# A4 — Panel Schedule
# Generated from A1-io-list.yaml
#
metadata:
  project: "Kingsford Hotel Bacolod \u2014 BMS"
  generated_from: A1-io-list.yaml
  generator: _playbook/tools/generate-a4-panel-schedule.py
  controller_sizing_rule: 1 DDC controller per 40 physical I/O, +1 network gateway if Network drops present. Refine after Q-008 confirms wiring topology.
  power_estimate_basis: ~25W per controller, ~5W per network device. Excludes UPS/transformer overhead.
summary:
  total_panels: 8
  total_physical_io: 523
  total_hli_subpoints: 23
  total_network_drops: 8
  total_io_points: 554
  total_controllers_estimated: 21
  total_power_watts_estimated: 565
  panel_summary_table:
  - panel: PNL-2F
    location: 2F / panel
    physical_io: 138
    network: 1
    controllers: 4
    power_w: 105
    equipment_count: 35
  - panel: PNL-3F
    location: 3F / panel
    physical_io: 105
    network: 1
    controllers: 3
    power_w: 80
    equipment_count: 33
  - panel: PNL-BOH-2F
    location: 2F / panel
    physical_io: 12
    network: 1
    controllers: 2
    power_w: 55
    equipment_count: 2
  - panel: PNL-BSMT
    location: Basement / panel
    physical_io: 23
    network: 1
    controllers: 2
    power_w: 55
    equipment_count: 4
  - panel: PNL-CHPLANT-GND
    location: Plant Room / Plant Room (Basement) / panel
    physical_io: 65
    network: 1
    controllers: 2
    power_w: 55
    equipment_count: 31
  - panel: PNL-GF
    location: GF / Main Switchgear / Sub-Distribution Board / panel
    physical_io: 126
    network: 1
    controllers: 4
    power_w: 105
    equipment_count: 47
  - panel: PNL-HE-GF
    location: panel
    physical_io: 0
    network: 1
    controllers: 2
    power_w: 55
    equipment_count: 1
  - panel: PNL-RD
    location: Roofdeck / panel
    physical_io: 54
    network: 1
    controllers: 2
    power_w: 55
    equipment_count: 8
panels:
- id: PNL-2F
  location: 2F / panel
  system_scope:
  - Network
  - VENT-AHU
  - VENT-DOAS
  - VENT-EAS
  - VENT-FCU
  equipment_served:
    instance_count: 35
    instances:
    - AHU-BALL-2F
    - AHU-REST-2F
    - DOAS-2F
    - EAS-2F
    - FCU-2F.01
    - FCU-2F.02
    - FCU-2F.03
    - FCU-2F.04
    - FCU-2F.05
    - FCU-2F.06
    - FCU-2F.07
    - FCU-2F.08
    - FCU-2F.09
    - FCU-2F.10
    - FCU-2F.11
    - FCU-2F.12
    - FCU-2F.13
    - FCU-2F.14
    - FCU-2F.15
    - FCU-2F.16
    - FCU-2F.17
    - FCU-2F.18
    - FCU-2F.19
    - FCU-2F.20
    - FCU-2F.21
    - FCU-2F.22
    - FCU-2F.23
    - FCU-2F.24
    - FCU-2F.25
    - FCU-2F.26
    - FCU-2F.27
    - FCU-2F.28
    - FCU-2F.29
    - FCU-2F.30
    - NET-PNL-2F
    by_class:
      FCU (guestroom/zone, hardwired): 90
      AHU (Chilled-Water-Served): 24
      DOAS Unit: 21
      Exhaust Fan (General): 3
      BMS Network Drop: 1
  io_summary:
    physical_io: 138
    hli_subpoints: 0
    network_drops: 1
    total: 139
    by_type:
      AI: 19
      AO: 12
      DI: 47
      DO: 60
      Network: 1
    by_co:
      BMS Contractor: 14
      Equipment Supplier: 83
      ME Contractor: 42
  controller_estimate:
    ddc_controllers: 4
    network_gateway: 1
    total_controllers: 4
    rule: 1 DDC per 40 physical I/O, plus 1 network gateway if BACnet/Modbus integration on panel
  power_estimate_w: 105
  enclosure_assumption: Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
  notes: ''
- id: PNL-3F
  location: 3F / panel
  system_scope:
  - Network
  - VENT-AHU
  - VENT-EAS
  - VENT-FCU
  equipment_served:
    instance_count: 33
    instances:
    - AHU-AMEN-3F
    - EAS-3F
    - FCU-3F.01
    - FCU-3F.02
    - FCU-3F.03
    - FCU-3F.04
    - FCU-3F.05
    - FCU-3F.06
    - FCU-3F.07
    - FCU-3F.08
    - FCU-3F.09
    - FCU-3F.10
    - FCU-3F.11
    - FCU-3F.12
    - FCU-3F.13
    - FCU-3F.14
    - FCU-3F.15
    - FCU-3F.16
    - FCU-3F.17
    - FCU-3F.18
    - FCU-3F.19
    - FCU-3F.20
    - FCU-3F.21
    - FCU-3F.22
    - FCU-3F.23
    - FCU-3F.24
    - FCU-3F.25
    - FCU-3F.26
    - FCU-3F.27
    - FCU-3F.28
    - FCU-3F.29
    - FCU-3F.30
    - NET-PNL-3F
    by_class:
      FCU (guestroom/zone, hardwired): 90
      AHU (Chilled-Water-Served): 12
      Exhaust Fan (General): 3
      BMS Network Drop: 1
  io_summary:
    physical_io: 105
    hli_subpoints: 0
    network_drops: 1
    total: 106
    by_type:
      AI: 5
      AO: 4
      DI: 36
      DO: 60
      Network: 1
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 67
      ME Contractor: 34
  controller_estimate:
    ddc_controllers: 3
    network_gateway: 1
    total_controllers: 3
    rule: 1 DDC per 40 physical I/O, plus 1 network gateway if BACnet/Modbus integration on panel
  power_estimate_w: 80
  enclosure_assumption: Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
  notes: ''
- id: PNL-BOH-2F
  location: 2F / panel
  system_scope:
  - Network
  - VENT-AHU
  equipment_served:
    instance_count: 2
    instances:
    - AHU-BOH-2F
    - NET-PNL-BOH-2F
    by_class:
      AHU (Chilled-Water-Served): 12
      BMS Network Drop: 1
  io_summary:
    physical_io: 12
    hli_subpoints: 0
    network_drops: 1
    total: 13
    by_type:
      AI: 5
      AO: 4
      DI: 3
      Network: 1
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 4
      ME Contractor: 4
  controller_estimate:
    ddc_controllers: 1
    network_gateway: 1
    total_controllers: 2
    rule: 1 DDC per 40 physical I/O, plus 1 network gateway if BACnet/Modbus integration on panel
  power_estimate_w: 55
  enclosure_assumption: Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
  notes: ''
- id: PNL-BSMT
  location: Basement / panel
  system_scope:
  - Network
  - PL-Boiler
  - VENT-AHU
  - VENT-EAS
  equipment_served:
    instance_count: 4
    instances:
    - AHU-BOH-BSMT
    - EAS-BSMT
    - NET-PNL-BSMT
    - SB-1
    by_class:
      AHU (Chilled-Water-Served): 12
      Steam Boiler: 8
      Exhaust Fan (General): 3
      BMS Network Drop: 1
  io_summary:
    physical_io: 23
    hli_subpoints: 0
    network_drops: 1
    total: 24
    by_type:
      AI: 9
      AO: 5
      DI: 9
      Network: 1
    by_co:
      BMS Contractor: 10
      Equipment Supplier: 10
      ME Contractor: 4
  controller_estimate:
    ddc_controllers: 1
    network_gateway: 1
    total_controllers: 2
    rule: 1 DDC per 40 physical I/O, plus 1 network gateway if BACnet/Modbus integration on panel
  power_estimate_w: 55
  enclosure_assumption: Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
  notes: ''
- id: PNL-CHPLANT-GND
  location: Plant Room / Plant Room (Basement) / panel
  system_scope:
  - HVAC-Chillers
  - HVAC-Pumps
  - Network
  - PL-Calorifiers
  - PL-HeatPumps
  - PL-HotWater
  - PL-RecircPumps
  equipment_served:
    instance_count: 31
    instances:
    - BTU-CHWS-MAIN
    - CAL-1
    - CAL-2
    - CAL-3
    - CAL-4
    - CAL-5
    - CAL-6
    - CH-1
    - CH-2
    - CH-3
    - CHWP-1.1
    - CHWP-1.2
    - CHWP-1.3
    - CHWP-1.STBY
    - COWP-1
    - COWP-2
    - COWP-3
    - HDR-CHW-BP
    - HDR-CHWR
    - HDR-CHWS
    - HDR-HW
    - HP-1
    - HP-2
    - HP-3
    - NET-PNL-CHPLANT-GND
    - RP-1
    - RP-2
    - RP-3
    - RP-4
    - RP-5
    - RP-6
    by_class:
      Primary CHW Pump: 15
      Condenser Water Pump: 12
      Recirculating Pump: 12
      Heat Pump: 9
      Calorifier (Hot Water Storage Tank): 6
      Hot Water Header Set: 6
      Chiller (Package Water-Cooled): 3
      CHW Supply Main Header: 3
      CHW Return Main Header: 3
      CHW Bypass Header: 3
      Primary CHW Pump (Standby): 2
      BTU Meter: 1
      BMS Network Drop: 1
  io_summary:
    physical_io: 65
    hli_subpoints: 10
    network_drops: 1
    total: 76
    by_type:
      AI: 20
      AO: 1
      DI: 41
      DO: 3
      HLI: 10
      Network: 1
    by_co:
      BMS Contractor: 23
      Equipment Supplier: 53
  controller_estimate:
    ddc_controllers: 2
    network_gateway: 1
    total_controllers: 2
    rule: 1 DDC per 40 physical I/O, plus 1 network gateway if BACnet/Modbus integration on panel
  power_estimate_w: 55
  enclosure_assumption: Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
  notes: ''
- id: PNL-GF
  location: GF / Main Switchgear / Sub-Distribution Board / panel
  system_scope:
  - Network
  - Power-EE
  - VENT-AHU
  - VENT-DOAS
  - VENT-EAS
  - VENT-FCU
  equipment_served:
    instance_count: 47
    instances:
    - AHU-LOBBY-GF
    - DOAS-GF
    - EAS-GF
    - FCU-GF.01
    - FCU-GF.02
    - FCU-GF.03
    - FCU-GF.04
    - FCU-GF.05
    - FCU-GF.06
    - FCU-GF.07
    - FCU-GF.08
    - FCU-GF.09
    - FCU-GF.10
    - FCU-GF.11
    - FCU-GF.12
    - FCU-GF.13
    - FCU-GF.14
    - FCU-GF.15
    - FCU-GF.16
    - FCU-GF.17
    - FCU-GF.18
    - FCU-GF.19
    - FCU-GF.20
    - FCU-GF.21
    - FCU-GF.22
    - FCU-GF.23
    - FCU-GF.24
    - FCU-GF.25
    - FCU-GF.26
    - FCU-GF.27
    - FCU-GF.28
    - FCU-GF.29
    - FCU-GF.30
    - MTR-FDR-01
    - MTR-FDR-02
    - MTR-FDR-03
    - MTR-FDR-04
    - MTR-FDR-05
    - MTR-FDR-06
    - MTR-FDR-07
    - MTR-FDR-08
    - MTR-FDR-09
    - MTR-FDR-10
    - MTR-MAIN-1
    - MTR-MAIN-2
    - MTR-MAIN-3
    - NET-PNL-GF
    by_class:
      FCU (guestroom/zone, hardwired): 90
      DOAS Unit: 21
      AHU (Chilled-Water-Served): 12
      Multifunction Power Meter (Feeder): 10
      Exhaust Fan (General): 3
      Multifunction Power Meter (Main): 3
      BMS Network Drop: 1
  io_summary:
    physical_io: 126
    hli_subpoints: 13
    network_drops: 1
    total: 140
    by_type:
      AI: 14
      AO: 8
      DI: 44
      DO: 60
      HLI: 13
      Network: 1
    by_co:
      BMS Contractor: 23
      Equipment Supplier: 79
      ME Contractor: 38
  controller_estimate:
    ddc_controllers: 4
    network_gateway: 1
    total_controllers: 4
    rule: 1 DDC per 40 physical I/O, plus 1 network gateway if BACnet/Modbus integration on panel
  power_estimate_w: 105
  enclosure_assumption: Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
  notes: ''
- id: PNL-HE-GF
  location: panel
  system_scope:
  - Network
  equipment_served:
    instance_count: 1
    instances:
    - NET-PNL-HE-GF
    by_class:
      BMS Network Drop: 1
  io_summary:
    physical_io: 0
    hli_subpoints: 0
    network_drops: 1
    total: 1
    by_type:
      Network: 1
    by_co:
      BMS Contractor: 1
  controller_estimate:
    ddc_controllers: 1
    network_gateway: 1
    total_controllers: 2
    rule: 1 DDC per 40 physical I/O, plus 1 network gateway if BACnet/Modbus integration on panel
  power_estimate_w: 55
  enclosure_assumption: Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
  notes: ''
- id: PNL-RD
  location: Roofdeck / panel
  system_scope:
  - HVAC-Chillers
  - HVAC-Cooling-Towers
  - Network
  - VENT-DOAS
  - VENT-PAHU
  equipment_served:
    instance_count: 8
    instances:
    - CT-1
    - CT-2
    - CT-3
    - CT-COMMON
    - DOAS-RD
    - HDR-COW
    - NET-PNL-RD
    - PAHU-RD
    by_class:
      DOAS Unit: 21
      Cooling Tower: 18
      Precooled Air Handling Unit: 10
      Condenser Water Header: 3
      Cooling Tower (Common): 2
      BMS Network Drop: 1
  io_summary:
    physical_io: 54
    hli_subpoints: 0
    network_drops: 1
    total: 55
    by_type:
      AI: 21
      AO: 10
      DI: 23
      Network: 1
    by_co:
      BMS Contractor: 17
      Equipment Supplier: 32
      ME Contractor: 6
  controller_estimate:
    ddc_controllers: 2
    network_gateway: 1
    total_controllers: 2
    rule: 1 DDC per 40 physical I/O, plus 1 network gateway if BACnet/Modbus integration on panel
  power_estimate_w: 55
  enclosure_assumption: Wall-mount IP54 metal cabinet, sized per controller count + 30% spare
  notes: ''