# A2 — Equipment Takeoff
# Generated from A1-io-list.yaml on $(date) — see metadata.generator
# Schema: see _playbook/checklists/working-documents.md (A2)
#
metadata:
  project: "Kingsford Hotel Bacolod \u2014 BMS"
  generated_from: A1-io-list.yaml
  generator: _playbook/tools/generate-a2-equipment-takeoff.py
  regenerate: Re-run the generator after A1 changes. Hand edits to make_model_assumed and notes can be preserved by editing equipment-class-defaults.yaml or adding per-instance overrides below.
summary:
  total_instances: 161
  by_equipment_class:
    FCU (guestroom/zone, hardwired): 90
    Multifunction Power Meter (Feeder): 10
    BMS Network Drop: 8
    AHU (Chilled-Water-Served): 6
    Calorifier (Hot Water Storage Tank): 6
    Recirculating Pump: 6
    Exhaust Fan (General): 4
    Chiller (Package Water-Cooled): 3
    Primary CHW Pump: 3
    Condenser Water Pump: 3
    Cooling Tower: 3
    DOAS Unit: 3
    Heat Pump: 3
    Multifunction Power Meter (Main): 3
    BTU Meter: 1
    Primary CHW Pump (Standby): 1
    Cooling Tower (Common): 1
    CHW Bypass Header: 1
    CHW Return Main Header: 1
    CHW Supply Main Header: 1
    Condenser Water Header: 1
    Hot Water Header Set: 1
    Precooled Air Handling Unit: 1
    Steam Boiler: 1
  by_location:
    2F: 35
    GF: 33
    3F: 32
    Plant Room: 27
    Sub-Distribution Board: 10
    panel: 8
    Roofdeck: 7
    Basement: 3
    Plant Room (Basement): 3
    Main Switchgear: 3
  by_panel:
    PNL-GF: 47
    PNL-2F: 35
    PNL-3F: 33
    PNL-CHPLANT-GND: 31
    PNL-RD: 8
    PNL-BSMT: 4
    PNL-BOH-2F: 2
    PNL-HE-GF: 1
  by_primary_co:
    Equipment Supplier: 120
    BMS Contractor: 41
takeoff:
- id: AHU-AMEN-3F
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: 3F
  system: VENT-AHU
  panel: PNL-3F
  primary_co: BMS Contractor
  io_summary:
    physical_io: 12
    hli_subpoints: 0
    network_drops: 0
    total: 12
    by_type:
      AI: 5
      AO: 4
      DI: 3
    by_co:
      BMS Contractor: 4
      Equipment Supplier: 4
      ME Contractor: 4
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: AHU-BALL-2F
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: 2F
  system: VENT-AHU
  panel: PNL-2F
  primary_co: BMS Contractor
  io_summary:
    physical_io: 12
    hli_subpoints: 0
    network_drops: 0
    total: 12
    by_type:
      AI: 5
      AO: 4
      DI: 3
    by_co:
      BMS Contractor: 4
      Equipment Supplier: 4
      ME Contractor: 4
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: AHU-BOH-2F
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: 2F
  system: VENT-AHU
  panel: PNL-BOH-2F
  primary_co: BMS Contractor
  io_summary:
    physical_io: 12
    hli_subpoints: 0
    network_drops: 0
    total: 12
    by_type:
      AI: 5
      AO: 4
      DI: 3
    by_co:
      BMS Contractor: 4
      Equipment Supplier: 4
      ME Contractor: 4
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: AHU-BOH-BSMT
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: Basement
  system: VENT-AHU
  panel: PNL-BSMT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 12
    hli_subpoints: 0
    network_drops: 0
    total: 12
    by_type:
      AI: 5
      AO: 4
      DI: 3
    by_co:
      BMS Contractor: 4
      Equipment Supplier: 4
      ME Contractor: 4
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: AHU-LOBBY-GF
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: GF
  system: VENT-AHU
  panel: PNL-GF
  primary_co: BMS Contractor
  io_summary:
    physical_io: 12
    hli_subpoints: 0
    network_drops: 0
    total: 12
    by_type:
      AI: 5
      AO: 4
      DI: 3
    by_co:
      BMS Contractor: 4
      Equipment Supplier: 4
      ME Contractor: 4
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: AHU-REST-2F
  equipment_class: AHU (Chilled-Water-Served)
  quantity: 1
  location: 2F
  system: VENT-AHU
  panel: PNL-2F
  primary_co: BMS Contractor
  io_summary:
    physical_io: 12
    hli_subpoints: 0
    network_drops: 0
    total: 12
    by_type:
      AI: 5
      AO: 4
      DI: 3
    by_co:
      BMS Contractor: 4
      Equipment Supplier: 4
      ME Contractor: 4
  make_model_assumed: Standard CHW-served AHU with VFD-driven supply fan, modulating CHW valve, and OA/RA dampers
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: BMS supplies sensors (T/RH/CO2). Dampers and CHW valve supplied by ME contractor. Fan + VFD by Equipment Supplier.
- id: BTU-CHWS-MAIN
  equipment_class: BTU Meter
  quantity: 1
  location: Plant Room
  system: HVAC-Chillers
  panel: PNL-CHPLANT-GND
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 1
    network_drops: 0
    total: 1
    by_type:
      HLI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Ultrasonic or insertion-type BTU meter with Modbus output (Onicon, Aichi, Kamstrup)
  network_type: Modbus RTU/TCP
  typical_supplier: BMS contractor
  notes: System-level energy submeter.
- id: CAL-1
  equipment_class: Calorifier (Hot Water Storage Tank)
  quantity: 1
  location: Plant Room
  system: PL-Calorifiers
  panel: PNL-CHPLANT-GND
  primary_co: BMS Contractor
  io_summary:
    physical_io: 1
    hli_subpoints: 0
    network_drops: 0
    total: 1
    by_type:
      AI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Pressurised hot-water storage tank with internal coil, sized per design hot water demand
  network_type: Hardwired
  typical_supplier: Plumbing contractor
  notes: BMS supplies tank temperature sensor (immersion or strapped probe).
- id: CAL-2
  equipment_class: Calorifier (Hot Water Storage Tank)
  quantity: 1
  location: Plant Room
  system: PL-Calorifiers
  panel: PNL-CHPLANT-GND
  primary_co: BMS Contractor
  io_summary:
    physical_io: 1
    hli_subpoints: 0
    network_drops: 0
    total: 1
    by_type:
      AI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Pressurised hot-water storage tank with internal coil, sized per design hot water demand
  network_type: Hardwired
  typical_supplier: Plumbing contractor
  notes: BMS supplies tank temperature sensor (immersion or strapped probe).
- id: CAL-3
  equipment_class: Calorifier (Hot Water Storage Tank)
  quantity: 1
  location: Plant Room
  system: PL-Calorifiers
  panel: PNL-CHPLANT-GND
  primary_co: BMS Contractor
  io_summary:
    physical_io: 1
    hli_subpoints: 0
    network_drops: 0
    total: 1
    by_type:
      AI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Pressurised hot-water storage tank with internal coil, sized per design hot water demand
  network_type: Hardwired
  typical_supplier: Plumbing contractor
  notes: BMS supplies tank temperature sensor (immersion or strapped probe).
- id: CAL-4
  equipment_class: Calorifier (Hot Water Storage Tank)
  quantity: 1
  location: Plant Room
  system: PL-Calorifiers
  panel: PNL-CHPLANT-GND
  primary_co: BMS Contractor
  io_summary:
    physical_io: 1
    hli_subpoints: 0
    network_drops: 0
    total: 1
    by_type:
      AI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Pressurised hot-water storage tank with internal coil, sized per design hot water demand
  network_type: Hardwired
  typical_supplier: Plumbing contractor
  notes: BMS supplies tank temperature sensor (immersion or strapped probe).
- id: CAL-5
  equipment_class: Calorifier (Hot Water Storage Tank)
  quantity: 1
  location: Plant Room
  system: PL-Calorifiers
  panel: PNL-CHPLANT-GND
  primary_co: BMS Contractor
  io_summary:
    physical_io: 1
    hli_subpoints: 0
    network_drops: 0
    total: 1
    by_type:
      AI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Pressurised hot-water storage tank with internal coil, sized per design hot water demand
  network_type: Hardwired
  typical_supplier: Plumbing contractor
  notes: BMS supplies tank temperature sensor (immersion or strapped probe).
- id: CAL-6
  equipment_class: Calorifier (Hot Water Storage Tank)
  quantity: 1
  location: Plant Room
  system: PL-Calorifiers
  panel: PNL-CHPLANT-GND
  primary_co: BMS Contractor
  io_summary:
    physical_io: 1
    hli_subpoints: 0
    network_drops: 0
    total: 1
    by_type:
      AI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Pressurised hot-water storage tank with internal coil, sized per design hot water demand
  network_type: Hardwired
  typical_supplier: Plumbing contractor
  notes: BMS supplies tank temperature sensor (immersion or strapped probe).
- id: CH-1
  equipment_class: Chiller (Package Water-Cooled)
  quantity: 1
  location: Plant Room (Basement)
  system: HVAC-Chillers
  panel: PNL-CHPLANT-GND
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 0
    hli_subpoints: 1
    network_drops: 0
    total: 1
    by_type:
      HLI: 1
    by_co:
      Equipment Supplier: 1
  make_model_assumed: Tier-1 BACnet IP chiller (Trane/York/Carrier/Daikin), water-cooled centrifugal or screw, sized per design cooling load
  network_type: BACnet/IP
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: BMS reads via chiller's native BACnet gateway. BMS supplies external T-sensors on entering/leaving CHW & CW pipes.
- id: CH-2
  equipment_class: Chiller (Package Water-Cooled)
  quantity: 1
  location: Plant Room (Basement)
  system: HVAC-Chillers
  panel: PNL-CHPLANT-GND
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 0
    hli_subpoints: 1
    network_drops: 0
    total: 1
    by_type:
      HLI: 1
    by_co:
      Equipment Supplier: 1
  make_model_assumed: Tier-1 BACnet IP chiller (Trane/York/Carrier/Daikin), water-cooled centrifugal or screw, sized per design cooling load
  network_type: BACnet/IP
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: BMS reads via chiller's native BACnet gateway. BMS supplies external T-sensors on entering/leaving CHW & CW pipes.
- id: CH-3
  equipment_class: Chiller (Package Water-Cooled)
  quantity: 1
  location: Plant Room (Basement)
  system: HVAC-Chillers
  panel: PNL-CHPLANT-GND
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 0
    hli_subpoints: 1
    network_drops: 0
    total: 1
    by_type:
      HLI: 1
    by_co:
      Equipment Supplier: 1
  make_model_assumed: Tier-1 BACnet IP chiller (Trane/York/Carrier/Daikin), water-cooled centrifugal or screw, sized per design cooling load
  network_type: BACnet/IP
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: BMS reads via chiller's native BACnet gateway. BMS supplies external T-sensors on entering/leaving CHW & CW pipes.
- id: CHWP-1.1
  equipment_class: Primary CHW Pump
  quantity: 1
  location: Plant Room
  system: HVAC-Pumps
  panel: PNL-CHPLANT-GND
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 2
    network_drops: 0
    total: 5
    by_type:
      DI: 3
      HLI: 2
    by_co:
      Equipment Supplier: 5
  make_model_assumed: End-suction or split-case centrifugal with VFD, sized per design CHW flow
  network_type: Hardwired (BMS reads VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: VFD typically Equipment Supplier provided with BACnet card.
- id: CHWP-1.2
  equipment_class: Primary CHW Pump
  quantity: 1
  location: Plant Room
  system: HVAC-Pumps
  panel: PNL-CHPLANT-GND
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 2
    network_drops: 0
    total: 5
    by_type:
      DI: 3
      HLI: 2
    by_co:
      Equipment Supplier: 5
  make_model_assumed: End-suction or split-case centrifugal with VFD, sized per design CHW flow
  network_type: Hardwired (BMS reads VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: VFD typically Equipment Supplier provided with BACnet card.
- id: CHWP-1.3
  equipment_class: Primary CHW Pump
  quantity: 1
  location: Plant Room
  system: HVAC-Pumps
  panel: PNL-CHPLANT-GND
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 2
    network_drops: 0
    total: 5
    by_type:
      DI: 3
      HLI: 2
    by_co:
      Equipment Supplier: 5
  make_model_assumed: End-suction or split-case centrifugal with VFD, sized per design CHW flow
  network_type: Hardwired (BMS reads VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: VFD typically Equipment Supplier provided with BACnet card.
- id: CHWP-1.STBY
  equipment_class: Primary CHW Pump (Standby)
  quantity: 1
  location: Plant Room
  system: HVAC-Pumps
  panel: PNL-CHPLANT-GND
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 2
    hli_subpoints: 0
    network_drops: 0
    total: 2
    by_type:
      DI: 2
    by_co:
      Equipment Supplier: 2
  make_model_assumed: Same as Primary CHW Pump (1 standby for N+1 redundancy)
  network_type: Hardwired (BMS reads VFD via BACnet HLI)
  typical_supplier: Mechanical contractor
  notes: Standby unit per A-CHW-001.
- id: COWP-1
  equipment_class: Condenser Water Pump
  quantity: 1
  location: Plant Room
  system: HVAC-Pumps
  panel: PNL-CHPLANT-GND
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 4
    hli_subpoints: 0
    network_drops: 0
    total: 4
    by_type:
      DI: 3
      DO: 1
    by_co:
      Equipment Supplier: 4
  make_model_assumed: End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious)
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: BMS reads aux contacts; commands start via DO.
- id: COWP-2
  equipment_class: Condenser Water Pump
  quantity: 1
  location: Plant Room
  system: HVAC-Pumps
  panel: PNL-CHPLANT-GND
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 4
    hli_subpoints: 0
    network_drops: 0
    total: 4
    by_type:
      DI: 3
      DO: 1
    by_co:
      Equipment Supplier: 4
  make_model_assumed: End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious)
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: BMS reads aux contacts; commands start via DO.
- id: COWP-3
  equipment_class: Condenser Water Pump
  quantity: 1
  location: Plant Room
  system: HVAC-Pumps
  panel: PNL-CHPLANT-GND
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 4
    hli_subpoints: 0
    network_drops: 0
    total: 4
    by_type:
      DI: 3
      DO: 1
    by_co:
      Equipment Supplier: 4
  make_model_assumed: End-suction or split-case centrifugal, fixed-speed (typical) or VFD (energy-conscious)
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: BMS reads aux contacts; commands start via DO.
- id: CT-1
  equipment_class: Cooling Tower
  quantity: 1
  location: Roofdeck
  system: HVAC-Cooling-Towers
  panel: PNL-RD
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 6
    hli_subpoints: 0
    network_drops: 0
    total: 6
    by_type:
      AI: 1
      AO: 1
      DI: 4
    by_co:
      BMS Contractor: 1
      Equipment Supplier: 5
  make_model_assumed: Induced-draft counterflow open cooling tower (Marley/BAC/EVAPCO), sized per condenser water flow
  network_type: Hardwired
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: BMS supplies basin level sensors and condenser water header T-sensors.
- id: CT-2
  equipment_class: Cooling Tower
  quantity: 1
  location: Roofdeck
  system: HVAC-Cooling-Towers
  panel: PNL-RD
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 6
    hli_subpoints: 0
    network_drops: 0
    total: 6
    by_type:
      AI: 1
      AO: 1
      DI: 4
    by_co:
      BMS Contractor: 1
      Equipment Supplier: 5
  make_model_assumed: Induced-draft counterflow open cooling tower (Marley/BAC/EVAPCO), sized per condenser water flow
  network_type: Hardwired
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: BMS supplies basin level sensors and condenser water header T-sensors.
- id: CT-3
  equipment_class: Cooling Tower
  quantity: 1
  location: Roofdeck
  system: HVAC-Cooling-Towers
  panel: PNL-RD
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 6
    hli_subpoints: 0
    network_drops: 0
    total: 6
    by_type:
      AI: 1
      AO: 1
      DI: 4
    by_co:
      BMS Contractor: 1
      Equipment Supplier: 5
  make_model_assumed: Induced-draft counterflow open cooling tower (Marley/BAC/EVAPCO), sized per condenser water flow
  network_type: Hardwired
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: BMS supplies basin level sensors and condenser water header T-sensors.
- id: CT-COMMON
  equipment_class: Cooling Tower (Common)
  quantity: 1
  location: Roofdeck
  system: HVAC-Cooling-Towers
  panel: PNL-RD
  primary_co: BMS Contractor
  io_summary:
    physical_io: 2
    hli_subpoints: 0
    network_drops: 0
    total: 2
    by_type:
      AI: 2
    by_co:
      BMS Contractor: 2
  make_model_assumed: Common BMS sensors at cooling tower area (OA T/RH, condenser headers)
  network_type: Hardwired
  typical_supplier: BMS contractor
  notes: "Field instrumentation only \u2014 no equipment per se."
- id: DOAS-2F
  equipment_class: DOAS Unit
  quantity: 1
  location: 2F
  system: VENT-DOAS
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 21
    hli_subpoints: 0
    network_drops: 0
    total: 21
    by_type:
      AI: 9
      AO: 4
      DI: 8
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 12
      ME Contractor: 4
  make_model_assumed: Dedicated Outdoor Air System with energy recovery wheel, supply + exhaust fans, CHW coil
  network_type: BACnet/IP
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: Native BACnet controller typical. BMS supplies external sensors (OA T/RH/Flow, indoor T/RH, exhaust T) and modulating valve actuator.
- id: DOAS-GF
  equipment_class: DOAS Unit
  quantity: 1
  location: GF
  system: VENT-DOAS
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 21
    hli_subpoints: 0
    network_drops: 0
    total: 21
    by_type:
      AI: 9
      AO: 4
      DI: 8
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 12
      ME Contractor: 4
  make_model_assumed: Dedicated Outdoor Air System with energy recovery wheel, supply + exhaust fans, CHW coil
  network_type: BACnet/IP
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: Native BACnet controller typical. BMS supplies external sensors (OA T/RH/Flow, indoor T/RH, exhaust T) and modulating valve actuator.
- id: DOAS-RD
  equipment_class: DOAS Unit
  quantity: 1
  location: Roofdeck
  system: VENT-DOAS
  panel: PNL-RD
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 21
    hli_subpoints: 0
    network_drops: 0
    total: 21
    by_type:
      AI: 9
      AO: 4
      DI: 8
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 12
      ME Contractor: 4
  make_model_assumed: Dedicated Outdoor Air System with energy recovery wheel, supply + exhaust fans, CHW coil
  network_type: BACnet/IP
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: Native BACnet controller typical. BMS supplies external sensors (OA T/RH/Flow, indoor T/RH, exhaust T) and modulating valve actuator.
- id: EAS-2F
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 2F
  system: VENT-EAS
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EAS-3F
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: 3F
  system: VENT-EAS
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EAS-BSMT
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: Basement
  system: VENT-EAS
  panel: PNL-BSMT
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: EAS-GF
  equipment_class: Exhaust Fan (General)
  quantity: 1
  location: GF
  system: VENT-EAS
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Constant-speed in-line, ceiling, or roof-mounted general exhaust fan
  network_type: Hardwired
  typical_supplier: Mechanical contractor
  notes: "BMS reads aux contacts only \u2014 no control points."
- id: FCU-2F.01
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.02
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.03
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.04
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.05
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.06
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.07
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.08
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.09
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.10
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.11
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.12
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.13
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.14
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.15
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.16
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.17
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.18
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.19
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.20
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.21
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.22
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.23
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.24
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.25
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.26
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.27
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.28
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.29
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-2F.30
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 2F
  system: VENT-FCU
  panel: PNL-2F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.01
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.02
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.03
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.04
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.05
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.06
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.07
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.08
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.09
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.10
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.11
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.12
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.13
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.14
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.15
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.16
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.17
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.18
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.19
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.20
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.21
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.22
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.23
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.24
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.25
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.26
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.27
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.28
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.29
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-3F.30
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: 3F
  system: VENT-FCU
  panel: PNL-3F
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.01
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.02
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.03
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.04
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.05
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.06
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.07
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.08
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.09
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.10
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.11
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.12
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.13
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.14
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.15
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.16
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.17
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.18
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.19
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.20
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.21
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.22
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.23
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.24
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.25
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.26
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.27
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.28
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.29
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: FCU-GF.30
  equipment_class: FCU (guestroom/zone, hardwired)
  quantity: 1
  location: GF
  system: VENT-FCU
  panel: PNL-GF
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 1
      DO: 2
    by_co:
      Equipment Supplier: 2
      ME Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: HDR-CHW-BP
  equipment_class: CHW Bypass Header
  quantity: 1
  location: Plant Room
  system: HVAC-Chillers
  panel: PNL-CHPLANT-GND
  primary_co: BMS Contractor
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      AI: 2
      AO: 1
    by_co:
      BMS Contractor: 3
  make_model_assumed: BMS dP/dT sensors + motorized bypass valve (BMS-supplied)
  network_type: Hardwired
  typical_supplier: BMS contractor
  notes: BMS controls bypass valve to maintain CHW differential.
- id: HDR-CHWR
  equipment_class: CHW Return Main Header
  quantity: 1
  location: Plant Room
  system: HVAC-Chillers
  panel: PNL-CHPLANT-GND
  primary_co: BMS Contractor
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      AI: 3
    by_co:
      BMS Contractor: 3
  make_model_assumed: BMS T+P sensors on CHW return manifold
  network_type: Hardwired
  typical_supplier: BMS contractor
  notes: Field instrumentation only.
- id: HDR-CHWS
  equipment_class: CHW Supply Main Header
  quantity: 1
  location: Plant Room
  system: HVAC-Chillers
  panel: PNL-CHPLANT-GND
  primary_co: BMS Contractor
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      AI: 3
    by_co:
      BMS Contractor: 3
  make_model_assumed: BMS T+P sensors on CHW supply manifold
  network_type: Hardwired
  typical_supplier: BMS contractor
  notes: Field instrumentation only.
- id: HDR-COW
  equipment_class: Condenser Water Header
  quantity: 1
  location: Roofdeck
  system: HVAC-Chillers
  panel: PNL-RD
  primary_co: BMS Contractor
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      AI: 3
    by_co:
      BMS Contractor: 3
  make_model_assumed: BMS T sensors on condenser water headers at roofdeck
  network_type: Hardwired
  typical_supplier: BMS contractor
  notes: Field instrumentation only.
- id: HDR-HW
  equipment_class: Hot Water Header Set
  quantity: 1
  location: Plant Room
  system: PL-HotWater
  panel: PNL-CHPLANT-GND
  primary_co: BMS Contractor
  io_summary:
    physical_io: 6
    hli_subpoints: 0
    network_drops: 0
    total: 6
    by_type:
      AI: 6
    by_co:
      BMS Contractor: 6
  make_model_assumed: Hot water supply/return manifolds with BMS T sensors and make-up cold water T sensor
  network_type: Hardwired
  typical_supplier: BMS contractor
  notes: Field instrumentation on existing piping.
- id: HP-1
  equipment_class: Heat Pump
  quantity: 1
  location: Plant Room
  system: PL-HeatPumps
  panel: PNL-CHPLANT-GND
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Air-source or water-source heat pump for hot water heating
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor / Equipment supplier
  notes: BMS reads pump status/HOA/trip via aux contacts.
- id: HP-2
  equipment_class: Heat Pump
  quantity: 1
  location: Plant Room
  system: PL-HeatPumps
  panel: PNL-CHPLANT-GND
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Air-source or water-source heat pump for hot water heating
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor / Equipment supplier
  notes: BMS reads pump status/HOA/trip via aux contacts.
- id: HP-3
  equipment_class: Heat Pump
  quantity: 1
  location: Plant Room
  system: PL-HeatPumps
  panel: PNL-CHPLANT-GND
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 3
    hli_subpoints: 0
    network_drops: 0
    total: 3
    by_type:
      DI: 3
    by_co:
      Equipment Supplier: 3
  make_model_assumed: Air-source or water-source heat pump for hot water heating
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor / Equipment supplier
  notes: BMS reads pump status/HOA/trip via aux contacts.
- id: MTR-FDR-01
  equipment_class: Multifunction Power Meter (Feeder)
  quantity: 1
  location: Sub-Distribution Board
  system: Power-EE
  panel: PNL-GF
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 1
    network_drops: 0
    total: 1
    by_type:
      HLI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)
  network_type: Modbus RTU
  typical_supplier: BMS contractor
  notes: Daisy-chained on Modbus bus(es) back to BMS gateway.
- id: MTR-FDR-02
  equipment_class: Multifunction Power Meter (Feeder)
  quantity: 1
  location: Sub-Distribution Board
  system: Power-EE
  panel: PNL-GF
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 1
    network_drops: 0
    total: 1
    by_type:
      HLI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)
  network_type: Modbus RTU
  typical_supplier: BMS contractor
  notes: Daisy-chained on Modbus bus(es) back to BMS gateway.
- id: MTR-FDR-03
  equipment_class: Multifunction Power Meter (Feeder)
  quantity: 1
  location: Sub-Distribution Board
  system: Power-EE
  panel: PNL-GF
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 1
    network_drops: 0
    total: 1
    by_type:
      HLI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)
  network_type: Modbus RTU
  typical_supplier: BMS contractor
  notes: Daisy-chained on Modbus bus(es) back to BMS gateway.
- id: MTR-FDR-04
  equipment_class: Multifunction Power Meter (Feeder)
  quantity: 1
  location: Sub-Distribution Board
  system: Power-EE
  panel: PNL-GF
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 1
    network_drops: 0
    total: 1
    by_type:
      HLI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)
  network_type: Modbus RTU
  typical_supplier: BMS contractor
  notes: Daisy-chained on Modbus bus(es) back to BMS gateway.
- id: MTR-FDR-05
  equipment_class: Multifunction Power Meter (Feeder)
  quantity: 1
  location: Sub-Distribution Board
  system: Power-EE
  panel: PNL-GF
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 1
    network_drops: 0
    total: 1
    by_type:
      HLI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)
  network_type: Modbus RTU
  typical_supplier: BMS contractor
  notes: Daisy-chained on Modbus bus(es) back to BMS gateway.
- id: MTR-FDR-06
  equipment_class: Multifunction Power Meter (Feeder)
  quantity: 1
  location: Sub-Distribution Board
  system: Power-EE
  panel: PNL-GF
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 1
    network_drops: 0
    total: 1
    by_type:
      HLI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)
  network_type: Modbus RTU
  typical_supplier: BMS contractor
  notes: Daisy-chained on Modbus bus(es) back to BMS gateway.
- id: MTR-FDR-07
  equipment_class: Multifunction Power Meter (Feeder)
  quantity: 1
  location: Sub-Distribution Board
  system: Power-EE
  panel: PNL-GF
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 1
    network_drops: 0
    total: 1
    by_type:
      HLI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)
  network_type: Modbus RTU
  typical_supplier: BMS contractor
  notes: Daisy-chained on Modbus bus(es) back to BMS gateway.
- id: MTR-FDR-08
  equipment_class: Multifunction Power Meter (Feeder)
  quantity: 1
  location: Sub-Distribution Board
  system: Power-EE
  panel: PNL-GF
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 1
    network_drops: 0
    total: 1
    by_type:
      HLI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)
  network_type: Modbus RTU
  typical_supplier: BMS contractor
  notes: Daisy-chained on Modbus bus(es) back to BMS gateway.
- id: MTR-FDR-09
  equipment_class: Multifunction Power Meter (Feeder)
  quantity: 1
  location: Sub-Distribution Board
  system: Power-EE
  panel: PNL-GF
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 1
    network_drops: 0
    total: 1
    by_type:
      HLI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)
  network_type: Modbus RTU
  typical_supplier: BMS contractor
  notes: Daisy-chained on Modbus bus(es) back to BMS gateway.
- id: MTR-FDR-10
  equipment_class: Multifunction Power Meter (Feeder)
  quantity: 1
  location: Sub-Distribution Board
  system: Power-EE
  panel: PNL-GF
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 1
    network_drops: 0
    total: 1
    by_type:
      HLI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Multifunction power meter with Modbus output, sub-feeder class (smaller form factor)
  network_type: Modbus RTU
  typical_supplier: BMS contractor
  notes: Daisy-chained on Modbus bus(es) back to BMS gateway.
- id: MTR-MAIN-1
  equipment_class: Multifunction Power Meter (Main)
  quantity: 1
  location: Main Switchgear
  system: Power-EE
  panel: PNL-GF
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 1
    network_drops: 0
    total: 1
    by_type:
      HLI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Multifunction power meter with Modbus output (Schneider PM-series, ABB M2M, Siemens SENTRON), main switchgear class
  network_type: Modbus RTU/TCP
  typical_supplier: BMS contractor
  notes: Mounted in main switchgear or on dedicated BMS-side panel.
- id: MTR-MAIN-2
  equipment_class: Multifunction Power Meter (Main)
  quantity: 1
  location: Main Switchgear
  system: Power-EE
  panel: PNL-GF
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 1
    network_drops: 0
    total: 1
    by_type:
      HLI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Multifunction power meter with Modbus output (Schneider PM-series, ABB M2M, Siemens SENTRON), main switchgear class
  network_type: Modbus RTU/TCP
  typical_supplier: BMS contractor
  notes: Mounted in main switchgear or on dedicated BMS-side panel.
- id: MTR-MAIN-3
  equipment_class: Multifunction Power Meter (Main)
  quantity: 1
  location: Main Switchgear
  system: Power-EE
  panel: PNL-GF
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 1
    network_drops: 0
    total: 1
    by_type:
      HLI: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: Multifunction power meter with Modbus output (Schneider PM-series, ABB M2M, Siemens SENTRON), main switchgear class
  network_type: Modbus RTU/TCP
  typical_supplier: BMS contractor
  notes: Mounted in main switchgear or on dedicated BMS-side panel.
- id: NET-PNL-2F
  equipment_class: BMS Network Drop
  quantity: 1
  location: panel
  system: Network
  panel: PNL-2F
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 0
    network_drops: 1
    total: 1
    by_type:
      Network: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: NET-PNL-3F
  equipment_class: BMS Network Drop
  quantity: 1
  location: panel
  system: Network
  panel: PNL-3F
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 0
    network_drops: 1
    total: 1
    by_type:
      Network: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: NET-PNL-BOH-2F
  equipment_class: BMS Network Drop
  quantity: 1
  location: panel
  system: Network
  panel: PNL-BOH-2F
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 0
    network_drops: 1
    total: 1
    by_type:
      Network: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: NET-PNL-BSMT
  equipment_class: BMS Network Drop
  quantity: 1
  location: panel
  system: Network
  panel: PNL-BSMT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 0
    network_drops: 1
    total: 1
    by_type:
      Network: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: NET-PNL-CHPLANT-GND
  equipment_class: BMS Network Drop
  quantity: 1
  location: panel
  system: Network
  panel: PNL-CHPLANT-GND
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 0
    network_drops: 1
    total: 1
    by_type:
      Network: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: NET-PNL-GF
  equipment_class: BMS Network Drop
  quantity: 1
  location: panel
  system: Network
  panel: PNL-GF
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 0
    network_drops: 1
    total: 1
    by_type:
      Network: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: NET-PNL-HE-GF
  equipment_class: BMS Network Drop
  quantity: 1
  location: panel
  system: Network
  panel: PNL-HE-GF
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 0
    network_drops: 1
    total: 1
    by_type:
      Network: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: NET-PNL-RD
  equipment_class: BMS Network Drop
  quantity: 1
  location: panel
  system: Network
  panel: PNL-RD
  primary_co: BMS Contractor
  io_summary:
    physical_io: 0
    hli_subpoints: 0
    network_drops: 1
    total: 1
    by_type:
      Network: 1
    by_co:
      BMS Contractor: 1
  make_model_assumed: "(class default not defined \u2014 add to equipment-class-defaults.yaml)"
  network_type: TBD
  typical_supplier: TBD
  notes: ''
- id: PAHU-RD
  equipment_class: Precooled Air Handling Unit
  quantity: 1
  location: Roofdeck
  system: VENT-PAHU
  panel: PNL-RD
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 10
    hli_subpoints: 0
    network_drops: 0
    total: 10
    by_type:
      AI: 4
      AO: 3
      DI: 3
    by_co:
      BMS Contractor: 3
      Equipment Supplier: 5
      ME Contractor: 2
  make_model_assumed: Precool AHU at Roofdeck with CHW coil, VFD-driven fresh air fan; no exhaust path
  network_type: Hardwired (VFD via BACnet HLI)
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: 'Precool function: cools outdoor air before it''s distributed to other systems. BMS supplies OA/supply T sensors.'
- id: RP-1
  equipment_class: Recirculating Pump
  quantity: 1
  location: Plant Room
  system: PL-RecircPumps
  panel: PNL-CHPLANT-GND
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 2
    hli_subpoints: 0
    network_drops: 0
    total: 2
    by_type:
      DI: 2
    by_co:
      Equipment Supplier: 2
  make_model_assumed: Hot water recirculating pump, fixed-speed (typical for hotwater systems)
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor
  notes: BMS reads aux contacts only.
- id: RP-2
  equipment_class: Recirculating Pump
  quantity: 1
  location: Plant Room
  system: PL-RecircPumps
  panel: PNL-CHPLANT-GND
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 2
    hli_subpoints: 0
    network_drops: 0
    total: 2
    by_type:
      DI: 2
    by_co:
      Equipment Supplier: 2
  make_model_assumed: Hot water recirculating pump, fixed-speed (typical for hotwater systems)
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor
  notes: BMS reads aux contacts only.
- id: RP-3
  equipment_class: Recirculating Pump
  quantity: 1
  location: Plant Room
  system: PL-RecircPumps
  panel: PNL-CHPLANT-GND
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 2
    hli_subpoints: 0
    network_drops: 0
    total: 2
    by_type:
      DI: 2
    by_co:
      Equipment Supplier: 2
  make_model_assumed: Hot water recirculating pump, fixed-speed (typical for hotwater systems)
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor
  notes: BMS reads aux contacts only.
- id: RP-4
  equipment_class: Recirculating Pump
  quantity: 1
  location: Plant Room
  system: PL-RecircPumps
  panel: PNL-CHPLANT-GND
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 2
    hli_subpoints: 0
    network_drops: 0
    total: 2
    by_type:
      DI: 2
    by_co:
      Equipment Supplier: 2
  make_model_assumed: Hot water recirculating pump, fixed-speed (typical for hotwater systems)
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor
  notes: BMS reads aux contacts only.
- id: RP-5
  equipment_class: Recirculating Pump
  quantity: 1
  location: Plant Room
  system: PL-RecircPumps
  panel: PNL-CHPLANT-GND
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 2
    hli_subpoints: 0
    network_drops: 0
    total: 2
    by_type:
      DI: 2
    by_co:
      Equipment Supplier: 2
  make_model_assumed: Hot water recirculating pump, fixed-speed (typical for hotwater systems)
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor
  notes: BMS reads aux contacts only.
- id: RP-6
  equipment_class: Recirculating Pump
  quantity: 1
  location: Plant Room
  system: PL-RecircPumps
  panel: PNL-CHPLANT-GND
  primary_co: Equipment Supplier
  io_summary:
    physical_io: 2
    hli_subpoints: 0
    network_drops: 0
    total: 2
    by_type:
      DI: 2
    by_co:
      Equipment Supplier: 2
  make_model_assumed: Hot water recirculating pump, fixed-speed (typical for hotwater systems)
  network_type: "Hardwired (LZ) or HLI (HZ \u2014 per A-PL-001)"
  typical_supplier: Plumbing contractor
  notes: BMS reads aux contacts only.
- id: SB-1
  equipment_class: Steam Boiler
  quantity: 1
  location: Basement
  system: PL-Boiler
  panel: PNL-BSMT
  primary_co: BMS Contractor
  io_summary:
    physical_io: 8
    hli_subpoints: 0
    network_drops: 0
    total: 8
    by_type:
      AI: 4
      AO: 1
      DI: 3
    by_co:
      BMS Contractor: 5
      Equipment Supplier: 3
  make_model_assumed: Fire-tube steam boiler with multi-stage burner, fuel-oil fired (typical for hotel laundry)
  network_type: Hardwired
  typical_supplier: Mechanical contractor / Equipment supplier
  notes: BMS supplies steam pressure, feedwater T, fluegas T+O2 sensors. Boiler equipment provides aux contacts for status/HOA/trip points.