# 02 — Classification

**Project:** Kingsford Hotel Bacolod — BMS
**Date:** 2026-04-28

## Discipline

- **Primary:** BMS
- **Secondary:** Power metering (EE) integration via Modbus

## Stage

- **Greenfield (new construction)**
- Cited evidence:
  - EE Plan stamped *"Electrical Construction Bulletin No.8"*, November 2025 — design adjustments for new construction
  - BMS Points list stamped *"Construction Bulletin"* Oct 2025
  - No existing-system inventory provided (no controller make/model/age, no head-end specs, no demolition scope)
  - Cover letter wording "Rehabilitation" treated as weak evidence per Phase-2 triangulation rule
- Q-018 raised for the customer to confirm the wording mismatch.

## Scope type

- [x] Supply
- [x] Installation
- [x] Programming
- [x] Testing & Commissioning
- [ ] Training (assumed in scope per standard practice; Q-015 confirms duration)
- [ ] Maintenance (assumed not in scope; offered as Option in 7.0; Q-016 confirms)

## Facility type

- Hotel / Hospitality (Kingsford Hotel Bacolod). No casino floor evident in the inputs — straight hotel, not `bms-hospitality-casino`.

## Estimated tier

- **Medium** — basis: Megaworld standard BMS scope across guestroom + plant + back-of-house systems. AB2 baseline order-of-magnitude was ~700 I/O, ~135 equipment instances, ~18 panels — consistent with medium tier (200–1500 points).

## Implications for later phases

- Required-doc checklist column: `bms-greenfield`
- Module catalog: `_playbook/modules/bms/`
- Stage assumption set: greenfield (no demolition, no cutover, no hot-work after-hours premium)
- Special considerations: power metering uses Modbus RTU/TCP via gateway; integration with future PMS / FDAS deferred to Option

## Default brand standards (no customer override found)

Customer MC Standards documents do not call out specific BMS brands. Defaults from `_playbook/checklists/default-brand-standards.md` apply:
- BMS / PLC / FDAS / SCADA components — **Siemens** (Desigo PXC for DDC, Climatix for unit controllers, PXM30 for I/O, Desigo CC for head-end; QAA/QFA/QAM/QFM/QBM for sensors; VAI/VKF/SAS for valve actuators; 7KM PAC for power meters; Cerberus PRO for FDAS interface).
- Head-end PCs — **Dell** (PowerEdge R650 for servers, OptiPlex for workstations, Precision for graphics PC).
- Other categories chosen per project (see 99-decision-log.md).