pump
  equipment_instance: HP-HZ-2
  location: Roof Deck HW Plant
  panel: BMS-PNL-RD-MECH
  point_description: Pump motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0686
  system: hot_water
  equipment_class: Heat Pump
  equipment_instance: HP-HZ-2
  location: Roof Deck HW Plant
  panel: BMS-PNL-RD-MECH
  point_description: Pump motor H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0687
  system: hot_water
  equipment_class: Heat Pump
  equipment_instance: HP-HZ-2
  location: Roof Deck HW Plant
  panel: BMS-PNL-RD-MECH
  point_description: Pump motor trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0688
  system: hot_water
  equipment_class: Recirculating Pump
  equipment_instance: RP-HZ-2
  location: Roof Deck HW Plant
  panel: BMS-PNL-RD-MECH
  point_description: Pump motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0689
  system: hot_water
  equipment_class: Recirculating Pump
  equipment_instance: RP-HZ-2
  location: Roof Deck HW Plant
  panel: BMS-PNL-RD-MECH
  point_description: Pump motor H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0690
  system: hot_water
  equipment_class: Recirculating Pump
  equipment_instance: RP-HZ-2
  location: Roof Deck HW Plant
  panel: BMS-PNL-RD-MECH
  point_description: Pump motor trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0691
  system: hot_water
  equipment_class: Calorifier (Hot Water Storage Tank)
  equipment_instance: HWT-HZ-3
  location: Roof Deck HW Plant
  panel: BMS-PNL-RD-MECH
  point_description: Tank temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0692
  system: hot_water
  equipment_class: Heat Pump
  equipment_instance: HP-HZ-3
  location: Roof Deck HW Plant
  panel: BMS-PNL-RD-MECH
  point_description: Pump motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0693
  system: hot_water
  equipment_class: Heat Pump
  equipment_instance: HP-HZ-3
  location: Roof Deck HW Plant
  panel: BMS-PNL-RD-MECH
  point_description: Pump motor H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0694
  system: hot_water
  equipment_class: Heat Pump
  equipment_instance: HP-HZ-3
  location: Roof Deck HW Plant
  panel: BMS-PNL-RD-MECH
  point_description: Pump motor trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0695
  system: hot_water
  equipment_class: Recirculating Pump
  equipment_instance: RP-HZ-3
  location: Roof Deck HW Plant
  panel: BMS-PNL-RD-MECH
  point_description: Pump motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0696
  system: hot_water
  equipment_class: Recirculating Pump
  equipment_instance: RP-HZ-3
  location: Roof Deck HW Plant
  panel: BMS-PNL-RD-MECH
  point_description: Pump motor H/O/A status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0697
  system: hot_water
  equipment_class: Recirculating Pump
  equipment_instance: RP-HZ-3
  location: Roof Deck HW Plant
  panel: BMS-PNL-RD-MECH
  point_description: Pump motor trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0698
  system: hot_water
  equipment_class: Hot Water Header Set
  equipment_instance: HW-HEADERS
  location: Lower Ground HW Plant
  panel: BMS-PNL-LG-PLUMB
  point_description: HW supply header temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0699
  system: hot_water
  equipment_class: Hot Water Header Set
  equipment_instance: HW-HEADERS
  location: Lower Ground HW Plant
  panel: BMS-PNL-LG-PLUMB
  point_description: Make-up cold water header temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0700
  system: hot_water
  equipment_class: Hot Water Header Set
  equipment_instance: HW-HEADERS
  location: Lower Ground HW Plant
  panel: BMS-PNL-LG-PLUMB
  point_description: HW return temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0701
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Supply steam pressure
  type: AI
  field_device: Pressure Transmitter
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0702
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Low water level alarm
  type: HLI
  field_device: Equipment Supplier level sensor
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0703
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: High water level alarm
  type: HLI
  field_device: Equipment Supplier level sensor
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0704
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Burner power
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0705
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Small-fire control signal
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0706
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Big-fire control signal
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0707
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Burner status
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0708
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Burner-fire running status
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0709
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Blower motor status
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0710
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Fuel-oil pump status
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0711
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Waterfeed pump status
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0712
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Burner trip alarm
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0713
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Blower trip alarm
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0714
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Oil pump trip alarm
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0715
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Motorized blowdown valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0716
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Motorized blowdown valve status
  type: DI
  field_device: Auxiliary Contact
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0717
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Feedwater supply temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0718
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Fluegas temperature
  type: AI
  field_device: Temperature Sensor (high-temp)
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0719
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Fluegas oxygen level
  type: AI
  field_device: Oxygen Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0720
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Steam supply pressure (high alarm)
  type: AI
  field_device: Pressure Transmitter
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0721
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Boiler firing-rate command
  type: AO
  field_device: 0-10V / 4-20 mA
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0722
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Supply steam pressure
  type: AI
  field_device: Pressure Transmitter
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0723
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Low water level alarm
  type: HLI
  field_device: Equipment Supplier level sensor
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0724
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: High water level alarm
  type: HLI
  field_device: Equipment Supplier level sensor
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0725
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Burner power
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0726
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Small-fire control signal
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0727
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Big-fire control signal
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0728
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Burner status
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0729
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Burner-fire running status
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0730
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Blower motor status
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0731
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Fuel-oil pump status
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0732
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Waterfeed pump status
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0733
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Burner trip alarm
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0734
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Blower trip alarm
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0735
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Oil pump trip alarm
  type: HLI
  field_device: —
  c_o: Equipment Supplier
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0736
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Motorized blowdown valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0737
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Motorized blowdown valve status
  type: DI
  field_device: Auxiliary Contact
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0738
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Feedwater supply temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0739
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Fluegas temperature
  type: AI
  field_device: Temperature Sensor (high-temp)
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0740
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Fluegas oxygen level
  type: AI
  field_device: Oxygen Sensor
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0741
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Steam supply pressure (high alarm)
  type: AI
  field_device: Pressure Transmitter
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0742
  system: steam
  equipment_class: Steam Boiler
  equipment_instance: SB-2
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Boiler firing-rate command
  type: AO
  field_device: 0-10V / 4-20 mA
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0743
  system: power_metering
  equipment_class: Multifunction Power Meter (Main)
  equipment_instance: PM-MAIN
  location: Main Switchgear Room
  panel: BMS-PNL-GF
  point_description: Main power meter (kW, kWh, V, A, PF, kVAR)
  type: Network
  field_device: Modbus RTU/TCP
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0744
  system: power_metering
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-CHILLER-1
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Feeder power meter (kW, kWh, V, A)
  type: Network
  field_device: Modbus RTU/TCP
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0745
  system: power_metering
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-CHILLER-2
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Feeder power meter (kW, kWh, V, A)
  type: Network
  field_device: Modbus RTU/TCP
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0746
  system: power_metering
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-CHILLER-3
  location: 2nd Level Mechanical Room
  panel: BMS-PNL-LG-CHILLER
  point_description: Feeder power meter (kW, kWh, V, A)
  type: Network
  field_device: Modbus RTU/TCP
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0747
  system: power_metering
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-CASINO-FB
  location: 2nd Floor Casino
  panel: BMS-PNL-2F-CASINO
  point_description: Feeder power meter (kW, kWh, V, A)
  type: Network
  field_device: Modbus RTU/TCP
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0748
  system: power_metering
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-KITCHEN-2F
  location: 2nd Floor BOH
  panel: BMS-PNL-2F-CASINO
  point_description: Feeder power meter (kW, kWh, V, A)
  type: Network
  field_device: Modbus RTU/TCP
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0749
  system: power_metering
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-LOBBY-GF
  location: Ground Floor
  panel: BMS-PNL-GF
  point_description: Feeder power meter (kW, kWh, V, A)
  type: Network
  field_device: Modbus RTU/TCP
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0750
  system: power_metering
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-ELEVATOR
  location: Ground Floor
  panel: BMS-PNL-GF
  point_description: Feeder power meter (kW, kWh, V, A)
  type: Network
  field_device: Modbus RTU/TCP
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0751
  system: power_metering
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-LIGHTING-GUEST
  location: 3rd Floor Amenity
  panel: BMS-PNL-3F
  point_description: Feeder power meter (kW, kWh, V, A)
  type: Network
  field_device: Modbus RTU/TCP
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0752
  system: power_metering
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-LAUNDRY-LG
  location: Lower Ground Laundry
  panel: BMS-PNL-LG-PLUMB
  point_description: Feeder power meter (kW, kWh, V, A)
  type: Network
  field_device: Modbus RTU/TCP
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list
- id: P0753
  system: power_metering
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: PM-ROOFDECK-MECH
  location: Roof Deck Mechanical
  panel: BMS-PNL-RD-MECH
  point_description: Feeder power meter (kW, kWh, V, A)
  type: Network
  field_device: Modbus RTU/TCP
  c_o: BMS Contractor
  source: BMS Points list (TUEC) + ME/PL Points list