# B3 — Commissioning Point Inventory
#
metadata:
  project: "Kingsford Hotel Bacolod \u2014 BMS"
  generated_from: A1-io-list.yaml + A2-equipment-takeoff.yaml
  generator: _playbook/tools/generate-b1-b3-programming-and-commissioning.py
  rates:
    hrs_per_p2p_point: 0.15
    hrs_per_functional_test: 1.5
    hrs_per_integrated_test: 4.0
summary:
  p2p_points: 523
  functional_tests: 161
  integrated_tests: 8
  total_test_items: 692
tc_hours:
  point_to_point: 78.5
  functional_per_equipment: 241.5
  integrated_sequences: 32.0
  total_tc_hours: 352.0
  person_days_at_8hr: 44.0
p2p_breakdown_by_panel:
  PNL-2F: 138
  PNL-GF: 126
  PNL-3F: 105
  PNL-CHPLANT-GND: 65
  PNL-RD: 54
  PNL-BSMT: 23
  PNL-BOH-2F: 12
functional_test_inventory:
- equipment: AHU-AMEN-3F
  equipment_class: AHU (Chilled-Water-Served)
  location: 3F
- equipment: AHU-BALL-2F
  equipment_class: AHU (Chilled-Water-Served)
  location: 2F
- equipment: AHU-BOH-2F
  equipment_class: AHU (Chilled-Water-Served)
  location: 2F
- equipment: AHU-BOH-BSMT
  equipment_class: AHU (Chilled-Water-Served)
  location: Basement
- equipment: AHU-LOBBY-GF
  equipment_class: AHU (Chilled-Water-Served)
  location: GF
- equipment: AHU-REST-2F
  equipment_class: AHU (Chilled-Water-Served)
  location: 2F
- equipment: BTU-CHWS-MAIN
  equipment_class: BTU Meter
  location: Plant Room
- equipment: CAL-1
  equipment_class: Calorifier (Hot Water Storage Tank)
  location: Plant Room
- equipment: CAL-2
  equipment_class: Calorifier (Hot Water Storage Tank)
  location: Plant Room
- equipment: CAL-3
  equipment_class: Calorifier (Hot Water Storage Tank)
  location: Plant Room
- equipment: CAL-4
  equipment_class: Calorifier (Hot Water Storage Tank)
  location: Plant Room
- equipment: CAL-5
  equipment_class: Calorifier (Hot Water Storage Tank)
  location: Plant Room
- equipment: CAL-6
  equipment_class: Calorifier (Hot Water Storage Tank)
  location: Plant Room
- equipment: CH-1
  equipment_class: Chiller (Package Water-Cooled)
  location: Plant Room (Basement)
- equipment: CH-2
  equipment_class: Chiller (Package Water-Cooled)
  location: Plant Room (Basement)
- equipment: CH-3
  equipment_class: Chiller (Package Water-Cooled)
  location: Plant Room (Basement)
- equipment: CHWP-1.1
  equipment_class: Primary CHW Pump
  location: Plant Room
- equipment: CHWP-1.2
  equipment_class: Primary CHW Pump
  location: Plant Room
- equipment: CHWP-1.3
  equipment_class: Primary CHW Pump
  location: Plant Room
- equipment: CHWP-1.STBY
  equipment_class: Primary CHW Pump (Standby)
  location: Plant Room
- equipment: COWP-1
  equipment_class: Condenser Water Pump
  location: Plant Room
- equipment: COWP-2
  equipment_class: Condenser Water Pump
  location: Plant Room
- equipment: COWP-3
  equipment_class: Condenser Water Pump
  location: Plant Room
- equipment: CT-1
  equipment_class: Cooling Tower
  location: Roofdeck
- equipment: CT-2
  equipment_class: Cooling Tower
  location: Roofdeck
- equipment: CT-3
  equipment_class: Cooling Tower
  location: Roofdeck
- equipment: CT-COMMON
  equipment_class: Cooling Tower (Common)
  location: Roofdeck
- equipment: DOAS-2F
  equipment_class: DOAS Unit
  location: 2F
- equipment: DOAS-GF
  equipment_class: DOAS Unit
  location: GF
- equipment: DOAS-RD
  equipment_class: DOAS Unit
  location: Roofdeck
- equipment: EAS-2F
  equipment_class: Exhaust Fan (General)
  location: 2F
- equipment: EAS-3F
  equipment_class: Exhaust Fan (General)
  location: 3F
- equipment: EAS-BSMT
  equipment_class: Exhaust Fan (General)
  location: Basement
- equipment: EAS-GF
  equipment_class: Exhaust Fan (General)
  location: GF
- equipment: FCU-2F.01
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.02
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.03
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.04
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.05
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.06
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.07
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.08
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.09
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.10
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.11
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.12
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.13
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.14
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.15
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.16
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.17
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.18
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.19
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.20
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.21
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.22
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.23
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.24
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.25
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.26
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.27
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.28
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.29
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-2F.30
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 2F
- equipment: FCU-3F.01
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.02
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.03
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.04
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.05
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.06
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.07
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.08
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.09
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.10
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.11
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.12
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.13
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.14
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.15
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.16
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.17
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.18
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.19
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.20
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.21
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.22
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.23
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.24
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.25
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.26
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.27
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.28
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.29
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-3F.30
  equipment_class: FCU (guestroom/zone, hardwired)
  location: 3F
- equipment: FCU-GF.01
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.02
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.03
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.04
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.05
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.06
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.07
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.08
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.09
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.10
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.11
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.12
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.13
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.14
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.15
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.16
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.17
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.18
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.19
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.20
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.21
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.22
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.23
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.24
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.25
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.26
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.27
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.28
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.29
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: FCU-GF.30
  equipment_class: FCU (guestroom/zone, hardwired)
  location: GF
- equipment: HDR-CHW-BP
  equipment_class: CHW Bypass Header
  location: Plant Room
- equipment: HDR-CHWR
  equipment_class: CHW Return Main Header
  location: Plant Room
- equipment: HDR-CHWS
  equipment_class: CHW Supply Main Header
  location: Plant Room
- equipment: HDR-COW
  equipment_class: Condenser Water Header
  location: Roofdeck
- equipment: HDR-HW
  equipment_class: Hot Water Header Set
  location: Plant Room
- equipment: HP-1
  equipment_class: Heat Pump
  location: Plant Room
- equipment: HP-2
  equipment_class: Heat Pump
  location: Plant Room
- equipment: HP-3
  equipment_class: Heat Pump
  location: Plant Room
- equipment: MTR-FDR-01
  equipment_class: Multifunction Power Meter (Feeder)
  location: Sub-Distribution Board
- equipment: MTR-FDR-02
  equipment_class: Multifunction Power Meter (Feeder)
  location: Sub-Distribution Board
- equipment: MTR-FDR-03
  equipment_class: Multifunction Power Meter (Feeder)
  location: Sub-Distribution Board
- equipment: MTR-FDR-04
  equipment_class: Multifunction Power Meter (Feeder)
  location: Sub-Distribution Board
- equipment: MTR-FDR-05
  equipment_class: Multifunction Power Meter (Feeder)
  location: Sub-Distribution Board
- equipment: MTR-FDR-06
  equipment_class: Multifunction Power Meter (Feeder)
  location: Sub-Distribution Board
- equipment: MTR-FDR-07
  equipment_class: Multifunction Power Meter (Feeder)
  location: Sub-Distribution Board
- equipment: MTR-FDR-08
  equipment_class: Multifunction Power Meter (Feeder)
  location: Sub-Distribution Board
- equipment: MTR-FDR-09
  equipment_class: Multifunction Power Meter (Feeder)
  location: Sub-Distribution Board
- equipment: MTR-FDR-10
  equipment_class: Multifunction Power Meter (Feeder)
  location: Sub-Distribution Board
- equipment: MTR-MAIN-1
  equipment_class: Multifunction Power Meter (Main)
  location: Main Switchgear
- equipment: MTR-MAIN-2
  equipment_class: Multifunction Power Meter (Main)
  location: Main Switchgear
- equipment: MTR-MAIN-3
  equipment_class: Multifunction Power Meter (Main)
  location: Main Switchgear
- equipment: NET-PNL-2F
  equipment_class: BMS Network Drop
  location: panel
- equipment: NET-PNL-3F
  equipment_class: BMS Network Drop
  location: panel
- equipment: NET-PNL-BOH-2F
  equipment_class: BMS Network Drop
  location: panel
- equipment: NET-PNL-BSMT
  equipment_class: BMS Network Drop
  location: panel
- equipment: NET-PNL-CHPLANT-GND
  equipment_class: BMS Network Drop
  location: panel
- equipment: NET-PNL-GF
  equipment_class: BMS Network Drop
  location: panel
- equipment: NET-PNL-HE-GF
  equipment_class: BMS Network Drop
  location: panel
- equipment: NET-PNL-RD
  equipment_class: BMS Network Drop
  location: panel
- equipment: PAHU-RD
  equipment_class: Precooled Air Handling Unit
  location: Roofdeck
- equipment: RP-1
  equipment_class: Recirculating Pump
  location: Plant Room
- equipment: RP-2
  equipment_class: Recirculating Pump
  location: Plant Room
- equipment: RP-3
  equipment_class: Recirculating Pump
  location: Plant Room
- equipment: RP-4
  equipment_class: Recirculating Pump
  location: Plant Room
- equipment: RP-5
  equipment_class: Recirculating Pump
  location: Plant Room
- equipment: RP-6
  equipment_class: Recirculating Pump
  location: Plant Room
- equipment: SB-1
  equipment_class: Steam Boiler
  location: Basement
integrated_test_inventory:
- Chiller plant sequencing (chiller staging + CHW pump + COW pump + cooling tower fan)
- CHW differential pressure control (PCHWP VFD speed via header dP)
- AHU supply-air temperature control (modulating CHW valve loop)
- DOAS demand-controlled ventilation (CO2-based fresh air modulation)
- Hotwater system sequencing (heat pump + recirculating pump + tank temp)
- Boiler firing rate vs. steam pressure
- Cooling tower fan staging vs. condenser water temperature
- Energy savings algorithm verification (max-demand limiting + load shedding)
notes:
- 'P2P = point-to-point verification: every physical I/O calibrated, range-checked, polarity verified, scaled correctly.'
- 'Functional test: per-equipment sequence verification (e.g., does the AHU CHW valve modulate correctly to maintain supply air temp?).'
- 'Integrated test: cross-system sequence (e.g., chiller staging triggers correctly when load increases).'
- "Owner T&C / SAT: separate from this \u2014 handled in proposal as an item under 5.5 in WBS."