# A1 — Consolidated I/O List
# Generated by _scripts/build-a1.py
#
metadata:
  project: "Kingsford Hotel Bacolod \u2014 BMS"
  date: '2026-04-28'
  source: MC Standards (ME + PL Points list) + Project-specific equipment count per A-002
  status: draft
  notes: "Project-specific BMS sheets are raster (BMS-01..04+); MC Standards is the readable text source. Equipment counts per typical Kingsford-tier hospitality scope; refine at shop drawing stage. Guestroom\
    \ FCU count is sample (3 floors \xD7 30) \u2014 Q-005 / Q-008 will refine."
io_list:
- id: P0001
  system: HVAC-Chillers
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-1
  location: Plant Room (Basement)
  point_description: Chiller 1 BACnet HLI (status, motor current, kW, evap/cond temps, refrigerant pressures, oil sump T+P)
  type: HLI
  field_device: BACnet IP card
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Chiller plant sequencing'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0002
  system: HVAC-Chillers
  equipment_class: CHW Supply Main Header
  equipment_instance: HDR-CHWS
  location: Plant Room
  point_description: Entering Chilled Water Temperature CH-1
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Chiller'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0003
  system: HVAC-Chillers
  equipment_class: CHW Return Main Header
  equipment_instance: HDR-CHWR
  location: Plant Room
  point_description: Leaving Chilled Water Temperature CH-1
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Chiller'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0004
  system: HVAC-Chillers
  equipment_class: Condenser Water Header
  equipment_instance: HDR-COW
  location: Roofdeck
  point_description: Condenser Water Supply T CH-1
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Chiller'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0005
  system: HVAC-Chillers
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-2
  location: Plant Room (Basement)
  point_description: Chiller 2 BACnet HLI (status, motor current, kW, evap/cond temps, refrigerant pressures, oil sump T+P)
  type: HLI
  field_device: BACnet IP card
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Chiller plant sequencing'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0006
  system: HVAC-Chillers
  equipment_class: CHW Supply Main Header
  equipment_instance: HDR-CHWS
  location: Plant Room
  point_description: Entering Chilled Water Temperature CH-2
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Chiller'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0007
  system: HVAC-Chillers
  equipment_class: CHW Return Main Header
  equipment_instance: HDR-CHWR
  location: Plant Room
  point_description: Leaving Chilled Water Temperature CH-2
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Chiller'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0008
  system: HVAC-Chillers
  equipment_class: Condenser Water Header
  equipment_instance: HDR-COW
  location: Roofdeck
  point_description: Condenser Water Supply T CH-2
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Chiller'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0009
  system: HVAC-Chillers
  equipment_class: Chiller (Package Water-Cooled)
  equipment_instance: CH-3
  location: Plant Room (Basement)
  point_description: Chiller 3 BACnet HLI (status, motor current, kW, evap/cond temps, refrigerant pressures, oil sump T+P)
  type: HLI
  field_device: BACnet IP card
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Chiller plant sequencing'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0010
  system: HVAC-Chillers
  equipment_class: CHW Supply Main Header
  equipment_instance: HDR-CHWS
  location: Plant Room
  point_description: Entering Chilled Water Temperature CH-3
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Chiller'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0011
  system: HVAC-Chillers
  equipment_class: CHW Return Main Header
  equipment_instance: HDR-CHWR
  location: Plant Room
  point_description: Leaving Chilled Water Temperature CH-3
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Chiller'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0012
  system: HVAC-Chillers
  equipment_class: Condenser Water Header
  equipment_instance: HDR-COW
  location: Roofdeck
  point_description: Condenser Water Supply T CH-3
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Chiller'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0013
  system: HVAC-Chillers
  equipment_class: CHW Bypass Header
  equipment_instance: HDR-CHW-BP
  location: Plant Room
  point_description: CHW differential pressure
  type: AI
  field_device: Differential Pressure Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Plant'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0014
  system: HVAC-Chillers
  equipment_class: CHW Bypass Header
  equipment_instance: HDR-CHW-BP
  location: Plant Room
  point_description: Bypass valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Plant'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0015
  system: HVAC-Chillers
  equipment_class: CHW Bypass Header
  equipment_instance: HDR-CHW-BP
  location: Plant Room
  point_description: Bypass valve status
  type: AI
  field_device: Position Feedback
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Plant'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0016
  system: HVAC-Chillers
  equipment_class: BTU Meter
  equipment_instance: BTU-CHWS-MAIN
  location: Plant Room
  point_description: 'Plant CHW BTU (Modbus: flow, supply T, return T, kW, kWh)'
  type: HLI
  field_device: Ultrasonic BTU Meter
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Energy reporting'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: Modbus
- id: P0017
  system: HVAC-Pumps
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-1.1
  location: Plant Room
  point_description: Pump motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0018
  system: HVAC-Pumps
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-1.1
  location: Plant Room
  point_description: Pump HOA status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0019
  system: HVAC-Pumps
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-1.1
  location: Plant Room
  point_description: Pump trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0020
  system: HVAC-Pumps
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-1.1
  location: Plant Room
  point_description: VFD speed feedback (BACnet HLI)
  type: HLI
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0021
  system: HVAC-Pumps
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-1.1
  location: Plant Room
  point_description: VFD speed command (BACnet HLI)
  type: HLI
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0022
  system: HVAC-Pumps
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-1.2
  location: Plant Room
  point_description: Pump motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0023
  system: HVAC-Pumps
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-1.2
  location: Plant Room
  point_description: Pump HOA status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0024
  system: HVAC-Pumps
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-1.2
  location: Plant Room
  point_description: Pump trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0025
  system: HVAC-Pumps
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-1.2
  location: Plant Room
  point_description: VFD speed feedback (BACnet HLI)
  type: HLI
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0026
  system: HVAC-Pumps
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-1.2
  location: Plant Room
  point_description: VFD speed command (BACnet HLI)
  type: HLI
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0027
  system: HVAC-Pumps
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-1.3
  location: Plant Room
  point_description: Pump motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0028
  system: HVAC-Pumps
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-1.3
  location: Plant Room
  point_description: Pump HOA status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0029
  system: HVAC-Pumps
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-1.3
  location: Plant Room
  point_description: Pump trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0030
  system: HVAC-Pumps
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-1.3
  location: Plant Room
  point_description: VFD speed feedback (BACnet HLI)
  type: HLI
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0031
  system: HVAC-Pumps
  equipment_class: Primary CHW Pump
  equipment_instance: CHWP-1.3
  location: Plant Room
  point_description: VFD speed command (BACnet HLI)
  type: HLI
  field_device: VFD BACnet card
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0032
  system: HVAC-Pumps
  equipment_class: Primary CHW Pump (Standby)
  equipment_instance: CHWP-1.STBY
  location: Plant Room
  point_description: Pump motor status (standby)
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0033
  system: HVAC-Pumps
  equipment_class: Primary CHW Pump (Standby)
  equipment_instance: CHWP-1.STBY
  location: Plant Room
  point_description: Pump trip alarm (standby)
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0034
  system: HVAC-Pumps
  equipment_class: Condenser Water Pump
  equipment_instance: COWP-1
  location: Plant Room
  point_description: Pump motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0035
  system: HVAC-Pumps
  equipment_class: Condenser Water Pump
  equipment_instance: COWP-1
  location: Plant Room
  point_description: Pump HOA status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0036
  system: HVAC-Pumps
  equipment_class: Condenser Water Pump
  equipment_instance: COWP-1
  location: Plant Room
  point_description: Pump trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0037
  system: HVAC-Pumps
  equipment_class: Condenser Water Pump
  equipment_instance: COWP-1
  location: Plant Room
  point_description: Pump start command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0038
  system: HVAC-Pumps
  equipment_class: Condenser Water Pump
  equipment_instance: COWP-2
  location: Plant Room
  point_description: Pump motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0039
  system: HVAC-Pumps
  equipment_class: Condenser Water Pump
  equipment_instance: COWP-2
  location: Plant Room
  point_description: Pump HOA status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0040
  system: HVAC-Pumps
  equipment_class: Condenser Water Pump
  equipment_instance: COWP-2
  location: Plant Room
  point_description: Pump trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0041
  system: HVAC-Pumps
  equipment_class: Condenser Water Pump
  equipment_instance: COWP-2
  location: Plant Room
  point_description: Pump start command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0042
  system: HVAC-Pumps
  equipment_class: Condenser Water Pump
  equipment_instance: COWP-3
  location: Plant Room
  point_description: Pump motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0043
  system: HVAC-Pumps
  equipment_class: Condenser Water Pump
  equipment_instance: COWP-3
  location: Plant Room
  point_description: Pump HOA status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0044
  system: HVAC-Pumps
  equipment_class: Condenser Water Pump
  equipment_instance: COWP-3
  location: Plant Room
  point_description: Pump trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0045
  system: HVAC-Pumps
  equipment_class: Condenser Water Pump
  equipment_instance: COWP-3
  location: Plant Room
  point_description: Pump start command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Pumps'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0046
  system: HVAC-Cooling-Towers
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roofdeck
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Cooling tower'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0047
  system: HVAC-Cooling-Towers
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roofdeck
  point_description: Fan HOA status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Cooling tower'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0048
  system: HVAC-Cooling-Towers
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roofdeck
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Cooling tower'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0049
  system: HVAC-Cooling-Towers
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roofdeck
  point_description: Fan VFD speed command
  type: AO
  field_device: VFD analog input
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Cooling tower'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0050
  system: HVAC-Cooling-Towers
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roofdeck
  point_description: Fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Cooling tower'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0051
  system: HVAC-Cooling-Towers
  equipment_class: Cooling Tower
  equipment_instance: CT-1
  location: Roofdeck
  point_description: Basin water level low
  type: DI
  field_device: Float Switch
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Cooling tower'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0052
  system: HVAC-Cooling-Towers
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roofdeck
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Cooling tower'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0053
  system: HVAC-Cooling-Towers
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roofdeck
  point_description: Fan HOA status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Cooling tower'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0054
  system: HVAC-Cooling-Towers
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roofdeck
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Cooling tower'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0055
  system: HVAC-Cooling-Towers
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roofdeck
  point_description: Fan VFD speed command
  type: AO
  field_device: VFD analog input
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Cooling tower'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0056
  system: HVAC-Cooling-Towers
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roofdeck
  point_description: Fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Cooling tower'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0057
  system: HVAC-Cooling-Towers
  equipment_class: Cooling Tower
  equipment_instance: CT-2
  location: Roofdeck
  point_description: Basin water level low
  type: DI
  field_device: Float Switch
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Cooling tower'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0058
  system: HVAC-Cooling-Towers
  equipment_class: Cooling Tower
  equipment_instance: CT-3
  location: Roofdeck
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Cooling tower'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0059
  system: HVAC-Cooling-Towers
  equipment_class: Cooling Tower
  equipment_instance: CT-3
  location: Roofdeck
  point_description: Fan HOA status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Cooling tower'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0060
  system: HVAC-Cooling-Towers
  equipment_class: Cooling Tower
  equipment_instance: CT-3
  location: Roofdeck
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Cooling tower'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0061
  system: HVAC-Cooling-Towers
  equipment_class: Cooling Tower
  equipment_instance: CT-3
  location: Roofdeck
  point_description: Fan VFD speed command
  type: AO
  field_device: VFD analog input
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Cooling tower'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0062
  system: HVAC-Cooling-Towers
  equipment_class: Cooling Tower
  equipment_instance: CT-3
  location: Roofdeck
  point_description: Fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Cooling tower'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0063
  system: HVAC-Cooling-Towers
  equipment_class: Cooling Tower
  equipment_instance: CT-3
  location: Roofdeck
  point_description: Basin water level low
  type: DI
  field_device: Float Switch
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Cooling tower'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0064
  system: HVAC-Cooling-Towers
  equipment_class: Cooling Tower (Common)
  equipment_instance: CT-COMMON
  location: Roofdeck
  point_description: Outdoor air temperature
  type: AI
  field_device: Outdoor Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Cooling tower'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0065
  system: HVAC-Cooling-Towers
  equipment_class: Cooling Tower (Common)
  equipment_instance: CT-COMMON
  location: Roofdeck
  point_description: Outdoor air relative humidity
  type: AI
  field_device: Humidity Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Cooling tower'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0066
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD
  location: Roofdeck
  point_description: OA Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0067
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD
  location: Roofdeck
  point_description: OA Humidity
  type: AI
  field_device: Humidity Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0068
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD
  location: Roofdeck
  point_description: OA Flow
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0069
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD
  location: Roofdeck
  point_description: Indoor Mixed Air T
  type: AI
  field_device: Temperature Sensor
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0070
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD
  location: Roofdeck
  point_description: Indoor Mixed Air RH
  type: AI
  field_device: Humidity Sensor
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0071
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD
  location: Roofdeck
  point_description: Indoor Supply Air T
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0072
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD
  location: Roofdeck
  point_description: Indoor Exhaust Air T
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0073
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD
  location: Roofdeck
  point_description: Recovery wheel motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0074
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD
  location: Roofdeck
  point_description: Recovery wheel trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0075
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD
  location: Roofdeck
  point_description: Supply fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0076
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD
  location: Roofdeck
  point_description: Supply fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0077
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD
  location: Roofdeck
  point_description: Supply fan VFD speed command
  type: AO
  field_device: VFD analog input
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0078
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD
  location: Roofdeck
  point_description: Supply fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0079
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD
  location: Roofdeck
  point_description: Exhaust fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0080
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD
  location: Roofdeck
  point_description: Exhaust fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0081
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD
  location: Roofdeck
  point_description: Exhaust fan VFD speed command
  type: AO
  field_device: VFD analog input
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0082
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD
  location: Roofdeck
  point_description: Exhaust fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0083
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD
  location: Roofdeck
  point_description: OA motorized damper status
  type: DI
  field_device: Damper Position Switch
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0084
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD
  location: Roofdeck
  point_description: OA motorized damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0085
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD
  location: Roofdeck
  point_description: CHWS coil valve status
  type: DI
  field_device: Position Feedback
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0086
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-RD
  location: Roofdeck
  point_description: CHWS coil valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0087
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-GF
  location: GF
  point_description: OA Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0088
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-GF
  location: GF
  point_description: OA Humidity
  type: AI
  field_device: Humidity Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0089
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-GF
  location: GF
  point_description: OA Flow
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0090
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-GF
  location: GF
  point_description: Indoor Mixed Air T
  type: AI
  field_device: Temperature Sensor
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0091
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-GF
  location: GF
  point_description: Indoor Mixed Air RH
  type: AI
  field_device: Humidity Sensor
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0092
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-GF
  location: GF
  point_description: Indoor Supply Air T
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0093
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-GF
  location: GF
  point_description: Indoor Exhaust Air T
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0094
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-GF
  location: GF
  point_description: Recovery wheel motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0095
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-GF
  location: GF
  point_description: Recovery wheel trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0096
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-GF
  location: GF
  point_description: Supply fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0097
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-GF
  location: GF
  point_description: Supply fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0098
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-GF
  location: GF
  point_description: Supply fan VFD speed command
  type: AO
  field_device: VFD analog input
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0099
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-GF
  location: GF
  point_description: Supply fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0100
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-GF
  location: GF
  point_description: Exhaust fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0101
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-GF
  location: GF
  point_description: Exhaust fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0102
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-GF
  location: GF
  point_description: Exhaust fan VFD speed command
  type: AO
  field_device: VFD analog input
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0103
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-GF
  location: GF
  point_description: Exhaust fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0104
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-GF
  location: GF
  point_description: OA motorized damper status
  type: DI
  field_device: Damper Position Switch
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0105
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-GF
  location: GF
  point_description: OA motorized damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0106
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-GF
  location: GF
  point_description: CHWS coil valve status
  type: DI
  field_device: Position Feedback
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0107
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-GF
  location: GF
  point_description: CHWS coil valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0108
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F
  point_description: OA Temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0109
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F
  point_description: OA Humidity
  type: AI
  field_device: Humidity Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0110
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F
  point_description: OA Flow
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0111
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F
  point_description: Indoor Mixed Air T
  type: AI
  field_device: Temperature Sensor
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0112
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F
  point_description: Indoor Mixed Air RH
  type: AI
  field_device: Humidity Sensor
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0113
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F
  point_description: Indoor Supply Air T
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0114
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F
  point_description: Indoor Exhaust Air T
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0115
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F
  point_description: Recovery wheel motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0116
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F
  point_description: Recovery wheel trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0117
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F
  point_description: Supply fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0118
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F
  point_description: Supply fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0119
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F
  point_description: Supply fan VFD speed command
  type: AO
  field_device: VFD analog input
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0120
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F
  point_description: Supply fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0121
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F
  point_description: Exhaust fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0122
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F
  point_description: Exhaust fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0123
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F
  point_description: Exhaust fan VFD speed command
  type: AO
  field_device: VFD analog input
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0124
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F
  point_description: Exhaust fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0125
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F
  point_description: OA motorized damper status
  type: DI
  field_device: Damper Position Switch
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0126
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F
  point_description: OA motorized damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0127
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F
  point_description: CHWS coil valve status
  type: DI
  field_device: Position Feedback
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0128
  system: VENT-DOAS
  equipment_class: DOAS Unit
  equipment_instance: DOAS-2F
  location: 2F
  point_description: CHWS coil valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: DOAS'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0129
  system: VENT-PAHU
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-RD
  location: Roofdeck
  point_description: OA temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: PAHU'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0130
  system: VENT-PAHU
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-RD
  location: Roofdeck
  point_description: OA flow
  type: AI
  field_device: Flow Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: PAHU'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0131
  system: VENT-PAHU
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-RD
  location: Roofdeck
  point_description: Supply T
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: PAHU'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0132
  system: VENT-PAHU
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-RD
  location: Roofdeck
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: PAHU'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0133
  system: VENT-PAHU
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-RD
  location: Roofdeck
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: PAHU'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0134
  system: VENT-PAHU
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-RD
  location: Roofdeck
  point_description: Fan VFD speed command
  type: AO
  field_device: VFD analog input
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: PAHU'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0135
  system: VENT-PAHU
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-RD
  location: Roofdeck
  point_description: Fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: PAHU'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0136
  system: VENT-PAHU
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-RD
  location: Roofdeck
  point_description: OA damper command
  type: AO
  field_device: Damper Actuator
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: PAHU'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0137
  system: VENT-PAHU
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-RD
  location: Roofdeck
  point_description: CHWS valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: PAHU'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0138
  system: VENT-PAHU
  equipment_class: Precooled Air Handling Unit
  equipment_instance: PAHU-RD
  location: Roofdeck
  point_description: CHWS valve status
  type: DI
  field_device: Position Feedback
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: PAHU'
  panel: PNL-RD
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0139
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-LOBBY-GF
  location: GF
  point_description: Return Air T
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0140
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-LOBBY-GF
  location: GF
  point_description: Return Air RH
  type: AI
  field_device: Humidity Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0141
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-LOBBY-GF
  location: GF
  point_description: Supply Air T
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0142
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-LOBBY-GF
  location: GF
  point_description: Return CO2
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0143
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-LOBBY-GF
  location: GF
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0144
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-LOBBY-GF
  location: GF
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0145
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-LOBBY-GF
  location: GF
  point_description: Fan VFD speed command
  type: AO
  field_device: VFD analog input
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0146
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-LOBBY-GF
  location: GF
  point_description: Fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0147
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-LOBBY-GF
  location: GF
  point_description: CHWS valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0148
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-LOBBY-GF
  location: GF
  point_description: CHWS valve status
  type: DI
  field_device: Position Feedback
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0149
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-LOBBY-GF
  location: GF
  point_description: OA damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0150
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-LOBBY-GF
  location: GF
  point_description: RA damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0151
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BALL-2F
  location: 2F
  point_description: Return Air T
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0152
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BALL-2F
  location: 2F
  point_description: Return Air RH
  type: AI
  field_device: Humidity Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0153
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BALL-2F
  location: 2F
  point_description: Supply Air T
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0154
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BALL-2F
  location: 2F
  point_description: Return CO2
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0155
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BALL-2F
  location: 2F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0156
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BALL-2F
  location: 2F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0157
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BALL-2F
  location: 2F
  point_description: Fan VFD speed command
  type: AO
  field_device: VFD analog input
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0158
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BALL-2F
  location: 2F
  point_description: Fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0159
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BALL-2F
  location: 2F
  point_description: CHWS valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0160
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BALL-2F
  location: 2F
  point_description: CHWS valve status
  type: DI
  field_device: Position Feedback
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0161
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BALL-2F
  location: 2F
  point_description: OA damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0162
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BALL-2F
  location: 2F
  point_description: RA damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0163
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-REST-2F
  location: 2F
  point_description: Return Air T
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0164
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-REST-2F
  location: 2F
  point_description: Return Air RH
  type: AI
  field_device: Humidity Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0165
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-REST-2F
  location: 2F
  point_description: Supply Air T
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0166
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-REST-2F
  location: 2F
  point_description: Return CO2
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0167
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-REST-2F
  location: 2F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0168
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-REST-2F
  location: 2F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0169
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-REST-2F
  location: 2F
  point_description: Fan VFD speed command
  type: AO
  field_device: VFD analog input
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0170
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-REST-2F
  location: 2F
  point_description: Fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0171
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-REST-2F
  location: 2F
  point_description: CHWS valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0172
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-REST-2F
  location: 2F
  point_description: CHWS valve status
  type: DI
  field_device: Position Feedback
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0173
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-REST-2F
  location: 2F
  point_description: OA damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0174
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-REST-2F
  location: 2F
  point_description: RA damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0175
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-AMEN-3F
  location: 3F
  point_description: Return Air T
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0176
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-AMEN-3F
  location: 3F
  point_description: Return Air RH
  type: AI
  field_device: Humidity Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0177
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-AMEN-3F
  location: 3F
  point_description: Supply Air T
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0178
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-AMEN-3F
  location: 3F
  point_description: Return CO2
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0179
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-AMEN-3F
  location: 3F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0180
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-AMEN-3F
  location: 3F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0181
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-AMEN-3F
  location: 3F
  point_description: Fan VFD speed command
  type: AO
  field_device: VFD analog input
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0182
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-AMEN-3F
  location: 3F
  point_description: Fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0183
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-AMEN-3F
  location: 3F
  point_description: CHWS valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0184
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-AMEN-3F
  location: 3F
  point_description: CHWS valve status
  type: DI
  field_device: Position Feedback
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0185
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-AMEN-3F
  location: 3F
  point_description: OA damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0186
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-AMEN-3F
  location: 3F
  point_description: RA damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0187
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BOH-2F
  location: 2F
  point_description: Return Air T
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-BOH-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0188
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BOH-2F
  location: 2F
  point_description: Return Air RH
  type: AI
  field_device: Humidity Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-BOH-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0189
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BOH-2F
  location: 2F
  point_description: Supply Air T
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-BOH-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0190
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BOH-2F
  location: 2F
  point_description: Return CO2
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-BOH-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0191
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BOH-2F
  location: 2F
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-BOH-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0192
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BOH-2F
  location: 2F
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-BOH-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0193
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BOH-2F
  location: 2F
  point_description: Fan VFD speed command
  type: AO
  field_device: VFD analog input
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-BOH-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0194
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BOH-2F
  location: 2F
  point_description: Fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-BOH-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0195
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BOH-2F
  location: 2F
  point_description: CHWS valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-BOH-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0196
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BOH-2F
  location: 2F
  point_description: CHWS valve status
  type: DI
  field_device: Position Feedback
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-BOH-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0197
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BOH-2F
  location: 2F
  point_description: OA damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-BOH-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0198
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BOH-2F
  location: 2F
  point_description: RA damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-BOH-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0199
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BOH-BSMT
  location: Basement
  point_description: Return Air T
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-BSMT
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0200
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BOH-BSMT
  location: Basement
  point_description: Return Air RH
  type: AI
  field_device: Humidity Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-BSMT
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0201
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BOH-BSMT
  location: Basement
  point_description: Supply Air T
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-BSMT
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0202
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BOH-BSMT
  location: Basement
  point_description: Return CO2
  type: AI
  field_device: CO2 Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-BSMT
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0203
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BOH-BSMT
  location: Basement
  point_description: Fan motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-BSMT
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0204
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BOH-BSMT
  location: Basement
  point_description: Fan trip alarm
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-BSMT
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0205
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BOH-BSMT
  location: Basement
  point_description: Fan VFD speed command
  type: AO
  field_device: VFD analog input
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-BSMT
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0206
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BOH-BSMT
  location: Basement
  point_description: Fan VFD speed feedback
  type: AI
  field_device: VFD analog output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-BSMT
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0207
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BOH-BSMT
  location: Basement
  point_description: CHWS valve command
  type: AO
  field_device: Electric Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-BSMT
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0208
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BOH-BSMT
  location: Basement
  point_description: CHWS valve status
  type: DI
  field_device: Position Feedback
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-BSMT
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0209
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BOH-BSMT
  location: Basement
  point_description: OA damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-BSMT
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0210
  system: VENT-AHU
  equipment_class: AHU (Chilled-Water-Served)
  equipment_instance: AHU-BOH-BSMT
  location: Basement
  point_description: RA damper command
  type: AO
  field_device: Damper Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: AHU'
  panel: PNL-BSMT
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0211
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.01
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0212
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.01
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0213
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.01
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0214
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.02
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0215
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.02
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0216
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.02
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0217
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.03
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0218
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.03
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0219
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.03
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0220
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.04
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0221
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.04
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0222
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.04
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0223
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.05
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0224
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.05
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0225
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.05
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0226
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.06
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0227
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.06
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0228
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.06
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0229
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.07
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0230
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.07
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0231
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.07
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0232
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.08
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0233
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.08
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0234
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.08
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0235
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.09
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0236
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.09
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0237
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.09
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0238
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.10
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0239
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.10
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0240
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.10
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0241
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.11
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0242
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.11
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0243
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.11
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0244
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.12
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0245
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.12
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0246
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.12
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0247
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.13
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0248
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.13
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0249
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.13
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0250
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.14
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0251
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.14
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0252
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.14
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0253
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.15
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0254
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.15
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0255
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.15
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0256
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.16
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0257
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.16
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0258
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.16
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0259
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.17
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0260
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.17
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0261
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.17
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0262
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.18
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0263
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.18
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0264
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.18
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0265
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.19
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0266
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.19
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0267
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.19
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0268
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.20
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0269
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.20
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0270
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.20
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0271
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.21
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0272
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.21
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0273
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.21
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0274
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.22
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0275
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.22
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0276
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.22
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0277
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.23
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0278
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.23
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0279
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.23
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0280
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.24
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0281
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.24
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0282
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.24
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0283
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.25
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0284
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.25
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0285
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.25
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0286
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.26
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0287
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.26
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0288
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.26
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0289
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.27
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0290
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.27
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0291
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.27
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0292
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.28
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0293
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.28
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0294
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.28
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0295
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.29
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0296
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.29
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0297
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.29
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0298
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.30
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0299
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.30
  location: 3F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0300
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-3F.30
  location: 3F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0301
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.01
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0302
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.01
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0303
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.01
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0304
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.02
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0305
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.02
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0306
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.02
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0307
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.03
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0308
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.03
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0309
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.03
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0310
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.04
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0311
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.04
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0312
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.04
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0313
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.05
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0314
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.05
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0315
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.05
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0316
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.06
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0317
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.06
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0318
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.06
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0319
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.07
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0320
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.07
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0321
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.07
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0322
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.08
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0323
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.08
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0324
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.08
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0325
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.09
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0326
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.09
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0327
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.09
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0328
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.10
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0329
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.10
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0330
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.10
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0331
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.11
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0332
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.11
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0333
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.11
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0334
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.12
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0335
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.12
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0336
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.12
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0337
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.13
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0338
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.13
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0339
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.13
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0340
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.14
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0341
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.14
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0342
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.14
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0343
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.15
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0344
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.15
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0345
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.15
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0346
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.16
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0347
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.16
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0348
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.16
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0349
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.17
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0350
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.17
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0351
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.17
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0352
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.18
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0353
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.18
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0354
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.18
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0355
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.19
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0356
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.19
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0357
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.19
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0358
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.20
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0359
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.20
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0360
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.20
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0361
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.21
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0362
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.21
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0363
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.21
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0364
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.22
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0365
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.22
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0366
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.22
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0367
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.23
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0368
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.23
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0369
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.23
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0370
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.24
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0371
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.24
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0372
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.24
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0373
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.25
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0374
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.25
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0375
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.25
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0376
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.26
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0377
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.26
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0378
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.26
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0379
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.27
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0380
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.27
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0381
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.27
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0382
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.28
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0383
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.28
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0384
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.28
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0385
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.29
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0386
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.29
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0387
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.29
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0388
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.30
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0389
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.30
  location: 2F
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0390
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-2F.30
  location: 2F
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0391
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.01
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0392
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.01
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0393
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.01
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0394
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.02
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0395
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.02
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0396
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.02
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0397
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.03
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0398
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.03
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0399
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.03
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0400
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.04
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0401
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.04
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0402
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.04
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0403
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.05
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0404
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.05
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0405
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.05
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0406
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.06
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0407
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.06
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0408
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.06
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0409
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.07
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0410
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.07
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0411
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.07
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0412
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.08
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0413
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.08
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0414
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.08
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0415
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.09
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0416
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.09
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0417
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.09
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0418
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.10
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0419
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.10
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0420
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.10
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0421
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.11
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0422
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.11
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0423
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.11
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0424
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.12
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0425
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.12
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0426
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.12
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0427
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.13
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0428
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.13
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0429
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.13
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0430
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.14
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0431
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.14
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0432
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.14
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0433
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.15
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0434
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.15
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0435
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.15
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0436
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.16
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0437
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.16
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0438
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.16
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0439
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.17
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0440
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.17
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0441
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.17
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0442
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.18
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0443
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.18
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0444
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.18
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0445
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.19
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0446
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.19
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0447
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.19
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0448
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.20
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0449
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.20
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0450
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.20
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0451
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.21
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0452
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.21
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0453
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.21
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0454
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.22
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0455
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.22
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0456
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.22
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0457
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.23
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0458
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.23
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0459
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.23
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0460
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.24
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0461
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.24
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0462
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.24
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0463
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.25
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0464
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.25
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0465
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.25
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0466
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.26
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0467
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.26
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0468
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.26
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0469
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.27
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0470
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.27
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0471
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.27
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0472
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.28
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0473
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.28
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0474
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.28
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0475
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.29
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0476
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.29
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0477
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.29
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0478
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.30
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0479
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.30
  location: GF
  point_description: Fan command
  type: DO
  field_device: Relay Output
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0480
  system: VENT-FCU
  equipment_class: FCU (guestroom/zone, hardwired)
  equipment_instance: FCU-GF.30
  location: GF
  point_description: CHWS valve command (3-position)
  type: DO
  field_device: Valve Actuator
  c_o: ME Contractor
  description_of_operations_ref: 'DoO: FCU'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0481
  system: VENT-EAS
  equipment_class: Exhaust Fan (General)
  equipment_instance: EAS-GF
  location: GF
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: EAS'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0482
  system: VENT-EAS
  equipment_class: Exhaust Fan (General)
  equipment_instance: EAS-GF
  location: GF
  point_description: Fan HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: EAS'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0483
  system: VENT-EAS
  equipment_class: Exhaust Fan (General)
  equipment_instance: EAS-GF
  location: GF
  point_description: Fan trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: EAS'
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0484
  system: VENT-EAS
  equipment_class: Exhaust Fan (General)
  equipment_instance: EAS-2F
  location: 2F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: EAS'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0485
  system: VENT-EAS
  equipment_class: Exhaust Fan (General)
  equipment_instance: EAS-2F
  location: 2F
  point_description: Fan HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: EAS'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0486
  system: VENT-EAS
  equipment_class: Exhaust Fan (General)
  equipment_instance: EAS-2F
  location: 2F
  point_description: Fan trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: EAS'
  panel: PNL-2F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0487
  system: VENT-EAS
  equipment_class: Exhaust Fan (General)
  equipment_instance: EAS-3F
  location: 3F
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: EAS'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0488
  system: VENT-EAS
  equipment_class: Exhaust Fan (General)
  equipment_instance: EAS-3F
  location: 3F
  point_description: Fan HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: EAS'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0489
  system: VENT-EAS
  equipment_class: Exhaust Fan (General)
  equipment_instance: EAS-3F
  location: 3F
  point_description: Fan trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: EAS'
  panel: PNL-3F
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0490
  system: VENT-EAS
  equipment_class: Exhaust Fan (General)
  equipment_instance: EAS-BSMT
  location: Basement
  point_description: Fan status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: EAS'
  panel: PNL-BSMT
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0491
  system: VENT-EAS
  equipment_class: Exhaust Fan (General)
  equipment_instance: EAS-BSMT
  location: Basement
  point_description: Fan HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: EAS'
  panel: PNL-BSMT
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0492
  system: VENT-EAS
  equipment_class: Exhaust Fan (General)
  equipment_instance: EAS-BSMT
  location: Basement
  point_description: Fan trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: EAS'
  panel: PNL-BSMT
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0493
  system: PL-Calorifiers
  equipment_class: Calorifier (Hot Water Storage Tank)
  equipment_instance: CAL-1
  location: Plant Room
  point_description: Tank temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Calorifier'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0494
  system: PL-Calorifiers
  equipment_class: Calorifier (Hot Water Storage Tank)
  equipment_instance: CAL-2
  location: Plant Room
  point_description: Tank temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Calorifier'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0495
  system: PL-Calorifiers
  equipment_class: Calorifier (Hot Water Storage Tank)
  equipment_instance: CAL-3
  location: Plant Room
  point_description: Tank temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Calorifier'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0496
  system: PL-Calorifiers
  equipment_class: Calorifier (Hot Water Storage Tank)
  equipment_instance: CAL-4
  location: Plant Room
  point_description: Tank temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Calorifier'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0497
  system: PL-Calorifiers
  equipment_class: Calorifier (Hot Water Storage Tank)
  equipment_instance: CAL-5
  location: Plant Room
  point_description: Tank temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Calorifier'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0498
  system: PL-Calorifiers
  equipment_class: Calorifier (Hot Water Storage Tank)
  equipment_instance: CAL-6
  location: Plant Room
  point_description: Tank temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Calorifier'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0499
  system: PL-HotWater
  equipment_class: Hot Water Header Set
  equipment_instance: HDR-HW
  location: Plant Room
  point_description: HW Supply Header T
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: HW'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0500
  system: PL-HotWater
  equipment_class: Hot Water Header Set
  equipment_instance: HDR-HW
  location: Plant Room
  point_description: HW Return Header T
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: HW'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0501
  system: PL-HotWater
  equipment_class: Hot Water Header Set
  equipment_instance: HDR-HW
  location: Plant Room
  point_description: Make-up Cold Water T
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: HW'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0502
  system: PL-HotWater
  equipment_class: Hot Water Header Set
  equipment_instance: HDR-HW
  location: Plant Room
  point_description: MUCW pressure
  type: AI
  field_device: Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: HW'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0503
  system: PL-HotWater
  equipment_class: Hot Water Header Set
  equipment_instance: HDR-HW
  location: Plant Room
  point_description: HW circulating flow
  type: AI
  field_device: Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: HW'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0504
  system: PL-HotWater
  equipment_class: Hot Water Header Set
  equipment_instance: HDR-HW
  location: Plant Room
  point_description: HW return T
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: HW'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0505
  system: PL-HeatPumps
  equipment_class: Heat Pump
  equipment_instance: HP-1
  location: Plant Room
  point_description: Pump motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: HP'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0506
  system: PL-HeatPumps
  equipment_class: Heat Pump
  equipment_instance: HP-1
  location: Plant Room
  point_description: Pump HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: HP'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0507
  system: PL-HeatPumps
  equipment_class: Heat Pump
  equipment_instance: HP-1
  location: Plant Room
  point_description: Pump trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: HP'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0508
  system: PL-HeatPumps
  equipment_class: Heat Pump
  equipment_instance: HP-2
  location: Plant Room
  point_description: Pump motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: HP'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0509
  system: PL-HeatPumps
  equipment_class: Heat Pump
  equipment_instance: HP-2
  location: Plant Room
  point_description: Pump HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: HP'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0510
  system: PL-HeatPumps
  equipment_class: Heat Pump
  equipment_instance: HP-2
  location: Plant Room
  point_description: Pump trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: HP'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0511
  system: PL-HeatPumps
  equipment_class: Heat Pump
  equipment_instance: HP-3
  location: Plant Room
  point_description: Pump motor status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: HP'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0512
  system: PL-HeatPumps
  equipment_class: Heat Pump
  equipment_instance: HP-3
  location: Plant Room
  point_description: Pump HOA
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: HP'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0513
  system: PL-HeatPumps
  equipment_class: Heat Pump
  equipment_instance: HP-3
  location: Plant Room
  point_description: Pump trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: HP'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0514
  system: PL-RecircPumps
  equipment_class: Recirculating Pump
  equipment_instance: RP-1
  location: Plant Room
  point_description: Pump status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: RP'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0515
  system: PL-RecircPumps
  equipment_class: Recirculating Pump
  equipment_instance: RP-1
  location: Plant Room
  point_description: Pump trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: RP'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0516
  system: PL-RecircPumps
  equipment_class: Recirculating Pump
  equipment_instance: RP-2
  location: Plant Room
  point_description: Pump status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: RP'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0517
  system: PL-RecircPumps
  equipment_class: Recirculating Pump
  equipment_instance: RP-2
  location: Plant Room
  point_description: Pump trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: RP'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0518
  system: PL-RecircPumps
  equipment_class: Recirculating Pump
  equipment_instance: RP-3
  location: Plant Room
  point_description: Pump status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: RP'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0519
  system: PL-RecircPumps
  equipment_class: Recirculating Pump
  equipment_instance: RP-3
  location: Plant Room
  point_description: Pump trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: RP'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0520
  system: PL-RecircPumps
  equipment_class: Recirculating Pump
  equipment_instance: RP-4
  location: Plant Room
  point_description: Pump status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: RP'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0521
  system: PL-RecircPumps
  equipment_class: Recirculating Pump
  equipment_instance: RP-4
  location: Plant Room
  point_description: Pump trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: RP'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0522
  system: PL-RecircPumps
  equipment_class: Recirculating Pump
  equipment_instance: RP-5
  location: Plant Room
  point_description: Pump status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: RP'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0523
  system: PL-RecircPumps
  equipment_class: Recirculating Pump
  equipment_instance: RP-5
  location: Plant Room
  point_description: Pump trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: RP'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0524
  system: PL-RecircPumps
  equipment_class: Recirculating Pump
  equipment_instance: RP-6
  location: Plant Room
  point_description: Pump status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: RP'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0525
  system: PL-RecircPumps
  equipment_class: Recirculating Pump
  equipment_instance: RP-6
  location: Plant Room
  point_description: Pump trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: RP'
  panel: PNL-CHPLANT-GND
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0526
  system: PL-Boiler
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Basement
  point_description: Steam pressure
  type: AI
  field_device: Steam Pressure Sensor (high-T)
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Boiler'
  panel: PNL-BSMT
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0527
  system: PL-Boiler
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Basement
  point_description: Feedwater temperature
  type: AI
  field_device: Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Boiler'
  panel: PNL-BSMT
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0528
  system: PL-Boiler
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Basement
  point_description: Fluegas temperature
  type: AI
  field_device: High-Temperature Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Boiler'
  panel: PNL-BSMT
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0529
  system: PL-Boiler
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Basement
  point_description: Fluegas O2
  type: AI
  field_device: Zirconia O2 Sensor
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Boiler'
  panel: PNL-BSMT
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0530
  system: PL-Boiler
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Basement
  point_description: Blowdown valve command
  type: AO
  field_device: Motorized Blowdown Valve
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Boiler'
  panel: PNL-BSMT
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0531
  system: PL-Boiler
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Basement
  point_description: Burner status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Boiler'
  panel: PNL-BSMT
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0532
  system: PL-Boiler
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Basement
  point_description: Burner trip
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Boiler'
  panel: PNL-BSMT
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0533
  system: PL-Boiler
  equipment_class: Steam Boiler
  equipment_instance: SB-1
  location: Basement
  point_description: HOA status
  type: DI
  field_device: Auxiliary Contact
  c_o: Equipment Supplier
  description_of_operations_ref: 'DoO: Boiler'
  panel: PNL-BSMT
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: ''
- id: P0534
  system: Power-EE
  equipment_class: Multifunction Power Meter (Main)
  equipment_instance: MTR-MAIN-1
  location: Main Switchgear
  point_description: Modbus HLI (V/I/kW/kWh/PF/THD per phase)
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  description_of_operations_ref: Energy reporting
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: Modbus RTU
- id: P0535
  system: Power-EE
  equipment_class: Multifunction Power Meter (Main)
  equipment_instance: MTR-MAIN-2
  location: Main Switchgear
  point_description: Modbus HLI (V/I/kW/kWh/PF/THD per phase)
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  description_of_operations_ref: Energy reporting
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: Modbus RTU
- id: P0536
  system: Power-EE
  equipment_class: Multifunction Power Meter (Main)
  equipment_instance: MTR-MAIN-3
  location: Main Switchgear
  point_description: Modbus HLI (V/I/kW/kWh/PF/THD per phase)
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  description_of_operations_ref: Energy reporting
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: Modbus RTU
- id: P0537
  system: Power-EE
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: MTR-FDR-01
  location: Sub-Distribution Board
  point_description: Modbus HLI (V/I/kW/kWh)
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  description_of_operations_ref: Energy reporting
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: Modbus RTU
- id: P0538
  system: Power-EE
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: MTR-FDR-02
  location: Sub-Distribution Board
  point_description: Modbus HLI (V/I/kW/kWh)
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  description_of_operations_ref: Energy reporting
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: Modbus RTU
- id: P0539
  system: Power-EE
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: MTR-FDR-03
  location: Sub-Distribution Board
  point_description: Modbus HLI (V/I/kW/kWh)
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  description_of_operations_ref: Energy reporting
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: Modbus RTU
- id: P0540
  system: Power-EE
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: MTR-FDR-04
  location: Sub-Distribution Board
  point_description: Modbus HLI (V/I/kW/kWh)
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  description_of_operations_ref: Energy reporting
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: Modbus RTU
- id: P0541
  system: Power-EE
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: MTR-FDR-05
  location: Sub-Distribution Board
  point_description: Modbus HLI (V/I/kW/kWh)
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  description_of_operations_ref: Energy reporting
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: Modbus RTU
- id: P0542
  system: Power-EE
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: MTR-FDR-06
  location: Sub-Distribution Board
  point_description: Modbus HLI (V/I/kW/kWh)
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  description_of_operations_ref: Energy reporting
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: Modbus RTU
- id: P0543
  system: Power-EE
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: MTR-FDR-07
  location: Sub-Distribution Board
  point_description: Modbus HLI (V/I/kW/kWh)
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  description_of_operations_ref: Energy reporting
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: Modbus RTU
- id: P0544
  system: Power-EE
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: MTR-FDR-08
  location: Sub-Distribution Board
  point_description: Modbus HLI (V/I/kW/kWh)
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  description_of_operations_ref: Energy reporting
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: Modbus RTU
- id: P0545
  system: Power-EE
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: MTR-FDR-09
  location: Sub-Distribution Board
  point_description: Modbus HLI (V/I/kW/kWh)
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  description_of_operations_ref: Energy reporting
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: Modbus RTU
- id: P0546
  system: Power-EE
  equipment_class: Multifunction Power Meter (Feeder)
  equipment_instance: MTR-FDR-10
  location: Sub-Distribution Board
  point_description: Modbus HLI (V/I/kW/kWh)
  type: HLI
  field_device: Modbus Power Meter
  c_o: BMS Contractor
  description_of_operations_ref: Energy reporting
  panel: PNL-GF
  source: MC Standards (ME/PL Points list) + project-specific equipment count per A-002
  notes: Modbus RTU
- id: P0547
  system: Network
  equipment_class: BMS Network Drop
  equipment_instance: NET-PNL-RD
  location: panel
  point_description: BACnet/IP drop at PNL-RD
  type: Network
  field_device: RJ45 + Cat6 to edge switch
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Network'
  panel: PNL-RD
  source: A5 architecture
  notes: ''
- id: P0548
  system: Network
  equipment_class: BMS Network Drop
  equipment_instance: NET-PNL-3F
  location: panel
  point_description: BACnet/IP drop at PNL-3F
  type: Network
  field_device: RJ45 + Cat6 to edge switch
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Network'
  panel: PNL-3F
  source: A5 architecture
  notes: ''
- id: P0549
  system: Network
  equipment_class: BMS Network Drop
  equipment_instance: NET-PNL-2F
  location: panel
  point_description: BACnet/IP drop at PNL-2F
  type: Network
  field_device: RJ45 + Cat6 to edge switch
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Network'
  panel: PNL-2F
  source: A5 architecture
  notes: ''
- id: P0550
  system: Network
  equipment_class: BMS Network Drop
  equipment_instance: NET-PNL-GF
  location: panel
  point_description: BACnet/IP drop at PNL-GF
  type: Network
  field_device: RJ45 + Cat6 to edge switch
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Network'
  panel: PNL-GF
  source: A5 architecture
  notes: ''
- id: P0551
  system: Network
  equipment_class: BMS Network Drop
  equipment_instance: NET-PNL-BSMT
  location: panel
  point_description: BACnet/IP drop at PNL-BSMT
  type: Network
  field_device: RJ45 + Cat6 to edge switch
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Network'
  panel: PNL-BSMT
  source: A5 architecture
  notes: ''
- id: P0552
  system: Network
  equipment_class: BMS Network Drop
  equipment_instance: NET-PNL-CHPLANT-GND
  location: panel
  point_description: BACnet/IP drop at PNL-CHPLANT-GND
  type: Network
  field_device: RJ45 + Cat6 to edge switch
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Network'
  panel: PNL-CHPLANT-GND
  source: A5 architecture
  notes: ''
- id: P0553
  system: Network
  equipment_class: BMS Network Drop
  equipment_instance: NET-PNL-BOH-2F
  location: panel
  point_description: BACnet/IP drop at PNL-BOH-2F
  type: Network
  field_device: RJ45 + Cat6 to edge switch
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Network'
  panel: PNL-BOH-2F
  source: A5 architecture
  notes: ''
- id: P0554
  system: Network
  equipment_class: BMS Network Drop
  equipment_instance: NET-PNL-HE-GF
  location: panel
  point_description: BACnet/IP drop at PNL-HE-GF
  type: Network
  field_device: RJ45 + Cat6 to edge switch
  c_o: BMS Contractor
  description_of_operations_ref: 'DoO: Network'
  panel: PNL-HE-GF
  source: A5 architecture
  notes: ''